0% found this document useful (0 votes)
300 views5 pages

Cable Sizing

The document provides a cable schedule for a 20 MW solar PV plant in Phalodi, Rajasthan. It lists 9 cable tags from P1 to P9 specifying the from and to locations, core numbers, cable size, run length and total length. The total length of 3.5C x 300 AL cable is 3894.3 meters. The second page continues the cable schedule and provides cable sizes and their resistance and reactance values. The last section gives the derating factors used to determine cable currents.

Uploaded by

Pravin Narkhede
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
300 views5 pages

Cable Sizing

The document provides a cable schedule for a 20 MW solar PV plant in Phalodi, Rajasthan. It lists 9 cable tags from P1 to P9 specifying the from and to locations, core numbers, cable size, run length and total length. The total length of 3.5C x 300 AL cable is 3894.3 meters. The second page continues the cable schedule and provides cable sizes and their resistance and reactance values. The last section gives the derating factors used to determine cable currents.

Uploaded by

Pravin Narkhede
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

PROJECT:

20 MW PV SOLAR PLANT AT PHALODI, RAJASTHAN

Sr. No.

Cable
Tag

P1

P2

P3

P4

P5

P6

P7

P8

P9

LT CABLE SCHEDULE
MEPC-1146(A)-T-EN-E-1-CBL-06

From

To

Core Nos.

Location

Equipment

Term.
No.

Location

Equipment

Term.
No.

car port

cluster-1

car port

ACDB

car port

WALK WAY

WALK WAY

WALK WAY

WALK WAY

WALK WAY

WALK WAY

WALK WAY

ACDB

SUB ACDB-1

SUB ACDB-2

SUB ACDB-6

SUB ACDB-5

SUB ACDB-4

SUB ACDB-3

ACDB

car port

WALK WAY

TRANSFO

SUB ACDB-2

WALK WAY

WALK WAY

ACDB

SUB ACDB-5

WALK WAY

WALK WAY

SUB ACDB-4

SUB ACDB-3

R
Y

WALK WAY

WALK WAY

ACDB

TRAFO

Cable Size
(C x Sq. mm)

RUN

MAHINDRA EPC

Length per run Total Length


(Mtr.)
(Mtr.)

Load

Voltage

Kw

kV

Pf

Full load Derating Cable current Design Resistance at 90


Current Factor
Rating
current
deg C

Reactance

Voltage drop

cable
suitability

Amp

Amp

Amp

R (ohm/km)

R (ohm/km)

Id>Ifl

3.5C X 300 AL

350

350

120.000

0.415

0.90

185.5

0.60

371

223

0.128

0.071

3.96%

ok

3.5C X 300 AL

35

140

450.000

0.415

0.90

695.6

0.60

1484

890

0.128

0.071

0.37%

ok

3.5C X 300 AL

275

275

100.000

0.415

0.90

154.6

0.60

371

223

0.128

0.071

2.59%

ok

3.5C X 300 AL

317

634

200.000

0.415

0.90

309.2

0.60

742

445

0.128

0.071

2.99%

ok

3.5C X 300 AL

277

277

100.000

0.415

0.90

154.6

0.60

371

223

0.128

0.071

2.61%

ok

3.5C X 300 AL

275

550

200.000

0.415

0.90

309.2

0.60

742

445

0.128

0.071

2.59%

ok

3.5C X 300 AL

272

815

300.000

0.415

0.90

463.7

0.60

1113

668

0.128

0.071

2.56%

ok

3.5C X 300 AL

218

653

400.000

0.415

0.90

618.3

0.60

1113

668

0.128

0.071

2.74%

ok

3.5C X 300 AL

40

200

600.000

0.415

0.90

927.5

0.60

1855

1113

0.128

0.071

0.45%

ok

SHT. 1 / 5

PROJECT:
20 MW PV SOLAR PLANT AT PHALODI, RAJASTHAN

Sr. No.

Cable
Tag

LT CABLE SCHEDULE
MEPC-1146(A)-T-EN-E-1-CBL-06

From
Location

To
Equipment

Term.
No.

Location

Core Nos.
Equipment

Cable Size
(C x Sq. mm)

RUN

Length per run Total Length


(Mtr.)
(Mtr.)

Term.
No.

SHT. 2 / 5

MAHINDRA EPC

Load

Voltage

Kw

kV

Pf

Full load Derating Cable current Design Resistance at 90


Current Factor
Rating
current
deg C
Amp

Amp

Amp

R (ohm/km)

Reactance

Voltage drop

cable
suitability

R (ohm/km)

Id>Ifl

Sum of Total Length (Mtr.)


Cable Size (C x Sq. mm)
3.5C X 300 AL
Grand Total

Total
3894.3
3894

Size

Current

4C X 50 AL

134

0.82

0.0792

4C X 70 AL

165

0.567

0.0752

4C X 95 AL

198

0.41

0.0734

4C X 185 AL

285

0.21

0.0727

3.5C X 400 AL
3.5C X 300 AL
3.5C X 240 AL
4C X 35 AL
1C X 630 AL

437

0.1

0.0705

371

0.128

0.0711

325

0.151

0.0719

115

1.11

0.0794

666

0.06

0.0843

4C X 4 CU

44

5.9

0.0947

4C X 10 CU

72

2.34

0.0852

4C X 16 AL

73

2.44

0.0815

3C X 4 CU

44

5.9

0.0947

Derating factor
Variation in ground temp
0.91
Group Derating
0.62
Thermal Resistivity
1
Depth of laying
1
Total
0.600