Grounding Principles The Need To Ground: European American Australian
Grounding Principles The Need To Ground: European American Australian
It is a fundamental fact that electricity ALWAYS flows to the point of lowest potential. The task is to ensure that electricity, including faults, lightning and electronic noise, flows to this point with maximum safety to people, while maintaining the reliability of equipment. Therefore we must ensure the safe, controlled flow of electricity with minimum voltage drop to earth in all cases.
Efficiently dissipate lightning surge energy that may arrive via downconductors of the lightning protection system; Efficiently dissipate electrical surges and faults to minimize the chances of injury from either "step potentials" or "touch potentials"; Provide a stable reference for electrical and RF circuits at the facility to minimize noise during normal operation; Be properly bonded to provide an equipotential plane under fault conditions; Be electrically and mechanically robust to assure performance over the "life" of the facility (nominally 40 years from construction date).
IEC 10234AS3000-IEEE Std 80 1 AS2307 IEC 61364- NFPA 70 5 (NEC) ENV 61024-1 BS 1400 BS 7430 BS6651 UL 96A CSA C22.194 NFPA 780 IEEE 837 IEEE 1100 AS 1768-
1. Personnel Safety
Avoid hazardous Step and Touch Potentials (shock) or even death by low impedance grounding and bonding between metallic equipment, chassis, piping, and other conductive objects so that currents, due to faults or lightning, do not result in hazardous voltage rise.
A direct, low impedance path to ground and bonding between electrical services, protective devices, equipment and other conductive objects so that faults or lightning currents are quickly dissipated and do not result in hazardous voltages within the building. Proper grounding also facilitates the operation of over-current protective devices.
Proper grounding aids in electrical noise reduction and ensures: 1. Minimal impedance between the signal ground points throughout the building. 2. Minimal voltage potential between interconnected equipment. 3. Minimal effect of electrical and magnetic field coupling.
STEP POTENTIAL
Step Potential is the voltage difference between a person's feet caused by the dissipation gradient of a fault entering the earth.
TOUCH POTENTIAL
Touch Potential is similar to "Step Potential" except that the fault current passes through the person's arm and torso on the way to the ground. Another function of the grounding system is to provide a reference for circuit conductors to stabilize their voltage to ground during normal operation. The earth itself is not essential to provide a reference function; another suitable inductive body may be used instead. The function of a grounding electrode system and a ground terminal is to provide a system of conductors, which ensures electrical contact with the earth.
Ground Resistance
When current flows from a ground electrode into the surrounding soil, it is often described as flowing through a series of concentric shells of increasing diameter. Each successive shell has a greater area for current flow and consequently, lower resistance. At some point distant from the earth conductor the current dissipation becomes so large and current density so small, that the resistance is negligible. In theory, the ground resistance may be derived from the general formula:
This formula illustrates why the shells of concentric earth decrease in resistance the farther they are from the ground rod:
In the case of ground resistance, uniform earth (or soil) resistivity throughout the volume is assumed, although this is seldom the case in nature. The equations for systems of electrodes are very complex and often expressed only as approximations. The most commonly used formula for single ground electrode systems, developed by Professor H. R. Dwight of the Massachusetts Institute of Technology, is the following:
R = resistance in ohms of the ground rod to the earth (or soil) L = grounding electrode length r = grounding electrode radius P= average resistivity in ohms-cm.
Soil Composition
Soil types vary in content and consistency. Black dirt or soils with high organic content, are usually good conductors because they retain higher moisture levels and have a higher electrolyte level. Sandy soils, which drain faster, have a much lower moisture content and electrolyte level. Therefore they have higher impedance. Solid rock and volcanic ash contain virtually no moisture or electrolytes and hence high levels of resistivity. Soils have generally been deposited in layers or strata. These strata can have different values of soil resistivity. By measuring the resistivity of the soil at varying depths, it is possible to develop a profile, which can be used to identify the most appropriate ground electrode design.
Moisture Content
Moisture content has the largest influence on soil resistivity because it helps chemicals in the soil that surround ground conductors carry the electric current. In general, the higher the moisture content the lower the soil's resistivity. Moisture retention can be influenced by local climate conditions and electrolytic mechanisms such as mineral content, soil ionization, consistent grain size, even distribution and packing density. Systems designed for areas which typically have very dry soil and arid climates may need to use enhancement materials or other means to achieve lower soil resistivity.
Temperature
High temperatures and drought, or temperatures below freezing and deep frosts, can cause high resistivity in soils that have much lower values in the preceding months. When moisture turns to ice, resistivity increases sharply. Areas with regular rainfall and no ground frost are more likely to have low soil resistivity, in comparison to those regions that are arid or have permafrost. In areas subject to freezing winters driving the ground rod below the frost line is necessary to maintain a low resistivity.
Where: A = distance between the electrodes in centimeters B = electrode depth in centimeters If A > 20 B, the formula becomes: p = 2 AR (with A in cm) p = 191.5 AR (with A in feet) p = Soil resistivity (ohm-cm) This value is average resistivity of the ground at a depth equivalent to the distance "A" between two electrodes.
One single ground electrode may be sufficient for an electrical installation in a built up area where the local supply authority utilizes a multiple or common multiple earth neutral (MEN or CMEN) system. However, it may not provide an adequately low impedance for lightning current injection.
This is a common option for installations where, because of rock, driving an electrode is impractical. It is not recommended for lightning protection systems as there is only one path. Very high ground voltages will be experienced at the injection point.
Since the connection to the strip is at the center, any fault/injection current travels in two directions. This layout has lower impedance, but it is generally not adequate for lightning protection systems.
Radial Grounding, Single Radials A design that is well suited to lightning protection in areas of medium resistivity. The radials can run to 100 feet in length.
Radial Grounding, Multiple Radials Crows foot design. Well suited to lightning as it allows energy to diverge as each conductor takes a share of the current, offering a lower impedance. Voltage gradients leading away from the injection point will be lower, reducing danger from step potentials.
Equipotential Mesh Electrodes Minimize the risk of step and touch potential hazard by positioning a mat and bonding it to the structure or operating handle at locations where personnel may be required to operate switchgear or stand in the course of their duties. Low ground impedance.
Grid with Ground Rods It may be advantageous to add ground rods to the grid. In doing so, it may be possible to access a low resistivity soil layer. Care must be taken to ensure each ground rod is spaced at least twice the installation depth.
Ring Electrode Installations, including communications huts, pad mount transformers and fences surrounding high voltage installations, are generally surrounded by a ground ring. This practice also reduces the hazard of step and touch potential.