VENT AXIA System Calculator
VENT AXIA System Calculator
The Queen Suppliers of Unit Ventilation Equipment Vent-Axia, Crawley, West Sussex
SYSTEM CALCULATOR
CONTENTS
Your Vent-Axia System Calculator What is Ventilation ? Table 1 - Guide to Ventilation Rates (Air Changes per Hour) and Component Velocities Provision for Air Replacement Selecting the Fan Design of a Ducted System 100mm to 400mm dia Component System Resistances Example 1 System Resistance Curve Calculation Example 1 (Fig 1.10) Example 2 Supply System Resistance Curve Calculation Extract System, Resistance Curve Calculation Example 2 (Fig 2.10) Example 3 Supply System Resistance Curve Calculation Extract System Resistance Curve Calculation Plan view (Prestige Office (BANK) (8 A.C.H)
Page 6 Page 7 Page 8/9 Page 10/16 Page 17/19 Page 20/21 Page 22 Page 23/24 Page 25/26 Page 27 Page 28 Page 29/31 Page 32/33 Page 34 Page 35
WHAT IS VENTILATION ?
Ventilation can be simply described as air circulation, the extraction of stale, overheated and contaminated air and the supply and distribution of fresh air in amounts necessary to provide healthy and comfortable conditions for the occupants of a room. This creates an environment which stimulates the occupants to higher efficiency. When dealing with a particular ventilation problem, the three following basic decisions have to be made:1. Type of System - required, ie. extract, intake, or a combination of both, positive or negative pressure. Ventilation Rate - Air Changes Per Hour (ACH) necessary for the conditions (see Table 1, page 3). Provision for air replacement - will existing openings be sufficient, or are special arrangements necessary? TYPE OF SYSTEM An Extract system is designed to remove foul air, usually at high level, unless the fumes are heavier than air, when extraction would take place near floor level. This extraction creates an area of negative pressure causing the fresher replacement air to flow into the room through doors, windows, or through suitably spaced low level intake grilles. This is by far the most common, economical and simplest system for normal ventilation work. b) An Intake system - blows in fresh air, which mixes with the air already in the room and forces its way out to the atmosphere through any available openings. Careful location and speed control of intake fans and evenly distributed air supply diffusers are necessary to prevent draughty conditions. Even in warm weather, incoming air may need to be tempered and/or filtered, in which case careful planning should be given to the position of the diffusers. If filtered air is required, an intake system is essential, and the room should be under a slight positive pressure, so that any leakage of air is outwards from the room. A Combined system using both extract and supply systems can be more effective than extract only in large offices, as controlled mechanical intake can be used to give positive gentle air movement in warm weather to create a feeling of freshness. It also reduces the number and size of openings required in the structure for replacement fresh air. Heat Recovery units can be incorporated in this type of system for energy saving during the Winter months and under certain conditions, a degree of cooling during spring and early summer. Where buildings are air conditioned, these savings will continue in the summer.
2.
3.
1. a)
c)
2.
VENTILATION RATE The points which affect this are:a) b) c) d) e) f) the purpose for which the area to be ventilated is used. the number of occupants. the type of activity they are engaged in. heat gains from other sources eg. electrical equipment and lighting etc. the amount of steam, dust and odours from production processes. Whether there are any particular environmental requirements for the building, such as temperature, humidity, levels of filtration etc.
The Guide to Ventilation Rates (See Table 1, page 3) is based on Vent-Axias extensive experience of all normal conditions in the UK. The figures should be doubled for work in hot climates and increased by 50% if there is a possibility of tobacco smoke. If in doubt, take the highest ACH figures as control switches can always be used to reduce the ventilation rate. The Building Regulations, 1991, Approved Document F, 1995 Edition now covers Non Domestic Buildings. We recommend that all ventilation work is designed to conform to the Approved Document.
