Fluorescent Ballast Troubleshooting Guide
Fluorescent Ballast Troubleshooting Guide
29
Pages 31-49 from the Advance Transformer Co. FLB Pocket Guide
TROUBLESHOOTING
Any work performed on the lighting system, including inspection, troubleshooting and maintenance, should be done with the fixture properly de-energized and the circuit locked and tagged according to Occupational Safety and Health Act (OSHA) requirements.
INOPERATIVE FIXTURE
Often when a fixture becomes inoperative, the cause is not attributable to the ballast. It is therefore important to examine all components of the fixture before removing the ballast for replacement. The following procedure is recommended:
1. Change or check all lamps to ensure satisfactory operation. 2. As lamps are removed, examine all sockets to ensure proper and positive contact with lamp pins. 3. If starters are used, each starter should be checked and replaced wherever necessary. 4. Examine all connections within the fixture to ensure their conformance with the wiring instructions appearing on the ballast. 5. Examine and test ballast.
33
TROUBLESHOOTING
TROUBLESHOOTING
Open Channel Cover To Visually Inspect Condition Of Ballast And Connections. Check Lamps And Ballast For Matching
Everything Okay
If Improper Correct
Cut Leads To Socket With Voltage Out Of Tolerance Measure Voltage At Ballast
Everything Okay
Everything Okay
Check Spacing Between Lamps And Sockets Lamp Must Be Seat In Socket
Everything Okay
Replace Ballast
Voltage At Ballast Out Of Tolerance Replace Ballast Voltage At Ballast Within Tolerance Problem With Wiring Or Socket
34
35
TROUBLESHOOTING CYCLING
The National Electrical Code stipulates that most ballasts installed indoors must contain a cut-out device that protects the ballast from overheating. If abnormal ambient conditions cause the ballast to overheat, the thermal protection devices switch disconnects the ballast from the line. Once cooled, the ballast is reconnected and restarts the lamps. If the conditions persist, the ballast will switch off again repeatedly in a process called cycling.
TROUBLESHOOTING
LAMP CYCLING
Open Channel Cover To Visually Inspect Condition Of Ballast And Connections. Check Lamps And Ballast For Matching Everything Okay If Improper Correct
Remove Insulation
36
37
TROUBLESHOOTING PREHEAT
To measure starting current and operating current, the ammeter must be connected between the colored high voltage secondary lead of the ballast and the lamp. To determine starting voltage, remove lamp and connect voltmeter between respective primary and secondary leads of each lamp according to ballast wiring diagram.
This problem may also be caused by cold temperatures. In this case, the lamps may need to be jacketed or otherwise shielded from the cold drafts. Also, check that the lamps are rated for the actual temperature measured. This problem may also be caused by low input voltage; check and correct. Next, check for ballast and lamp compatibility and replace the wrong component. Replace lamp with known good lamp. If condition still exists, change ballast.
Lamp Type F4T5 F6T5 F8T5 F13T5 F14T8 F14T12 F15T8 F15T12 F18T8 F19T8 F20T12 F25T12 F30T8 F40T12 F90T17
Operating Current (Ampere) .17 .16 .145 .165 .365 .38 .305 .325 .385 .355 .38 .46 .355 .43 1.50
Starting Current (Ampere) .16-.25 .16 -.25 .16 -.25 .18 -.27 .44 -.65 .44 -.65 .44 -.65 .44 -.65 .35 -.80 .35 -.80 .44 -.65 .41-.95 .40-.65 .55 -.75 1.45 - 2.2
Starting Voltage (Minimum) (Open Circuit) 108 108 108 180 108 108 108 108 108 108 108 108 176 176 132
38
39
TROUBLESHOOTING
Other causes of difficulty could be (1) low or high circuit voltage, (2) improper lamp holder contact, (3) pinched wires or (4) improper lamps.
Lamp Type F24T12 F36T12 F40T12/IS F40T17/IS F42T6 F48T12 F64T6 F72T8 F72T12 F96T8 (200mA) F96T8 (265mA) F96T12
Black White
Ballast
Red Blue
Black White
Ballast
Red Blue
Correct Wiring
There have been many installations of Preheat fluorescent lighting in which two lamp ballasts are operating with one lamp on and one lamp out, or with shorted starters. These conditions will cause premature ballast failures due to the ballast coils being operated above their coil temperature limitation. Thus it is advisable that all inoperative lamps and starters be immediately replaced.
* For Single Lamp, measure voltage between Red & White leads. For Two Lamp (SERIES SEQUENCE), measure voltage between Red & White Insert lamp in Red & White position, then read voltage between Blue & Black. For Two Lamp (Lead Lag), measure voltage between Red & White and Blue & White leads. For Electronic (parallel), measure voltage between Red & Blue leads.
