Tesys Contactors: Characteristics
Tesys Contactors: Characteristics
TeSys contactors
Model d
Type of contactor
LC1D50D95
Environment
Rated insulation voltage (Ui) Conforming to EN 60947-4-1, overvoltage category III, degree of pollution: 3 Conforming to UL, CSA Rated impulse withstand voltage (Uimp) Conforming to standards Conforming to EN 60947
V V kV
690 600 6
1000
IEC 947-1, 947-4-1, NFC 63-110, VDE 0660, BS 5424, JEM 1038, EN 60947-1, EN 60947-4-1. GL, DNV, PTB, RINA pending UL, CSA Complies with SNCF, Sichere Trennung recommendations Conforming to VDE 0106 parts 101 and A1 (project 2/89) Conforming to VDE 0106 Power connection Coil connection Protection against direct finger contact IP 2X Protection against direct finger contact IP 2X (except LC1-D40D80) TH C C C m - 60+ 80 - 5+ 60 - 40+ 70, for operation at Uc 3000 30 possible, in relation to normal vertical mounting plane V1 C gn gn gn gn 960 10 15 2 4 4 4 3 4 8 15 8 10 8 10 6 15 V 400
Product certifications
Separation insulation
(1) Protection ensured for the connection cross-sections shown on the next page and for connection via cable. (2) In the least favourable direction, without change of contact state (coil supplied at Ue).
Characteristics
TeSys contactors
Model d Connections for power and control circuits
Type of contactor
LC1-
D25
D40
Solid cable 1 conductor without cable end 2 conductors Screwdriver 6 sided key Tightening torque Connection via spring terminals 1 conductor Flexible cable without cable end 2 conductors Connection via bars or lugs Bar cross-section Lug external of screw Screwdriver Phillips head flat screwdriver Phillips head flat screwdriver
6 8 6 8 6 8 5 5 4 9 4 12
8 M3.5 N 2 6 1.7
10 M4 N 2 6 2.5
10 M4 N 2 6 2.5
12 M5 N 2 6 2.5
13 M5 N 2 8 6
16 M6 N 3 8 6
3 x 16 17 M6 8 10 8
5 x 25 25 M8 13 14
Solid cable 1 conductor without cable end 2 conductors Screwdriver Tightening torque Connection via spring terminals Flexible cable 1 conductor without cable end 2 conductors Connection via bars or lugs Lug external of screw Screwdriver Tightening torque Phillips head flat screwdriver Phillips head flat screwdriver
N.m
mm2 mm2
2.5 2.5
2.5 2.5
2.5 2.5
2.5 2.5
mm mm
(1) (1)
8 M3.5
8 M3.5 N 2 6 1.2
8 M3.5 N 2 6 1.2
8 M3.5 N 2 N6 1.2
N 2 6 N.m 1.2 (1) Spade connector or cable lug, see connection via cable above.
Characteristics
TeSys contactors
Model d
Type of contactor
LC1-
D09
DT20
D12
DT25
D18
DT32
D25
DT40
Pole characteristics
Rated operational current (Ie) (Ue 440 V) Rated operational voltage (Ue) Frequency limits Conventional thermal current (Ith) Rated making capacity (440 V) Rated breaking capacity (440 V) Permissible short-time rating No current flowing for preceding 15 minutes at 40 C In AC-3, 60 C In AC-1, 60 C Up to Of the operating current 60 C Conforming to IEC 947 Conforming to IEC 947 For 1 s For 10 s For 1 min For 10 min Without thermal overload relay, fuse gG With thermal overload relay Average impedance per pole Power dissipation per pole for the above operating currents At Ith and 50 Hz AC-3 AC-1 type 1 type 2 A A A A A A A m W W A A V Hz A 9 25 690 25400 25 250 250 210 105 61 30 25 20 20 20 12 25 690 25400 25 250 250 210 105 61 30 40 25 25 18 32 690 25400 32 300 300 240 145 84 40 50 35 32 25 40 690 25400 40 450 450 380 240 120 50 63 40 40
See pages 2/52 and 2/53, for aM or gG fuse ratings corresponding to the associated thermal overload relay 2.5 0.20 1.56 2.5 0.36 1.56 2.5 0.8 2.5 2 1.25 3.2
0.81.1 Uc on 50 Hz and 0.851.1 Uc on 60 Hz at 60 C 0.30.6 Uc at 60 C 50 Hz coil Cos 50/60 Hz coil 50 Hz coil Cos 50/60 Hz coil 60 Hz coil Cos 50/60 Hz coil 60 Hz coil Cos 50/60 Hz coil VA VA VA VA VA VA VA VA W 0.75 70 0.3 7 0.75 70 0.3 7.5 23 1222 419 15
" 50 Hz Inrush
Sealed
" 60 Hz Inrush
Sealed
Heat dissipation Operating time (3) Mechanical life in millions of operating cycles
ms ms
Maximum operating rate In operating cycles per hour 3600 at ambient temperature 60 C (1) Protection ensured for the connection cross-sections shown on page 2/33 and for connection via cable. (2) In the least favourable direction, without change of contact state (coil supplied at Ue). (3) The closing time C is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time O is measured from the moment the coil supply is switched off to the moment the main poles separate.
