Cahier Technique No 196: Integration of Local Power Generation in Industrial Sites and Commercial Buildings
Cahier Technique No 196: Integration of Local Power Generation in Industrial Sites and Commercial Buildings
T. Hazel
"Cahiers Techniques" is a collection of documents intended for engineers and technicians, people in the industry who are looking for more in-depth information in order to complement that given in product catalogues. Furthermore, these "Cahiers Techniques" are often considered as helpful "tools" for training courses. They provide knowledge on new technical and technological developments in the electrotechnical field and electronics. They also provide better understanding of various phenomena observed in electrical installations, systems and equipments. Each "Cahier Technique" provides an in-depth study of a precise subject in the fields of electrical networks, protection devices, monitoring and control and industrial automation systems. The latest publications can be downloaded from the Schneider Electric internet web site. Code: http://www.schneider-electric.com Section: Experts' place Please contact your Schneider Electric representative if you want either a "Cahier Technique" or the list of available titles. The "Cahiers Techniques" collection is part of the Schneider Electrics "Collection technique".
Foreword The author disclaims all responsibility subsequent to incorrect use of information or diagrams reproduced in this document, and cannot be held responsible for any errors or oversights, or for the consequences of using information and diagrams contained in this document. Reproduction of all or part of a "Cahier Technique" is authorised with the prior consent of the Scientific and Technical Division. The statement "Extracted from Schneider Electric "Cahier Technique" no. ....." (please specify) is compulsory.
no. 196
Integration of local power generation in industrial sites and commercial buildings
Terence HAZEL Terry Hazel received his BSc in Electrical Engineering from the University of Manitoba Canada in 1970. He then worked in Perth Australia for a year as power coordination engineer, and in Frankfurt Germany as a consulting engineer until he joined Merlin Gerin in 1980. For 15 years was the technical team leader for several major international projects involving process control and power distribution. He has since been with the tendering section of the industrial projects department and often meets with clients during the front end engineering stage to discuss and compare the various possible electrical distribution systems. He is an active member of IEEE and has presented papers dealing with electrical power distribution at Industry Applications Society conferences.
Lexicon
Black start: The capability of starting generator sets without the presence of a utility supply. Damage curve: A current-versus-time curve showing the allowable limit without permanent damage to equipment. Equipment commissioning: Performance of the testing and adjustment at site leading up to and including the energization of a piece of equipment. An example would be the operation of one generator set. Frequency droop: The absolute change in frequency between steady state no load and steady state full load, typically 4%. An increase in power output results in a decrease of frequency for generator sets operating alone in this mode. Isochronous speed governing: Governing with steady-state speed regulation of essentially zero magnitude. Load sharing: Centralized elaboration and sending of set points for generator set loading. This ensures that all sets will share the load in an equal manner proportional to their power rating. Load shedding: Voluntary disconnection of low priority loads when the available power is insufficient to supply the total plant load. Residual voltage: The voltage on a busbar after disconnection from the supply. This voltage is generated by rotating machines which remain connected to the busbar. Spinning reserve: The difference between the total available capacity of all generating sets already coupled to the system and their actual loading. Static switch: A fast acting switch normally consisting of a power electronics device which will transfer the load from the power conversion module of a UPS to another supply without delay or unacceptable transients. Synchronism-check relay: A verification relay whose function is to operate when two input voltage phasors are within predetermined limits. Synchroscope: An instrument embodying a
continuously rotatable element whose position is a measure of the instantaneous phase difference between the voltages across a circuit-breaker. System commissioning: Performance of additional testing and adjustments at site of equipment which have been commissioned to ensure correct operation of the system comprised of the equipment. An example would be the parallel operation of several generating sets including synchronizing, and load shedding features. System stability: A system is considered stable if bounded input disturbances result in bounded output disturbances. For an electrical distribution system, changes in load, faults, switching operation, etc. will not cause wide fluctuations in voltage or frequency if it is stable. Unit substations: A substation containing the electrical distribution equipment necessary for supplying the loads of a particular plant production unit. It typically contains medium voltage switchgear, power and distribution transformers, low voltage switchgear and MCC. Voltage restrained overcurrent relay: An overcurrent protection relay having a voltage input which opposes the typical response of the relay to the current inputs. This is used for generators since they deliver much lower shortcircuit currents than utility connections having the same capacity. Voltage waveform distortion: The difference between the actual voltage waveform and a pure sinusoidal waveform, often expressed as total harmonic distortion,
THD = 2 Uh U1
where Uh is the harmonic voltage and U1 is the fundamental of the voltage waveform. X/R ratio: The ratio of the electrical distribution system inductance to the resistance. This ratio determines the time constant of the d.c. component of the short-circuit current which is an important factor in defining the rating of highvoltage circuit-breakers.
