recorded or calculated. A series of value-timestamp combinations is the history of that point. It's also common to store additional metadata with tags such as: path to field device and PLC register, design time comments, and even alarming information.
SCADA is not a specific technology, but a type of application. SCADA stands for Supervisory Control and Data Acquisition any application that gets data about a system in order to control that system is a SCADA application. A SCADA application has two elements: 1. The process/system/machinery you want to monitor a control this can be a power plant, a water system, a network, a system of traffic lights, or anything else. 2. A network of intelligent devices that interfaces with the first system through sensors and control outputs. This network, which is the SCADA system, gives you the ability to measure and control specific elements of the first system. You can build a SCADA system using several different kinds of technologies and protocols. This white paper will help you evaluate your options and decide what kind of SCADA system is best for your needs.
9.1.2 WHERE IS SCADA USED? You can use SCADA to manage any kind of equipment. Typically, SCADA systems are used to automate complex industrial processes where human control is impractical systems where there are more control factors, and more fast-moving control factors, than human beings can comfortably manage. Around the world, SCADA systems control:
Electric power generation, transmission and distribution: Electric utilities use SCADA systems to detect current flow and line voltage, to monitor the operation of circuit breakers, and to take sections of the power grid online or offline.
Water and sewage: State and municipal water utilities use SCADA to monitor and regulate water flow, reservoir levels, pipe pressure and other factors.
84
Buildings, facilities and environments: Facility managers use SCADA to control HVAC, refrigeration units, lighting and entry systems.
Manufacturing:
SCADA
systems
manage
parts
inventories
for
just-in-time
manufacturing, regulate industrial automation and robots, and monitor process and quality control.
Mass transit: Transit authorities use SCADA to regulate electricity to subways, trams and trolley buses; to automate traffic signals for rail systems; to track and locate trains and buses; and to control railroad crossing gates.
Traffic signals: SCADA regulates traffic lights, controls traffic flow and detects out-oforder signals.
As Im sure you can imagine, this very short list barely hints at all the potential applications for SCADA systems. SCADA is used in nearly every industry and public infrastructure project anywhere where automation increases efficiency. Whats more, these examples dont show how deep and complex SCADA data can be. In every industry, managers need to control multiple factors and the interactions between those factors. SCADA systems provide the sensing capabilities and the computational power to track everything thats relevant to your operations.
9.1.3 HOW DOES A SCADA SYSTEM WORK? A SCADA system performs four functions: 1. Data acquisition 2. Networked data communication 3. Data presentation 4. Control These functions are performed by four kinds of SCADA components: 1. Sensors (either digital or analog) and control relays that directly interface with the managed system.
85
2. Remote telemetry units (RTUs). These are small computerized units deployed in the field at specific sites and locations. RTUs serve as local collection points for gathering reports from sensors and delivering commands to control relays. 3. SCADA master units. These are larger computer consoles that serve as the central processor for the SCADA system. Master units provide a human interface to the system and automatically regulate the managed system in response to sensor inputs. 4. The communications network that connects the SCADA master unit to the RTUs in the field.
9.1.4 THE WORLDS SIMPLEST SCADA SYSTEM The simplest possible SCADA system would be a single circuit that notifies you of one event. Imagine a fabrication machine that produces widgets. Every time the machine finishes a widget, it activates a switch. The switch turns on a light on a panel, which tells a human operator that a widget has been completed. Obviously, a real SCADA system does more than this simple model. But the principle is the same. A full-scale SCADA system just monitors more stuff over greater distances. Lets look at what is added to our simple model to create a full-scale SCADA system:
86
Some of those sensors measure simple events that can be detected by a straightforward on/off switch, called a discrete input (or digital input). For example, in our simple model of the widget fabricator, the switch that turns on the light would be a discrete input. In real life, discrete inputs are used to measure simple states, like whether equipment is on or off, or tripwire alarms, like a power failure at a critical facility. Some sensors measure more complex situations where exact measurement is important. These are analog sensors, which can detect continuous changes in a voltage or current input. Analog sensors are used to track fluid levels in tanks, voltage levels in batteries, temperature and other factors that can be measured in a continuous range of input. For most analog factors, there is a normal range defined by a bottom and top level. For example, you may want the temperature in a server room to stay between 60 and 85 degrees Fahrenheit. If the temperature goes above or below this range, it will trigger a threshold alarm. In more advanced systems, there are four threshold alarms for analog sensors, defining Major Under, Minor Under, Minor Over and Major Over alarms.
