NSCP Chapter 3 Version 5
NSCP Chapter 3 Version 5
\
|
+ + =
A
h A
d
3 . 4
1 1
2
(305-1)
Where:
b S
P
A
1
2.3
=
b = diameter of round post or footing or diagonal
dimension of square post or footing, meters.
d = depth of embedment in earth in meters but not
over 3.5 meters for purpose of computing
lateral pressure.
h = distance in meters from ground surface to point
of application of P.
P = applied lateral force in kilonewtons .
S
1
= allowable lateral soil-bearing pressure as set
forth in Table 304-1 based on a depth of one
third the depth of embedment (kPa).
S
3
= allowable lateral soil-bearing pressure as set
forth in Table 304-1 based on a depth equal to
the depth of embedment (kPa).
305.7.2.2 Constrained. The following formula may
be used to determine the depth of embedment required to
resist lateral loads where constraint is provided at the
ground surface, such as a rigid floor or pavement.
b S
Ph
25 4 d
3
2
. = (305-2)
305.7.2.3 Vertical load. The resistance to vertical
loads is determined by the allowable soil-bearing pressure
set forth in Table 304-1.
305.7.3 Backfill. The backfill in the annular space
around column not embedded in poured footings shall be by
one of the following methods:
1. Backfill shall be of concrete with an ultimate
strength of 15 MPa at 28 days. The hole shall not be
less than 100 mm larger than the diameter of the
column at its bottom or 100 mm larger than the
diagonal dimension of a square or rectangular
column.
2. Backfill shall be of clean sand. The sand shall be
thoroughly compacted by tamping in layers not more
than 200 mm in thickness.
305.7.4 Limitations. The design procedure outlined in
this section shall be subject to the following limitations:
305.7.4.1 The frictional resistance for retaining walls
and slabs on silts and clays shall be limited to one half of
the normal force imposed on the soil by the weight of the
footing or slab.
305.7.4.1 Posts embedded in earth shall not be used to
provide lateral support for structural or nonstructural
materials such as plaster, masonry or concrete unless
bracing is provided.
305.8 GRILLAGE FOOTINGS
When grillage footings of structural steel shapes are used
on soils, they shall be completely embedded in concrete.
Concrete cover shall be at least 150 mm on the bottom and
at least 100 mm at all other points.
305.9 BLEACHER FOOTINGS
Footings for open-air seating facilities shall comply with
Chapter 3.
EXCEPTI ONS:
Temporary open-air portable bleachers may be supported
upon wood sills or steel plates placed directly upon the
ground surface, provided soil pressure does not exceed 50
kPa.
PILES - GENERAL REQUIREMENTS 3-14
National Structural Code of the Philippines, Volume 1
SECTION 306 - PILES - GENERAL
REQUIREMENTS
306.1 GENERAL
Pile foundations shall be designed and installed on the basis
of a foundation investigation as defined in Section 303
where required by the building official.
The investigation and report provisions of Section 303 shall
be expanded to include, but not be limited to, the following:
1. Recommended pile types and installed capacities.
2. Driving criteria.
3. Installation procedures.
4. Field inspection and reporting procedures (to include
procedures for verification of the installed bearing
capacity where required).
5. Pile load test requirements.
The use of piles not specifically mentioned in this chapter
shall be permitted, subject to the approval of the building
official upon submission of acceptable test data,
calculations or other information relating to the properties
and load-carrying capacities of such piles.
306.2 INTERCONNECTION
Individual pile caps and caissons of every structure
subjected to seismic forces shall be interconnected by ties.
Such ties shall be capable of resisting, in tension or
compression, a minimum horizontal force equal to 10
percent of the largest column vertical load.
EXCEPTI ON:
Other approved methods may be used where it can be
demonstrated that equivalent restraint can be provided.
