Generator
Generator
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
When using mobile generators a high level of protection against hazards caused by electrical currents must be ensured ... despite lack of time despite temporary use despite cramped conditions despite different types and number of items of electrical equipment despite electrical equipment is operated by ordinary persons
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
IEC 60364-4-41 (DIN VDE 0100-410:1997-01) Erection of power installations with nominal voltages up to 1000V Part 41: Protection for safety IEC 60364-5-551 (DIN VDE 0100-551:1997-08) Selection and erection of electrical equipment Section 551: Low-voltage generating sets
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
High personal safety shall be guaranteed. A trained electrician shall not be required. Neither shall there be a limit to the number of items of electrical equipment nor a limit to the cable lenght. The generator shall be ready for use immediately. An earth rod shall not be imperative, for example because of a solid ground like rock, stone, asphalt. The protective measure shall be applicable to each generator.
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
According to clause 551 almost all protective measures in accordance with IEC 60364-4-41 are permitted.
All exposed conductive parts of the installation shall be connected to the earthed point of the power system (IEC 364-4-41, subclause 413.1.3.1). The impedance of the fault loop shall be such that automatic disconnection of the supply will occur within 0.2 s (400 V) or 0.4 s (230 V) (IEC 364-4-41 subclause 413.1.3.3). Only RCDs are permitted (IEC 364-5-551, subclause 551.4.4.2). Only TN-S systems are permitted (IEC 364-4-410, subclause 413.1.3.8).
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
An earthing rod is required to connect the PE conductor to the earth electrode ! The conditions for disconnection shall be verified by a trained electrician ! The function of the RCD shall be verified by a trained electrician !
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
No live conductor of the installation shall be directly connected to earth. Insulation monitoring to initiate an audible and/or visual signal shall be provided (IEC 364-4-41, subclause 413.1.5.4). Neither insulation monitoring nor disconnection in case of a double fault are necessary provided that all exposed conductive parts are connected via the PE conductor and earthing resistance 100 ; the voltage decreases to 50 V in the event of two faults occurring simultaneously (DIN VDE 0100-551 Annex ZB).
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
The insulation monitoring device recognizes and signals the first insulation fault at an early stage !
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
10
Usually an RCD is ineffective in an IT system, since the condition of operation is influenced by system leakage capacitances upstream and downstream the measuring current transformer ! The system leakage capacitance is not sufficiently high to trigger an RCD ! Condition of operation CV >> CN
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
11
Isolating transformer / motor generator with isolated windings (IEC 364-4-41 subclause 413.5.1.1). Live parts shall not be connected to earth (IEC 364-4-41, subclause 413.5.1.3). Socket outlets shall have a protective conductor contact (IEC 364-4-41, subclause 413.5.3.2). Except where supplying Class II equipment all flexible cables shall embody a protective conductor (IEC 364-4-41, subclause 413.5.3.3). The exposed conductive parts of the separated circuit shall be connected together by insulated nonearthed equipotential bonding conductors (IEC 364-4-41, subclause 413.5.3.1).
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
12
The leakage current ICE is caused by parasitic system leakage capacitances. In view of the fact that system leakage capacitances caused by generating sets usually are negligible, capacitive currents are only caused by cords and electrical equipment.
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
13
Summary
TN systems incorporating an RCD do not meet practical requirements owing to the fact that an earth rod is required a skilled electrician is required it cannot be applied by ordinary persons. In IT systems already the first fault is indicated by the insulation monitoring device, but an earth rod is required too ! Protection by electrical separation is the best solution where one item of electrical equipment is supplied ! Problem: protection by electrical separation where two or more items of electrical equipment are supplied ?