87
88
An advanced SCADA master can add a great deal of intelligence and automation to your systems management, making your job much easier.
9.5 CONTROL
Unfortunately, our miniature SCADA system monitoring the widget fabricator doesnt include any control elements. So lets add one. Lets say the human operator also has a button on his control panel. When he presses the button, it activates a switch on the widget fabricator that brings more widget parts into the fabricator. Now lets add the full computerized control of a SCADA master unit that controls the entire factory. You now have a control system that responds to inputs elsewhere in the system. If the machines that make widget parts break down, you can slow down or stop the widget fabricator. If the part fabricators are running efficiently, you can speed up the widget fabricator. If you have a sufficiently sophisticated master unit, these controls can run completely automatically, without the need for human intervention. Of course, you can still manually override the automatic controls from the master station. In real life, SCADA systems automatically regulate all kinds of industrial processes. For example, if too much pressure is building up in a gas pipeline, the SCADA system can automatically open a release valve. Electricity production can be adjusted to meet demands on the power grid. Even these real-world examples are simplified; a full-scale SCADA system can adjust the managed system in response to multiple inputs.
9.6 ARCHITECTURE
In this section we are going to details which describe the common architecture required for the SCADA products. 9.6.1 HARDWARE ARCHITECTURE The basic hardware of the SCADA system is distinguished into two basic layers: the "client layer" which caters for the man machine interaction and the "data server layer" which handles most of the process data control activities. The data servers communicate with devices in the
89
field through process controllers. Process controllers, e.g. PLCs, are connected to the data servers either directly or via networks or field buses that are proprietary (e.g. Siemens H1), or non-proprietary (e.g. Profibus). Data servers are connected to each other and to client stations via an Ethernet LAN. Fig.1. shows typical hardware architecture.
9.6.2 SOFTWARE ARCHITECTURE The SCADA products are multi-tasking and are based upon a real-time database (RTDB) located in one or more servers. Servers are responsible for data acquisition and handling like polling controllers, alarm checking, calculations, logging and archiving) on a set of parameters, typically to which those are connected. However, it is possible to have dedicated servers for particular tasks, e.g. historian, data logger, alarm handler. Fig. 2 shows a SCADA architecture that is generic for the product.
90
9.7 COMMUNICATION
9.7.1 INTERNAL COMMUNICATION Server-client and server-server communication is in general on a publish-subscribe and eventdriven basis and uses a TCP/IP protocol, i.e., a client application subscribes to a parameter which is owned by a particular server application and only changes to that parameter are then communicated to the client application. 9.7.2 ACCESS TO DEVICES The data servers poll the controllers at a user defined polling rate. The polling rate may be different for different parameters. The controllers pass the requested parameters to the data
91
servers. Time stamping of the process parameters is typically performed in the controllers and this time-stamp is taken over by the data server. If the controller and communication protocol used support unsolicited data transfer then the products will support this too. The products provide communication drivers for most of the common PLCs and widely used field-buses, e.g., Modbus. Of the three field buses that are recommended are, both Profibus and Worldfip are supported but CANbus often not. Some of the drivers are based on third party products (e.g., Applicom cards) and therefore have additional cost associated with them. VME on the other hand is generally not supported. A single data server can support multiple communications protocols; it can generally support as many such protocols as it has slots for interface cards. The effort required to develop new drivers is typically in the range of 2-6 weeks depending on the complexity and similarity with existing drivers, and a driver development toolkit is provided for this.