D32
DT60
D38
D40
D50
D65
D80
D95
D115
D150
65 80 1000 25400 80 1000 1000 900 520 260 110 160 125
80 125 1000 25400 125 1100 1100 990 640 320 135 200 160
95 125 1000 25400 125 1100 1100 1100 800 400 135 200 160
115 200 1000 25400 200 1260 1100 1100 950 550 250 250 200
150 200 1000 25400 200 1660 1400 1400 1200 580 250 315 250
See pages 2/52 and 2/53, for aM or gG fuse ratings corresponding to the associated thermal overload relay 2 2 5 2 2 5 2 3 5 1.5 2.4 5.4 1.5 3.7 9.6 1 4.2 6.4 0.8 5.1 12.5 0.8 7.2 12.5 0.6 7.9 24 0.6 13.5 24
12690
24660
24500
0.81.1 Uc on 50 Hz and 0.851.1 Uc on 60 Hz at 60 C 0.30.6 Uc at 60 C 0.75 70 0.3 7 0.75 70 0.3 7.5 23 1222 419 15 3600
0.851.1 Uc at 55 C 0.30.6 Uc at 55 C 0.81.1 Uc on 50 Hz and 0.851.1 Uc on 60 Hz at 55 C 0.30.6 Uc at 55 C 200 0.75 245 20 0.3 26 220 0.75 245 22 0.3 26 610 2026 812 16 6 3600 2026 812 16 6 3600 2026 812 16 6 3600 2035 620 10 4 3600 2035 620 10 4 3600
0.851.1 Uc at 55 C 0.30.5 Uc at 55 C 0.81.15 Uc on 50/60 Hz at 55 C 0.30.5 Uc at 55 C 300 0.8 280350 22 0.3 218 300 0.8 280350 22 0.3 218 38 2050 620 8 8 2400 0.9 280350 0.9 218 0.9 280350 0.9 218 34.5 2035 4075 8 1200
Schneider Electric
2/35
Characteristics (continued)
TeSys contactors
Model d
Opening O ms 20 2035 2035 4075 Note: The arcing time depends on the circuit switched by the poles. For normal 3-phase applications, the arcing time is usually less than 10 ms. The load is isolated from the supply after a time equal to the sum of the opening time and the arcing time. Time constant (L/R) Mechanical life at Uc Maximum operating rate at ambient temperature 60 C In millions of operating cycles In operating cycles per hour ms 28 30 3600 65 20 3600 75 20 3600 25 8 1200
Inrush Sealed
W W ms ms
C O
ms
40 30
Maximum operating rate At ambient temperature 60 C ops/h 3600 (1) Operating times depend on the type of contactor electromagnet and its control mode. The closing time C is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time O is measured from the moment the coil supply is switched off to the moment the main poles separate. (2) In the least favourable direction, without change of contact state.
