Control Valve Calibration Procedure (Fisher HC6010)
Control Valve Calibration Procedure (Fisher HC6010)
Page index
1. POSITIONER SPECIFICATION 2. POSITIONER AND ACTUATOR AIR FLOW 3. POSITIONER ATTACHMENT 4. 4 SIGNAL LINE CONNECTION 5. CALIBRATION PROCEDURE 6. MANUAL OPERATION 7.CONTROL VALVE LIMIT SWITCHES 8.ALARM AND STATUS
1. Positioner Specification
ElectricalSpecification PowerSupply l Communication MinimumOperatingCurrent MaximumVoltage AnalogInputSignal PositionerSpecification Linearity AirConsumption MaximumAirSupply 0.5%ofoutputspan 1.4bar(20psi) 10 bar(145psi) 1130Vdc d Hartprotocol 3.5mAwithoutmicroprocessor 30Vdc 4 20mA
Flow diagram on how the actuator moves closing and opening position in digital g g p gp g and analog mode.
positioner
actuator
positioner
4
Air to Open Actuator 1. Insert the alignment pin in the hole marked A 2. The feedback arm rotates counterclockwise, from A to B as air pressure to the casing or lower cylinder increases. g y Air to Close Actuator 1. Insert the alignment pin in the hole marked B 2. The feedback arm rotates clockwise from B to A as air pressure to the casing or upper cylinder increases. increases
4 20mA Source
Hart Communicator
8
10
6. Manual Operation
Handwheel Handwheel lock Position travel indicator
Rotate the handwheel lock Anti-clockwise to operate the handwheel Start to rotate the handwheel lock to desire direction Clockwise for closing Anti clockwise for opening If the handwheel reach the maximum turn, you can check the position i t h k th iti in travel indicator if it is fully close l i di t i f ll l or fully open.
11
Limit switch for open position when control valve is in fully open the contact is close for open, fully open feedback.
Limit switch for close position when control valve is in fully close the contact is open for close, fully close feedback.
12
2 1 -2 -3 1 3 4
13