92
protocols used were still mostly proprietary, which led to significant security problems for any SCADA system that received attention from a hacker. Since the protocols were proprietary, very few people beyond the developers and hackers knew enough to determine how secure a SCADA installation was. Since both parties had vested interests in keeping security issues quiet, the security of a SCADA installation was often badly overestimated, if it was considered at all.
93
A Human-Machine Interface or HMI is the apparatus which presents process data to a human operator, and through which the human operator controls the process. An HMI is usually linked to the SCADA system's databases and software programs, to provide trending, diagnostic data, and management information such as scheduled maintenance procedures, logistic information, detailed schematics for a particular sensor or machine, and expert-system troubleshooting guides. The HMI system usually presents the information to the operating personnel graphically, in the form of a mimic diagram. This means that the operator can see a schematic representation of the plant being controlled. For example, a picture of a pump connected to a pipe can show the operator that the pump is running and how much fluid it is pumping through the pipe at the moment. The operator can then switch the pump off. The HMI software will show the flow rate of the fluid in the pipe decrease in real time. Mimic diagrams may consist of line graphics and schematic symbols to represent process elements, or may consist of digital photographs of the process equipment overlain with animated symbols. The HMI package for the SCADA system typically includes a drawing program that the operators or system maintenance personnel use to change the way these points are represented in the interface. These representations can be as simple as an on-screen traffic light, which represents the state of an actual traffic light in the field, or as complex as a multi-projector display representing the position of all of the elevators in a skyscraper or all of the trains on a railway. An important part of most SCADA implementations is alarm handling. The system monitors whether certain alarm conditions are satisfied, to determine when an alarm event has occurred. Once an alarm event has been detected, one or more actions are taken (such as the activation of one or more alarm indicators, and perhaps the generation of email or text messages so that management or remote SCADA operators are informed). In many cases, a SCADA operator may have to acknowledge the alarm event; this may deactivate some alarm indicators, whereas other indicators remain active until the alarm conditions are cleared. Alarm conditions can be explicit - for example, an alarm point is a digital status point that has either the value NORMAL or ALARM that is calculated by a formula based on the values in other analogue and digital points - or implicit: the SCADA system might automatically monitor whether the value in an analogue point lies outside high and low limit values associated with that point. Examples of
94
alarm indicators include a siren, a pop-up box on a screen, or a colored or flashing area on a screen (that might act in a similar way to the "fuel tank empty" light in a car); in each case, the role of the alarm indicator is to draw the operator's attention to the part of the system 'in alarm' so that appropriate action can be taken. In designing SCADA systems, care is needed in coping with a cascade of alarm events occurring in a short time, otherwise the underlying cause (which might not be the earliest event detected) may get lost in the noise. Unfortunately, when used as a noun, the word 'alarm' is used rather loosely in the industry; thus, depending on context it might mean an alarm point, an alarm indicator, or an alarm event.
95
10. SENSORS
10.1 10.2 FLOW SENSOR PRESSURE SENSOR
10.2.1 TYPES OF PRESSURE MEASUREMENT
96
10. SENSORS
10.1 FLOW SENSOR
A flow sensor is a device for sensing the rate of fluid flow. Typically a flow sensor is the sensing element used in a flow meter, or flow logger, to record the flow of fluids. As is true for all sensors, absolute accuracy of a measurement requires functionality for calibration. There are various kinds of flow sensors and flow meters, including some that have a vane that is pushed by the fluid, and can drive a rotary potentiometer, or similar device. Other flow sensors are based on sensors which measure the transfer of heat caused by the moving medium. This principle is common for microsensors to measure flow. Flow meters are related to devices called velocimeters that measure velocity of fluids flowing through them. Laser-based interferometry is often used for air flow measurement, but for liquids, it is often easier to measure the flow. Another approach is Doppler-based methods for flow measurement. Hall effect sensors may also be used, on a flapper valve, or vane, to sense the position of the vane, as displaced by fluid flow.