306.3 DETERMINATION OF ALLOWABLE
LOADS
The allowable axial and lateral loads on piles shall be
determined by an approved formula, by a foundation
investigation or by load tests. Static axial compressive pile
load test shall be in accordance with ASTM Standard D-
1143, and lateral load testing of piles shall conform with
ASTM Standard D-3966. Dynamic pile tests shall be in
accordance with ASTM Standard D-4945. Static axial
tensile load testing to determine the uplift capacity of pile-
soil systems shall be in accordance with ASTM Standard
D-3689.
306.4 STATIC LOAD TEST
Static axial compressive pile load test shall be in
accordance with ASTM Standard D-1143. The building
official may require that the test be conducted under the
supervision of a registered civil engineer experienced and
knowledgeable in the practice of static pile load testing
When the allowable axial compressive load of a single pile
is determined by a static load test, one of the following
methods shall be used:
Method 1. It shall not exceed 50 percent of the yield point
under test load. The yield point shall be defined as that
point at which an increase in load produces a
disproportionate increase in settlement.
Method 2. It shall not exceed one half of the load, which
causes a net settlement, after deducting rebound, of
0.03mm/kN of test load, which has been applied for a
period of at least 24 hours.
Method 3. It shall not exceed one half of that load under
which, during a 40-hour period of continuous load
application, no additional settlement takes place.
306.5 DYNAMIC LOAD TEST
High-strain dynamic load test may be used to determine the
bearing capacity of piles, in accordance with ASTM
Standard D-4945. The building official may require that
the test be conducted by a registered civil engineer
experienced and knowledgeable in the practice of dynamic
load testing.
306.6 COLUMN ACTION
All piles standing unbraced in air, water or material not
capable of lateral support shall conform with the applicable
column formula as specified in this code. Such piles driven
into firm ground may be considered fixed and laterally
supported at 1.5 meters below the ground surface and in
soft material at 3 meters the ground surface unless
otherwise prescribed by the building official after a
foundation investigation by an approved agency.
306.7 GROUP ACTION
Consideration shall be given to the reduction of allowable
pile load when piles are placed in groups.
Where soil conditions make such load reductions advisable
or necessary, the allowable axial and lateral loads
determined for a single pile shall be reduced by any rational
method or formula submitted to the building official.
PILES - GENERAL REQUIREMENTS 3-15
National Structural Code of the Philippines, Volume 1
306.8 PILES IN SUBSIDING AREAS
Where piles are driven through subsiding fills or other
subsiding strata and derive support from underlying firmer
materials, consideration shall be given to the downward
frictional forces, which may be imposed on the piles by the
subsiding upper strata.
Where the influence of subsiding fills is considered as
imposing loads on the pile, the allowable stresses specified
in this chapter may be increased if satisfactory
substantiating data are submitted.
306.9 JETTING
Jetting shall not be used except where and as specifically
permitted by the building official. When used, jetting shall
be carried out in such a manner that the carrying capacity of
existing piles and structures shall not be impaired. After
withdrawal of the jet, piles shall be driven down until the
required resistance is obtained.
306.10 PROTECTION OF PILE MATERIALS
Where the boring records of site conditions indicate
possible deleterious action on pile materials because of soil
constituents, changing water levels or other factors, such
materials shall be adequately protected by methods or
processes approved by the geotechnical engineer.
The effectiveness of such methods or processes for the
particular purpose shall have been thoroughly established
by satisfactory service records or other evidence, which
demonstrates the effectiveness of such protective measures.
306.11 ALLOWABLE LOADS
The allowable loads based on soil conditions shall be
established in accordance with Section 306.
EXCEPTI ON:
Any uncased cast-in-place pile may be assumed to develop
a frictional resistance equal to one sixth of the bearing
value of the soil material at minimum depth as set forth in
Table 305-1 but not to exceed 25 kPa unless a greater value
is allowed by the building official after a foundation
investigation as specified in Section 303 is submitted.
Frictional resistance and bearing resistance shall not be
assumed to act simultaneously unless recommended after a
foundation investigation as specified in Section 303.