Contents
1 Types of engine generator sets 2 Rated power for generator set applications 3 Typical applications 4 Operation of generator sets 3.1 Stand-by generator sets 3.2 Production generator sets 4.1 Starting and stopping of generator sets 4.2 Stand alone operation 4.3 Parallel operation with utility supply 4.4 Parallel operation with other generator sets 5 Transfer schemes and synchronization 5.1 Automatic transfer on loss of supply 5.2 Maintenance transfer 5.3 Synchronization of generator circuit-breaker 5.4 Synchronization of bus-tie, bus coupler, or utility incoming circuit-breakers 6 Generator set protection 6.1 General protection philosophy 6.2 Electrical protection 6.3 Machine protection 7 Connection of generators to electrical network 8 Load shedding 9 Interfacing generator with electrical distribution system 9.1 Typical split of supply between generator set manufacturer and switchgear manufacturer 9.2 Information to be exchanged 9.3 Integration of generator set into electrical distribution supervisory system 10 Installation of engine generator sets 10.1 Location 10.2 Air intake and exhaust 10.3 Compliance with local regulations 10.4 Special tools and spare parts 11 Conclusion Bibliography 7.1 Connection to generator circuit-breaker 7.2 Connection of generator neutral point p. 4 p. 5 p.7 p. 9 p. 11 p. 12 p. 12 p. 12 p. 14 p. 14 p. 14 p. 15 p. 16 p. 17 p. 18 p. 19 p. 19 p. 20 p. 21 p. 21 p. 22 p. 23 p. 23 p. 23 p. 24 p. 24 p. 24
The main types of prime movers used in engine driven generator sets for industrial sites and commercial buildings are Diesel engines, gas turbines, and steam turbines. Turbines are used mainly for production sets whereas Diesel engines can be used for both production and standby sets. Most of the topics covered in this cahier technique are not dependant on the type of
prime mover used, and therefore the general term generator set will be used. The choice of the prime mover is determined by such considerations as the availability and type of fuel and is not covered in this cahier technique. Since Diesel engines are very often used some specific information about Diesel generator sets will be given.
Above is an example of a combined oil treatment and power plant. It incorporates two gas turbine generator sets with an output of approx. 100 MW.
(Courtesy of GE Energy Products France S.A.).
In most industrial plants, however, power generation is not the main purpose. The plant may have one or several Diesel generator units to produce the necessary electrical power, mainly for stand-by, and possibly for local consumption requirements. The picture shows a 1 MW Diesel generator unit.
(Courtesy of Houvenaghel/Hennequin S.A.).