97
A pressure sensor measures pressure, typically of gases or liquids. Pressure is an expression of the force required to stop a fluid from expanding, and is usually stated in terms of force per unit area. A pressure sensor usually acts as a transducer; it generates a signal as a function of the pressure imposed. For the purposes of this article, such a signal is electrical.
98
Pressure sensors are used for control and monitoring in thousands of everyday applications. Pressure sensors can also be used to indirectly measure other variables such as fluid/gas flow, speed, water level, and altitude. Pressure sensors can alternatively be called pressure transducers, pressure transmitters, pressure senders, pressure indicators and piezometers, manometers, among other names. Pressure sensors can vary drastically in technology, design, performance, application suitability and cost. A conservative estimate would be that there may be over 50 technologies and at least 300 companies making pressure sensors worldwide. There is also a category of pressure sensors that are designed to measure in a dynamic mode for capturing very high speed changes in pressure. Example applications for this type of sensor would be in the measuring of combustion pressure in an engine cylinder or in a gas turbine. These sensors are commonly manufactured out of piezoelectric materials such as quartz. Some pressure sensors, such as those found in some traffic enforcement cameras, function in a binary (on/off) manner, i.e., when pressure is applied to a pressure sensor, the sensor acts to complete or break an electrical circuit. These types of sensors are also known as a pressure switch.
Pressure sensors can be classified in term of pressure ranges they measure, temperature ranges of operation, and most importantly the type of pressure they measure. In terms of pressure type, pressure sensors can be divided into five categories:
99
This sensor measures the pressure relative to perfect vacuum pressure (0 PSI or no pressure). Atmospheric pressure, is 101.325 kPa (12.7 PSI) at sea level with reference to vacuum.
This sensor is used in different applications because it can be calibrated to measure the pressure relative to a given atmospheric pressure at a given location. A tire pressure gauge is an example of gauge pressure indication. When the tire pressure gauge reads 0 PSI, there is really 12.7 PSI (atmospheric pressure) in the tire.
This sensor is used to measure pressure less than the atmospheric pressure at a given location. This has the potential to cause some confusion as industry may refer to a vacuum sensor as one which is referenced to either atmospheric pressure (ie measure Negative gauge pressure) or relative to absolute vacuum.
This sensor measures the difference between two or more pressures introduced as inputs to the sensing unit, for example, measuring the pressure drop across an oil filter. Differential pressure is also used to measure flow or level in pressurized vessels.
This sensor is the same as the gauge pressure sensor except that it is previously calibrated by manufacturers to measure pressure relative to sea level pressure.
100
Force Collector Types These types of electronic pressure sensors generally use a force collector (such a diaphragm, piston, bourdon tube, or bellows) to measure strain (or deflection) due to applied force (pressure) over an area.
Uses the piezoresistive effect of bonded or formed strain gages to detect strain due to applied pressure. Common technology types are Silicon (Monocrystalline), Polysilicon Thin Film, Bonded Metal Foil, Thick Film, and Sputtered Thin Film. Generally, the strain gauges are connected to form a Wheatstone bridge circuit to maximize the output of the sensor. This is the most commonly employed sensing technology for general purpose pressure measurement. Generally, these technologies are suited to measure absolute, gauge, vacuum, and differential pressures.
CAPACITIVE
Uses a diaghragm and pressure cavity to create a variable capacitor to detect strain due to applied pressure. Common technologies use metal, ceramic, and silicon diaphragms. Generally, these technologies are most applied to low pressures (Absolute, Differential and Gauge)
ELECTROMAGNETIC
Measures the displacement of a diaphragm by means of changes in inductance (reluctance), LVDT, Hall Effect, or by eddy current principal.
PIEZOELECTRIC
Uses the piezoelectric effect in certain materials such as quartz to measure the strain upon the sensing mechanism due to pressure. This technology is commonly employed for the measurement of highly dynamic pressures.
