0% found this document useful (0 votes)
747 views

Type 2 Co-Ordination Chart

This document provides a type 2 coordination table for motor protection. It lists motors of varying power ratings and currents. For each motor, it specifies the corresponding manual motor starter or miniature circuit breaker type, instantaneous tripping current, contactor type, and overload relay type and current setting range. The table is for a 400V system with a short circuit current rating of 50kA and direct online nonsilent starting.

Uploaded by

born2engineer
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
747 views

Type 2 Co-Ordination Chart

This document provides a type 2 coordination table for motor protection. It lists motors of varying power ratings and currents. For each motor, it specifies the corresponding manual motor starter or miniature circuit breaker type, instantaneous tripping current, contactor type, and overload relay type and current setting range. The table is for a 400V system with a short circuit current rating of 50kA and direct online nonsilent starting.

Uploaded by

born2engineer
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Type 2 Co-ordination Table

Type 2 Co-ordination Table

SCPD type : MCB


Rated voltage : 400 V
Short circuit current : 50 kA
Starting type : DOL-NS
Coordination type : IEC Type 2
Overload relay : EOL
Motor
Rated Power Rated Current
[kW]
[A]
0.06
0.2
0.09
0.3
0.12
0.44
0.18
0.6
0.25
0.85
0.37
1.1
0.55
1.5
0.75
1.9
1.1
2.7
1.5
3.6
2.2
4.9
3
6.5
4
8.5
5.5
11.5
7.5
15.5
11
22
15
29
* with DB16E

Miniatured Circuit Breakers


Instantaneous Tripping Current
Type
[A]
MO132-0.25
2.44
MO132-0.4
3.9
MO132-0.63
6.14
MO132-1.0
11.5
MO132-1.0
11.5
MO132-1.6
18.4
MO132-1.6
18.4
MO132-2.5
28.75
MO132-4.0
50
MO132-4.0
50
MO132-6.3
78.75
MO132-10
125
MO132-10
125
MO132-16
200
MO132-16
200
MO132-25
313
MO132-32
400

Contactor
Type
AF09
AF09
AF09
AF09
AF09
AF09
AF09
AF09
AF26
AF26
AF26
AF26
AF26
AF30
AF30
AF30
AF30

Overload Relay
Current setting range
Type
[A]
EF19-0.32
0.10 - 0.32
EF19-1.0
0.30 - 1.00
EF19-1.0
0.30 - 1.00
EF19-1.0
0.30 - 1.00
EF19-1.0
0.30 - 1.00
EF19-2.7
0.80 - 2.70
EF19-2.7
0.80 - 2.70
EF19-2.7
0.80 - 2.70
E16DU-6.3 *
1.90 - 6.30
E16DU-6.3 *
1.90 - 6.30
E16DU-6.3 *
1.90 - 6.30
E16DU-18.9 *
5.70 - 18.90
E16DU-18.9 *
5.70 - 18.90
EF45-30
9.00 - 30.00
EF45-30
9.00 - 30.00
EF45-30
9.00 - 30.00
EF45-45
15.00 - 45.00

Type 2 Co-ordination Table

SCPD type : MCCB


Rated voltage : 400 V
Short circuit current : 36 kA
Starting type : DOL-NS
Coordination type : IEC Type 2
Motor
Rated Power

Rated Current

[kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

[A]
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.5
22
28.5
36
42
56
68
83
98
132
160
195
230
280
350
430
520
540
610

Moulded Case Circuit Breakers


Instantaneous Tripping
Type
Current
[A]
T2N160 MF 1.6
21
T2N160 MF 1.6
21
T2N160 MF 2
26
T2N160 MF 3.2
42
T2N160 MF 4
52
T2N160 MF 5
65
T2N160 MF 8.5
110
T2N160 MF 11
145
T2N160 MF 12.5
163
T2N160 MA 20
210
T2N160 MA 32
288
T2N160 MA 52
392
T2N160 MA 52
469
T2N160 MA 52
547
T2N160 MA 80
840
T2N160 MA 80
960
T2N160 MA 100
1,200.00
T3N250 MA 160
1,440.00
T3N250 MA 200
1,800.00
T3N250 MA 200
2,400.00
T4N320 PR221-I In320
2,720.00
T5N400 PR221-I In400
3,200.00
T5N400 PR221-I In400
4,000.00
T5N630 PR221-I In630
5,040.00
T6N630 PR221-I In630
6,300.00
T6N800 PR221-I In800
7,200.00
T6N800 PR221-I In800
8,000.00
T6N800 PR221-I In800
8,000.00

