Over Current Protection Annex
Over Current Protection Annex
Annex
(by Dominik Pieniazek, P.E. VI Engineering, LLC)
51 50
51 50
Residual CT connection
ia+ib+ic Ia Ib Ic 51 G
51
Zero sequence q CT
Basic Guides for Protective Relay Settings Suggested Rules of Thumb for MV Equipment Transformers Bus Feeders Motors Capacitors
Primary Phase Settings CT Ratio: 200% FLA Set pickup to comply with NEC 450-3, but as a rule of thumb setting should be less than 300% of transformer self cooled rating or 150% of transformer maximum rating. Try to set the time dial such that pickup time for maximum through fault is in the neighborhood of 1.0 seconds or less. If higher, ensure that ANSI d damage points i t are not t exceeded. d d Set instantaneous at between 160% and 200% of maximum through fault (assume infinite bus). Ensure that available system short circuit allows this. Time Dial set at 1.0 to 1.5 seconds at maximum fault. Do not exceed 2.0 seconds which is the mechanical damage point.
Primary Ground Settings Set 50G if primary winding is delta connected connected. Provide time delay (approx 20 msec) when setting digital relays with zero sequence CTs. No time delay when using elecro-mechanical relays with zero sequence CTs. CT considerations: Residually connected neutral. CT mismatch and residual magnetization will not allow the most sensitive setting. Recommend to delay above inrush. CT. Care must be taken to ensure that cables are Zero sequence CT properly placed and cable shields are properly terminated.
ia ib ic 51 50 ia+ib+ic i ib i ia+ib+ic 50 N Ia Ib Ic 50 G
Ia Ib Ic
Residual CT connection
Zero sequence CT
Primary Fuse Rating of power transformer: 135% FLA < Fuse < 250% FLA FLA. Try to stay in the range of 150% 150%. Primary fuse rating of power transformer should be approximately 200% FLA if transformer has a secondary main. Generally use E-rated fuses. Note that TOC characteristics of fuses are not all the same.
Secondary Low-Resistance Grounded Set pickup for 20% to 50% of maximum ground fault. Note that ground resistors typically have a continuous rating of 25-50% of nominal. This value can be specified when purchasing the equipment equipment. Example: 2000 A main breaker (2000:5 CTs), it may make sense to specify an 400 A ground resistor with a continuous rating of 50% (200 A) such that a 2000:5 residually connected CT input can be used with a minimum pickup (0.1 x CT = 0.5 A secondary, 200 A primary). 2 0 seconds at maximum Set the time dial such that at the time to trip is 2.0 ground fault I t curve. curve Typical resistor is rated for 10 seconds at Protect resistor using It nominal current (to be specified at time of order).
Secondary Solidly Grounded (for balanced three phase industrial loads) If secondary is solidly grounded and neutral relay is available (using CT on X0 bushing), bushing) set pickup at approximately 50% of phase element and ensure transformer 2 second damage point is protected. Coordinate TOC with main breaker (or partial differential) ground relay. Decrease the primary phase element by 58% (to account for transformer damage curve shift). This is the equivalent current seen on the primary (delta) for a secondary ground fault (refer to the Symmetrical Components presentation t ti on Feb F b 2-3, 2 3 2010 b by D Dr. K Kurt t Ed Ederhoff). h ff)
50T 51T
Phase-Gnd
51 NT
51 Main
51 N
Primary P i Side Sid Wye-Grounded W G d d Transformer T f If primary is solidly grounded and neutral relay is available, set pickup at approximately 50% of phase element. This must coordinate with upstream line p protection devices ( (i.e. 21P, , 21G, , 67, , 67G ). ) If its at the utility y level, , they will review and provide settings. generator step-up p p transformers ( (GSU), ), the HV 51NT should typically yp y be the For g last device to trip for upstream ground faults. Ensure that the GSU damage curve and the H0 grounding conductor is protected.
51B
For a fault F f lt between b t the th transformer and main breaker, the partial differential bus relays will not detect current (other than motor contribution).
Trip Dire ection 67
67
N.C.
51B
Set 67 pickup at 40% of transformer FLA. Coordinate with time curve with 50T/51T
Both transformer primar primary overcurrent relays will detect see the same current. A directional overcurrent relay is required to prevent tripping of both transformers via 50T/51T.
51M 51 Tie
51M
For a fault between the transformer and main breaker, the main and tie breaker relays will all see the same current (other than motor contribution).
Trip Directio on
67
N.C.
67
The tie Th ti breaker b k will ill t trip i f followed ll d by the respective transformer primary overcurrent. A directional overcurrent relay y is required q to prevent loss of one bus.
Trip Direction n
Set 67 pickup at 40% of transformer FLA. Coordinate with time curve with 51Tie
Instantaneous Trip p set at 200% LRC. A higher g p pickup p may y be used depending p g on system y available short circuit, however, do not lower below 160% LRC unless you know that the relay filters/removes the DC component. Ensure that the instantaneous trip setting will not cause a motor starter to attempt interrupting p g a fault beyond y its rating. g Ground Overcurrent. For Zero Sequence CT (BYZ) set ground Trip at 10A primary and Alarm at 5A primary. Set for instantaneous if using electromechanical and set at 20 msec delay y( (minimum) ) if using g digital g relays. y For solidly grounded systems, ensure that the ground trip setting will not cause a motor starter to attempt interrupting a fault beyond its rating. Mechanical Jam set 150% FLA at 2 sec, unless application pp does not allow this ( (i.e. g grinder, crusher, etc).
R Recommended d d References R f
Recommended References
Applied Protective Relaying Westinghouse Protective P t ti Relaying R l i Theory Th and d Applications A li ti ABB Power P T&D Company, C Edited Edit d b by W Walter lt El Elmore Protective Relaying for Power Systems IEEE Press, Edited by Stanley H. Horowitz Protective Relaying y g for Power Systems y II IEEE Press, , Edited by y Stanley y H. Horowitz Protective Relaying, Principles and Applications J. Lewis Blackburn AC Motor Protection Stanley E. Zocholl Industrial and Commercial Power System Applications Series ABB Power T&D Company Analyzing and Applying Current Transformers - Stanley E. Zocholl