306.12 USE OF HIGHER ALLOWABLE PILE
STRESSES
Allowable compressive stresses greater than those specified
in Section 307 shall be permitted when substantiating data
justifying such higher stresses are submitted to and
approved by the building official. Such substantiating data
shall be included in the foundation investigation report in
accordance with Section 306.1.
PILES - SPECIFIC REQUIREMENTS 3-16
National Structural Code of the Philippines, Volume 1
SECTION 307 - PILES - SPECIFIC
REQUIREMENTS
307.1 ROUND WOOD PILES
307.1.1 Material. Except where untreated piles are
permitted, wood piles shall be pressure treated. Untreated
piles may be used only when it has been established that the
cutoff will be below lowest groundwater level assumed to
exist during the life of the structure.
307.1.2 Allowable stresses. The allowable unit stresses
for round woodpiles shall not exceed those set forth in
Chapter 6.
The allowable values listed in, for compression parallel to
the grain at extreme fiber in bending are based on load
sharing as occurs in a pile cluster. For piles which support
their own specific load, a safety factor of 1.25 shall be
applied to compression parallel to the grain values and 1.30
to extreme fiber in bending values.
307.2 UNCASED CAST-IN-PLACE
CONCRETE PILES
307.2.1 Material. Concrete piles cast in place against
earth in drilled or bored holes shall be made in such a
manner as to ensure the exclusion of any foreign matter and
to secure a full-sized shaft.
The length of such pile shall be limited to not more than 30
times the average diameter. Concrete shall have a specified
compressive strength f
c
of not less than 17.5 MPa.
EXCEPTI ON:
The length of pile may exceed 30 times the diameter
provided the design and installation of the pile foundation
is in accordance with an approved foundation investigation
report.
307.2.2 Allowable stresses. The allowable compressive
stress in the concrete shall not exceed 0.33f
c
. The
allowable compressive stress of reinforcement shall not
exceed 34 percent of the yield strength of the steel or 175
MPa.
307.3 METAL-CASED CONCRETE PILES
307.3.1 Material. Concrete used in metal-cased concrete
piles shall have a specified compressive strength f
c
of not
less than 17.5 MPa.
307.3.2 Installation. Every metal casing for a concrete
pile shall have a sealed tip with a diameter of not less than
200 mm.
Concrete piles cast in place in metal shells shall have shells
driven for their full length in contact with the surrounding
soil and left permanently in place. The shells shall be
sufficiently strong to resist collapse and sufficiently
watertight to exclude water and foreign material during the
placing of concrete.
Piles shall be driven in such order and with such spacing as
to ensure against distortion of or injury to piles already in
place. No pile shall be driven within four and one-half
average pile diameters of a pile filled with concrete less
than 24 hours old unless approved by the geotechnical
engineer.
307.3.3 Allowable stresses. Allowable stresses shall not
exceed the values specified in Section 307.2.2, except that
the allowable concrete stress may be increased to a
maximum value of 0.40f
c
for that portion of the pile
meeting the following conditions:
1. The thickness of the metal casing is not less than 1.7
mm (No. 14 carbon sheet steel gage).
2. The casing is seamless or is provided with seams of
equal strength and is of a configuration that will
provide confinement to the cast-in-place concrete.
3. The specified compressive strength f
c
shall not
exceed 35 MPa and the ratio of steel minimum
specified yield strength F
y
to concrete specified
compressive strength f
c
shall not be less than 6.
4 The pile diameter is not greater than 400 mm.
307.4 PRECAST CONCRETE PILES
307.4.1 Materials. Precast concrete piles shall have a
specified compressive strength f
c
of not less than 20 MPa,
and shall develop a compressive strength of not less than 20
MPa before driving.
307.4.2 Reinforcement ties. The longitudinal
reinforcement in driven precast concrete piles shall be
laterally tied with steel ties or wire spirals. Ties and spirals
shall not be spaced more than 75 mm apart, center to center,
for a distance of 600 mm from the ends and not more than
200 mm elsewhere. The gage of ties and spirals shall be as
follows:
1. For piles having a diameter of 400 mm or less, wire
shall not be smaller than 5.5 mm (No. 5 B.W.gage).