OPTICAL
Uses the physical change of an optical fiber to detect strain due to applied pressure. A common example of this type utilizes Fiber Bragg Gratings. This technology is employed in challenging
101
applications where the measurement may be highly remote, under high temperature, or may benefit from the technologies inherent immunity to electromagnetic interference.
POTENTIOMETRIC
Uses the motion of a wiper along a resistive mechanism to detect the strain caused by applied pressure.
10.4 APPLICATIONS
There are many applications for pressure sensors:
PRESSURE SENSING
This is the direct use of pressure sensors to measure pressure. This is useful in weather instrumentation, aircraft, cars, and any other machinery that has pressure functionality implemented.
ALTITUDE SENSING
This is useful in aircraft, rockets, satellites, weather balloons, and many other applications. All these applications make use of the relationship between changes in pressure relative to the altitude. This relationship is governed by the following equation:
This equation is calibrated for an altimeter, up to 36,090 feet (9,000 m). Outside that range, an error will be introduced which can be calculated differently for each different pressure sensor. These error calculations will factor in the error introduced by the change in temperature as we go up. Barometric pressure sensors can have an altitude resolution of less than 1 meter, which is significantly better than GPS systems (about 20 meters altitude resolution). In navigation
102
applications altimeters are used to distinguish between stacked road levels for car navigation and floor levels in buildings for pedestrian navigation.
FLOW SENSING
This is the use of pressure sensors in conjunction with the venturi effect to measure flow. Differential pressure is measured between two segments of a venturi tube that have a different aperture. The pressure difference between the two segments is directly proportional to the flow rate through the venturi tube. A low pressure sensor is almost always required as the pressure difference is relatively small.
A pressure sensor may also be used to calculate the level of a fluid. This technique is commonly employed to measure the depth of a submerged body (such as a diver or submarine), or level of contents in a tank (such as in a water tower). For most practical purposes, fluid level is directly proportional to pressure. In the case of fresh water where the contents are under atmospheric pressure, 1psi = 27.7 inH20 / 1Pa = 9.81 mmH20. The basic equation for such a measurement is P=p*g*h Where , P = Pressure, P = Density of the Fluid, g = Standard Gravity, h = Height of fluid column above pressure sensor
LEAK TESTING
A pressure sensor may be used to sense the decay of pressure due to a system leak. This is commonly done by either comparison to a known leak using differential pressure, or by means of utilizing the pressure sensor to measure pressure change over time.
103
Sufficient capacities to support the equipment at your site but not more capacity than you actually will use. At every site, you want an RTU that can support your expected growth over a reasonable period of time, but its simply wasteful to spend your budget on excess capacity that you wont use.
Rugged construction and ability to withstand extremes of temperature and humidity. You know how punishing on equipment your sites can be. Keep in mind that your SCADA system needs to be the most reliable element in your facility.
Secure redundant power supply. You need your SCADA system up and working 24/7, no excuses. Your RTU should support battery power and, ideally, two power inputs.
Redundant communication ports. Network connectivity is as important to SCADA operations as a power supply. A secondary serial port or internal modem will keep your RTU online even if the LAN fails. Plus, RTUs with multiple communication ports easily support a LAN migration strategy.
Nonvolatile memory (NVRAM) for storing software and/or firmware. NVRAM retains data even when power is lost. New firmware can be easily downloaded to NVRAM storage, often over LAN so you can keep your RTUs capabilities up to date without excessive site visits.
104
Intelligent control. As I noted above, sophisticated SCADA remotes can control local systems by themselves according to programmed responses to sensor inputs. This isnt necessary for every application, but it does come in handy for some users.
Watchdog timer to ensure that the RTU restarts after a power failure.
