Risk of Using Balancing Dampers or Long Lengths of Flexible Ducting

1) Manually adjusting balancing dampers can result in excessive noise and drafts at minimum airflow settings. 2) If a damper is adjusted to reduce pressure by 50 Pa at 100% airflow, friction losses follow the square law so pressure would be reduced by over 90 Pa at 30% airflow. 3) This could lead to pressures over 90 Pa in the diffuser neck at low airflow, causing issues.

Uploaded by

irfanbaig36
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views1 page

Risk of Using Balancing Dampers or Long Lengths of Flexible Ducting

1) Manually adjusting balancing dampers can result in excessive noise and drafts at minimum airflow settings. 2) If a damper is adjusted to reduce pressure by 50 Pa at 100% airflow, friction losses follow the square law so pressure would be reduced by over 90 Pa at 30% airflow. 3) This could lead to pressures over 90 Pa in the diffuser neck at low airflow, causing issues.

Uploaded by

irfanbaig36
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

A VERY GOOD REASON NOT TO USE MANUALLY ADJUSTABLE BALANCING DAMPERS:

100 Pa

100 Pa

.
CONTROL DISC AT 30% CONTROL DISC FULLY OPEN NECK PRESS 37.5 Pa NECK PRESS 94.4 Pa

As am extreme example, let us assume the duct has been correctly designed & the Duct Static Pressure has been set at 100 Pa as the balancing technician feels he would like a safety margin. (Typical VAV box thinking): AT 100%: Diffuser is typically selected for 50Pa (previous example) so normal friction losses expected in the flex is 12.5Pa. The balancing damper has to be adjusted to loose another 50Pa to get to the 37.5 Pa expected in the neck of the diffuser. AT 30%: The setting of the balancing damper has a different effect since Friction Losses over the balancing damper follow the square law:
Duct static Pressure Friction losses across damper & Flex combined @ 100% Flow STATIC PRESSURE IN THE NECK AT 100% FLOW: Friction losses across damper & Flex combined at 30% Flow STATIC PRESSURE IN THE NECK AT 30% FLOW IS THEREFORE = = = = = 100 Pa 62.5 Pa

37.5 Pa
62.5 (30/100)2 = 5.6 Pa

94.4 Pa

RESULT EXCESSIVE NOISE, DRAFTY CONDITIONS AND EXCESS COOLING AT MINIMUM FLOW STATUS