PILES - SPECIFIC REQUIREMENTS 3-17
National Structural Code of the Philippines, Volume 1
2. For piles, having a diameter of more than 400 mm
and less than 500 mm, wire shall not be smaller than
6 mm (No.4 B.W.gage).
3. For piles having a diameter of 500 mm and larger,
wire shall not be smaller than 6.5 mm
(No.3 B.W. gage).
307.4.3 Allowable stresses. Precast concrete piling shall
be designed to resist stresses induced by handling and
driving as well as by loads. The allowable stresses shall not
exceed the values specified in Section 307.2.2.
307.5 PRECAST PRESTRESSED CONCRETE
PILES (PRETENSIONED)
307.5.1 Materials. Precast prestressed concrete piles
shall have a specified compressive strength f
c
of not less
than 35 MPa and shall develop a compressive strength of
not less than 27 MPa before driving.
307.5.2 Reinforcement
307.5.2.1 Longitudinal reinforcement. The
longitudinal reinforcement shall be high-tensile seven-wire
strand conforming to ASTM Standards. Longitudinal
reinforcement shall be laterally tied with steel ties or wire
spirals.
307.5.2.2 Transverse reinforcement. Ties or spiral
reinforcement shall not be spaced more than 75 mm apart,
center to center, for a distance of 600 mm from the ends
and not more than 200 mm elsewhere.
At each end of the pile, the first five ties or spirals shall be
spaced 25 mm center to center.
For piles having a diameter of 600 mm or less, wire shall
not be smaller than 5.5 mm (No. 5 B.W.gage).
For piles having a diameter greater than 600 mm but less
than 900 mm, wire shall not be smaller than 6 mm
(No. 4 B.W.gage).
For piles having a diameter greater than 900 mm, wire shall
not be smaller than 6 mm (No.3 B.W.gauge).
307.5.3 Allowable stresses. Precast prestressed piling
shall be designed to resist stresses induced by handling and
driving as well as by loads. The effective prestress in the
pile shall not be less than 2.5 MPa for piles up to 10 meters
in length, 4 MPa for piles up to 15 meters in length, and 5
MPa for piles greater than 15 meters in length.
The compressive stress in the concrete due to externally
applied load shall not exceed:
f
c
= 0.33f
c
- 0.27 f
pc
(307-1)
Where:
f
pc
= effective prestress stress on the gross section.
Effective prestress shall be based on an assumed loss of 200
MPa in the prestressing steel. The allowable stress in the
prestressing steel shall not exceed the values specified in
Section 418.5.
307.6 STRUCTURAL STEEL PILES
307.6.1 Material. Structural steel piles, steel pipe piles
and fully welded steel piles fabricated from plates shall
conform to one of the material specifications listed in
Section 501.3.
307.6.2 Allowable stresses. The allowable axial stresses
shall not exceed 0.35 of the minimum specified yield
strength F
y
or 85 MPa, whichever is less.
EXCEPTI ON:
When justified in accordance with Section 306.12, the
allowable axial stress may be increased above 85 MPa and
0.35F
y
, but shall not exceed 0.5F
y
.
307.6.3 Minimum dimensions. Sections of driven H-
piles shall comply with the following:
1. The flange projection shall not exceed 14 times the
minimum thickness of metal in either the flange or
the web, and the flange widths shall not be less than
80 percent of the depth of the section.
2. The nominal depth in the direction of the web shall
not be less than 200 mm.
3. Flanges and webs shall have a minimum nominal
thickness of 10 mm.
Sections of driven pipe piles shall have an outside diameter
of not less than 250 mm and a minimum thickness of not
less than 6 mm.
307.7 CONCRETE-FILLED STEEL PIPE
PILES
307.7.1 Material. The steel pipe of concrete-filled steel
pipe piles shall conform to one of the material
specifications listed in Section 501.3. The concrete in
PILES - SPECIFIC REQUIREMENTS 3-18
National Structural Code of the Philippines, Volume 1
concrete-filled steel pipe piles shall have a specified
compressive strength f
c
of not less than 17.5 MPa.
