Uponor Control System Installation Operation Manual
Uponor Control System Installation Operation Manual
Uponor Control System Radio Installation Manual Controller and Thermostats, UK, IRL
9416-054-10 / IOM- V_07-02
In keeping with our policy of continuous improvement and development, Uponor reserves the right to change specifications without prior notice.
U p onor Hou si ng Solu t ions Lt d. S n a peth or pe Hous e R u g by Road L u t ter w or th Le i ces ter s hi re L E 17 4 HN U p onor Centra l Eu ro pe P O B ox 1 6 4 1 (In dus trie st ra sse 56) D - 9 7 4 3 3 Has s fu r t U p onor N ordi c P O B ox 1 0 1 S E - 7 3 0 6 1 Vi r s bo H S South, West A re a m anag em ent Upo nor Hi s pan i a S . A.U. Calle C, n 24 Po l gono Indus tr i al n 1 E - 28 9 3 8 M s tol es (M a drid) U p onor Cor pora ti on Ro ber t Huber i n ti e 3 b P. O. Box 3 7 F I - 01 5 1 1 VAN TAA
T F W E
+44 ( 0) 1 4 5 5 5 5 0 3 5 5 +44 ( 0) 1 4 5 5 5 5 0 3 6 6 w w w.up o no rho us in g s o lutio ns .co .uk hse nqu irie s @ u p o no r.co .uk
T F
Table of contents
1. General recommendations and explanations .................................................................................................... 4 2. The Uponor Control System .............................................................................................................................. 5 2.1 Example of a system...................................................................................................................................... 5 2.2 Uponor Control System components................................................................................................................. 5 3. Installation ....................................................................................................................................................... 6 3.1 Preparation before installation ......................................................................................................................... 6 3.2 Installation of the components ........................................................................................................................ 6 3.2.1 Mounting the antenna............................................................................................................................ 6 3.2.2 Mounting the controller.......................................................................................................................... 7 3.3 Connections.................................................................................................................................................. 8 3.3.1 Controller description ............................................................................................................................ 8 3.3.2 Connecting the antenna to the controller.................................................................................................. 8 3.3.3 Connecting the actuators to the controller ................................................................................................ 8 3.3.4 Installation of the options ...................................................................................................................... 8 3.3.5 Connecting the controller to the mains................................................................................................... 10 3.4 Room thermostats ....................................................................................................................................... 10 3.4.1 Mark room thermostats ....................................................................................................................... 11 3.4.2 Insert batteries................................................................................................................................... 11 3.4.3 Register room thermostats ................................................................................................................... 11 3.4.4 Mount the room thermostats ................................................................................................................ 12 3.4.5 Thermostat setup................................................................................................................................ 14 3.4.6 Mark the external sensor thermostats .................................................................................................... 14 3.4.7 Insert batteries................................................................................................................................... 14 3.4.8 Connect the sensor and put switch on right position ................................................................................ 14 3.4.9 Register external sensor thermostats..................................................................................................... 14 3.4.10 Cancelling the registration of a channel ................................................................................................ 14 3.4.11 Mount external sensor thermostats...................................................................................................... 14 3.4.12 Set min and max temperature for floor sensor ...................................................................................... 14 3.4.13 Close the thermostats........................................................................................................................ 14 3.4.14 Carry out communication test ............................................................................................................. 14 3.5 External sensor thermostats ......................................................................................................................... 14 3.5.1 Introduction ....................................................................................................................................... 14 3.5.2 Registration and marking ..................................................................................................................... 14 3.5.3 Wiring ............................................................................................................................................... 15 3.5.4 Floor sensor setting............................................................................................................................. 15 3.5.5 Finishing the registration of the thermostats ........................................................................................... 15 3.6 Testing the communication between the thermostats and the controller .............................................................. 16 3.6.1 Testing the communication between the room thermostats and the controller ............................................. 16 3.6.2 Testing the communication between the external sensor thermostats and the controller ............................... 16 3.7 Finishing the installation ............................................................................................................................... 16 3.8 Actuators test ............................................................................................................................................. 16 3.9 Resetting.................................................................................................................................................... 17 3.9.1 Cancelling the registration of a channel.................................................................................................. 17 3.9.2 Resetting the system........................................................................................................................... 17 4. 5. 6. 7. Troubleshooting ............................................................................................................................................. 18 Installation report ...................................................................................................................................fold-out Technical data .........................................................................................................................................fold-out Wiring diagram / Controller description ..................................................................................................fold-out
Power supply WARNING The Uponor Control System uses a 230VAC 50Hz power supply. In case of emergency, immediately disconnect the plug from the 230V mains. Do not use water to clean the Uponor Control System. Do not expose the Uponor Control System to flammable vapors or gases.