The power output requirement for the generator set is probably the most important criterion to be defined. The output of a generator set is typically
Active power axis Under-excited machine Over-excited machine Normal operation point, cos = 0.8 Stator current limit Rated engine power
Pn
Excitation current limit Stability limit
Qn
The active power output depends on the type of fuel used, and on site conditions including ambient temperature, cooling medium temperature, altitude, and relative humidity. It also depends on load characteristics such as possible overloading and load variations over time. The ISO 3046-1 standard for Diesel engines defines three different types of power ratings, and a standard definition of overload capability. The different power ratings are: c continuous power rating: The engine can supply 100% rated power for an unlimited time. This rating is normally used for production sets. c prime power rating: The engine can supply a base load for an unlimited time, and 100% rated power for a limited time. The base load and acceptable time for 100% rated power are different for each manufacturer. Typical values are a base load of 70% of the rated power, and 100% rated power during 500 hours per year.
c standby power rating: This is the maximum power that the engine can deliver and is limited in time, typically less than 500 hours per year. This rating should only be applied to generator sets which are used exclusively for emergency power. Since the engine is incapable of supplying more power, a security factor of at least 10% should be used when defining the standby power rating. The standard overload capacity is defined as 10% more power during 1 hour for every 12 hours of operation. There is no overload capacity with a standby power rating. Most manufacturers allow the standard overload capacity with the continuous power rating and the prime power rating, but since there are exceptions, the overload capacity should always be specified together with the type of power rating used. A typical example is a Diesel engine having a continuous power rating of 1550 kW, a prime power rating of 1760 kW, and a standby power rating of 1880 kW.
When generator sets are used as a prime source of electrical energy the following points should be considered: c provide for parallel operation with other sets and/or with utility, c allow for long maintenance periods (overhaul), c ensure black-start capabilities, c use low speed equipment for long life (maximum 750 rpm for Diesel engines). When used as a standby source: c ensure quick and reliable start-up and loading, c implement reliable load shedding to avoid overloading or stalling, c allow for periodic testing under load, c provide for parallel operation with utility if set is used during peak loads, c supply magnetizing current for distribution transformers. One common application for standby generators is to supply UPS (uninterrupted power supply) equipment during power outages. Since the
generator has a relatively high impedance as compared to a utility supply, voltage waveform distortion can occur due to harmonic currents generated by the UPS. Generator manufacturers normally derate their machines by up to 60% to ensure correct voltage waveforms when loads are UPS equipment without harmonic current filtering. The engine must also be able to supply the power absorbed by the UPS which is determined by P= UPS output kW + battery recharge kW + auxil. load UPS efficiency
For preliminary generator set sizing where detailed UPS information is unavailable, the battery charger kW can be estimated to be 25% of the UPS output kW, and the UPS efficiency can be estimated to be 90%. Final determination of the generator set should be based on specified values of acceptable voltage distortion, and the actual UPS data such as efficiency, and harmonic currents.
3 Typical applications
G
Q1 Q3 Q2
Normal loads
~~
Static switch UPS
Emergency loads
Critical loads
For large industrial sites a centralized emergency power supply system as shown in figure 4 is often used. The main emergency switchboard is normally supplied from the utility, although in some sites
one of the generator sets may be in constant operation. The emergency switchboard is designed to allow generator sets to operate in parallel and also to be connected to the utility supply.
33 kV
G
6 kV
Essential loads
Normal loads
Essential loads
Typical unit substation - medium voltage switchboard (ATS: Automatic transfer system)
The automatic transfer from the utility to the emergency supply is performed in each unit substation. Since the emergency switchboard is normally energized, fast transfers (described in section 5.1) without loss of plant load can be used. The use of a centralized emergency supply has the following advantages:
c fewer generator sets for the site (normally maximum of 2), c permanently energized emergency supply allowing fast transfer schemes to be used, c no loss of emergency supply due to maintenance of one generator set. Generator sets for such systems are normally in the 1-4 MW range.