307.7.2 Allowable stresses. The allowable axial stresses
shall not exceed 0.35 of the minimum specified yield
strength F
y
of the steel plus 0.33 of the specified
compressive strength f
c
of concrete, provided F
y
shall not
be assumed greater than 250 MPa for computational
purposes.
EXCEPTI ON:
When justified in accordance with Section 306.12, the
allowable stresses may be increased to 0.50 F
y
.
307.7.3 Minimum dimensions. Driven piles of uniform
section shall have a nominal outside diameter of not less
than 200 mm.
FOUNDATION CONSTRUCTION - SEISMIC ZONE 4 3-19
National Structural Code of the Philippines, Volume 1
SECTION 308 - FOUNDATION
CONSTRUCTION-SEISMIC ZONE 4
308.1 GENERAL
In Seismic Zones 4, the further requirements of this section
shall apply to the design and construction of foundations,
foundation components and the connection of
superstructure elements thereto. See Section 421.9 for
additional requirements for structural concrete foundations
resisting seismic forces.
308.2 FOUNDATION AND GEOTECHNICAL
INVESTIGATIONS
Where a structure is determined to be in Seismic Zone 4 in
accordance with Section 208.4, an investigation shall be
conducted and shall include an evaluation of the following
potential hazards resulting from earthquake motions: slope
instability, liquefaction and surface rupture due to faulting
or lateral spreading.
In addition, the following investigations shall also be met:
1. A determination of lateral pressures on basement and
retaining walls due to earthquake motions.
2. An assessment of potential consequences of any
liquefaction and soil strength loss, including estimation
of differential settlement, lateral movement or
reduction in foundation soil-bearing capacity, and shall
address mitigation measures. Such measures shall be
given consideration in the design of the structure and
can include but are not limited to ground stabilization,
selection of appropriate foundation type and depths,
selection of appropriate structural systems to
accommodate anticipated displacements or any
combination of these measures. The potential for
liquefaction and soil strength loss shall be evaluated for
site peak ground acceleration magnitudes and source
characteristics consistent with the design earthquake
ground motions. Peak ground acceleration shall be
determined from a site-specific study taking into
account soil amplification effects, as specified in
Section 208.4.
308.3 FOOTINGS AND FOUNDATIONS
Where a structure is assigned to Seismic Zone 4 in
accordance with Section 208.4, individual spread footings
founded on soil defined in Section 208.4.3 as Soil profile
Type S
E
or S
F
shall be interconnected by ties. Ties shall be
capable of carrying, in tension or compression, unless it is
demonstrated that equivalent restraint is provided by
reinforced concrete beams within slabs on grade or
reinforced concrete slabs on grade.
308.4 PIER AND PILE FOUNDATIONS
Where a structure is assigned to Seismic Zone 4 in
accordance with Section 208.4, the following shall apply.
Individual pile caps, piers or piles shall be interconnected
by ties. Ties shall be capable of carrying, in tension and
compression, unless it can be demonstrated that equivalent
restraint is provided by reinforced concrete beams within
slabs on grade, reinforced concrete slabs on grade,
confinement by competent rock, hard cohesive soils or very
dense granular soils. Concrete shall have a specified
compressivestrength of not less than 3,000 psi (20.68 MPa)
at 28 days.
Exception: Piers supporting foundation walls, isolated
interior posts detailed so the pier is not subject to lateral
loads, lightly loaded exterior decks and patios and
occupancy category IV and V specified in Section 103 not
exceeding two stories of light-frame construction, are not
subject to interconnection if it can be shown the soils are of
adequate stiffness, subject to the approval of the building
official.
308.4.1 Connection to pile cap. For piles required to resist
uplift forces or provide rotational restraint, design of
anchorage of piles into the pile cap shall be provided
considering the combined effect of axial forces due to uplift
and bending moments due to fixity to the pile cap.