CAUTION Important note on functionality. Non observance of this note may cause malfunctions. Information. Important operating advice and information. See another document.
The Uponor Control System uses radio waves. The frequency used is reserved for similar applications and the chances of interference from other radio sources is very low. However, in some rare special cases, it may not be possible to establish a perfect communication. The transmission range is sufficient for most applications, but each building has different obstacles affecting communication and maximum transmission distance. If communication trouble exists, Uponor can support the system with accessories, such as repeaters, for solving the exceptional problems.
99
Technical constraints Keep installation/data cables away from power cables > 50V to avoid interference. The electrical circuits of the boiler and the pump must be protected by a maximum 6A circuit-breaker.
Result of an action. Press button. LED off. LED on. LED blinks. LED flickers.
>
Underfloor Heating
2.2
2.1
Example of a system
Item
Description Thermostat Display T-75 Fastening screws Batteries Table stand Wall bracket Fastening screws Adhesive strip Thermostat T-55
1 2 3
4 5 2 6
Mark
Description Thermostat Display T-75 Thermostat T-55 Thermostat Public T-53: This thermostats can be used as a room thermostat or for a floor sensor. Thermostat Public T-53 with floor sensor Controller C-55 Antenna for Controller C-55 The floor sensor can be used for maximum or minimum limitation of the floor temperature, regardless of the room temperature. Uponor Controller C-55 Uponor Thermostat Public T-53 Uponor Thermostat T-55
1 2 3 4 5 6
7 2 3 8 2 3 9 2 10 11 12 13 6 6
Bag with fastening screws and adhesive strip Batteries Thermostat Public T-53 Bag with fastening screws and adhesive strip Batteries Controller C-55
6 adhesive strip
Antenna
Connection cable for antenna, length 0.3 m Connection cable for antenna, length 3 m Installation and Operation Manual Floor sensor Instruction (for floor sensor)
14 15
3. Installation
Installation steps Uponor recommends that you follow the steps described below to guarantee the best possible installation:
3.2
3.2.1
Description 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Preparation before installation Installation of controller and antenna Connection of components to controller (Actuators, pump, H/C relay) Registrations and mounting of room thermostats Registrations and mounting of external sensor thermostats Testing the communication between the thermostats and the controller Finishing the installation
Decide if the antenna are to be mounted on the back of the controller or on the wall.
3.1
Before beginning the installation: Verify the contents of the package with the list shown in Section 2 to make sure you have all the necessary components; Check whether a floor sensor has been mounted; Study the wiring diagram in the fold-out or inside the controller cover. Clip the antenna at the back of a controller
STOP
If the controller is installed inside a metal cabinet, the end of the antenna or the whole antenna must be outside the cabinet.
Study the drawings of the underfloor heating system. If the locations of the controllers and thermostats are not specified, determine the best positions: A controller with antenna should be installed close to each manifold; A power outlet is required for the connection of the controller to the mains; The mounting locations for the Uponor Control System must be protected from running and dripping water; Use one thermostat for every room with underfloor heating.
1 2 3 4
Use 0.3 m antenna cable Connect the RJ 9 connector into the antenna Clip the antenna into the controller Run the cable of the antenna into the hole of the controller Connect to terminals 9 and 10
Underfloor Heating
3.2.2
Position the controller just above the manifold. Check position of 230V socket. Check that the cover of the controller can easily be removed. Check that the connectors and switches are easily accessible.
STOP
The controller has to be mounted horizontally. There is a risk for overheating if the controller is mounted vertically or on a horizontal surface.
1 2 3 4
Connect the RJ 9 connector into the antenna Drill the wall (6 mm) Fix anchor and screw on the wall Let the screw protrude from the wall (3 mm) Hang the antenna on the screw
1 2 3
Use the double sided adhesive strip to fix the antenna on a smooth wall such as glazed ceramic tiles.
Drill the wall (6 mm) Press the anchor into the hole Attach the controller to the wall with screws
1 2
Connect the RJ 9 connector into the antenna Stick the antenna on the wall
3.3
99
Connections
See wiring diagram in the fold-out.
Correct installation: Thermostat Display #01 controls channels 01a,01b and 02a,02b, External sensor thermostat #01 communicates the floor temperature to the controller, Thermostat Display #03 controls channels 03 and 04. ...
3.3.1 Mark
Controller description Description Terminal block for connection of antenna and options Interface RJ 9 connector Push-button and LED from 01 to 12 for channel registration Test push-button and LED Quick connectors for the actuators Socket for the connection of the data stick Power LED 230VAC 50Hz compartment
1 2 3 4 5 6 7 8
3.3.2
(Only if the antenna is mounted on the wall) Remove plastic part at the cable entrance on the side of the controller. Pull cable under the strain release and connect to terminals 09 and 10 (symbol , non polarized).