Contactor

Overload Relay

Type

Type

A9
A9
A9
A9
A16
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A145
A145
A185
A210
A260
A300
AF400
AF460
AF580
AF580
AF750

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU42
TA75DU52
TA75DU52
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA200DU175
TA200DU200
E320DU320
E320DU320
E320DU320
E500DU500
E500DU500
E800DU800
E800DU800
E800DU800

Current setting range


[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
.10 - 14
13 - 19
18 - 25
29 - 42
36 - 52
36 - 52
60 - 80
60 - 80
80 - 110
80 - 110
130 - 175
150 - 200
100 - 320
100 - 320
100 - 320
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800

Type 2 Co-ordination Table

SCPD type : MCCB


Rated voltage : 400 V
Short circuit current : 35 kA
Starting type : SD-NS
Coordination type : IEC Type 2
Overload relay : TOL
Motor
Rated Power
[kW]
18.5
22
30
37
45
55
75
90
110
132
160
200
250

Rated Current
[A]
35
41
55
66
80
97
132
160
195
230
280
350
430

Moulded Case Circuit Breakers


Type
T2N160 MA52
T2N160 MA52
T2N160 MA80
T2N160 MA80
T2N160 MA100
T2N160 MA100
T3N250 MA160
T3N250 MA200
T3N250 MA200
T4N320 PR221-I In320
T5N400 PR221-I In400
T5N630 PR221-I In630
T5N630 PR221-I In630

Instantaneous Tripping Current


[A]
469
547
720
840
1,050.00
1,200.00
1,700.00
2,000.00
2,400.00
2,880.00
3,600.00
4,410.00
5,670.00

Contactor type
Line

Delta Star

A50
A50
A63
A75
A75
A75
A95
A110
A145
A145
A185
A210
A260

A50
A50
A63
A75
A75
A75
A95
A110
A145
A145
A185
A210
A260

A26
A26
A30
A30
A30
A40
A75
A95
A95
A110
A145
A185
A210

Overload Relay
Type
TA75DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA110DU110
TA200DU135
TA200DU175
TA200DU175
TA450DU235
TA450DU310

Current setting range


[A]
18.00 - 25.00
22.00 - 32.00
29.00 - 42.00
36.00 - 52.00
45.00 - 63.00
45.00 - 63.00
66.00 - 90.00
80.00 - 110.00
100.00 - 135.00
130.00 - 175.00
130.00 - 175.00
165.00 - 235.00
220.00 - 310.00

Type 2 Co-ordination Table

SCPD type : MCCB


Rated voltage : 400 V
Short circuit current : 50 kA
Starting type : SD-NS
Coordination type : IEC Type 2
Overload relay : TOL/EOL
Frequency : 50-60 Hz

Motor
Rated
Power
[kW]
18.5
22
30
37
45
55
75
90
110
132
132
160
160
200
200
250
250
290
315
355

Rated
Current
[A]
35
41
55
66
80
97
132
160
195
230
230
280
280
350
350
430
430
520
545
610

Moulded Case Circuit Breakers


Type
T2S160 MA52
T2S160 MA52
T2S160 MA80
T2S160 MA80
T2S160 MA100
T2S160 MA100
T3S250 MA160
T3S250 MA200
T3S250 MA200
T4S320 PR221-I In320
T4S320 PR221-I In320
T5S400 PR221-I In400
T5S400 PR221-I In400
T5S630 PR221-I In630
T5S630 PR221-I In630
T5S630 PR221-I In630
T5S630 PR221-I In630
T6S630 PR221-I In630
T6S800 PR221-I In800
T6S800 PR221-I In800

Instantaneous Tripping
Current
[A]
469
547
720
840
1,050.00
1,200.00
1,700.00
2,000.00
2,400.00
2,880.00
2,880.00
3,600.00
3,600.00
4,410.00
4,410.00
5,670.00
5,670.00
6,300.00
7,200.00
8,000.00

Contactor type

Overload Relay

Line

Delta

Star

Type

A50
A50
A63
A75
A75
A75
A95
A110
A145
A145
A145
A185
A185
A210
A210
A260
A260
AF400
AF400
AF400

A50
A50
A63
A75
A75
A75
A95
A110
A145
A145
A145
A185
A185
A210
A210
A260
A260
AF400
AF400
AF400

A26
A26
A30
A30
A30
A40
A75
A95
A95
A110
A110
A145
A145
A185
A185
A210
A210
AF260
AF260
AF260

TA75DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA110DU110
TA200DU135
E200DU200
TA200DU175
E200DU200
TA200DU175
E320DU320
TA450DU235
E320DU320
TA450DU310
E500DU500
E500DU500
E500DU500