Anchorage shall develop a minimum of 25 percent of the
strength of the pile in tension. Anchorage into the pile cap
shall be capable of developing the following: In the case of
uplift, the lesser of the nominal tensile strength of the
longitudinal reinforcement in a concrete pile, or the
nominal tensile strength of a steel pile, or the pile uplift soil
nominal strength factored by 1.3 or the axial tension force
resulting from the load combinations of Section 203. In the
case of rotational restraint, the lesser of the axial and shear
forces, and moments resulting from the load combinations
of Section 203 or development of the full axial, bending
and shear nominal strength of the pile.
308.4.2 Design details for piers, piles and grade beams.
Piers or piles shall be designed and constructed to withstand
maximum imposed curvatures from earthquake ground
motions and structure response. Curvatures shall include
free-field soil strains modified for soil-pile-structure
interaction coupled with pier or pile deformations induced
by lateral pier or pile resistance to structure seismic forces.
Concrete piers or piles on soil type S
E
or S
F
sites, as
determined in Section 208.4.3, shall be designed and
detailed in accordance with Sections 410 within seven pile
diameters of the pile cap and the interfaces of soft to
FOUNDATION CONSTRUCTION - SEISMIC ZONE 4 3-20
National Structural Code of the Philippines, Volume 1
medium stiff clay or liquefiable strata. Grade beams shall
be designed as beams in accordance Section 4. When grade
beams have the capacity to resist the forces from the load
combinations in Section 203.
308.4.3 Flexural strength. Where the vertical lateral-
force-resisting elements are columns, the grade beam or
pile cap flexural strengths shall exceed the column flexural
strength. The connection between batter piles and grade
beams or pile caps shall be designed to resist the nominal
strength of the pile acting as a short column. Batter piles
and their connection shall be capable of resisting forces and
moments from the load combinations of Section 203.
308.5 DRIVEN PILE FOUNDATIONS
308.5.1 Precast Concrete Piles. Where a structure is
assigned to Seismic Zone 4 the longitudinal reinforcement
with a minimum steel ratio of 0.01 shall be provided
throughout the length of precast concrete piles. Within three
pile diameters of the bottom of the pile cap, the longitudinal
reinforcement shall be confined with closed ties or spirals
of a minimum 3/8 inch (9.5 mm) diameter. Ties or spirals
shall be provided at a maximum spacing of eight times the
diameter of the smallest longitudinal bar, not to exceed 6
inches (152 mm). Throughout the remainder of the pile, the
closed ties or spirals shall have a maximum spacing of 16
times the smallest longitudinal bar diameter not to exceed 8
inches (203 mm).
308.5.2 Precast Prestressed piles. Where a structure is
assigned to Seismic Zone 4, the following shall apply. The
minimum volumetric ratio of spiral reinforcement shall not
be less than 0.007 or the amount required by the following
formula for the upper 20 feet (6096 mm) of the pile.
0.12
s c yh
f f =
(308.5.1)
Where:
f
c
= Specified compressive strength of concrete, psi
(MPa).
f
yh
= Yield strength of spiral reinforcement,
psi (586 MPa).
s
= Spiral reinforcement index (vol. spiral/vol.
core).
At least one-half the volumetric ratio required by Equation
4-1 shall be provided below the upper 20 feet (6096 mm) of
the pile. The pile cap connection by means of dowels. Pile
cap connection by means of developing pile reinforcing
strand is permitted provided that the pile reinforcing strand
results in a ductile connection.
Where the total pile length in the soil is 35 feet (10 668
mm) or less, the lateral transverse reinforcement in the
ductile region shall occur through the length of the pile.
Where the pile length exceeds 35 feet (10 668 mm), the
ductile pile region shall be taken as the greater of 35 feet
(10 668 mm) or the distance from the underside of the pile
cap to the point of zero curvature plus three times the least
pile dimension.