40
41
TROUBLESHOOTING
If an Electromagnetic Slimline Ballast is operated with one lamp on and one lamp off, the ballast will experience higher coil temperatures which could result in premature ballast failures. In cases of short ballast life, check this factor. Electronic Slimline ballasts generally are not effected by lamp failure.
Lamp Lamp Red Series Sequence| Ballast Blue White Black Lamp
White Black
Lamp
Red Blue
CORRECT
CORRECT
Lamp
Red Blue
Lamp
INCORRECT
Lamp
Lamp
Parallel Ballast
Blue Blue
INCORRECT
CORRECT
42
43
TROUBLESHOOTING
Rapid Start 430 MA. Lamp Type F14T12 F15T8 F15T12 F20T12 F17T8 F25T8 F25T12 F30T12 F32T8 F40T8 F40T10 F40T12 FC6T9 FC8T9 FC12T9 FC16T9 FC8T9 & FC12T9 FC12T9 & FC16T9
Filament Voltage 7.5 - 9.0 7.5 - 9.0 7.5 - 9.0 7.5 - 9.0 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5
Starting Voltage (Minimum) Single Lamp Two Lamp -20 F 0F 50 F -20 F 50 F 0F 225 145 110 140 85 195 260 195 155 115 190 235 310 256 203 240 155 290 325 365 240 210 290 350 420 395 283 340 260 410 455 430 330 280 360 445 775 450 490 465 330 360 295 480 160 160 225 225 300 300 205 205 270 270 355 355 240 240 310 310 400 400 250 250 350 350 470 470 265 265 360 360 470 470 300 300 400 400 500 500
Filament Voltage 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.6 - 4.8 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5 3.4 - 4.5
NOTE: Electronic ballasts generally provide starting voltages higher than those listed in the above tables. These open circuit voltages are listed on the ballasts label. Filament voltages for electronic and electromagnetic ballasts are the same.
44
45
TROUBLESHOOTING
Refer to the figure on page 48. BLUE-BLUE, YELLOWYELLOW, RED-RED LEADS are the built-in filament windings which supply a voltage of 3.4 to 4.5 volts to the lamp cathodes. If the cathodes are not properly heated, premature lamp end blackening will result. The lack of heating could be due to:
1. 2. 3. 4. 5. 6. 7. 8. 9.
Improper seating of the lamp within the socket. Broken sockets. Broken lamp pins. Too great of socket spacing. Damaged lamp cathode(s). Ballast lead wire not properly connected to socket. Low supply voltage. Inadequate ballast filament voltage. Improper wiring.
To determine if there is adequate voltage at the lamp cathodes, measure the voltage at the socket terminals. The voltage at the sockets should read between 3.4 and 4.5 volts. If there is adequate voltage, the lamp end blackening can be due to conditions 1, 2, 3, 4, or 5. If the voltage is not adequate it can be due to one or more of conditions 6, 7, 8, or 9. If random starting of Rapid Start lamps is experienced, be sure the fixture is properly grounded. As previously stated, for completely reliable starting in Rapid Start circuits it is necessary to have a starting aid. The starting aid should be an electrically grounded metal strip at least 1 inch wide and extending the full length of the lamp. The lamp should be within 1/2 inch of the grounded strip for 40 watt lamps and smaller, (3/4 inch for T8 lamps) and 1 inch for higher output lamps.
47
46
TROUBLESHOOTING
If, under high humidity conditions, Rapid Start lamps start slowly or do not start at all although the cathodes are properly heated, this may be due to dirt on the lamps which is offsetting the silicon coating on the lamps, or it may be due entirely to a poor silicon coating. If it is a new installation (in operation only a few months) which experiences random starting under high humidity conditions, in most cases it will be due to low supply voltage or poor silicon coating on the lamps. When random starting is experienced under high humidity conditions in an installation in operation for a longer period of time this is usually due to dirt on the lamps. The lamps should be washed in water to remove the dirt. Sometimes with a two lamp Rapid Start series ballast only one lamp will light to full brilliance and the other will not light. Refer to the figure below. If the lamp between the Red leads and Yellow leads is lit and the other lamp is out, look for a pinched Yellow lead. If the lamp between the Red and Yellow leads does not light and the other does, it is probably due to a short within the ballast.
LAMP BLUE BLUE YELLOW YELLOW LAMP RED RED
BLACK
WHITE
FIG .I
48
49
Advance Transformer Co. OHare International Center 10275 West Higgins Road Rosemont, IL 60018 Tel: 800-322-2086 Fax: 800-423-1882 Customer Support / Technical Service: 800-372-3331