Current
setting range
[A]
18.00 - 25.00
22.00 - 32.00
29.00 - 42.00
36.00 - 52.00
45.00 - 63.00
45.00 - 63.00
66.00 - 90.00
80.00 - 110.00
100.00 - 135.00
60.00 - 200.00
130.00 - 175.00
60.00 - 200.00
130.00 - 175.00
100.00 - 320.00
165.00 - 235.00
100.00 - 320.00
220.00 - 310.00
150.00 - 500.00
150.00 - 500.00
150.00 - 500.00

Type 2 Co-ordination Table

Motor
Rated Power Rated Current
[kW]
[A]
0.06
0.2
0.09
0.3
0.12
0.44
0.18
0.6
0.25
0.85
0.37
1.1
0.55
1.5
0.75
1.9
1.1
2.7
1.5
3.6
2.2
4.9
3
6.5
4
8.5
5.5
11.5
7.5
15.5
11
22
15
29
18.5
35

Rated voltage : 400 V


Short circuit current : 50 kA
Starting type : DOL-NS
Coordination type : IEC Type 2
Manual Motor Starter
Instantaneous Tripping Current
Type
[A]
MS132-0,25
2.44
MS132-0,40
3.9
MS132-0,63
6.14
MS132-0,63
6.14
MS132-1,0
11.5
MS132-1,6
18.4
MS132-1,6
18.4
MS132-2,5
28.75
MS132-4,0
50
MS132-4,0
50
MS132-6,3
78.75
MS132-10
150
MS132-10
150
MS132-12
180
MS132-16
240
MS132-25
375
MS132-32
480
MS450-40
520

Contactor
Current setting range
[A]
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.40 - 0.63
0.63 - 1.00
1.00 - 1.60
1.00 - 1.60
1.60 - 2.50
2.50 - 4.00
2.50 - 4.00
4.00 - 6.30
6.30 - 10.00
6.30 - 10.00
8.00 - 12.00
10.00 - 16.00
20.00 - 25.00
25.00 - 32.00
28.00 - 40.00

Type
A9
A9
A9
A9
A9
A9
A9
A9
A16
A16
A26
A26
A26
A26
A30
A30
A30
A40

Type 2 Co-ordination Table

SCPD type : MMS


Rated voltage : 400 V
Short circuit current : 50 kA
Starting type : DOL-NS
Coordination type : IEC Type 2
Motor
Rated Power Rated Current
[kW]
[A]
0.06
0.22
0.09
0.34
0.12
0.44
0.18
0.72
0.25
0.83
0.37
1.12
0.55
1.45
0.75
1.9
1.1
2.59
1.5
3.45
2
4
2.2
4.8

Type
MS116-0,25
MS116-0,40
MS116-0,63
MS116-1,00
MS116-1,00
MS116-1,60
MS116-1,60
MS116-2,50
MS116-4,00
MS116-4,00
MS116-6,30
MS116-6,30

Manual Motor Starter


Instantaneous Tripping Current
[A]
3
4.8
7.56
12
12
19.2
19.2
30
48
48
75.6
75.6

Contactor
Current setting range
[A]
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1.00
0.63 - 1.00
1.00 - 1.60
1.00 - 1.60
1.60 - 2.50
2.50 - 4.00
2.50 - 4.00
4.00 - 6.30
4.00 - 6.30

Type
A9
A9
A9
A9
A9
A9
A9
A9
A16
A16
A16
A16

Type 2 Co-ordination Table

SCPD type : MMS


Rated voltage : 400 V
Short circuit current : 50 kA
Starting type : SD-NS
Coordination type : IEC Type 2
Motor

Manual Motor Starter

Rated Power

Rated Current

[kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2
2.2
3
4
5.5
7.5
11
15
18.5

[A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.59
3.45
4
4.8
6.5
8.5
11.5
15.5
22
29
35

Type
MS116-0,25
MS116-0,40
MS116-0,63
MS116-1,00
MS116-1,00
MS116-1,60
MS116-1,60
MS116-2,50
MS116-4,00
MS116-4,00
MS116-6,30
MS116-6,30
MS132-10
MS132-10
MS132-12
MS132-16
MS132-25
MS132-32
MS450-40