105
106
A programmable logic controller (PLC) or programmable controller is a digital computer used for automation of electromechanical processes, such as control of machinery on factory assembly lines, amusement rides, or lighting fixtures. PLCs are used in many industries and machines. Unlike general-purpose computers, the PLC is designed for multiple inputs and output arrangements, extended temperature ranges, immunity to electrical noise, and resistance to vibration and impact. Programs to control machine operation are typically stored in batterybacked or non-volatile memory. A PLC is an example of a real time system since output results must be produced in response to input conditions within a bounded time, otherwise unintended operation will result.
11.2 PROGRAMMING
PLC programs are typically written in a special application on a personal computer, then downloaded by a direct-connection cable or over a network to the PLC. The program is stored in
107
the PLC either in battery-backed-up RAM or some other non-volatile flash memory. Often, a single PLC can be programmed to replace thousands of relays. Under the IEC 6931-3 standard, PLCs can be programmed using standards-based programming languages. A graphical programming notation called Sequential Function Charts is available on certain programmable controllers. Initially most PLCs utilized Ladder Logic Diagram Programming, a model which emulated electromechanical control panel devices (such as the contact and coils of relays) which PLCs replaced. This model remains common today. IEC 6931-3 currently defines five programming languages for programmable control systems: FBD (Function block diagram), LD (Ladder diagram), ST (Structured text, similar to the Pascal programming language), IL (Instruction list, similar to assembly language) and SFC (Sequential function chart). These techniques emphasize logical organization of operations. While the fundamental concepts of PLC programming are common to all manufacturers, differences in I/O addressing, memory organization and instruction sets mean that PLC programs are never perfectly interchangeable between different makers. Even within the same product line of a single manufacturer, different models may not be directly compatible.
FIG 11.2: PART OF A LADDER DIAGRAM, INCLUDING CONTACTS AND COILS, COMPARES, TIMERS AND MONOSTABLE MULTIVIBRATORS
108
Ladder logic is a programming language that represents a program by a graphical diagram based on the circuit diagrams of relay-based logic hardware. It is primarily used to develop software for Programmable Logic Controllers (PLCs) used in industrial control applications. The name is based on the observation that programs in this language resemble ladders, with two vertical rails and a series of horizontal rungs between them. 11.2.2 ADDITIONAL FUNCTIONALITY Additional functionality can be added to a ladder logic implementation by the PLC manufacturer as a special block. When the special block is powered, it executes code on predetermined arguments. These arguments may be displayed within the special block.
+-------+
Remote Counter
+-------+
Interior Counter
+--------+ --------------------+ A + B +----------+ into C + +--------+ In this example, the system will count the number of times that the interior and remote unlock buttons are pressed. This information will be stored in memory locations A and B. Memory location C will hold the total number of times that the door has been unlocked electronically. PLCs have many types of special blocks. They include timers, arithmetic operators and comparisons, table lookups, text processing, PID control, and filtering functions. More powerful
109
PLCs can operate on a group of internal memory locations and execute an operation on a range of addresses, for example, to simulate a physical sequential drum controller or a finite state machine. In some cases, users can define their own special blocks, which effectively are subroutines or macros. The large library of special blocks along with high speed execution has allowed use of PLCs to implement very complex automation systems.
11.3 FEATURES
FIGURE 11.3: CONTROL PANEL WITH PLC (GREY ELEMENTS IN THE CENTER). THE UNIT CONSISTS OF
SEPARATE ELEMENTS, FROM LEFT TO RIGHT; POWER SUPPLY, CONTROLLER, RELAY UNITS FOR IN- AND OUTPUT
The main difference from other computers is that PLCs are armored for severe conditions (such as dust, moisture, heat, cold) and have the facility for extensive input/output (I/O) arrangements. These connect the PLC to sensors and actuators. PLCs read limit switches, analog process variables (such as temperature and pressure), and the positions of complex positioning systems. Some use machine vision. On the actuator side, PLCs operate electric motors, pneumatic or hydraulic cylinders, magnetic relays, solenoids, or analog outputs. The input/output arrangements may be built into a simple PLC, or the PLC may have external I/O modules attached to a computer network that plugs into the PLC.