TABLE 1 GUIDE TO VENTILATION RANGES (ACH) AND COMPONENT VELOCITIES ACH Location Assembly Halls Bakeries Banks Bathrooms Bedrooms Billiard Rooms * Boiler Rooms Cafes and Coffee Bars Canteens Cellars Changing Rooms - Main area Changing Rooms - Shower area Churches Cinemas and Theatres * Club rooms Compressor rooms Conference rooms Dance halls Dental surgeries Dye works Electroplating shops Engine rooms Entrance Halls & Corridors Factories and Workshops Foundries Garages (Showrooms) Glasshouses Gymnasiums Hairdressing Salons Hospitals - Sterilising - Wards Kitchens - Domestic # - Commercial Laboratories Launderettes Laundries Lavatories Lecture theatres Libraries Living rooms Mushroom Houses Offices Paint shops (not cellulose) Photo & X-ray darkrooms Public house bars Recording studios Recording Control rooms Restaurants Schoolrooms Shops and Showrooms Shower baths Stores & warehouses Swimming baths Toilets Utility rooms Welding shops
TYPICAL VELOCITIES OF DUCTED SYSTEMS (m/s) Main Branch Supply Exhaust Duct Duct Grilles Grilles 5-8 4-6 3-5 2-3 8 - 11 6-8 5-8 3-4 5-8 4-6 3-5 2-3 4-5 3-4 2-3 1.5 - 2 4-5 3-4 2-3 1.5 - 2 5-8 4-6 3-5 2-3 8 - 15 6 - 10 5 - 10 4 - 10 5-8 4-6 3-5 2-3 5-8 4-6 3-5 2-3 5-8 4-6 3-5 2-3 4-5 4-6 3-5 2-3 5-8 4-6 3-5 2-3 4-5 3-4 2-3 1.5 - 2 5-8 4-6 3-5 2-3 5-8 4-6 3-5 2-3 8 - 15 6 - 10 5 - 10 4 - 10 5-8 4-6 3-5 2-3 5-8 4-6 3-5 2-3 5-8 4-6 3-5 2-3 8 - 15 6 - 10 5 - 10 4 - 10 8 - 15 6 - 10 5 - 10 4 - 10 8 - 15 6 - 10 5 - 10 4 - 10 5-8 4-6 3-5 2-3 8 - 15 6 - 10 5 - 10 4 - 10 8 - 15 6 - 10 5 - 10 4 - 10 5-8 4-6 3-5 2-3 4-5 3-4 2-3 1.5 - 2
4-8 20 - 30 4-8 6 - 10 2-4 6-8 15 - 30 10 - 12 8 - 12 3 - 10 6 - 10 15 - 20 1-3 10 - 15 10 - 12 10 - 20 8 - 12 8 - 12 12 - 15 20 - 30 10 - 12 15 - 30 3-5 8 - 10 15 - 30 6-8 25 - 60 6 min 10 - 15 15 - 25 6-8 15 - 20 20 -30 6 - 15 10 - 15 10 - 30 6 - 15 5-8 3-5 3-6 6 - 10 6 - 10 10 - 20 10 - 15 10 - 15 10 - 12 15 - 25 8 - 12 5-7 8 - 15 15 - 20 3-6 10 - 15 6 - 10 15 - 20 15 - 30
5-8 5-8 4-5 4-5 8 - 11 5-8 8 - 11 8 - 11 5-8 4-5 4-5 4-5 5-8 5-8 8 - 11 5-8 5-8 4-5 4-5 5-8 5-8 5-8 5-8 5-8 8 - 11 4-5 5-8 8 - 15
4-6 4-6 3-4 3-4 6-8 4-6 6-8 6-8 4-6 3-4 3-4 3-4 4-6 4-6 6-8 4-6 4-6 3-4 3-4 4-6 4-6 4-6 4-6 4-6 6-8 3-4 4-6 6 - 10
3-5 3-5 2-3 2-3 5-8 3-5 5-8 5-8 3-5 2-3 2-3 2-3 3-5 3-5 5-8 3-5 3-5 2-3 2-3 3-5 3-5 3-5 3-5 3-5 5-8 2-3 3-5 5 - 10
2-3 2-3 1.5 - 2 1.5 - 2 3-4 2-3 3-4 3-4 2-3 1.5 - 2 1.5 - 2 1.5 - 2 2-3 2-3 3-4 2-3 2-3 1.5 - 2 1.5 - 2 2-3 2-3 2-3 2-3 2-3 3-4 1.5 - 2 2-3 4 - 10
* Increase by 50% where heavy smoking occurs or if the room is underground. # Some commercial kitchens may require higher ventilation rates, based on cooking equipment in use.
3.
PROVISION FOR AIR REPLACEMENT Whilst in a few cases the normal gaps around doors and windows are sufficient for this purpose, it is more often necessary and advisable to make special provision for replacement fresh air to be brought into the room through grilles, of a suitable size and design, fitted in doors or walls to minimise draughts. Special provision for air replacement must be considered if:a) b) Windows and doors are draught proofed or double glazed. The location of fans is such that satisfactory coverage of the space by crossventilation cannot be made with air pulled in from the available doors and windows. When the fan is installed in a room containing a fuel burning appliance, the installer must ensure that air replacement is adequate for both the fan and the fuel burning appliance. If it is necessary to pass ducting through a fire barrier then provision must be made for fire dampers in ducting, together with any other requirements necessary due to Fire and Buildings Regulations etc.
c)
d)
When considering air replacement, the location of suitable air intake points is as important as the location of the extract fans. The main points are:a) Aim for full cross-ventilation of the space. b) Eliminate dead spots by preventing short-circuiting of air flow straight from inlets to extract units without sweeping the room. Use sufficient correctly sized grilles to keep supply and extract air velocities between 1.5m/s and 3m/s, if possible. (See Table 1, page 3) If the room is very wide, say over 25m it may be necessary to extract centrally and bring in replacement air along each side. Supply and extract points external to the building should be a minimum of 2 metres apart.
c)
d)
e)
Air replacement should be provided at the minimum rate of 0.087m2 of free area per 1000m3/h of air moved. Air replacement grilles usually have a free area of approximately 60%. For example - a 300mm square grille will have a face area of 300 x 300 = 0.09m2, therefore 60% of 0.09 = 0.054m2 free area. This means that this grille will provide air replacement for the rate of .054 x 1000 = 620m3/h .087
4.
SELECTING THE FAN A fan is simply a machine for moving air and other gases by means of a rotating impeller. Vent-Axia manufactures three main types of impeller - Axial, Mixed Flow and Centrifugal. There are four main types of unit available in the Vent-Axia industrial fan range - In-Line Centrifugal Duct fans, In-Line Slim & Long Cased Axial fans, In-Line Powerflow Duct fans, In-Line Mixed Flow fans and High Performance Acoustic fans. The benefits of each of these fans are listed below and will help you to determine which unit is appropriate for your system.