3.3.3
STOP
Connecting the actuators to the controller Identify what room each loop on the manifold is supplying and decide which channel it should be connected to.
3.3.4
Installation of the options Systems with interface, please see the interface Manual. WARNING Mains supply 230VAC 50Hz Disconnect the 230V mains before installing or changing the device wiring. Using an interface with this system allows increased management possibilities.
Example installation: Each thermostat can control any desired channel, one or several. It simplifies installation and maintenance if actuators controlled by the same thermostat are wired to channels in sequence.
Underfloor Heating
Circulation pump relay The Uponor Control System can operate a circulation pump on heating/cooling demand. The controlled use of a circulation pump improves the efficiency and responsiveness of the underfloor heating. Example of an installation:
WARNING Do not apply voltage to the controller heating / cooling input. Damage to the Uponor Control System will occur.
Should your system include a cooling unit, it is possible to manage the Uponor Control System with the help of a heating / cooling switch input. The contact may be operated in different ways: timer, ancillary control system, 2 position switch. The heating / cooling input operates with the connection of a dry contact. When the contact of the relay is open, the system is in heating mode. When the contact of the relay is closed, the system is in cooling mode.
WARNING See the circulation pump supplier documentation before performing the connection.
1 2 3 4
The controller controls the circulation pump via connection on terminal block (dry contact). Heating / cooling relay Heating / cooling contact Controller heating / cooling input (potential free dry contact) Example of different type of heating / cooling relay input
1 2 3 4
Ensure the power is disconnected Open 230V compartment and fix cover to hanger Connect "L" wire from/to pump via relay Close 230V compartment
3.3.5
3.4
Room thermostats
The Uponor Control System may be controlled with the help of three types of thermostats. These may be used separately or together: Thermostat Display T-75:
1 2 3
Check that the wiring is complete (Actuators, Antenna) Check that the 230V compartment is closed Connect the plug to the mains Thermostat T-55:
10
Underfloor Heating
3.4.1
Mark room thermostats Type of batteries for the thermostats: 2x Alkaline AAA 1.5V. Respect the polarity. Mark the thermostats with the channel numbers they are to control e.g. 02, 03. For a system with an interface and several controllers the ID of the controller has to be added e.g. 1.02, 1.03, 2.02, 2.03.
Using a point, press the registration button of the thermostat for at least 5 seconds. For Thermostat Display T-75: The temperature is replaced by 2 lines When the temperature appears again the button can be released For Thermostat T-55 and Thermostat Public T-53: The LED of thermostat blinks one time only If registration is successful the LEDs of channels 02
If channel registration fails (the channel LEDs continues to flash or switch off), follow steps 2 to 4 once more.
5 6
Register all room thermostats Press Test push-button to end the registration process The Test LED switch off.
LED status
3.4.2
To cancel registration of a channel and to reset the controller: see: "3.9 Resetting", page: 17. Wrong registration of the channels will cause bad temperature control.
3.4.3
Example of registration: thermostat placed in a room, with 3 loops connected to channels 02 and 03.
Room with floor sensor The floor sensor has to be connected to a Thermostat Public T-53. This thermostat has to be registered to the same channel as the room thermostat, but can be mounted elsewhere. The room thermostat must be registered to the controller before the sensor thermostat. See: "3.5 External sensor thermostats" Example of installation: Thermostat Display #01 controls channels 01a,01b and 02a,02b, External sensor thermostat #01 communicates the floor temperature to the controller, Thermostat Display #03 controls channels 03 and 04. ...
3.4.4
Mount the room thermostats If no external sensors are used, go to "3.4.13 Close the thermostats".
3.4.4.1 Location of a thermostat (For all thermostats) On an indoor wall. 1.5 m to 1.8 m from the floor. Away from any source of humidity. Away from any source of heat (television, electronic equipment, fireplace...). Away from direct solar sunshine. Away from direct water splashes.
Uponor Wall frame can be used to hide marks on the wall or the box if needed.
3.4.4.2 Thermostat fixation There are various solutions to fix the thermostat : Fixing on the wall using a screw; The Thermostat Display T-75 #01 controls the room temperature. The Thermostat Public T-53 #01 has been added in order to provide the room with a floor sensor. It is possible to display the measured floor temperature if your system is fitted with an interface. Fixing on the wall using the bracket (option); Using the thermostat table stand (option).
12
Underfloor Heating
Installation using the thermostat table stand (option): Insert the metal stand in the appropriate holes at the back of the thermostat. Fix the bracket on the thermostat to lock in place the table stand.
Let the screws protrude 3 mm from the wall. or Fix the bracket on the wall (option). Hang the thermostat on the screw or on the bracket.