110
11.6 COMMUNICATIONS
PLCs have built in communications ports, usually 9-pin RS-232, but optionally EIA-485 or Ethernet. Modbus, BACnet or DF1 is usually included as one of the communications protocols. Other options include various fieldbuses such as DeviceNet or Profibus. Other communications protocols that may be used are listed in the List of automation protocols. Most modern PLCs can communicate over a network to some other system, such as a computer running a SCADA (Supervisory Control And Data Acquisition) system or web browser.
111
PLCs used in larger I/O systems may have peer-to-peer (P2P) communication between processors. This allows separate parts of a complex process to have individual control while allowing the subsystems to co-ordinate over the communication link. These communication links are also often used for HMI devices such as keypads or PC-type workstations.
11.7 EXAMPLES
(1) As an example, say a facility needs to store water in a tank. The water is drawn from the tank by another system, as needed, and our example system must manage the water level in the tank. Using only digital signals, the PLC has two digital inputs from float switches (Low Level and High Level). When the water level is above the switch it closes a contact and passes a signal to an input. The PLC uses a digital output to open and close the inlet valve into the tank. When the water level drops enough so that the Low Level float switch is off (down), the PLC will open the valve to let more water in. Once the water level rises enough so that the High Level switch is on (up), the PLC will shut the inlet to stop the water from overflowing. This rung is an example of seal-in (latching) logic. The output is sealed in until some condition breaks the circuit.
| | Low Level High Level | Fill Valve |
|------[/]------|------[/]----------------------(OUT)---------| | | | | | | | | | | | | |
An analog system might use a water pressure sensor or a load cell, and an adjustable (throttling) dripping out of the tank, the valve adjusts to slowly drip water back into the tank. In this system, to avoid 'flutter' adjustments that can wear out the valve, many PLCs incorporate "hysteresis" which essentially creates a "deadband" of activity. A technician adjusts this
112
deadband so the valve moves only for a significant change in rate. This will in turn minimize the motion of the valve, and reduce its wear. A real system might combine both approaches, using float switches and simple valves to prevent spills, and a rate sensor and rate valve to optimize refill rates and prevent water hammer. Backup and maintenance methods can make a real system very complicated.
(2) EXAMPLE OF A SIMPLE LADDER LOGIC PROGRAM The language itself can be seen as a set of connections between logical checkers (contacts) and actuators (coils). If a path can be traced between the left side of the rung and the output, through asserted (true or "closed") contacts, the rung is true and the output coil storage bit is asserted (1) or true. If no path can be traced, then the output is false (0) and the "coil" by analogy to electromechanical relays is considered "de-energized". The analogy between logical propositions and relay contact status is due to Claude Shannon. Ladder logic has contacts that make or break circuits to control coils. Each coil or contact corresponds to the status of a single bit in the programmable controller's memory. Unlike electromechanical relays, a ladder program can refer any number of times to the status of a single bit, equivalent to a relay with an indefinitely large number of contacts. So-called "contacts" may refer to physical ("hard") inputs to the programmable controller from physical devices such as pushbuttons and limit switches via an integrated or external input module, or may represent the status of internal storage bits which may be generated elsewhere in the program. Each rung of ladder language typically has one coil at the far right. Some manufacturers may allow more than one output coil on a rung.
--( )-- a regular coil, energized whenever its rung is closed --(\)-- a "not" coil, energized whenever its rung is open --[ ]-- A regular contact, closed whenever its corresponding coil is energized
113
The "coil" (output of a rung) may represent a physical output which operates some device connected to the programmable controller, or may represent an internal storage bit for use elsewhere in the program.
(3) Here is an example of what one rung in a ladder logic program might look like. In real life, there may be hundreds or thousands of rungs. For example: 1. ----[ ]---------|--[ ]--|------( ) X | | Y | | S
|--[ ]--| Z The above realises the function: S = X AND ( Y OR Z ) Typically, complex ladder logic is 'read' left to right and top to bottom. As each of the lines (or rungs) are evaluated the output coil of a rung may feed into the next stage of the ladder as an input. In a complex system there will be many "rungs" on a ladder, which are numbered in order of evaluation.