a)
Metal In-Line Centrifugal Duct fans (sizes 100 to 315mm ducting) - Medium air volumes up to 1650m3/h (0.458m3/s) - Medium pressure development up to 500 Pascals (Pa) - Non-overloading fan characteristics - Suitable where noise is not a priority In-Line Powerflow Duct fans (sizes 100 to 315mm ducting) - Medium air volumes up to 1510m3/h (0.42m3/s) - Medium pressure development up to 500 Pa - Medium sound levels - Lighter weight - Low profile for concealed applications In-Line Mixed Flow fans (sizes 100 to 400mm ducting) - High air volumes up to 4300m3/h (1.202m3/s) - Medium pressure development up to 240 Pa - Energy efficient - Medium sound levels - Compact in size Acoustic fans (sizes 100 to 400 ducting) - Medium air volumes up to 3700m3/h (1.04m3/s) - Medium pressure development up to 400 Pa - Quiet operating sound levels Slim & Long Cased Axial fans (sizes 250 to 400 ducting) - High air volumes up to 10,300m3/h (2.88m3/s) - Low to medium pressure development ranging from 60 Pa to 300 Pa - Energy efficient - Medium sound levels
b)
c)
d)
e)
b)
c)
d)
There are several ways of approaching designing and sizing ducted systems. The simplest is the velocity method, which involves selecting main and branch air velocities (See Table 1, page 3) used in conjunction with trial calculations. e) Sizing the duct(s) A calculation is necessary to establish a duct size, which will provide the Air velocity which equates most closely to the velocities given in Table 1.
Substitute the Air volume for the room (m3/h) you have previously calculated, and the velocity (from Table 1) in the equation below. VOLUME (m3/h) ---------------------------------------------------= m2 VELOCITY (m/s) x 3600 (FACTOR)
Select the next size up duct dia from (Table 2, page 7) and calculate the exact velocity in the duct in the equation below. VOLUME (m3/h) ------------------------------------- = m/s AREA (m2) x 3600
VELOCITY (m/s) =
If the resultant velocity is too high (See Table 1, page 3), then the duct diameter is too small, the system is likely to be noisy and it is unlikely that there is a fan in the VentAxia range to suit. If the resultant Velocity is lower than recommended, the system will be extremely quiet but the ducts oversized and the overall cost may rise unnecessarily. The Gross Cross Section are in m2 for Circular Ducting is as follows:Table 2 Duct Diameter 100mm 125mm 150mm 200mm 250mm 315mm 355mm 400mm f) = = = = = = = = = Free Area (m2) 0.00785m2 0.01227m2 0.01767m2 0.03142m2 0.04909m2 0.07794m2 0.09898m2 0.12566m2
In order to proceed to the next stage you need the following information: (See example 1) i. ii. The preferred duct diameter (calculation e) The air velocity m/s (calculation e)
iii. A list of Vent-Axia components including duct length and the number of bends (see catalogue for components). Select the correct duct diameter and component resistance chart and list the resistance in Pa (Pascals) against each items shown (see pages 10 to 16). Add up all of the component resistances for the Total System Static Resistance. Then using the current Vent-Axia Catalogue or Fan Selector Programme, select a fan that has the same duct diameter as per your system, ensuring that the fan produces a higher performance than required, as a speed controller can be used to reduce the fans performance to the correct level.
Ducting Component
Volume
(l/s)
(m /s
0.0471 0.05495 0.0628 0.07065 0.0785 254 150 20 Pa 23 Pa 19 Pa 283 166 26 Pa 26 Pa 23 Pa 10.7 Pa 13.2 Pa 10.7 Pa 13.2 Pa 17 Pa 5 Pa 9 Pa 25 Pa 11 Pa 50 Pa 20 Pa 21 Pa 6 Pa 11 Pa 30 Pa 14 Pa 60 Pa 24 Pa
(m3/h)
(cfm)
90 Flexible Bend
45 Flexible Bend
Plain
Segmented
10
Plain
Segmented
Duct Attenuator
600 Long
Backdraught Shutters
3-Way Splitters
4-Way Diffusers 5 Pa 4 Pa 4 Pa
Louvre Shutters
Wall Terminal
Roof Terminal
Ducting Component 25 0.0245 0.03681 0.0491 0.06135 88 52 0.4 Pa 0.5 Pa 1 Pa 0.2 Pa 0.4 Pa 1.5 Pa 23 Pa 10 Pa 600 Long 20 Pa 2 Pa 22 Pa 3 Pa 1 Pa 2 Pa 22 Pa 30 Pa 50 Pa 38 Pa 3 Pa 24 Pa 4 Pa 3 Pa 5 Pa 1 Pa 2 Pa 3 Pa 7.5 Pa 65 Pa 60 Pa 4 Pa 26 Pa 6 Pa 0.5 Pa 1 Pa 1.5 Pa 2 Pa 4 Pa 6 Pa 1.1 Pa 2 Pa 3 Pa 4.3 Pa 8 Pa 2.2 Pa 4 Pa 11 Pa 80 Pa 86 Pa 5 Pa 30 Pa 8 Pa 0.8 Pa 1.4 Pa 2.3 Pa 3.2 Pa 2 Pa 3.5 Pa 5.2 Pa 7.5 Pa 2.5 Pa 4 Pa 6.5 Pa 9.5 Pa 14 Pa 11 Pa 4.4 Pa 6 Pa 11 Pa 3 Pa 6 Pa 15 Pa 95 Pa 118 Pa 7 Pa 35 Pa 12 Pa 2 Pa 3.5 Pa 5 Pa 7 Pa 10 Pa 78 104 130 156 182 208 13 Pa 17 Pa 15 Pa 5.8 Pa 8 Pa 14 Pa 4 Pa 7 Pa 20 Pa 120 Pa 154 Pa 9 Pa 42 Pa 16 Pa 133 177 221 265 309 353 37 49 61 74 86 98 110