Characteristics (continued)
TeSys contactors
Model d
V V V A Hz V mA
690 690 600 10 25400 17 5 gG fuse: 10 A ": 140, $: 250 100 120 140 > 10 1.5 on energisation and on de-energisation
ms
d.c. supply category DC-13 Electrical life (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load. V W W W 24 96 48 14 48 76 38 12 125 76 38 12 250 76 32 440 44
1 million operating cycles 3 million operating cycles 10 million operating cycles AC-15
Millions of operating cycles
1 8 7 6 5 4 3 2
1 8 7 6 5 4 3 2 250 V
24 V 48 V 125 V
440 V
0,1 0,1 0,2 0,3 0,4 0,5 0,6 0,8 1 0,7 0,9 2 3 6 8 10 5 7 9 Current broken in A 4
0,1 0,1 0,2 0,3 0,4 0,5 0,6 0,8 1 0,7 0,9 2 3 6 8 10 5 7 9 Current broken in A 4
Characteristics
TeSys contactors
Auxiliary contact blocks without dust and damp protected contacts for model d contactors
LAD-R
LAD-8
Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature around the device Conforming to IEC 68 Conforming to VDE 0106 Storage Operation Permissible for operation at Uc Maximum operating altitude Without derating Phillips N 2 and 6 mm Flexible or solid cable with or without cable end Flexible or solid cable without cable end C C C m mm2 mm2 IEC 947-5-1, NF C 63-140, VDE 0660, EN 60947-5-1 UL, CSA TH Protection against direct finger contact IP 2X - 60+ 80 - 5+ 60 - 40+ 70 3000 Min.: 1 x 1; max.: 2 x 2.5 Max.: 2 x 2.5
Conforming to EN 60947-5-1 and VDE 0660. gG fuse A Conforming to EN 60947-5-1, I rms Permissible for: 1s 500 ms 100 ms A A A A M Guaranteed between N/C and N/O contacts Guaranteed between N/C and N/O on LAD-C22 Ambient air temperature for operation Repeat accuracy Drift up to 0.5 million operating cycles Drift depending on ambient air temperature ms ms C
Insulation resistance Non-overlap time Overlap time Time delay (LAD-T, R and S contact blocks) Accuracy only valid for setting range indicated on the front face
Characteristics
TeSys contactors
Auxiliary contact blocks with dust and damp protected contacts for model d contactors
LA1-DX
LA1-DX protected
Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature Cabling Conforming to IEC 68 Conforming to VDE 0106 Storage and operation Phillips N 2 and 6 mm Flexible or solid cable with or without cable end C IEC 947-5-1, VDE 0660 UL, CSA TH Protection against direct finger contact IP 2X - 25+ 70
mm2
Number of contacts
Contact characteristics
Rated operational voltage (Ue) Rated insulation voltage (Ui) Up to Conforming to IEC 947-5-1 Conforming to UL, CSA Conventional thermal current (Ith) Maximum operational current (Ie) Frequency of operational current Minimum switching capacity U min. I min. Short-circuit protection Rated making capacity Short-time rating For ambient temperature 40 C V V V A mA Hz V mA 50 250 50 3 0.3 > 10 5 Gold - Single break with crossed bars 50 250 50 3 0.3 > 10 5 Gold - Single break with crossed bars 690 690 600 10 10 25400 17 5 10 ": 140; $: 250 100 120 140 > 10 30 24 250 50 3 0.3 > 10 5 Gold - Single break with crossed bars
Conforming to EN 60947-5-1. gG fuse A Conforming to EN 60947-5-1, I rms Permissible for: 1s 500 ms 100 ms A A A A M In millions of operating cycles
Insulation resistance Mechanical durability Materials and technology used for dust and damp protected contacts
Characteristics
TeSys contactors
Auxiliary contact blocks with dust and damp protected contacts for model d contactors
1 8 7 6 5 4 3 2
0,1 0,1 0,2 0,3 0,4 0,5 0,6 0,8 1 0,7 0,9 2 3 6 8 10 5 7 9 Current broken in A 4
d.c. supply, category DC-13 Electrical durability (valid up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the power. V W W W 24 120 70 25 48 90 50 18 125 75 38 14 250 68 33 12 440 61 28 10
1 8 7 6 5 4 3 2 250 V
24 V 48 V 125 V
440 V
0,1 0,1 0,2 0,3 0,4 0,5 0,6 0,8 1 0,7 0,9 2 3 4 6 8 10 5 7 9 Current broken in A
Characteristics
TeSys contactors
Control modules, coil suppressor modules and mechanical latch blocks for model d contactors
Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature around the device Conforming to IEC 68 Conforming to VDE 0106 Storage Operation Permissible for operation at Uc C C C IEC 947-5-1 UL, CSA TH Protection against direct finger contact IP 2X - 40+ 80 - 25+ 55 - 25+ 70
Rated control circuit voltage (Uc) Maximum peak voltage Natural RC frequency 24/48 V 50/127 V 110/240 V 380/415 V
" 24415 3 Uc
$ 12250 Uc
" or $ 24250 2 Uc
Hz Hz Hz Hz
Certification Rated insulation voltage Rated control circuit voltage Power required Maximum operating rate On-load factor Mechanical durability at Uc
1200 1200 10 % 10 % In millions of operating cycles 0.5 0.5 Unlatching can be manually operated locally or electrically controlled for remote operation. The LA6-DK or LAD-6K latch coil and the LC1-D operating coil must not be energised simultaneously. The duration of the LA6-DK or LAD-6K and LC1-D control signals must be 100 ms.
