0% found this document useful (0 votes)
273 views

Room Data Sheet

The document provides a data sheet with design conditions and specifications for various rooms in a building including HV room, water pump room, fire pump room, tel. room, elevator room, toilets, janitor/disabled toilet, refuse room, retail shop, and food & beverage mall. It lists details like the space temperature, internal lighting, cooling internal load, occupancy, infiltration rate, and outside air requirements for each area.

Uploaded by

coolth2
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
273 views

Room Data Sheet

The document provides a data sheet with design conditions and specifications for various rooms in a building including HV room, water pump room, fire pump room, tel. room, elevator room, toilets, janitor/disabled toilet, refuse room, retail shop, and food & beverage mall. It lists details like the space temperature, internal lighting, cooling internal load, occupancy, infiltration rate, and outside air requirements for each area.

Uploaded by

coolth2
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

Al Majaz Room Data Sheet External Design Condition Summer Winter : 46C Db / 29.

0C Wb : 12C

Area Description

Space Temperature

Internal Lighting W/m

HV ROOM WATER PUMP ROOM FIRE PUMP ROOM TEL. ROOM ELV. ROOM TOILETS JANITOR / DISABLED TOILET REFUSE ROOM SHOP - RETAIL SHOP - F & B MALL

30C 40% - 60%RH 30C 40% - 60%RH 30C 40% - 60%RH 24C 45% - 55%RH 24C 45% - 55%RH 24C 45% - 55%RH 24C 45% - 55%RH 16C 45% - 55%RH 24C 45% - 55%RH 24C 45% - 55%RH 24C 45% - 55%RH

Lights = 16 watts/m Lights = 16 watts/m Lights = 16 watts/m Lights = 16 watts/m Lights = 16 watts/m Lights = 10 watts/m Lights = 10 watts/m Lights = 15 watts/m Lights = 18 watts/m Lights = 15 watts/m Lights = 18 watts/m

Cooling Internal Load Occupancy Remarks m / per. (No. of Per) (sensible / latent) Infiltration rate ACH

Power W/m

Misc. = 150 watts/m = motor rating / efficiency = motor rating / efficiency Misc. = 150 watts/m Misc. = 150 watts/m Misc. = 10 watts/m Misc. = 5 watts/m Misc. = 10 watts/m Misc. = 15 watts/m Misc. = 15 watts/m Misc. = 15 watts/m

1 Person 1 Person 1 Person 1 Person 1 Person As per no. of fixtures 1 Person 0 Persons 6.67 1 2.5

75/55 75/55 75/55 75/55 75/55 75/55 75/55 75/55 80/80 75/55

0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25

Ouside Air Extract Remarks

lps / person

l/s/m

ACH

supply temp C db

0.3 0.3 0.3 0.3 0.3 12 12

Ambient Temp. Ambient Temp. Ambient Temp. Ambient Temp. Ambient Temp. Ambient Temp. Ambient Temp. Ambient Temp. 15 ACH 15 ACH 6 ACH By Tenant By Tenant

7.8 4.7 4.6

Ambient Temp. Ambient Temp. Ambient Temp.