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
14
If several items of electrical equipment are connected, the following requirements in accordance with DIN VDE 0100-551 ANNEX ZB will apply: If the insulation resistance between live parts and the equipotential bonding drops below 100 /V (= 23 k/230 V) (value determined by insulation monitoring), disconnection of supply within 1 s is required. No limit to the cable length. Requirements for disconnection in the event of two faults occurring simultaneously must not be met. or as an alternative The product of the nominal voltage of the circuit in volts and the length in metres of the wiring system should not exceed 100 000, and the length of the wiring system should not exceed 500m and requirements for disconnection in the event of two faults occurring simultaneously must be met (IEC 364-4-41, subclause 413.5.3.4) or voltage must drop to 50 V in the event of a fault.
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
15
If two items of electrical equipment are connected, the following requirements in accordance with IEC 364-4-41 shall be met: Precautions shall be taken to protect the circuit against damage and insulation faults (subclause 413.5.3) The exposed conductive parts of the separated circuit shall be connected together by insulated non-earthed equipotential bonding conductors (subclause 413.5.3.1); All socket-outlets shall be provided with protective contacts (subclause 413.5.3.2); Except where supplying Class II equipment all flexible cables shall embody a protective conductor (subclause 413.5.3.3); The requirements for disconnection shall be met in the event of two faults occurring simultaneously (subclause 413.5.3.4);
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
16
In the event of two faults occurring simultaneously, disconnection shall be ensured within 0.2 s/0.4s! The breaking current is approx. 50 A when a 16 A circuit breaker is used ! -> insufficient personel safety The product of the nominal voltage of the circuit in volts and length in metres of the wiring system should not exceed 100 000Vm, and the length of the wiring should not exceed 500m -> limit to the cable length;
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
17
Monitoring by means of an insulation monitoring device. Disconnection within 1s, if insulation resistance is 100/V. No limit to the cable length. Requirements for disconnection must not be met in the event of two faults occuring simultaneously. Already the first fault is detected
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
18
The current flowing via the human body is limited to the value of the measuring current of the insulation monitoring
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
19
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
20
Example: pipe-laying
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
21
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
22
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
23
DIN VDE 0100-551 Annex ZB (Disconnection) 100 Ohm/Volt for 230V = 23 kOhm for 400V = 40 kOhm
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
24
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
25
Installation of an RCD Installation of an IMD Generator and equipment Class II Isolated windings Isolated windings Circuit breakers Isolated windings IMD
yes
approx.. 100m (2,5mm2) approx.. 100m (2,5mm2) approx.. 100m (2,5mm2) max. 500m approx.. 100m (2,5mm2) unlimited
high
yes
yes
unlimited
yes
very high
no
no
unlimited
no
very high
Protection by electrical separation (one consumer) Protection by electrical separation (two consumer) Circuit breaker Protection by electrical separation (two consumer) IMD with disconnection
no
no
one
no
very high
no
yes
unlimited
no
low
no
no
unlimited
no
very high
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
26
Summary
Protection by electrical separation is the best solution when one item of electrical equiment is supplied ! Protection by electrical separation with insulation monitoring and disconnection is the best solution when more then one item of electrical equipment is supplied.
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
27
Protection by electrical separation with insulation monitoring and disconnection 9 High personal safety is ensured 9 No skilled person is required 9 There is neither a limit to the number of items of electrical equipment nor a limit to the cable length 9 The mobile generator is ready for use immediately 9 An earth rod need not to be provided 9 The protective measure is applicable to each generator
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
28
Typ Nominal voltage Supply voltage Response value RALARM1 Response value RALARM2 Response time Notes
< 1s VerteilerEinbaugehuse
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
29
Complete solutions
Typ Nominal voltage Connection Plugs Response value RALARM Response time
VG12 AC 50...60Hz 230V Schuko Plug or other plugs Two Schuko plugs or other plugs 23 k < 1s
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
30
A-ISOMETER IR423
Measuring function
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
31
Sicherheitsverteiler VG12
Measuring function
Indication range LCD display 1k...1 M Connection monitoring system/earth Password Mounting adapter for different generators
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
32
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
33
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
34
Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com F80(GEN)_PPT_EN_200606 nderungen vorbehalten
35