Sticking onto a smooth wall: Use the double sided adhesive strip to fix the thermostat on a smooth wall such as glazed ceramic tiles. Use optional bracket for Thermostat display T-75.
Sticking onto a smooth wall: Use the double sided adhesive strip to fix the thermostat on a smooth wall such as glazed ceramic tiles.
13
3.4.5
Thermostat setup See Operation Manual for thermostat min/max and room temperature settings. For more information on external sensor settings: See: "3.5 External sensor thermostats", page: 14.
3.5
3.5.1
99
The Thermostat Public T-53 allows a floor or outdoor sensor to be fitted to the system. Configuration switches
3.4.6
Mark the external sensor thermostats See: "3.4.1 Mark room thermostats", page: 11.
99
The Thermostat Public T-53 has a terminal to permit the connection of different type of sensors. The switches has to be set according to the type of sensor used.
3.4.7
3.4.8
Connect the sensor and put switch on right position See: "3.5 External sensor thermostats", page: 14.
99
3.4.9
Register external sensor thermostats See: "3.4.3 Register room thermostats", page: 11.
1 2 3
Floor sensor Outdoor sensor (No used) (No used) Only one of the four switches must be on. When the thermostat is used as a room thermostat all switches should be off. If more than one switch is on: the LED flickers. It stops flashing when only one switch is on, or none at all.
99
3.4.10 Cancelling the registration of a channel See: "3.9 Resetting", page: 17.
99
3.4.11 Mount external sensor thermostats See: "3.5 External sensor thermostats", page: 14. 3.5.2 3.4.12 Set min and max temperature for floor sensor See: "3.5.4 Floor sensor setting", page: 15.
99
99
Registration and marking The registration procedure for a Thermostat Public T-53 fitted with a floor or outdoor sensor is similar as that followed for room thermostats. See: "3.4.3 Register room thermostats", page: 11. Marking the Thermostat Public T-53 is carried out in the same way as with the room thermostat, but add information floor or outdoor. See: "3.4.6 Mark the external sensor thermostats", page 14.
3.4.13 Close the thermostats See: controller Operation Manual, page: 10.
3.4.14 Carry out communication test See: "3.6 Testing the communication between the thermostats and the controller", page: 16.
99
14
Underfloor Heating
3.5.3
Wiring
It is possible to display the measured floor temperature if your system is fitted with an interface.
3.5.5
99
The procedure for completing the registration of a Thermostat Public T-53 fitted with a floor or outdoor sensor is the same as that followed for room thermostats. See: "3.4.3 Register room thermostats", page 11.
3.5.4
Floor sensor The limitation of the floor temperature is adjusted with a potentiometer. The temperature is set on the minimum or the maximum range of the potentiometer. So the Thermostat Public T-53 allows to have a minimum or a maximum floor limitation. The Thermostat Public T-53 sends the external sensor values to the controller: The floor temperature. The minimum or the maximum limitation temperature.
15
3.6 Testing the communication between the thermostats and the controller
3.6.1 Testing the communication between the room thermostats and the controller
3.6.2
Testing the communication between the external sensor thermostats and the controller
The procedure for testing a Thermostat Public T-53 fitted with an outdoor sensor is the same as that described under "3.6.1 Testing the communication between the room thermostats and the controller".
Where two thermostats are connected to the same channel, the procedure described under "3.6.1 Testing the communication between the room thermostats and the controller" must be carried out fully and separately for each thermostat.
3.7
Press the Test push-button The Test and channel LEDs with registered thermostats light up Make a complete check up of the installation :
1 2 3 4
Verify that the antenna is correctly mounted Check if the thermostats are powered Close the cover of the controller Close the thermostat covers where necessary Fill in the "Installation report" on the centre pages of booklet Give the manual and all information about the system to the end user
Using a point, briefly press the registration button of the thermostat Communication OK -> LED for the channels registered to the thermostat switch off NO Communication -> LED for the channels registered to the thermostat stay on See: "4. Troubleshooting", page: 18
3.8
Alternative: Thermostat Display T-75: Use the +/- keys of the thermostat to switch between high and low temperatures and make sure that the LED of the channel continues changing.
Actuators test
Press the button of the selected channel The LED lights up: the actuator is powered (time for actuator opening is ~ 5 min).
Alternative: Thermostat T-55: Use the control dial of the thermostat to switch between high and low temperatures and make sure that the LED of the channel continues changing.
The LED does not light up. See: "4. Troubleshooting", page: 18.
Press the Test button twice to end the actuator test (or wait 10 min)
16
Underfloor Heating
3.9
3.9.1
Resetting
Cancelling the registration of a channel
3.9.2
If there are problems with thermostat linking, thermostats mixed up, bad channel registration, etc, the system can be reset.