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
9 m/s
10 m/s 123
Volume
0.0736 0.08589 0.0982 0.11043 0.1227 398 234 16 Pa 21 Pa 19 Pa 7.3 Pa 10 Pa 17 Pa 5 Pa 9 Pa 25 Pa 11 Pa 50 Pa 20 Pa 442 260 20 Pa 26 Pa 23 Pa 9 Pa 12 Pa 21 Pa 6 Pa 11 Pa 30 Pa 14 Pa 60 Pa 24 Pa
(m3/h) (cfm)
90 Flexible Bend
45 Flexible Bend
Rigid Ducting, per 1 metre (spirally wound) Plain Segmented Plain Segmented
11
Duct Attenuator
Backdraught Shutters
3-Way Splitters
4-Way Diffusers 5 Pa 4 Pa 4 Pa
Louvre Shutters
Wall Terminal
Roof Terminal
Ducting Component
Volume
(l/s)
(m3/s)
0.12369 0.1414 0.15903 0.1767 573 337 15 Pa 21 Pa 19 Pa 5.8 Pa 10 Pa 17 Pa 5 Pa 9 Pa 25 Pa 11 Pa 50 Pa 20 Pa 636 374 17 Pa 26 Pa 23 Pa 7.2 Pa 12 Pa 21 Pa 6 Pa 11 Pa 30 Pa 14 Pa 60 Pa 24 Pa
(m3/h)
(cfm)
90 Flexible Bend
45 Flexible Bend
Plain
Segmented
12
Plain
Segmented
Duct Attenuator
600 Lomg
Backdraught Shutters
3-Way Splitters
4-Way Diffusers 5 Pa 4 Pa 4 Pa
Louvre Shutters
Wall Terminal
Roof Terminal
Ducting Component
Volume
(l/s)
(m3/s)
0.1885 0.21994 0.2514 0.28278 0.3142 1018 599 9 Pa 21 Pa 19 Pa 4.4 Pa 10 Pa 17 Pa 5 Pa 9 Pa 25 Pa 11 Pa 1131 666 12 Pa 26 Pa 23 Pa 5.4 Pa 12 Pa 21 Pa 6 Pa 11 Pa 30 Pa 14 Pa
(m3/h)
(cfm)
90 Flexible Bend
45 Flexible Bend
Plain
Segmented
13
Plain
Segmented
Duct Attenuator
600 Long
Heat Exchange 20 Pa 2 Pa
Backdraught Shutters
3-Way Splitters
4-Way Diffusers
Louvre Shutters
Wall Terminal
Roof Terminal
Ducting Component
Volume
(l/s)
(m /s)
0.2945 0.34363 0.3927 0.44181 0.4909 1591 936 7 Pa 21 Pa 19 Pa 3.4 Pa 10 Pa 17 Pa 5 Pa 9 Pa 25 Pa 11 Pa 1767 1040 8.5 Pa 26 Pa 23 Pa 4.2 Pa 12 Pa 21 Pa 6 Pa 11 Pa 30 Pa 14 Pa
(m3/h)
(cfm)
90 Flexible Bend
45 Flexible Bend
Plain
Segmented
14
Plain
Segmented
Duct Attenuator
600 Long
Heat Exchange 20 Pa 2 Pa
Backdraught Shutters
3-Way Splitters
4-Way Diffusers
Louvre Shutters
Wall Terminal
Roof Terminal
Ducting Component
Volume
(l/s)
(m3/s)
0.4676 0.54558 0.6235 0.70146 0.7794 2525 1486 5 Pa 21 Pa 19 Pa 2.9 Pa 10 Pa 17 Pa 5 Pa 9 Pa 25 Pa 11 Pa 2806 1652 6.5 Pa 26 Pa 23 Pa 3.6 Pa 12 Pa 21 Pa 6 Pa 11 Pa 30 Pa 14 Pa
(m /h)
(cfm)
90 Flexible Bend
45 Flexible Bend
Plain
Segmented
15
Plain
Segmented
Duct Attenuator
600 Long
Heat Exchange 20 Pa 2 Pa
Backdraught Shutters
3-Way Splitters
4-Way Diffusers
Louvre Shutters
Wall Terminal
Roof Terminal
Ducting Component
Volume
(l/s)
(m3/s)
(m3/h)
(cfm)
90 Flexible Bend
45 Flexible Bend
Plain
Segmented
16
Plain
Segmented
Duct Attenuator
600 Long
Heat Exchange
Backdraught Shutters
3-Way Splitters
4-Way Diffusers
Louvre Shutters
Wall Terminal
Roof Terminal
EXAMPLE 1
Example 1 is based on a typical, simple extract office scheme as per Fig 1.10 (page 22). First calculate the volume of the room (height x width x length) and multiply by the Air Changes per Hour. This equals the minimum air volume required per hour:Height x width x length x ACH = m3/h 2.4m x 4m x 5m x 10 = 480m3/h Calculate the duct size, which will provide the air velocity which equates most closely to the velocity given in Table 1 VOLUME (m3/h) ----------------------------------------------------------------------- = m2 VELOCITY m/s (see page 5) x 3600 = 0.0222m2
AREA =
Select the next size up duct dia from Table 2 (page 9), which in this case is 200mm diameter. (Gross cross section area = 0.03142m2). Select a suitable duct fan, which will cope with the calculated volume figure with a reasonable pressure development (eg. 100 to 150Pa) at the required air volume (in this case 480m3/h), which selects a ACH200-12, In-Line Centrifugal fan or ACM200-12 Mixed Flow fan. Design the ducted system (see Fig 1.10, page 22) for the room, bearing in mind the type of system (extract, intake or a combination of both), the provision for air replacement (will existing openings be sufficient, or are special arrangements necessary ?) and the location of grilles for intake and extract. Once you have decided on the system and selected the accessories required, you need to list the components. Calculate the velocity through the 200mm dia system at an air volume of 480m3/h (as per Calculation 1) to establish that it complies with Vent-Axias recommended duct velocities (See Table 1, page 3).