To other substations
To other substations
Earthing transformer
For example the highest load factor for N = 6 will be 80%. Bus-tie circuit-breakers are often used for maintenance purposes. During normal plant operation all bus-tie circuit-breakers are normally closed. Short-circuit calculations should always take operation with N generators into account since it is normal to connect standby sets prior to switching off sets for maintenance. A power supply using local generation is generally much weaker than a utility supply and therefore it is probable that load shedding will be required to maintain system stability during fault conditions. Determination of how much load must be shed requires dynamic simulation of the network for different fault conditions such as a loss of a generator or a short-circuit. Prior to the study it is
necessary to determine which operating configurations are to be considered. Operating conditions with the bus-tie circuit-breaker both in the open and the closed positions will greatly increase the complexity of the load shedding system since each busbar can be operated independently and will require specific load shedding criteria. For most plants it is recommended that only the standard operating configuration be used for the dynamic simulations and definition of the load shedding strategy. Figure 5 shows each generator having its own transformer. The use of generator transformers has several advantages: c provides flexibility in the choice of generator voltage, c reduces peak short-circuit current at main board, c allows use of high impedance generator grounding (reduces possible damage to generator).
Governer kW sharing and frequency regulation kvar sharing and voltage regulation G G Excitation regulator G
Load
push buttons to provide the voltage and speed adjustment signals. A synchroscope will let the operator know when the line and generator voltages are sufficiently in phase to close the circuit-breaker. For manual synchronization use of a synchronism check protection relay is recommended which will
inhibit closing of the circuit-breaker unless all conditions of frequency, voltage, and phase angle have been satisfied. Synchronization across the generator circuitbreaker is often included as a standard feature in generator set control equipment.
25
51
67
a
64F
46
49
51
32P
32Q
51V
Typical setting 0.75 Un, T 3 s T > longest time of 51, 51V, 67 1-5 % for turbine, 5-20 % for Diesel, T = 2 s 0.3 Sn, T = 2 s 0.15 In, inverse time curve 80% thermal capacity = alarm 120% thermal capacity = trip time constant 20 min operating time constant 40 min standstill 1.5 In, 2 s 10 A, 1 s 1.5 In, T= 2.5 s 1.1 Un, 2 s Overfrequency: 1.05 Fn, 2 s Underfrequency: 0.95 Fn, 2 s 5 % In In, 0.5 s Is0 10 % of earth-fault current, 0.5 s Frequency < 1 Hz, Voltage < 5 %, Phase angle <10 120 C 10 A, 0.1 s
Action General shut-down General shut-down General shut-down General shut-down Trip breaker only, overload may be temporary
General shut-down General shut-down General shut-down General shut-down General shut-down General shut-down General shut-down General shut-down Inhibit closing during synchronization Trip breaker only, overload may be temporary General shut-down General shut-down without lockout
Particularities of generator short-circuit currents As shown in the above table, it is the duty of the generator circuit-breaker to effectively isolate the generator from the network. Due to the low values of transient and permanent short-circuit currents, care must be taken in the choice and setting of the protection relays. In addition, in order to reduce losses in the generator, generator stator resistance is normally kept low by the manufacturers. This will result in high X/R ratios which cause generator short-circuit currents to have a d.c. component with a long time constant. The IEC 60056 defines test conditions for medium-voltage circuit-breakers. The test conditions are based on short-circuit currents having a d.c. component with a time constant of 45 ms. Since generator short-circuit currents may have time constants greatly exceeding this value, the circuit-breaker manufacturer must
choose the adequate circuit-breaker and demonstrate that it is suitable for the application. Possible delaying of circuit-breakers In addition to the significant d.c. component, the generator short-circuit current can also have zero-axis crossings which occur only after several periods resulting in unsuccessful interruption of the short-circuit current as shown in figure 9. This is due to the alternating component of the short-circuit current decreasing much more rapidly than the d.c. component. Since medium-voltage circuit-breakers require natural zero-axis crossing of the short-circuit current for successful interruption, it may be necessary to delay operation of the circuitbreaker until such time as zero-axis crossings do occur. Such delays must be taken into account in the protection relay coordination study and can also reduce the system stability.
Fault current
Fig. 9: generator short-circuit current with delayed zero-axis crossing on phases 1 & 3 (phase 2 interrupts correctly since short-circuit occurs here when voltage is at its peak on this phase, consequently short-circuit current, with 90 lag, starts at zero, without dc component).