Press the Test push-button The Test and channel LEDs with registered thermostats light up .
For the controller, press the Test button for 10 s. The Test LED flashes for at least 2 s, then all LED go off (except the POWER LED). All parameters are erased. New installation / registration after reset is necessary.
Press the push-button of the channel that is to be cancelled for 10 s The LED of the channel cancelled flashes then switches off . for 2 s
Press the Test push-button to leave registration mode The Test LED switches off .
STOP
In order to register a different thermostat to a channel, you first have to cancel the existing, not desired registration of this thermostat.
Pressing briefly the reset buttons is sufficient for the thermostats. New installation / registration after reset is not necessary.
17
4. Troubleshooting
Normal system operating conditions: The Power LED of the controller is lit up. All the channel LEDs are off if there is no demand for heating or cooling. The LEDs light up when the corresponding actuators are activated. While on stand-by, waiting for the actuators to be activated, the LEDs flash. LED of Thermostat T-55 and Thermostat Public T-53: - LED blinks one time only with each transmission. - LED blinks twice for low batteries. - Only for Thermostat Public T-53: LED flickers if several switches are in ON position.
Causes no voltage
Indication
Solution
See
power LED off in controller check that the controller is connected to the mains and that the wiring in the 230V compartment is OK 230V in socket but not in 230V compartment repeated radio alarms replace cable and plug change the location of the antenna (if the problem still is remaining, contact your installer for help checking the radio transmission and test with repeater for radio signals)
antenna mounted inside metal cabinet or too close to other shielding objects building structure unfavorable for radio transmission
18
Underfloor Heating
Technical data
General IP: IP30 (IP: degree of non-accessibility to the active parts of the product and degree of non-accessibility of water) Max ambient RH (relative humidity): 95% max at 20C.
Thermostat CE marking: - Low Voltage Tests: EN 60730-1* and EN 60730-2-9*** - EMC (Electromagnetic compatibility requirements) Tests: EN 60730-1 and EN 301-489-3 - ERM (Electromagnetic compatibility and radio spectrum Matters) Tests: EN 300 220-3 Approval and certification: - KNX: Konnex approval and certification Power supply: 2x Alkaline AAA 1.5V Voltage:2.2 V to 3.6 V Operating temperature: 0C to +45C Storage temperature: -10C to +65C Radio Frequency: 868.3 MHz Transmitter Duty Cycle: 1%
Interface CE marking: - Low Voltage Tests: EN 60730-1 and EN 60730-2-1 - EMC Tests: EN 60730-1 Power supply: 11VDC 10% from Controller Operating temperature: 0C to +55C Storage temperature: -20C to +70C Consumption: 1W max Usable in all Europe 0682
Antenna Power supply: 11VDC 10% from Controller Consumption: << 1W Radio Frequency: 868.3 MHz Transmitter Duty Cycle: 1% Receiver Class: 2 Mark Description Terminal block for connection of antenna and extensions Interface RJ 9 connector Push-button and LED from 01 to 12 for channel registration Test push-button and LED Quick connectors for the actuators Socket for the connection of the data stick Power LED 230VAC 50Hz compartment - Pump
Declaration of conformity: We hereby declare under our own responsibility that products dealt with by these instructions satisfy all essential demands linked to the R&TTE 1999/5/CE Directive dated March 1999.
1 2 3 4 5 6 7 8
Controller CE marking: - Low Voltage Tests: EN 60730-1* and EN 60730-2-1** - EMC Tests: EN 60730-1 and EN 301-489-3 - ERM Tests: EN 300 220-3 Power supply: 230VAC +10/-15% 50Hz Operating temperature: 0C to +55C Storage temperature: -20C to +70C Consumption: 70 W in full charge max Pump relay output: 230VAC +10%/-15%, 250VAC 2A max Heating/cooling input: Only Dry contact Valve outputs: 24VDC 10%, 436 mA max per output 1 and 2 24VDC 10%, 218 mA max per output 3 to 12 Supply connection: EU - Plug 1 m cable, pre-mounted Pump connection: wires 1.5mm max Heating / cooling connection: wires 1.5mm max * EN 60730-1 "Automatic electrical control to domestic use" ** EN 60730-2-1 "Particular Requirements for Electrical Controls for Electrical Household Appliances" ***EN 60730-2-9 "Specific rules for devices of thermo sensitive control"
Press, without turning, with a thin screwdriver on the white button of the terminal to insert or remove a wire
Installation report
option:
controller number
Channels
Rooms
controller number
Channels
Rooms
#2
#1
Floor sensor Yes Pump No
Floor sensor
Yes
24V
Relay
No
230V
Yes
#3
Pump
No
Underfloor Heating
Uponor Control System Radio Operation Manual Controller and Thermostats, UK, IRL
9416-054-10 / IOM- V_07-02
In keeping with our policy of continuous improvement and development, Uponor reserves the right to change specifications without prior notice.