Instantaneous Tripping Current


[A]
3
4.8
7.56
12
12
19.2
19.2
30
48
48
75.6
75.6
150
150
180
240
375
480
520

Contactor type
Current setting
range
[A]
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1.00
0.63 - 1.00
1.00 - 1.60
1.00 - 1.60
1.60 - 2.50
2.50 - 4.00
2.50 - 4.00
4.00 - 6.30
4.00 - 6.30
6.30 - 10.00
6.30 - 10.00
8.00 - 12.00
10.00 - 16.00
20.00 - 25.00
25.00 - 32.00
28.00 - 40.00

Line Delta

Star

A9
A9
A9
A9
A9
A9
A9
A9
A16
A16
A16
A16
AF26
AF26
AF26
AF26
AF30
AF30
AF38

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
AF09
AF09
AF09
AF09
AF09
AF09
AF12

A9
A9
A9
A9
A9
A9
A9
A9
A16
A16
A16
A16
AF26
AF26
AF26
AF26
AF30
AF30
AF38

Type 2 Co-ordination Table

Motor
Rated Power Rated Current
[kW]
[A]
0.06
0.22
0.09
0.34
0.12
0.44
0.18
0.72
0.25
0.83
0.37
1.12
0.55
1.45
0.75
1.9
1.1
2.59
1.5
3.45
2
4
2.2
4.8
3
6.48
4
8.6

Rated voltage : 400 V


Short circuit current : 25 kA
Starting type : DOL-NS
Coordination type : IEC Type 2
Manual Motor Starter
Instantaneous Tripping Current
Type
[A]
MS116-0,25
3
MS116-0,40
4.8
MS116-0,63
7.56
MS116-1,00
12
MS116-1,00
12
MS116-1,60
19.2
MS116-1,60
19.2
MS116-2,50
30
MS116-4,00
48
MS116-4,00
48
MS116-6,30
75.6
MS116-6,30
75.6
MS116-10,0
120
MS116-10,0
120

Contactor
Current setting range
[A]
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1.00
0.63 - 1.00
1.00 - 1.60
1.00 - 1.60
1.60 - 2.50
2.50 - 4.00
2.50 - 4.00
4.00 - 6.30
4.00 - 6.30
6.30 - 10.00
6.30 - 10.00

Type
A9
A9
A9
A9
A9
A9
A9
A9
A16
A16
A16
A16
A26
A26

Type 2 Co-ordination Table

SCPD type : Fuses


Rated voltage : 400 V
Short circuit current : 80 kA
Starting type : DOL-NS
Coordination type : IEC Type 2

Motor
Fuses IEC
Contactor
Overload Relay
Rated Power Rated Current
Rating
Current setting range
Switch-Fuse Type gG /aM Type and Size
Type
Type
[kW]
[A]
[A]
[A]
0.37
1.1
OS32D_
4
OFAA 00H
A9
TA25DU
1.00 - 1.40
0.55
1.5
OS32D_
6
OFAA 00H
A9
TA25DU
1.30 - 1.80
0.75
1.9
OS32D_
6
OFAA 00H
A9
TA25DU
1.70 - 2.40
1.1
2.7
OS32D_
10
OFAA 00H
A9
TA25DU
2.20 - 3.10
1.5
3.6
OS32D_
10
OFAA 00H
A9
TA25DU
3.50 - 5.00
1.5
3.6
OS32D_
10
OFAA 00H
A9
TA25DU
2.80 - 4.00
2.2
4.9
OS32D_
16
OFAA 00H
A9
TA25DU
4.50 - 6.50
3
6.5
OS32D_
20
OFAA 00H
A9
TA25DU
6.00 - 8.50
4
8.5
OS32D_
25
OFAA 00H
A9
TA25DU
7.50 - 11.00
5.5
11.5
OS32D_
32
OFAA 00H
A12
TA25DU
10.00 - 14.00
7.5
15.2
OS32D_
32
OFAA 00H
A16
TA25DU
13.00 - 19.00
7.5
15.2
OS32D_
40
OFAA 00H
A26
TA25DU
13.00 - 19.00
11
22
OS32D_
63
OFAA 00H
A26
TA25DU
18.00 - 25.00
15
29
OS32D_
80
OFAA 00H
A30
TA25DU
24.00 - 32.00
18.5
35
OS63D_
100
OFAA 00H
A40
TA42DU
29.00 - 42.00
18.5
35
OS63D_
100
OFAA 00H
A50
TA75DU
29.00 - 42.00
22
41
OS125D_
125
OFAA 00H
A50
TA75DU
36.00 - 52.00
30
55
OS125D_
125
OFAA 00H
A63
TA75DU
45.00 - 63.00
30
55
OS250D_
160
OFAA 1H
A63
TA75DU
45.00 - 63.00
37
66
OS250D_
200
OFAA 1H
A95
TA80DU
60.00 - 80.00
45
80
OS250D_
200
OFAA 1H
A95
TA110DU
65.00 - 90.00
45
80
OS250D_
250
OFAA 1H
A145 TA200DU
65.00 - 90.00
55
97
OS250D_
250
OFAA 1H
A145 TA200DU
80.00 - 110.00
75
132
OS400D_
315
OFAA 2H
A145 TA200DU
110.00 - 150.00
90
160
OS400D_
315
OFAA 2H
A185 TA200DU
130.00 - 175.00
110
195
OS400D_
400
OFAA 2H
A210 TA450DU
165.00 - 235.00
132
230
OS400D_
400
OFAA 2H
A260 TA450DU
220.00 - 310.00
160
280
OESA630D_
630
OFAA 3H
AF400 E500DU
150.00 - 500.00
200
350
OESA630D_
630
OFAA 3H
AF400 E500DU
150.00 - 500.00
250
430
OESA630D_
630
OFAA 3H
AF460 E500DU
150.00 - 500.00
295
546
OESA800D_
800
OFAF 3H
AF580 E800DU
250.00 - 800.00
315
540
OESA800D_
800
OFAF 3H
AF580 E800DU
250.00 - 800.00
355
610
OESA800D_
800
OFAF 3H
AF750 E800DU
250.00 - 800.00

