Fig. 13.52 Diagram of System in The Vicinity of A 7000 MW Nuclear Power Plant
Fig. 13.52 Diagram of System in The Vicinity of A 7000 MW Nuclear Power Plant
Simulation: A 5 second simulation was performed G3 is seen to lose synchronism and becomes monotonically unstable
similar behaviour for the other 7 units of the nuclear plant
Analysis:
How does the system come apart as a result of instability? Out-of-step protection does not operate on G3
Line Protection:
Mho distance relays have zone 1 coverage of about 75% of line length, and zone 2 over-reach of about 125% of line length Apparent impedance enters the zone 2 relays at bus 1 and enters zone 1 and zone 2 relays at bus 7
zone 1 relay at bus 7 would trip circuit 3 at bus 7 and send a transfer trip signal to breakers at bus 1 which would then trip circuit 3 at bus 1 true for the companion 500 kV circuit (#4) which would be tripped in an identical manner
Following the loss of the 500 kV circuits (at approximately 0.8 seconds), the remaining 230 kV circuits would become extremely over-loaded and would be lost through protection actions, thereby completely isolating the unstable plant from the system Impedance plot shows the impedance swing crosses the circuit at a point about 84% of the line length from bus 1
represents the electrical centre following the disturbance, and is theoretically where separation occurs