In the ductile region, the center-to-center spacing of the
spirals or hoop reinforcement shall not exceed one-fifth of
the least pile dimension, six times the diameter of the
longtitudinal strand, or 8 inches (203 mm), whichever is
smaller.
Circular spiral reinforcement shall be spliced by lapping
one full turn and bending the end of the spiral to a 90-
degree hook or by use of a mechanical or welded splice.
Where the transverse reinforcement consists of circular
spirals, the volumetric ratio of spiral transverse
reinforcement in the ductile region shall comply with the
following:
1 1.4
0.12 1
2
g
c
s
yh ch c g
A
f P
f A f A
(
| |
=
( |
( \ .
(308.5.2)
but not less than:
1 1.4
0.12
2
c
s
yh c g
f P
f f A
(
=
(
(
(308.5.3)
and need not exceed:
0.021
s
=
(308.5.4)
Where:
A
g
= Pile cross-sectional area, square inches
(mm2).
A
ch
= Core area defined by spiral outside diameter,
square inches (mm2).
f
c
= Specified compressive strength of concrete,
psi (MPa).
f
yh
= Yield strength of spiral reinforcement
P = Axial load on pile, pounds (kN).
s
= Volumetric ratio (vol. spiral/ vol. core).
This required amount of spiral reinforcement is permitted to
be obtained by providing an inner and outer spiral. When
transverse reinforcement consists of rectangular hoops and
cross ties, the total cross-sectional area of lateral transverse
reinforcement in the ductile region with spacings, and
perpendicular to dimension, hc, shall conform to:
1
0.3 1 1.4
2
g
c
sh c
yh ch c g
A
f P
A s h
f A f A
| | (
| |
= | ( |
|
( \ .
\ .
(308.5.5)
but not less than:
FOUNDATION CONSTRUCTION - SEISMIC ZONE 4 3-21
National Structural Code of the Philippines, Volume 1
1 1.4
0.12
2
c
sh c
yh c g
f P
A s h
f f A
| | (
= + | (
|
(
\ .
(308.5.6)
where:
f
yh
= 70,000 psi (483 MPa).
h
c
= Cross-sectional dimension of pile core
measured center to center of hoop
reinforcement, inch (mm).
s = Spacing of transverse reinforcement measured
along length of pile, inch (mm).
A
sh
= Cross-sectional area of tranverse
reinforcement, square inches (mm2).
f
c
= Specified compressive strength of concrete,
psi (MPa).
The hoops and cross ties shall be equivalent to deformed
bars not less than 10mm in size. Rectangular hoop ends
shall terminate at a corner with seismic hooks. Outside of
the length of the pile requiring transverse confinement
reinforcing, the spiral or hoop reinforcing with a volumetric
ratio not less than one-half of that required for transverse
confinement reinforcing shall be provided.
308.6 CAST-IN-PLACE CONCRETE
FOUNDATIONS
Where a structure is assigned to Seismic Zone 4 a minimum
longitudinal reinforcement ratio of 0.005 shall be provided
for uncased cast-in-place drilled or augered concrete piles,
piers or caissons in the top one-half of the pile length a
minimum length of 10 feet (3048 mm) below ground or
throughout the flexural length of the pile, whichever length
is greatest. The flexural length shall be taken as the length
of the pile to a point where the concrete section cracking
moment strength multiplied by 0.4 exceeds the required
moment strength at that point. There shall be a minimum of
four longitudinal bars with transverse confinement
reinforcement provided in the pile within three times the
least pile dimension of the bottom of the pile cap. A
transverse spiral reinforcement ratio of not less than one-
half of that required in Section 410 for other than Soil
Profile Type S
E
, S
F
or as determined in Section 208.4.3 or
liquefiable sites is permitted. Tie spacing throughout the
remainder of the concrete section shall neither exceed 12-
longitudinal-bar diameters, one-half the least dimension of
the section, nor 12 inches (305 mm). Ties shall be a
minimum of 10mm bars for piles with a least dimension up
to 20 inches (508 mm), and 12mm bars for larger piles.