VOLUME (m3/h) -----------------------------------------------------------------Cross Sectional Area (m2) x 3600 (See Table 2 on page 9)
m/s
4.24m/s
17
Select the component resistance chart appropriate to the fan diameter (ie. 200mm) and round to the next highest velocity (in this case 5m/s) for main duct components and 3m/s for branch duct components in this case, to obtain the individual resistance of each component. An appropriate starting point for calculating your System Resistance should be the extract (or supply) diffuser point in the room. As you can see by Fig 1.10 (page 22), there are two extract points in the office with, therefore, an equal amount of air from each grille, which will be:480m3/h _________ 2 = 240m3/h
The volume through the two intake grilles and subsidiary ducts will be: 240m3/h. Branch Duct Velocity (m/s) = 240m3/h __________________ 0.03142m2 x 3600 = 240 ______ 113.11 2.12m/s
As can be seen from Fig 1.20, the pressure loss of each 200mm grille @ 240m3/h is 30Pa. When setting the grille up on site the grille is to be unscrewed 15 full turns from fully closed to obtain the correct air volume.
STATIC PRESSURE Pa
SO UN DL EV EL dBA
30 Pa (resistance)
18
Next calculate the pressure loss of the Ducting. The resistance of the Ducting at different velocities can be found on the 200mm dia Component System Resistance Chart.
eg. 1 metre of 200mm dia Flexible Ducting, at a velocity of 4.24m/s, gives a pressure loss of 3 Pa per metre. 1 metre of 200mm Flexible Ducting, at a velocity of 2.12m/s, gives 1.0 Pa per metre. A 90 flexible bend, at a velocity of 2.12m/s, gives 2.5 Pa per bend. Lastly, calculate the resistance of the 3-Way Splitters and Wall Grilles, which can be found on the System Resistance Chart. eg. The pressure loss through a 3-Way Splitter, at a velocity of 4.24m/s, is 6 Pa. The pressure loss through a 200mm dia. Wall Termination, at a velocity of 4.24m/s equals 21 Pa. For systems using 2 similar branch ducts, only the pressure loss of one branch need be calculated, for dissimilar branch ducts, the branch with the highest pressure loss should be used. So the Total Static System Resistance of Example 1 is:-
1-off 200mm dia Circular Diffusers (30 Pa) Flexible ducting (1-Branch) 1-off 90 flexible bends at 2.12m/s Resistance = 1 x 2.5 Pa Straight duct 1.85 + 0.15 = 2m at 2.12m/s Resistance = 2 x 1 Pa Resistance of 3-Way Splitter at 4.24m/s Flexible ducting (main duct 0.25 + 0.75 = 1m at 4.24m/s Resistance = 1 x 3 Pa Resistance of 200mm Wall Termination Total Static System Resistance
= 30 Pa
= 2.5 Pa = 2 Pa = 6 Pa
= 3 Pa = 21 Pa = 64.5 Pa
19
Therefore, the most appropriate In-Line Duct Fan for this office system (as you can see in Fig 1.30) is the ACM200-12 Mixed Flow Fan, which is dimensionally compact, highly efficient, excellent performance for minimal cost, low noise development and has nonoverloading characteristics.
FIG. 1.30
20
The resistance varies as the square of the change in the air velocity: R V2. As velocity varies directly proportionally to volume, we can say that the Resistance varies as the square of the volume. The equation then becomes
NEW RESISTANCE =
(
2
X OLD RESISTANCE
Given the system resistance of 64.5 Pa at 480m3/h, what will be the resistance if a) 650m3/h, b) 550m3/h and c) 400m3/h are used? a) New Resistance =
b)
New R =
c)
New R =
( ) ( ) ( )
650 -------480 550 -------480 400 -------480
2
X 64.5 = 118 Pa
X 64.5 = 85 Pa
X 64.5 = 45 Pa
If these three points are plotted on Fig. 1.30 (page 20), a curve can be drawn through the three new and original points. This curve illustrates the air volume at differing resistances. Where the fan curve and system curve intersect is the operating point for the ACM200-12 in the Example 1 system, offering 580m3/h at approx. 94 Pa. Air Replacement In this instance a pair of 350mm x 350mm non vision grille with approximately 40% Free Area will be suitable to provide a good rate of air replacement. 0.350 x 0.350 = 0.1225m2 Face Area 0.1225 x 40% = 0.049m2 Free Area 0.049m2 0.087 x 1000 = 563m3/h
NOTE:- If the door or wall has a Fire Rating, a Fire Damper will have to be installed with suitable grilles to meet Fire Regulations.
