Special Features
High Reliability Compact Design
Enhanced insulating properties and reduced long-term operational costs by means of sealed metal enclosure filled with SF6 gas. Extensive experience in designing optimum phase and feeder spacing dimensions according to site conditions enable compact dimensions that reduce space requirements to less than 20% of conventional airinsulated substations.
Ensured personnel safety by earthed enclosure, numerous interlocks and lockout devices. Increased stability during earthquakes with a low center of gravity. Virtual elimination of long-term maintenance costs and contamination of critical components by means of SF6 gas-filled metal enclosures, automatic monitoring of operating mechanisms and SF6 gas system.
Safety
Assembly at factory and shipment in one complete bay dramatically reduces installation time and customer's costs. Minimized operation noise levels allow installation in urban and suburban indoor substations. Elimination of radio interference problems and individual painting of enclosures with the color of customer choice.
General
To meet the customer's various requirements of today's substations, we, HYOSUNG, design and manufacture a wide variety of SF6 Gas-Insulated-Switchgear(GIS) system. We believe that although many GIS manufacturers produce a product similar to ours, it is our ability of giving you a high quality system at a reasonable price that sets us apart. Our units are currently used in urban areas, closely built-up industrial areas, underground power substations of large commercial buildings, switchyards of power plants, as well as new or expanding substations. We, HYOSUNG, pride oureselves on our ability to design and manufacture a GIS that is 100% compatible with your existing and future needs anywhere in the world today. We design and construct a wide variety of high voltage SF6 GIS ranging from 25.8kV units to 800kV units, with short circuit ratings up to 63kA. All of our equipment complies with IEC, ANSI, IEEE and other international standards. We have shipped over 5,000 GIS bays to customers around the world.
04/05
Quality Assurance
3.1 Design Process
HYOSUNGs Research and Development activities are dedicated to providing our customers with the products in demand not only for today but for the future. The latest computer assisted software and systems are applied to the design analysis of each GIS for the best quality and reliability.
Clean Room
Dielectric Test
06/07
Rated voltage(kV) Type Rated interrupting current(kA) Lightning impulse withstand voltage(kV) AC withstand voltage(kV) Rated pressure (kPa / kg / G)
123/145
170
170
245 / 300
420 / 550
800
Three-phase Common-enclosure Type 25 / 31.5 / 40 550 / 650 230 / 275 490 / 5 123-145 Three-phase Common type 31.5 / 50 750 325 490 / 5 170 Three-phase Common type 31.5 / 50 750 325 490 / 5 170 Three-phase Isolated type 40 / 50 1050 460 490 / 5 245/300 Three-phase Isolated type
40 / 50 1425 / 1550 650 / 710 490 / 5 420 / 550 Three-phase Isolated type
Arrangement
* 800kV
GIS
1.1 4.5 3
4/5 11.5 6
10 15.5 7.0
08/09
10/11
Descriptions
CB(Circuit Breaker) ES(Earthing Switch) DS(Disconnector) CT(Current Transformer) VT(Voltage Transformer) Main Bus Operating Mechanism for CB Bushing
362kV & 800kV GIS under Commercial Operation Cross Section of Typical GIS 300-800kV
12/13
14/15
5.4 Busbars
To allow for greater compactness, HYOSUNG GIS utilize three-phase common-enclosure for voltage ratings from 25.8kV to 800kV and rated current up to 8,000A. The finger-type tulip connectors enable convenient plug-in and plug-out, while providing elasticity and tolerance. According to the rating current specified, the conductors are made of copper or aluminum and the enclosures are made of mild or stainless steel, or aluminum. The installation of bellows provides elasticity in assembly tolerance and protection against possible future foundation sinkage.
Busbar
The current transformer is the ring type (HYOSUNG maker) used for equipment protection. To prevent moisture, the ring types have epoxy-fiber-glass applied. The ring type current transformer can be used with both three-phase common-enclosure and isolated type GIS.
Earthing Switch
Enclosure Conductor
16/17
Voltage Transformer
5.7 Interfaces
HYOSUNG provides for customer use the connector, chamber, bushing and accessories that are necessary to connect any cable end. This facilitates future maintenance by allowing independent testing of key areas of HYOSUNG GIS without system degradation. Our engineers will design and install bushings used in gas-to-air, gas-to-oil, or standard cable connections. HYOSUNG provides the necessary connecting chamber, contacts, and bellows that are required to compensate for alignment errors and to absorb excess vibration.
Cable sealing end Cable Epoxy Cone SF6 Gas Shield Tulip Contact
Gas-to-Oil Bushing Bellows Conductor SF6 Gas Tulip Contact Transformer Bushing Transformer Oil
Gas-to-Air Bushing Terminal Upper Shield Bushing Conductor SF6 Gas Internal Shield Tulip Contact
18/19
Factory Storage
Site Installation
20/21
Safe Reliable
Inspection
1. Gas pressure and operating pressure check 2. Recording number of operations of CB and lightning arrester 1. Gas leakage test 2. Operating device inspection and lubrication 1. Detailed inspection of operating device 2. Internal check of CBs
Regular Inspection
Every 3 years
Compact
Detailed Inspection * 2
Every 6 years
*1 *2
Number of switching operations at rated current of circuit breaker Only CB portion is inspected. Busbar and disconnecting switch portions do not require inspection except for the operating device
Eco-friendly
Efficient Maintenance