IOSRJEN (WWW - Iosrjen.org) IOSR Journal of Engineering
IOSRJEN (WWW - Iosrjen.org) IOSR Journal of Engineering
\
| +
=
L
L L
L
V
jQ P
I (4.4)
When V
L
is considered as a reference, therefore;
( ) o u | o Z Z + Z = Z
th L th L DVR
V I Z V V
0
0
(4.5)
Here , and are the angle of V
DVR
, Z
th
and V
th
, respectively and is the load power factor angle with
|
|
.
|
\
|
=
L
L
P
Q
1
tan u
The power injection of the DVR can be written as
S
DVR
= V
DVR
I
L
*
(4.6)
Fig 4.1: Calculation for DVR Voltage Injection
4.2 Phase Locked Loop (PLL)
A PLL is a device which causes one signal to track another one. It keeps an output signal synchronizing
with a reference input signal in frequency as well as in phase. More, precisely the PLL is a servo system, which
Series Compensation Technique for Voltage Sag Mitigation
www.iosrjen.org 21 | P a g e
controls the phase of its output signal in such a way that the phase error between out phase and reference phase
reduce to a minimum.
The phase angle of the utility voltage is a critical piece of information for the operation of most
apparatuses such as controlled ac/dc converters, Static VAR compensators, cyclo-converters, active harmonic
filters and other energy storage system coupled with electric utility. This information may be used to
synchronize the turning on/off of power device, calculate and control the flow of active/ reactive power or
transform the feedback variable to reference frame suitable for control purposes. The angle information is
typically extracted using some form of phase locked loop (PLL). The quality of phase lock directly affects the
performance of the control loops in all the above applications. Voltage unbalance, frequency variation and phase
jumps are common disturbances faced by equipment interfaced with the electric utility. For application
purposes, frequency can vary from 47 Hz to 51 Hz. Any PLL used under such condition should not only be able
to phase lock as quickly as possible but also provide an output with low distortion.
4.2.1 Principle of Operation
As the phase information of a periodic input signal is not directly measurable, the phase angle () has
been estimated from measured instantaneous values of the input. Since phase angle () is related to the angular
frequency () as
= (4.7)
The plant equation is G(s) =
Which is shown in Fig 4.2
Figure 4.2: Plant Model
The objective here is to compute an accurate estimate ( ) of the actual phase () of the input
waveform. The accuracy of estimation is indicated by the estimation error (), defined as
= - (4.8)
To obtain a relation between the estimation error in terms measured variables, the SRF approach is adopted.
Let , , be a set of balanced, three phase voltage signals, defined as
= (4.9)
These are first transformed with respect to a stationary, Cartesian reference frame using the following
transformation.
= (4.10)
The transformed voltages are then referred to a rotating reference frame, which has same angular phase as the
estimator output, . This transformation is defined as
= (4.11)
Successively substituting (4.9) in (4.10) and the result of (4.10) in (4.11), the transformed quantities are
= V = (4.12)
Where,
=
V
2
3
As, for small values of (), Sin () () (4.13)
(4.2)is linearized as (4.14)
Series Compensation Technique for Voltage Sag Mitigation
www.iosrjen.org 22 | P a g e
An indication of the estimation error, (), is there by obtained from the q-axis equation of (4.13). This
offers immediate possibility to lock onto the utility phase by regulating to zero by a suitable controller H(s).
The estimation error is also made immune to magnitude variations of utility voltage. Fig.4.3 shows the
schematic of the control model of estimation loop and Fig.4.4 shows the schematic of simplified control model
of estimation loop.
Figure 4.3: Control Model of PLL System
Figure 4.4 Simplified Control Model of PLL System
4.4 Summary: This chapter has presents the modeling of the DVR and the principle of phase lock loop (PLL)
and its requirement in DVR system.
V. SIMULATION RESULTS
Simulation of the DVR is performed in MATLAB SIMULINK using the above control technique.
MATLAB SIMULINK is a very popular tool for mathematical computation and model based design and
SIMULINK Model is in generally pictorial representation of an application created using blocks provided by
MATLAB as well as third parties.
Minimal energy compensation technique, discussed in section 3.3.1, is adopted to control the rms value
of load voltage. Decoupled active power and reactive power control strategy is adopted to control the DVR
output voltage and DC bus voltage. In this control strategy, in d-q frame, d-axis reference voltage depends on
the DC bus voltage error and the q-axis voltage reference depends on the error in the rms value of load voltage.
So the voltage injection is in quadrature with the load current. Simulation is performed under two loaded
conditions, i.e balanced load and unbalanced load condition.
5.1 Balanced Voltage Sag
In order to understand the performance of the DVR along with control, a simple distribution network is
taken as shown in Figure 5.1.
Figure 5.1 Simple Distribution Systems Taken for Simulation
Voltage sags are simulated by temporary connection of balanced impedances at the supply side bus. A
DVR is connected to the system through a series transformer with a capability to insert a maximum voltage of
50% of the phase to- ground system voltage. Apart from this a series filter is also used to remove any high
frequency components of power. The load considered in the study is a 10 MVA capacity with 0.9 p.f., lagging.
The results are shown in the next section.
Symmetrical sag is simulated by connecting a three-phase reactance (inductance in series with
resistance) to the bus bar. The three-phase reactance is a balanced one.
The results are shown in Figure 5.2 (a), (b), (c) are the each phase voltages at point of common
connection (PCC). In this the 40 % sag is initiated at 200ms and it is kept until 400ms, with total voltage sag
duration 200ms.