21
ROOM SIZE:- H(height) 2.4 METRES x W(width) 5 METRES x L(length) 6 METRES TYPE OF ROOM:- OFFICE, ONE PERSON, NON-SMOKER. AIR CHANGES PER HOUR:- 10
22
EXAMPLE 2
The second example is a Conference Room using a combined system as per Fig 2.10 (page 28). Volume of Air required:Height x width x length x ACH = m3/h 2.4m x 7.5m x 7m x 12 = 1512m3/h As this is a combined system it will be required to supply and extract air at this rate ie. 1512m3/h for the supply and 1512m3/h for the extract. Determine main ducting size: 1512 m3/h -----------------------8 m/s x 3600
AREA =
= 0.0525m2
Select the next largest duct diameter from Table 2 and calculate the exact velocity in the duct in the equation below, in this case 315mm diameter ducting with an area of 0.07994m2. 1512 m3/h -----------------------------------0.07794m2 x 3600
Velocity (m/s) =
= 5.39m/s
As the conference room is not centrally heated and to provide a nominal temperature of eg. 20C (68F), a duct air heater has been incorporated into the system. The duct air heater must be thermostatically controlled. When a Duct Air Heater is used the fan should be wired through a Vent-Axia electric heater controller which includes an overrun timer so that when the heater is shut down the fan will cool the heating elements and remove residual heat. It is advisable to mount the duct air heater downstream of the supply fan to avoid heated air being pulled through the fan. The most effective method of cross ventilating the conference room is to use the 4-Way Diffusers. To select the most appropriate size refer to the relevant page in the Vent-Axia Industrial Range manual. From Fig 2.10 (page 28) you can see the two diffusers for supply and two for extract have been selected for full and effective cross ventilation. Air requirement per supply diffuser = 1512 = 756m3/h ----------2 1512 = 756m3/h ----------2
In this case 350mm square 4-Way Diffusers with 315mm diameter neck adapters would be suitable.
23
For systems using 2 similar branch ducts only the pressure loss of one branch need be calculated, for dissimilar branch ducts the branch with the highest pressure loss should be used. Calculate the total static resistance of the supply system, starting with the diffusers. Supply Diffuser totals:1 off diffusers with an air volume of 756m3/h at a resistance of 14 Pa per diffuser Resistance = 1 x 14 Pa = Flexible Ducting totals:1 off 315mm dia, 90 Bends @ 2.69m/s (velocity) Resistance = 1 x 2.5 Pa = 1 metre of 315 dia x 1 = 1m @ 2.69m/s (velocity) Resistance = 1 x 0.5 Pa = 1 metre of 315 dia x 4 = 4m @ 5.39m/s (velocity) Resistance = 4 x 2.5 Pa = 3 Way Splitter (size 400) totals:1 at a velocity of 5.39m/s Resistance - 1 x 8 Pa = 315mm dia Pre Filter Cassette totals:1 at a velocity of 5.39m/s Resistance (Clean) = 1 x 80 Pa 315mm dia Duct Air Heater totals:1 at a velocity of 5.39m/s Resistance = 1 x 11 Pa = 315mm dia Wall Termination Set totals:1 at a velocity of 5.39m/s Resistance = 1 x 31 Pa
14 Pa
2.5 Pa 0.5 Pa 10 Pa
8 Pa
80 Pa
11 Pa
31 Pa Total 157 Pa
NB. The 4.5kW Duct Air Heater will give an approximate 13C (23F) temperature rise above Ambient. The 4-Way Diffusers will give a throw of 3.3m at an angle of 155. This information is obtained from the relevant pages of the Vent-Axia Industrial Product Range Manual. Resistance figure is for a clean or new filter. As the filter is used, the trapped particles will affect the resistance. It is important to check and clean or replace filters regularly.
24
Now that we know the Air Volume (1512m3/h) and the Total Supply System Static Resistance (157 Pa) required, we need to select an Airtrak Fan that has quiet operating characteristics. The most suitable in-line duct fan for this system would be the ACQ315-14A Acoustic Fan (see Fig 2.20). AIRTRAK ACOUSTIC FANS
250 500 450 500 750 1000 1250 1500 1750 2000 2250 cfm 2.0 1.8
Actual Operating Point 1690m3/h@188Pa
System Curve
100 50
1 2 3 4 5 6 7 8
0 0 0 500 0.1 0.2 1000 0.3 1500 0.4 2000 0.5 0.6 2500 0.7 3000 0.8 3500 0.9 1.0
VOLUME
Volume 1512m3/h Spigot Dia 100 125 150 200 250 315 400A 400/H 1 2 3 4 5 6 7 8
FIG. 2.20
b)
New R
c)
New R
( ) ( ) ( )
1750 1512
---------
X 157 Pa = 210 Pa
---------1512
2000
X 157 Pa = 274 Pa
1250
---------
X 157 Pa = 107 Pa
1512
If these three points are plotted on Fig 2.20, a curve can be drawn through the three new and original points. Where the fan curve and system curve intersect is the operating air volume for the supply system in the Example 2, 1690m3/h at 188 Pa. A speed controller would be recommended.
25
ins w.g.
