Reinforcement Check
Reinforcement Check
PRESSURE DESIGN OF PIPE TO PIPE BRANCH HEADER 6 3.404 1.920 50 122 168.3 250.3 1 0.4 0 0.64 BRANCH 6 3.404
NOMINAL BORE (INCHES) WALL THICKNESS (mm) P, DESIGN PRESSURE (N/mm2) DESIGN TEMP (OC) DESIGN TEMP (OF) D, PIPE OD (mm) ALLOWABLE STRESS, S (N/mm2) E, QUALITY FACTOR FROM TABLE 302.3.4 Y COEFFICIENT FROM TABLE 304.1.1 CORROSION ALLOWANCE (mm) PRESSURE DESIGN THICKNESS, t (mm) PD/2(SE+PY) 2
Th=
3.404
Tb=
3.404
D h=
Db=
1.920 50 122 168.3 IF PIPE < 14"THEN MANUALLY INPUT 250.3 1 0.4 0 0.64
th=
tb=
A1 (mm2) 3 4 AVAILABLE AREA WITHOUT REINFORCING PAD= A2+A3 A2 = AREA RESULTING FROM EXCESS THICKNESS IN THE RUN PIPE WALL A2 (mm2) d2 d2 d2 d2 (mm) THEREFORE A2 (mm2) 5 A3 = AREA RESULTING FROM EXCESS THICKNESS IN THE BRANCH PIPE WALL THEREFORE A3 (mm2) 2L4(Tb-tb-c)/Sin = = = (2d2-d1)(Th-th-c) "HALF WIDTH" OF REINFORCEMENT ZONE
190.0171
d1 or (Tb-c)+(Th-c)+d1/2 WHICHEVER IS THE GREATER BUT IN ANY CASE NOT MORE THAN D h = = = 228.3842 228.3842 630.4493 OR 121.0001
66.44445
6 7
REINFORCING PAD REQUIRED? REINFORCEMENT ZONE REINFORCEMENT ZONE IS A PARALLELOGRAM OF LENGTH 2d2 AND WIDTH L4 L4 = HEIGHT OF REINFORCEMENT ZONE OUTSIDE OF RUN PIPE OR = WHICHEVER IS LESS THEREFORE L4 (mm) = = =
NO
2.5(Th-c) 2.5(Tb-c)+Tr
8.51 8.51
8.51 0
A4 = AREA OF ANY OTHER METAL PROVIDED BY WELDS AND PROPERLY ATTACHED REINFORCEMENT A4 = (2d2-DbSin) x Tr 696.89375 = 367 % OF = A1 0 190.0171 YES
PRESSURE DESIGN OF PIPE TO PIPE BRANCH HEADER 6 2.9785 2.940 50 122 168.3 216 1 0.4 1.5 1.14 BRANCH 6 2.9785
NOMINAL BORE (INCHES) WALL THICKNESS (mm) P, DESIGN PRESSURE (N/mm2) DESIGN TEMP (OC) DESIGN TEMP (OF) D, PIPE OD (mm) ALLOWABLE STRESS, S (N/mm2) E, QUALITY FACTOR FROM TABLE 302.3.4 Y COEFFICIENT FROM TABLE 304.1.1 CORROSION ALLOWANCE (mm) PRESSURE DESIGN THICKNESS, t (mm) PD/2(SE+PY) 2
Th=
3.404 10530
Tb=
3.404
D h=
Db=
2.940 50 122 168.3 IF PIPE < 14"THEN MANUALLY INPUT 216 1 0.4 0 1.14
th=
tb=
A1 (mm2) 3 4 AVAILABLE AREA WITHOUT REINFORCING PAD= A2+A3 A2 = AREA RESULTING FROM EXCESS THICKNESS IN THE RUN PIPE WALL A2 (mm2) d2 d2 d2 d2 (mm) THEREFORE A2 (mm2) 5 A3 = AREA RESULTING FROM EXCESS THICKNESS IN THE BRANCH PIPE WALL THEREFORE A3 (mm2) 2L4(Tb-tb-c)/Sin = = = (2d2-d1)(Th-th-c) "HALF WIDTH" OF REINFORCEMENT ZONE
184.9367
d1 or (Tb-c)+(Th-c)+d1/2 WHICHEVER IS THE GREATER BUT IN ANY CASE NOT MORE THAN D h = = = 162.343 162.343 55.08739 OR 85.6285
13.59723
6 7
REINFORCING PAD REQUIRED? REINFORCEMENT ZONE REINFORCEMENT ZONE IS A PARALLELOGRAM OF LENGTH 2d2 AND WIDTH L4 L4 = HEIGHT OF REINFORCEMENT ZONE OUTSIDE OF RUN PIPE OR = WHICHEVER IS LESS THEREFORE L4 (mm) = = =
YES
2.5(Th-c) 2.5(Tb-c)+Tr
3.69625 7.44625
3.69625 0
A4 = AREA OF ANY OTHER METAL PROVIDED BY WELDS AND PROPERLY ATTACHED REINFORCEMENT A4 = (2d2-DbSin) x Tr 68.684616 = 37.1 % OF = A1 0 184.9367 NO