Characteristics
TeSys contactors
Electronic serial timer modules for model d contactors
Module type
LA4-DT (On-delay)
Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature around the device Rated insulation voltage (Ui) Cabling IEC 255-5 UL, CSA TH Protection against direct finger contact IP 2X C C C V - 40+ 80 - 25+ 55 - 25+ 70 250
Conforming to IEC 68 Conforming to VDE 0106 Storage Operation For operation at Uc Conforming to EN 60947-5-1 Phillips N 2 and 6 mm Flexible or solid cable with or without cable end
Operating diagrams
LA4-DT On-delay electronic timers LA4-DR Off-delay electronic timers U supply (A1-A2) U supply (A1-A2) Time delay output Contactor coil Red LED Red LED
1 0 1 0 t 1 0 1 0 1 0 t
40 ms
Characteristics
TeSys contactors
Interface modules for model d contactors
Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature around the device Conforming to IEC 68 Conforming to VDE 0106 Storage Operation Permissible for operation at Uc C C C IEC 255-5 UL, CSA TH Protection against direct finger contact IP 2X - 40+ 80 - 25+ 55 - 25+ 70
Other characteristics
Module type LA4DFBQ With relay Conforming to EN 60947-5-1 Conforming to EN 60947-5-1 V V 5 415 LA4DFB With relay 250 250 LA4DFE With relay LA4LA4DLB DLE With relay + override LA4DWB Solid state
Rated insulation voltage Rated operational voltage Indication of input state Input signals
By integral LED which illuminates when the contactor coil is energised Control voltage (E1-E2) Permissible variation Current consumption at 20 C State 0 guaranteed for U I State 1 guaranteed for U V V mA V mA V $ 24 1730 25 < 2.4 <2 17 By diode By diode 3 ms At 20 C With coil: " 24250 V " 100250 V " 380415 V W 4 0.6 10 4 0.6 10 4 0.6 3 4 0.6 3 4 0.6 20 1 0.4 LC1-D40D115 LC1-D09D38, DT20DT60 $ 24 $ 48 $ 24 $ 48 $ 24
1730 3360 1730 3360 530 25 < 2.4 <2 17 15 < 4.8 < 1.3 33 25 < 2.4 <2 17 15 < 4.8 < 1.3 33 8.5 for 5 V 15 for 24 V < 2.4 <2 5
Built-in protection Electrical durability at 220/240 V Maximum immunity time to micro-breaks Power dissipated Direct mounting without contactor
LC1-D40D150
With coil:
Operating times depend on the type of contactor electromagnet and its control mode. The closing time C is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time O is measured from the moment the coil supply is switched off to the moment the main poles separate. LC1-D09D38, DT20DT60 2030 1624 Min.: 1 x 1 Min.: 2 x 2.5
LC1-D40D65 LC1-D80 and D95
With LA4-DF, DL Cabling Phillips N 2 and 6 mm Flexible or solid cable with or without cable end
2834 2024
2843 1832