U p onor Hou si ng Solu t ions Lt d. S n a peth or pe Hous e R u g by Road L u t ter w or th Le i ces ter s hi re L E 17 4 HN U p onor Centra l Eu ro pe P O B ox 1 6 4 1 (In dus trie st ra sse 56) D - 9 7 4 3 3 Has s fu r t U p onor N ordi c P O B ox 1 0 1 S E - 7 3 0 6 1 Vi r s bo H S South, West A re a m anag em ent Upo nor Hi s pan i a S . A.U. Calle C, n 24 Po l gono Indus tr i al n 1 E - 28 9 3 8 M s tol es (M a drid) U p onor Cor pora ti on Ro ber t Huber i n ti e 3 b P. O. Box 3 7 F I - 01 5 1 1 VAN TAA
T F W E
+44 ( 0) 1 4 5 5 5 5 0 3 5 5 +44 ( 0) 1 4 5 5 5 5 0 3 6 6 w w w.up o no rho us in g s o lutio ns .co .uk hse nqu irie s @ u p o no r.co .uk
T F
Table of contents
1. General recommendations ................................................................................................................................ 4 2. The Uponor Control System .............................................................................................................................. 5 2.1 Overview of the system .................................................................................................................................. 5 2.2 Operating your installation.............................................................................................................................. 6 3. Thermostats ..................................................................................................................................................... 6 3.1 Changing the temperature format .................................................................................................................... 8 3.2 Changing the temperature setpoint .................................................................................................................. 8 3.3 Setting the min and max temperatures............................................................................................................. 9 3.4 Floor sensor settings ...................................................................................................................................... 9 3.5 Thermostat battery replacement.................................................................................................................... 10 4. System maintenance ...................................................................................................................................... 11 5. Diagnosis and resolution of alarms and faults ................................................................................................ 11 5.1 Normal system operating conditions: ............................................................................................................. 11 5.1.1 Controller .......................................................................................................................................... 11 5.1.2 Thermostat Display T-75...................................................................................................................... 11 5.1.3 Thermostat T-55 and Thermostat Public T-53 ......................................................................................... 11 5.2 Alarms ....................................................................................................................................................... 11 5.2.1 Controller .......................................................................................................................................... 12 5.2.2 Thermostat Display T-75...................................................................................................................... 12 5.2.3 Thermostat T-55 and Thermostat Public T-53 ......................................................................................... 12 5.3 Erasing the alarms....................................................................................................................................... 12 5.4 List of possible alarms and solutions .............................................................................................................. 13 5.5 List of possible failures and solutions.............................................................................................................. 14 6. Disposal of the product................................................................................................................................... 14
1. General recommendations
Safety measures Read and follow the instructions. Installation must be performed by a qualified person according to local regulations. Don't make changes in hardware or software, send damaged control devices to Uponor if they need to be repaired. It is prohibited to make changes or modifications not specified in this manual. Power must be switched off when carrying out the wiring. We decline any responsibility concerning damages and breakdowns that may result from the non-observance of these instructions! Power supply WARNING The Uponor Control System uses a 230VAC 50Hz power supply. In case of emergency, immediately disconnect the plug from the 230V mains. Do not use water to clean the Uponor Control System. Do not expose the Uponor Control System to flammable vapors or gases.
Limitations for radio waves The Uponor Control System uses radio waves. The frequency used is reserved for similar applications and the chances of interference from other radio sources is very low. However, in some rare special cases, it may not be possible to establish a perfect communication. The transmission range is sufficient for most applications, but each building has different obstacles affecting communication and maximum transmission distance. If communication trouble exists, Uponor can support the system with accessories, such as repeaters, for solving the exceptional problems.
Symbols used in this manual WARNING Risk of bodily injuries or pinching. Non observance may harm health or cause damage to product components.
STOP
CAUTION Important note on functionality. Non observance of this note may cause malfunctions. Information. Important operating advice and information. Reference to another document.
Technical constraints Keep installation/data cables away from power cables > 50V to avoid interference. The electrical circuits of the boiler and the pump must be protected by a maximum 6A circuit-breaker.
99
>
Underfloor Heating
Thermostat T-55 The thermostat is easy to use. The temperature settings can be adjusted with the help of a simple dial. The cover may be removed to allow min/max temperatures to be set. The 21C position is marked.
2.1
The controller manages the operation of the actuators, when required by the thermostats following a demand for heating or cooling. It is possible to add an interface to centralize and optimize the management of the system.
Thermostat Public T-53 The thermostat is designed for public location. An alarm is triggered as soon as the cover is opened. The button, switches and potentiometers are all hidden by a cover. The cover may be removed to allow min/max temperatures to be set. An external sensor can be connected.