Type 2 Co-ordination Table


SCPD type : Fuses
Rated voltage : 400 V
Short circuit current : 80 kA
Starting type : SD-NS
Coordination type : IEC Type 2
Motor
Fuses IEC
Rated Power Rated Current
Rating
Switch-Fuse Type gG /aM Type and Size
[kW]
[A]
[A]
4
8.6
OS32D_
20
OFAA 00H
5.5
11.5
OS32D_
25
OFAA 00H
7.5
15.2
OS32D_
32
OFAA 00H
11
22
OS32D_
40
OFAA 00H
15
29
OS32D_
50
OFAA 00H
18.5
35
OS63D_
63
OFAA 00H
22
41
OS63D_
80
OFAA 00H
30
55
OS63D_
100
OFAA 00H
37
66
OS125D_
125
OFAA 00H
45
80
OS125D_
125
OFAA 00H
55
97
OS250D_
160
OFAA 1H
75
132
OS250D_
200
OFAA 1H
90
160
OS250D_
250
OFAA 1H
110
195
OS250D_
250
OFAA 1H
132
230
OS400D_
315
OFAA 2H
160
280
OS400D_
315
OFAA 2H
160
280
OS400D_
400
OFAA 2H
200
350
OESA630D_
500
OFAA 3H
250
430
OESA630D_
500
OFAA 3H
295
540
OESA630D_
630
OFAA 3H
315
540
OESA630D_
630
OFAA 3H
355
610
OESA630D_
630
OFAA 3H
Note

Contact us for further information


ABB Limited
Design Institute
88/3, 88/6, Basavanahalli Village
562123, Bangalore North, Karnataka, INDIA
email: [email protected]

Contactor type
Line
A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185
A210
AF400
AF400
AF400
AF400
AF400

Delta Star
A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185
A210
AF400
AF400
AF400
AF400
AF400

A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110
A145
A145
A210
A260
A260
A260
A260

Overload Relay
Current setting range
Type
[A]
TA25DU
TA25DU
TA25DU
TA25DU
TA25DU
TA25DU
TA25DU
TA42DU
TA75DU
TA75DU
TA75DU
TA110DU
TA200DU
TA200DU
TA200DU
TA200DU
TA450DU
E500DU
E500DU
E500DU
E500DU
E500DU

4.50 - 6.50
6.00 - 8.50
7.50 - 11.00
10.00 - 14.00
13.00 - 19.00
18.00 - 25.00
24.00 - 32.00
29.00 - 42.00
36.00 - 52.00
45.00 - 63.00
45.00 - 63.00
65.00 - 90.00
80.00 - 110.00
100.00 - 135.00
130.00 - 175.00
130.00 - 175.00
130.00 - 185.00
150.00 - 500.00
150.00 - 500.00
150.00 - 500.00
150.00 - 500.00
150.00 - 500.00

1. Values mentioned charts are also suitable for 415V application.


2. For SD NS application, MCCB combination to be considered for 22kW and above
3. Product development is a continuous process and charts are subjected to revisions