Now calculate the Total Static Resistance of the extract system, starting as before with the grilles. Extract Diffusers totals:1 off diffusers with an air volume of 756m3/h at a resistance of 14 Pa per diffuser Resistance = 1 x 14 Pa Flexible Ducting totals:1 off 315mm dia, 90 Flexible Bend @ 2.69m/s Resistance = 1 x 2.5 Pa = 1 metre of 315 dia x 1 = 1m @ 2.69m/s Resistance = 0.5 Pa = 1 off 315mm dia, 90 Flexible Bend @ 5.39 m/s Resistance = 1 x 10 Pa = 4 metres of 315 dia @ 5.39m/s Resistance = 4 x 2.5 Pa = 3 Way Splitter (size 400) totals:1 at a velocity of 5.39m/s Resistance = 1 x 8 Pa = Roof Termination totals:1 at a velocity of 5.39m/s Resistance = 1 x 32 Pa =
14 Pa
2.5 Pa 0.5 Pa 10 Pa 10 Pa
8 Pa
32 Pa Total 77 Pa
NB. Again an ACQ315-14 would be the most appropriate extract fan to use (see Fig 2.30). AIRTRAK ACOUSTIC FANS
250 500 450 500 750 1000 1250 1500 1750 2000 2250 cfm 2.0 1.8
Actual Operating Point 1932m3/h@124Pa
Resistance100 77Pa
50
1
2 3 4 5 6 7 8
0 0 0 500 0.1 0.2 1000 0.3 1500 0.4 2000 0.5 0.6 2500 0.7 3000 0.8 3500 0.9 1.0
VOLUME
Volume 1512m3/h Spigot Dia 100 125 150 200 250 315 400A 400/H 1 2 3 4 5 6 7 8
FIG. 2.30
26
b)
New R =
c)
New R =
( ) ( ) ( )
1750 1512
----------
X 77 Pa = 103 Pa
2000
---------
X 77 Pa = 135 Pa
1512
1250
1512
---------
X 77 Pa = 53 Pa
If these three points are plotted on Fig 2.30, a curve can be drawn through the three new and original points. Where the fan curve intersect is the operating air volume for the extract system in the Example 3, 1932m3/h at 124 Pa. A speed controller would be recommended.
27
28
ROOM SIZE:- H(height) 2.4 METRES x W(width) 7.5 METRES x L(length) 7 METRES TYPE OF ROOM:- CONFERENCE ROOM, NON-SMOKING AIR CHANGES PER HOUR:- 12 PLAN VIEW OF OFFICE
EXAMPLE 3
The third example is a prestige office as per Fig. 3.10 (page 35). Volume of air required:Height x width x length x ACH = m3/h 2.4m x 5.5m x 7m x 8 = 740m3/h A combined system will be required to supply and extract air both at a rate of 740m3/h. As can be seen from Fig 3.10, 315mm diameter duct has been selected, so a heat exchange unit can be used in this system. Duct Velocity = 740m3/h ------------------------------------0.07794 x 3600 = 2.64m/s
The office is not centrally heated, therefore to provide a nominal temperature of eg. 20C, (68F) a duct air heater has been incorporated together with a heat exchanger. This will reduce running costs when the room is at a set temperature. The Duct Air Heater must be thermostatically controlled. When using a Duct Air Heater the fan should be wired through a Vent-Axia electric heater controller which includes an overrun timer so when the heater is shut down the fan will cool the heating element and remove residual heat. Mount the Duct Air Heater downstream of the supply fan to avoid heated air being pulled through the fan. In this installation the fan is mounted a considerable distance from the source of heat and therefore the air will be slightly cooler. The most effective way of cross ventilating the office would be to use the 4-Way Diffusers. To select the most appropriate size refer to the relevant page in the Vent-Axia Industrial Range Manual. From Fig 3.10 it can be seen that two diffusers for supply and two for extract have been selected for full and effective cross ventilation. Air requirement per supply diffuser = 740m3/h = 370m3/h ----------------2 740m3/h = 370m3/h ----------------2
In this case 300mm square 4-Way Diffusers with 250mm diameter neck adapters would be suitable. 250mm dia subsidiary duct velocity = 370m3/h = 2.09m/s ------------------------------0.04909 x 3600
29
For systems using 2 similar branch ducts only the pressure loss of one branch need be calculated, for dissimilar branch ducts the branch with the highest pressure loss should be used. Calculate the total resistance of the supply system, starting with the diffusers. Supply Diffuser totals:1 off Diffuser with an air volume of 370m3/h at a resistance of 4 Pa per Diffuser Resistance = 1 x 4 Pa = Flexible Ducting totals:1 off 250 dia 90 Bend 2.09m/s (velocity) Resistance = 1 x 2.5 Pa = 1 metre of 250 dia x 0.5 @ 2.09 m/s (velocity) Resistance = 0.5 x 1 Pa 1 off 315 dia 90 Bend @ 2.6m/s (velocity) Resistance = 1 x 3.5 Pa = 1 metre of 315 dia x 4.75 = 4.75m @ 2.6 m/s (velocity) Resistance = 4.75 x 0.5 Pa 3 Way Splitter (size 400) totals:1 at a velocity of 2.6 m/s Resistance = 1 x 3 Pa = Heat Exchange Unit totals:1 off at an Air volume of 740m3/h which has a resistance of 90 Pa = Pre-Filter Cassette totals:- (clean) 1 at a velocity of 2.6 m/s Resistance = 1 x 30 Pa = Duct Air Heater totals:2 at a velocity of 2.6 m/s Resistance = 2 x 3 Pa Wall Terminal Set totals:1 at a velocity of 2.6 m/s Resistance = 1 x 8 Pa = Total Supply System Resistance =
4 Pa
2.5 Pa
0.5 Pa
3.5 Pa
2.4 Pa
3 Pa
90 Pa
30 Pa
6 Pa
8 Pa 150 Pa
NB. The Duct Air Heater will give an approximate 20C (36F) temperature rise above ambient. The Heat Exchanger Unit will provide up to 70% Heat Recovery from extracted air. 4-Way Diffusers will give a throw of 2.2 metres at an angle of 160.
30
This information is obtained from the relevant pages of the Vent-Axia Industrial Product Range Manual. Knowing the Air Volume (740m3/h) and the Total Supply System Static Resistance (149.9 Pa) required, select an Airtrak fan. The most appropriate fan to use in this instance is the Powerflow fan (ACP315-12A), which has been designed to work in conjunction with the heat exchanger and also offers low noise levels and non-overloading characteristics (See Fig 3.20).