114
This represents a slightly more complex system for rung 2. After the first line has been evaluated, the output coil (S) is fed into rung 2, which is then evaluated and the output coil T could be fed into an output device (buzzer, light etc..) or into rung 3 on the ladder. (Note that the contact X on the second rung serves no useful purpose, as X is already defined in the 'AND' function of S from the 1st rung.) This system allows very complex logic designs to be broken down and evaluated.
115
116
12.1 OBJECTIVE
The aim of our project is to operate the pump and to achieve the control of the flow rate and pressure head developed by the pump. In the subsequent pages is shown the entire details of the construction and their functioning to achieve optimum consideration.
12.2 COMPONENTS
Water tank. Pipe assembly (nipples, union, flange, bushing, flexible pipe) Motor. Vertical 1 hp, 10 stage centrifugal pump. Nipples. Manual valve. Non return valve. Sensors (pressure transmitter, flow meter) Computer system. Programmable logic controller. Contactor base push button starter.
117
12.3 OPERATION
The following description will show the various functions performed by the parts and to accomplish these with automation the ladder diagrams are shown. This program governs the PLC and the operation is performed according to these steps:
The push button with contactor base is pushed to give a starting pulse to the motor. Now a push button is not constant value but is not continuous so a hold on the pulse is provided. If any time during operation the pump is to be shut dow then the stop push botton is pressed. Now after the pump commences to operate the sensors start reading after the first 10 seconds have passed so that the sensors read the value when the the pump is stabilized.
118
During the operation at every instant the fow and the pressure head are measured and the are compared with the required value or value range as per our requirement. The required range for the parameters controlled are:
For pressure head: 35 kg/m2 to 60 kg/ m2. For discharge/ flow rate: 50 lpm to 90 lpm.
119
Now this measured value is made to compare with the required range values. However due to various faults in the system the performance always doesnot occur in the requiredrange. If the value is between the specified range the operation is continued. If the value obtained from the sensor is less than the range value it will send to the PLC A signal to operate the motor for 10 more seconds so that the the pump is given a chance to stabilize. However, if it doesnot take place the motor is tripped and the operation ceased.
120
FIG 12.4: LADDER PROGRAMMING PART-4
In the other scenario the value occuring can be more than the range in this case the motor shall trip w/o any delay. The process shall continue to operate like this until one presses the red stop push button.
121
IMPLEMENTATION OF SCADA Pictorial representation of the entire system. Monitoring the sytem at each point. Communication with PLC. Controlling of ON and OFF of the system. Supervising the pressure and flow parameters and it also provides the analog instantaneous value. For system hazards it gives an alarm indication.
122
Component Pump & Motor Starter Pipeline Assembly Non Return Valve Ball Valve(Manual Valve) Pressure Transmitter(Sensor) Flow Meter(Sensor) Wiring Cost Programmable Logic Controller Wonder ware Intouch SCADA Software Total Costing
Cost(Approx.) in Rs. 8,000 1,250 1,250 450 270 2,350 97,000 980 40,000 23,000
1,74,550
123
13. CONCLUSION
124
13.CONCLUSION
In our endevour to achieve the automated pump control process we conclude that it has been successful to our aim. The following is project concluding status: The entire system to control the pumps pressure and discharge rate available is computerized. The pump can be switched on and off by simple buttons on the monitor of the computer. Once the pump is on the entire process control is achieved on the computer and the any deviation In the process would lead to auto tripping off of the pump. We have been successful In our endevour however we also been able to identify the purpose of this project. Such a control and monitoring system process in viable only in case of large systems as the cost incurred for small control and monitoring process is not viable. Manual labour is more beneficial at such places. However such system when applied to large processes on heavy duty floors in industries prove highly efficient and cost effective.
125