Series Compensation Technique for Voltage Sag Mitigation
www.iosrjen.org 23 | P a g e
As a result of DVR, the load voltage is kept at nominal value throughout the simulation, including the
voltage sag period. Observe that during normal operation, the DVR is doing nothing. Fig 5.3 (a), (b), (c) show
the 3-phase series injected voltage by DVR, load voltage and source voltage at PCC.
Fig (a) 3-Phase voltage at PCC
Fig (b) 3-Phase injected voltage
Fig (c) 3-Phase voltage at load point
Figure5.2: Simulation result of DVR response to a balanced voltage sag.
5.2 Unbalanced Voltage Sag
Fig 5.3 shows simulation result of DVR response to unbalanced voltage sag. Here, the breaker is
connected at 200ms and opened at 400ms. In this almost the unbalanced voltage sag is corrected to the supply
voltage.
Fig (a) 3-phase voltage at PCC
Fig (b) 3-phase injected voltage of the DVR
Figure(c) 3-phase voltages at load point
Fig 5.3 Simulation result of DVR response to unbalanced voltage sag.
Series Compensation Technique for Voltage Sag Mitigation
www.iosrjen.org 24 | P a g e
VI. CONCLUSION AND FUTURE SCOPE OF WORK
6.1 conclusion
The simulation of the DVR system for mitigation of balanced and unbalanced voltage sag is done in
Matlab Simulink and tested the performance for sag mitigation in series compensation technique. In shunt
compensation technique The Distribution static synchronous compensator(D-STATCOM) is also simulated and
extraction of the sequence components is performed for double phase and three phase faults.
From the simulations we can conclude that the series compensation technique is most reliable
compared to shunt compensation as shunt compensation requires more reactive power to be injected to the
system for the same sags. And the energy storage required is also more for shunt compensation.
6.2 Future Scope
- Three phase dynamic voltage restorer with auxiliary supply voltage has been used in the simulation study.
Instead of auxiliary voltage supply we can also use capacitor bank and study the results.
- In three phase system multi level inverters or a chain of single phase inverters for each phase may be used
in the DVR topology and such systems may be studied.
- The super conducting magnetic energy storage systems (SMES) may be used in the DVR structure in large
systems. Such systems may be studied.
- Filters may be needed to reduce the total harmonic distortion in the distribution system because of the
switching devices used in the DVR. Such filters may be active or passive types. Hybrid type filters may be
used to reduce costs. A comparative study of such filters may be carried out.
- PI controllers are used in the simulation study to control the PCC voltage. A major limitation of PI
controller is that, it does not guarantee the system stability under varying load conditions. Therefore, it may
be desirable to employ advanced control techniques based on Fuzzy, Neural logic and study the system
stability.
- Multilevel inverters and H-bridge inverters are used for reducing the harmonic injection. This may be a
fruitful extension.
- A study of employing D-STATCOM to comprehensively mitigate at the same time the effects of
harmonics, voltage sags/swells, and parasitic effects of switching disturbances and improve power factor
has become necessary due to ever increasing use of power electronic equipment.
- One can code the algorithms in the DSP processor and can see the performance of the devices for
compensating sag in hardware.
REFERENCES
[1] N.G Hingroni and I Gyugyi. Understanding FACTS: Concepts and Technology of flexible AC Transmi ssion System, IEEE Press,
New York, 2000
[2] Math H.J.Bollenunderstanding power quality problems:Voltage sags and interruptions,IEE Press,New York, 2001N. Woodley,
Experience with an inverter-based dynamic voltage restorer, IEEE Trans. Power Delivery, vo1.14, no.3. July 1999 pp. 1181 -1184.
[3] Ambra Sannino, Michelle Ghans Miller, Math H.J. Bollen, Overview of Voltage Sag Mitigation. Power Engineering Society Winter
Meeting, 2000. IEEE, Volume: 4, 23-27 Jan, 2000, pages: 2872 2878 vol.4 10.
[4] V.K.Ramachandramurthy,C.Fitzer, A.Arulampalam,"Control of a battery supported Dynamic Voltage Restorer(DVR),"IEEE
proceedings of Transmission and Distribution, Vol. 149, no. 5, pp.533-542, 2002.
BIOGRAPHY
Nagendrababu Vasa, II-M.Tech Power Electronics, Department of Electrical & Electronics Engineering, Sri
Venkateswara Engineering College, Suryapet.
Sreekanth G, II-M.Tech Power Electronics, Department of Electrical & Electronics Engineering, Sri Venkateswara
Engineering College, Suryapet.
Mr.N.Narender Reddy was born in 1984. He graduated from Jawaharlal Nehru Technological University, Hyderabad in
the year 2006. He received M.Tech degree from Jawaharlal Nehru Technological University, Hyderabad,ear 2010. He is
presently working as Assistant Professor in the Department of Electrical and Electronics Engineering at Sri Venkateswara
Engineering College,Suryapet India. His research area includes HVE and Drives.
Dr.A.Srujana has obtained his B. Tech degree from KITS, Warangal, in 1998 and M. Tech degree From J.N.T.U
,Hyderabad, India, in 2002.She Has obtained her Ph.D from J.N.T.U ,Hyderabad in 2011. She has 14 years of teaching
experience. Presently he is working as Professor & H.O.D E.E.E at Sri venkateswara engineering college,Suryapet.