AIRTRAK POWERFLOW
125 500 450 250 375 500 625 750 875 cfm 2.0 1.8
Actual Operating Point 817m3/h@181Pa
0.2
5 6 7&8 9
600 0.15
800 0.2
1200 0.35
1400 0.4
VOLUME
Volume 740m3/h Size 100 125 150 160 200 250 300 315A 315/H 1 2 3 4 5 6 7 8 9
FIG. 3.20
31
b)
New R =
c)
New R =
( ) ( ) ( )
--------740 800
X 149.9 Pa = 175 Pa
--------740
900
X 149.9 Pa = 222 Pa
-------740
600
X 149.9 Pa = 99 Pa
If these three points are plotted on Fig 3.20 a curve can be drawn through the three new and original points. Where the fan curve and system curve intersect is the operating air volume for the supply system in the Example 3, 817m3/h at 181 Pa. We now need to calculate the Total Resistance of the extract system, starting as before with the grilles. Extract Diffuser total:1 off Diffusers with an air volume of 370m3/h at a Resistance of 4 Pa per Diffuser Resistance = 1 x 4 Pa = Flexible Ducting totals:1 off 250 dia, 90 Flexible Bend @ 2.09 m/s (velocity) Resistance = 1 x 2.5 Pa = 1 metre of 250 dia x 0.5 = 1m @ 2.09 m/s (velocity) Resistance = 0.5 x 1 Pa = 2 off 315 dia, 90 Flexible Bends @ 2.6 m/s (velocity) Resistance = 2 x 2.5 Pa = 1 metre of 315 dia x 5.25m (total) @ 2.6 m/s (velocity) Resistance = 5.25 x 0.5 Pa = 3 Way-Splitters (size 400) totals:1 at a velocity of 2.6 m/s Resistance = 1 x 3 Pa =
4 Pa
2.5 Pa
0.5 Pa
5 Pa
2.6 Pa
3 Pa
32
Heat Exchanger Unit total:1 off at an air volume of 740m3/h which has a resistance of 90 Pa Roof Termination Set total:1 at a velocity of 2.6 m/s Resistance = 1 x 9 Pa Total Extract System Resistance
90 Pa
9 Pa 116 Pa
AIRTRAK POWERFLOW
125 500 450 250 375 500 625 750 875 cfm 2.0 1.8
Actual Operating Point 883m3/h@156Pa
Resistance 116.6Pa
0.2
5 6 7&8 9
600 0.15
800 0.2
1200 0.35
1400 0.4
VOLUME
Volume 740m3/h Size 100 125 150 160 200 250 300 315A 315/H 1 2 3 4 5 6 7 8 9
FIG. 3.30
33
b)
New R =
c)
New R =
( ) ( ) ( )
---------740 900 800
X 116.6 Pa = 136 Pa
--------740
X 116.6 Pa = 172 Pa
600 --------740
X 116.6 Pa = 76 Pa
If these three points are plotted on Fig 3.30 (page 33) a curve can be drawn through the three new and original points. Where the fan curve and system curve intersect is the operating air volume for the Extract system in the Example 3, 883m3/h at 156 Pa.
34
35
The Local Fire Officer must be consulted and all recommendations adhered to, before quoting either verbally or in writing for systems that breach separate firebreak walls and partitions or require fire resistant ducting. Whilst every care has been taken to ensure that this calculator is accurate and free from errors or omissions, no liability whatsoever can be accepted by Vent-Axia Ltd where it has been used wholly or in part for calculations involved in the precise design of ducted system.
36
SALES CENTRES
SCOTLAND 12 Lambhill Quadrant, Scotland Street Trading Estate, Kinning Park, Glasgow G41 1SB Tel: 0141 429 1166 Fax: 0141 429 6616 NORTH WEST Unit 2, Caledonia Way, Stretford Motorway Estate, Barton Dock Road, Manchester M32 OZH Tel: 0161 865 8421 Fax: 0161 865 0098 NORTH EAST 5 Dolly Lane, Leeds LS9 7TT Tel: 0113 245 2985 Fax: 0113 242 4430 MIDLANDS 70 Albert Road, Stechford, Birmingham B33 9AH Tel: 0121 783 8601 Fax: 0121 784 7506 SOUTH WEST 4 Dowry Square, Bristol BS8 4SS Tel: 0117 927 7567 Fax: 0117 922 5631 EASTERN Newton Road, Crawley, West Sussex RH10 2JA Tel: 01293 530202 Fax: 01293 565169 LONDON Newton Road, Crawley, West Sussex RH10 2JA Tel: 0181 549 2271 Fax: 01293 565169 SOUTH EAST Newton Road, Crawley, West Sussex RH10 2JA Tel: 01293 530202 Fax: 01293 565169 NORTHERN IRELAND 11 Sydenham Road, Belfast BT3 9DH Tel: 01232 455528 Fax: 01232 452529 REPUBLIC OF IRELAND Vent-Axia Ventilation Ltd 921 Western Industrial Estate, Naas Road, Dublin 12 Republic of Ireland Tel: 01 450 4133 Fax: 01 450 4570 HEAD OFFICE/EXPORT SALES Vent-Axia Ltd Fleming Way, Crawley, West Sussex RH10 2NN Tel: 01293 526062 Fax: 01293 551188 Internet site at: http://www.vent-axia.com email: [email protected]
As part of the policy of continuous product improvement Vent-Axia reserves the right to alter specifications without notice. For current details please contact your nearest Vent-Axia Sales Centre. All sales made by Vent-Axia Limited are made only upon the terms of the Company's Conditions of Sales, a copy of which may be obtained on request.
SYS.CALC/762/0697