8 Load shedding
Load shedding is often required in order to ensure that the essential parts of the process are supplied with electrical energy during high load conditions, or when system disturbances occur. Since the only additional energy available in an electrical distribution system is the spinning reserve of rotating machinery, sites supplied by generator sets only have very limited reserves and are very susceptible to instability due to disturbances such as faults in the electrical distribution system. Three different scenarios requiring load shedding can be considered: c gradual increase in load c loss of a generator c electrical faults To ensure a reliable electrical supply to essential process equipment, each of the above cases must be studied to ensure that correct load shedding is implemented. In general the load shedding system must continually check the balance between the load and the available power in order to switch off non-essential loads required to maintain system stability. The effects and remedial measures for each scenario are described below. Gradual increase in load It is possible during certain periods that the total load exceeds the rated power of the generator sets. Due to the overload capacity of 10% for one hour normally provided with production sets, and the gradual increase of load, the load shedding system can perform all calculations in real time and generate load shedding signals to trip non-essential loads. The operators can switch the non-essential loads back on after the peak period has passed.
Loss of a generator The loss of a generator can suddenly result in the available power being much less than the load. It is necessary to shed non-essential loads immediately in order to ensure the stability of the electrical distribution system. If this is not done, other generators will be tripped due to overload, undervoltage or underfrequency and the whole electrical supply could be lost. The load shedding system normally prepares load shedding tables based on the scenario of loss of a generator so that when such an incident does occur, it can immediately send the trip signals. Load shedding can be achieved in less than 200 ms which is normally sufficient to prevent loss of system stability which could lead to a complete loss of the distribution system. Electrical faults When an electrical fault occurs, protection relays will detect the fault and circuit-breakers will isolate the faulty equipment. During the time required to eliminate the fault, the voltage at the fault can be very close to zero which can cause all the motors in the plant to decelerate. After the fault has been cleared, the motors will draw more current since they must be brought back up to speed. This can further reduce the voltage in certain portions of the network causing a snowball effect which can lead to tripping of circuit-breakers supplying healthy portions of the distribution system. In order to prevent such a loss of stability, load shedding based on voltage and/or frequency should be implemented. In order to determine how much load should be shed, and at what value of voltage or frequency, a stability study of the electrical distribution system is required. This study will modelize the dynamic response of the system to disturbances and enable the load shedding strategy to be prepared.
9.1 Typical split of supply between generator set manufacturer and switchgear manufacturer
It is very common for the generator set to be supplied by a different company than the company which supplied the switchgear to which it is connected. It is therefore beneficial for all parties to reduce the interfaces between the equipment to a minimum. A coordination meeting between the switchgear and generator set suppliers should be held prior to any detailed engineering. During this meeting the split of works, interfaces, information to be exchanged, and schedule should be determined. Correct definition should allow each supplier to do engineering, manufacturing, erection, testing, and equipment commissioning at site in an independent manner. System commissioning can then be done by both parties after all interfaces have been made. Keeping interfaces simple also enables each manufacturers responsibility to be clearly defined. Each supplier should be responsible for the installation of all equipment in his supply. Installing components supplied by one manufacturer in equipment supplied by the other should be avoided. A typical example is the generator excitation module which should be installed in a panel supplied by the generator manufacturer, and not in the switchgear. When generators can operate in parallel it is necessary to install protection gear in the switchgear for eliminating faults occurring between the generator and the switchgear. This protection gear should be in the switchgear manufacturers scope. Protection gear for the generator itself can be supplied either by the generator set manufacturer, or the switchgear manufacturer. Either solution is acceptable, and both require exchanges of information since equipment data for setting the relays will come from the generator set manufacturer, whereas information for the integration into the overall plant protection scheme will come from the switchgear manufacturer. When generator differential protection is used, it is quite common for the line-side current transformer to be installed in the switchgear and the neutral side current transformer to be installed in the generator neutral connection box. The supplier of the differential protection relay should define the characteristics of the line and neutral current transformers and each manufacturer should supply the current transformer to be installed in his equipment. It is not necessary nor for reasons mentioned previously is it desirable that one manufacturer supply the current transformers to be installed in the other manufacturers equipment. The auxiliary supplies for the generator set should be independent of those of the switchgear. The generator set should have its own battery backed d.c. supply.