The Uponor Control System may be controlled with the help of three types of thermostats. Designed for maximum comfort, the thermostats communicate with the controller through radio waves. They may be used individually or in combination with each other. They are fitted with the same battery type for power supply.
The controller drives the actuators according to the setting in the interface and the temperature information received from the thermostats. The controller is typically located near the hydraulic system manifolds.
5 1
Thermostat Display T-75 The thermostat shows the ambient or set temperature on its screen. The thermostat is designed for operative measurement, it is affected by temperature of surrounding surfaces as well as the ambient air temperature.
Interface I-75 (possible option) The interface gives you the opportunity to centralize and optimize the management of the system. The interface allows you to display and update easier and faster the operating parameters of the system. The interface also displays the causes of any alarms. It is simple and easy to use.
2.2
3. Thermostats
Thermostat Display T-75
The Uponor Control System controls your heating installation according to your needs. You simply have to set the temperatures you wish on the thermostats located in each room. Principle of operation: The temperature setpoint is setting with the thermostats. The order to change the temperature setpoint is controlled by the controller. Is there a temperature deviation the actuator opens or closes the valve, which varies the heat supply.
LCD display
For more information on your system, please see to the Installation Report in the fold-out.
Normal operation When the system is running in normal mode: The Power LED is on (visible on the upper right side of the controller cover), In Heating mode, in case of room temperatures lower than the temperatures set on the thermostat, the actuators are open. In Cooling mode, in case of room temperatures higher than the temperature set on the thermostat, the actuators are open. This can be seen in the small windows of the actuators.
LCD display Display of temperatures and menus Display of the temperature with a precision of 0.1 Displayed when setting the temperature set point Displayed during radio transmission Temperature format for the display Low battery indication
2 3 4
Temperature sensor for optimum measurement of ambient temperature + and - keys to set the thermostat parameters Thermostat resetting push button
Underfloor Heating
Thermostat T-55
1 2 3 4 5 6
1
Configuration button
Screw to open the thermostat Terminal for external sensor (non-polarized) Batteries Set point temperature potentiometer Configuration switches Floor sensor potentiometer Configuration button Radio transmission LED
2
Batteries
3
Radio transmission LED
4
Blue cam to set minimum temperature Red cam to set maximum temperature
5 6 7 8
STOP
CAUTION Your thermostats are allocated by your installer to precise rooms and locations. Any change of the location may cause abnormal temperature control.
3.1
Thermostat T-55
3 Wait for 5 s
The thermostat returns to the default display.
3.2
You can avail of an energy-saving mode (ECO Mode) if your system is fitted with a Thermostat Display T-75 and an Interface I-75. This ECO Mode may be activated from the interface menu and will allow you to achieve significant energy savings.
3 Wait for 5 s
The radio transmission icon is displayed, confirming that the set point has been recorded and sent, and returns to default display.
In order to set the temperature set point to its default value of 22.0C (72.0F), briefly press the + and - keys simultaneously.
1 2
Open the cover. See: "3.5 Thermostat battery replacement" Select the required temperature using the potentiometer
Underfloor Heating
3.3
3.4
The minimum and maximum temperatures (5 C and 35 C) of the Thermostat Display T-75 are pre-set. It is however possible to tailor these temperatures to your system if it is equipped with an interface.
Thermostat T-55
If your system includes a floor sensor, a potentiometer fitted behind the cover of the Thermostat Public T-53 allows you to adjust the minimum or maximum temperature settings for the floor. The floor sensor can be used for maximum or minimum limitation of the floor temperature, regardless of the room temperature. The maximum limitation can be used, for example, to prevent a sensitive floor covering from exposure to a too high temperature where there is a high heat demand. The minimum limitation can be used, for example, to keep a tile floor warm even when there is no general demand for heat supply to the room.
3 cam
The blue and red cam allow the minimum and maximum set point to be set as a deviation from the usual setpoint. Example: The usual set point is 21C The setting of the blue cam is -10C The setting of the red cam is +5C The temperature range for this room is 11C to 26C.
Thermostat Public T-53 It is not possible to set min/max temperatures using the Thermostat Public T-53.
3.5
10
Underfloor Heating
4. System maintenance
Regular checks on your system components are recommended in order to optimize performance. This system requires no maintenance, but every few years the batteries are to be changed. You have the possibility of centralizing and optimizing the management of the system by connecting an interface to the controller. The interface allows you to display and update easier and faster the operating parameters of the system. The interface also displays the causes of alarms and facilitates diagnosis.
The Power LED of the controller is lit up. All the channel LEDs are off if there is no demand for heating or cooling. The LEDs light up when the corresponding actuators are activated. While on stand-by, waiting for the actuators to be activated, the LEDs flash.
5.1.2 Thermostat batteries: The thermostats are powered by batteries. Discharged batteries must be replaced. See: "5.2 Alarms", page: 11. Controller: The Power LED of the controller is always lit up. When it blinks, this means that an alarm has been triggered. Open the controller cover. The LED of the channel from which the alarm originated is blinking rapidly. See: "5.2 Alarms", page: 11. Automatic exercise function: The system is fitted with an automatic exercise function. Set every 6 days +/- 24 hours, this function consists of a test-run designed to prevent the pump and actuators from seizing up, when they have not been activated since the last test.
5.1.3
5.2
Alarms
WARNING Note that some actions, e.g. actions involving 230V, wiring, etc., are to be performed by a qualified person.
The errors are indicated on the controller when the power LED blinks. The errors could be: If your system is fitted with an interface, the exercise function may be activated at any time. Loss of radio transmission from a thermostat for more than 3 hours. Low batteries on a thermostat.
STOP
Use a dry soft cloth to clean the Control System and all it's components. Do not use any detergent.
To contact your installer: See installation report in the fold-out to find the contact information of the installer. Please prepare the following information before contacting an installer: Installation report. Drawings of the underfloor heating system (if available).
If an interface is fitted to the system, alarms can be readily displayed without the need to take the controller apart. The interface displays clearly and accurately the causes of the various alarms.
11
5.2.1
The power LED of the controller always remains lit up. If it blinks, this means a problem has occurred. Please consult your Installation Report, which can be found in the Installation Manual. Open the controller cover and identify the LED(s) that are flickering in order to assess from which thermostat the alarm is originating.
5.2.2
Battery Alarm: Replace the batteries of the Thermostat when the symbol appears.
5.2.3
Battery Alarm: Replace the batteries of the thermostat when the red LED inside the thermostat blinks twice. (During a heat or cool demand)
Cover Alarm: The Thermostat Public T-53 includes a switch to warn in case of opening the cover. The status of the switch is transmitted by radio waves. Power LED and concerned channel LED blink.
5.3
Each LED switches off as the corresponding problem is solved, and the Power LED goes back to its normal state (i.e. always on).
12
Underfloor Heating
5.4
Causes
antenna out of position or wire disconnected short-circuit on a connected actuator
Solutions
mount antenna in correct position with wire correctly connected check the wiring of the actuators, replace the actuator use another channel (if an unused one is remaining)
Note
Controller C-55 power LED and concerned channel LED flash short-circuit on the actuator terminal/wiring error
the thermostat batteries are discharged batteries totally dead or wrong type of battery used batteries mounted upside down (reversed polarity) thermostat is out of the correct position
replace the batteries see "3.5 Thermostat battery replacement" mount batteries correctly move the thermostat
Thermostat Display T-75 transmitter working but with radio transmission icon is displayed but signals are received only if the thermostat is close to the antenna reduced signal intensity
replace the thermostat for info how to delete the assignment of the old thermostat and replace it with the new one, see Installation Manual
new installations in the house, shielding radio signals (e.g. drying cupboard, safe, metallic door) the thermostat batteries are discharged batteries totally dead or wrong type of battery used batteries mounted upside down (reversed polarity) thermostat is out of the correct position Thermostat T-55 and Thermostat Public T-53 in transmission LED no blinks one time transmitter broken in thermostat
try to find a new position for thermostat and/or antenna (or, if possible, the shielding object) replace the batteries see "3.5 Thermostat battery replacement" mount batteries correctly move the thermostat
replace the thermostat for info how to delete the assignment of the old thermostat and replace it with the new one, see Installation Manual
check the settings and put back in place the cover of the thermostat
13
5.5
Indication
press + or key to display the temperature set point on the thermostat
Causes
Solutions
Note
use max and min limitation to protect
menu temperature displayed on the room too cold (or too warm in Cooling mode) 1 thermostat drops after a while when the thermostat is moved see installation report and the controller/channel numbering under thermostat batteries cover
place the thermostat in the room supplied by the loops controlled by the thermostat
LED's are flashing the white indication can not be seen in the indicator window of the actuator room too warm (or too cold in cooling mode)
1
the corresponding loop is warm even after a long period without heat call
no heat demand (from underfloor heating system) room temperature OK, but the floor is cold
: To find out if a problem is caused by the supply system or the control system: loosen the actuators from the manifold, wait some minutes and check if the flow pipe of the floor heating loop warms up. After some more minutes, the return pipe also should warm up. If the pipes do not warm up, the trouble lies in the warm water supply, if the loops warm up, the cause could be the room control system. Supply system defect: no warm water in manifold. Check boiler and circulation pump.
2:
14
Underfloor Heating