This type of interfacing enables each supplier to design, manufacture, and test his equipment independently. Data exchanged directly via serial links should be avoided since this is much more difficult to define, commission, and trouble shoot. The amount of information to be exchanged does not justify this type of interface. The information typically exchanged is: c information from generator set: v ready to start (information) v ready for loading (information) v trip on fault (order)
v general alarm (information) v generator voltage (from voltage transformer, for synchronizing) c information to generator set: v start (order) v circuit-breaker on/off status (information) v busbar voltage (from voltage transformer, for synchronizing) v stand-alone operation, or parallel operation (information) v type of fault (information)
The installation of generator sets requires close cooperation among several disciplines such as electrical, construction, process, and mechanical.
The following information should be considered when designing the installation of the sets.
10.1 Location
The location should be chosen close to the load center to reduce voltage drop and losses in the connections. Due to the relatively large size of the equipment, adequate space must be allowed for the transportation to and from the location. The building housing the equipment must have adequate space to allow maintenance including overhauling, and be provided with the necessary overhead cranes. The generator set manufacturer should provide all information concerning space and access requirements on civil works guide drawings. In many locations noise emission will be a problem. The solution consists in sound proofing the generator set, the building, or a combination of both. Sound proofing will have a significant impact on cost and therefore must be defined prior to placing an order for equipment. Care must also be taken to avoid noise transmission via the generator set base.
11 Conclusion
Engine driven alternating current generating sets are often installed in industrial sites and commercial buildings as main sources of electrical energy or for supplying essential loads in case of loss of the utility supply. A good understanding of the electrical and mechanical characteristics of the generator sets and the standards which define them is important for correct choice of the equipment. The integration of the generator sets into the electrical distribution system has a large impact on most of the electrical equipment. The generators will contribute to the maximum available short-circuit current which must be taken into account in dimensioning the switchgear. The plant electrical protection
system must take into account the particularities of generators in order to ensure correct protection of persons and equipment but at the same time avoid nuisance tripping which results in loss of the supply of electrical power. The control system must enable the electrical distribution system to be operated in different configurations required for ensuring a reliable supply of power. The engineer responsible for the correct design of the complete electrical distribution system is confronted with many different types of problems to solve. Being aware of the problems and knowing typical solutions to them is the first step in ensuring that the final electrical distribution system will meet the requirements of the application.
Bibliography
Standards c IEC 60056: High voltage alternating current circuit breakers. c IEC 60255: Electrical relays. c IEC 60298: A.C. metal enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV. c IEC 60439-1: Low-voltage switchgear and controlgear assemblies. c ISO 3046: Reciprocating internal combustion engines. c ISO 8528: Reciprocating internal combustion engine driven alternating current generating sets.
Schneider Electric Cahiers Techniques c Electrical disturbances in LV Cahier Technique no. 141 R. CALVAS c Active harmonic conditioners and unity power factor rectifiers Cahier Technique no. 183 E. BETTEGA, J-N. FIORINA c Disjoncteurs au SF6 Fluarc et protection des moteurs MT Cahier Technique n 143 J. HENNEBERT et D. GIBBSo
Schneider Electric
Direction Scientifique et Technique, Service Communication Technique F-38050 Grenoble cedex 9 Fax : (33) 04 76 57 98 60
Real.: AK Edition: Schneider Electric Printing: Imprimerie du Pont de Claix - Claix - France - 1000 - 100 FF 01-00
34724