Grounding Bonding For Substation Communications
Grounding Bonding For Substation Communications
GROUNDING & BONDING CONSIDERATIONS FOR SUBSTATION COMMUNICATIONS AND SMART GRID
Developed and Presented By: Adrian G Zvarych, PE Principal Engineer TRC Engineering Member, IEEE 24 September 2009 [email protected] Additional Contributions & Peer Review By: Michael Cunningham, Senior Engineer - TRC
Class Objectives
1.
2. 3. 4.
5. 6.
Understand Substation Grounding/Bonding Design Goals to Satisfy Communications Requirements Review of Typical Substation Control House Grounding/Bonding Practices Review Typical Telecom Room Grounding/Bonding Practices Necessary Grounding & Bonding Elements for a Smart Grid Friendly and Communications Ready Substation Control House Look-Ahead for other opportunities Review
40
Years of Service
1969 2009
40
Years of Service
1969 2009
Analog to digital Discrete to multiplexed Local Information decision needs to remote and diverse needs Lower Reliability to High Reliability (design and need) Minimal regulation (self- on inter-industry regulation to increased scrutiny and regulation by others)
40
Years of Service
1969 2009
40
Years of Service
1969 2009
Need for high speed and reliable/secure relaying Need for remote and central monitoring and control of station equipment First discrete component solid state relaying deployed in substations in the 1970s
Single Side-Band Power Line Carrier more channels, more functionality Analog Point-To-Point Microwave Optical Networks
40
Years of Service
1969 2009
Analog Microwave (circa 1960s) Digital Microwave (circa 1980s) Spread Spectrum 900MHz (circa 1980s) Fiber (circa 1990s)
40
Years of Service
1969 2009
Advancements of Components/Technology
Protective Relaying Electromechanical Relays Solid State Relays Solid State Relays Microprocessor Relays Communications Copper Analog Microwave Digital Microwave 900MHz Licensed & Spread Spectrum/Unlicensed Fiber Discrete Analog Digital Multiplexed IP
40
Years of Service
1969 2009
DS0-24
OC192
DWDM
DS1-4
. . .
OC1-3
OC12-2
OC12-3 OC12-4
DS1-28
IMUX
OC48-4
JMUX JUNGLEMUX EXPANDABLE TO OC48 BANDWIDTH BROADBAND CARRIER CLASS NETWORKS
Higher density of low-signal voltage circuits (RS-232, RS-485) over copper in the control house More fiber in the control house More non-substation hardened devices entering the control house IT-Telecom teams becoming more involved in substation control houses Organizational awareness of substation environment vs data center/telecom room requirements
40
Years of Service
1969 2009
System Operators P&C Engineering Asset Management Customer Service Center Field Maintenance Personnel (line trucks, P&C, substation, etc.) Electric System Customers (indirectly) Personnel Managers Corporate Security (access management, surveillance) IT-Security Cyber-Security Teams Utility Interchange (Where Transmission Tammy draws the line) Others
40
Years of Service
1969 2009
Traditional Telemetry Watts, Vars, Volts, Amps Status Open, Closed, Major, Minor Control Open, Close, Raise, Lower Voice SCADA Analog/4 Wire AC Data Present Day All of the above, plus Temperature Outdoor Ambient, Control House Transformer Telemetry Winding Temps, Dissolved Gas, Tap Position Battery Voltage IP Services
40
Years of Service
1969 2009
Security Surveillance, Door Access Control High Speed Remote Access for IEDs Syncrophasors Local Employee LAN Access SCADA
Change Is Here
Increased data flow (to 27 TB/day or higher in larger utility systems) from substations Not just SCADA Non-Traditional organizations using or managing substation systems and information Increased deployment of non-station hardened equipment, despite efforts by IEEE to develop standards such as IEEE-1613
40
Years of Service
1969 2009
GOALS OF GROUNDING/BONDING SUBSTATION AND TELECOM BASICS AND DEFINITIONS REAL WORLD CASE STUDY
Substation Goals
Safety Step and Touch Ground Potential Rise Reliability Lightning Mast/Shielding Minimize Electrical System Damage and Outages Lightning/Transient Suppression Equipment Equalize potential differences across the station grid & in the control building Systems redundancy emphasized on Bulk Power and system-significant generation
40
Years of Service
1969 2009
Telecommunications Goals
Safety Bonding of metallic components Reliability Lightning protection and mitigation outdoor Single Point Ground Location for all attachments (Main Ground Bus) Minimize equipment damage Minimize telecom circuit outage time Equipment and systems redundancy emphasized on Broadband Reduce electrical noise Reference for DC voltage
40
Years of Service
1969 2009
Breakers Transformers Structures Static Wires/OPGW Distribution Neutrals Station Service Lightning Shielding (masts, overhead shield wires, etc.)
Control House
40
Years of Service
1969 2009
4/0 copper grounding conductors brought in from grid (multiple places typically) CAUTION!!! 4/0 conductors snaked through cable trench/cable tray system, reduced to AWG #6 as needed for rack/panel connection Relay/Metering/Control Panels tied to bond snake running through the trench or tray cable management system
Establish safe limits of potential differences human body interface Substation grounding practices review for safety/safe design practices Provide a procedure for the design of practical grounding systems based on the above Develop analytical methods to aid in the understanding of gradient problems
40
Years of Service
1969 2009
Core benefits of an IEEE 80 ground grid design for Telecommunications Excellent low net ground grid resistance, ohm is possible, depending on final design Site specific ground grid design Human safe design, from a step-and-touch perspective Ground Potential Rise voltage is typically limited and affected by step-and-touch design criteria
40
Years of Service
1969 2009
Safety minimize potential differences between metallic paths Reliability ensure proper comm circuit operation despite transient conditions Eliminate ground loops Establish single point ground reference point in any one defined area (such as a control building room) Provide an engineered design for grounding and bonding in an area with telecom equipment
40
Years of Service
1969 2009
1.
1.
2.
2.
3.
3. 4. 5.
4. 5.
40
Years of Service
6.
6.
TELECOM SITE Engineered on a site basis (can be templatized) Single point connection to ground field Racks are isolated from the floor and from each other DC (+) is grounded Floor materials are conductive/antistatic Minimum Bend Radius Specified for transient flow
1969 2009
Grounding Conductor a conductor used to connect equipment or the grounded circuit of a wiring system to a grounding electrode or electrodes (these do not normally carry current)
40
Years of Service
Example: AC Circuit electrical ground wire (the green wire), grounding wires used to interconnect racks, equipment bonding jumpers
1969 2009
40
Years of Service
1969 2009
Horizontal Equalizer
An insulated grounding conductor which has its origination point at the CHPGP, with the function of connecting conductive equipment in a home run fashion to the principal grounding point in the room
Halo Ground
A grounding conductor, supported on insulated stand-offs around the perimeter of the room, typically installed at seven feet or higher elevation, to which all peripheral equipment are bonded (HVAC, Heaters, Junction Boxes, etc.). The Halo is a radial connection, and not a complete electrical loop.
40
Years of Service
Cable-to-device or cable-cable connections. Outdoor connections are typically exothermic, inbuilding connections are typically mechanical compression, with two-hole lugs.
1969 2009
Attributes:
Collector Station (34kV-230kV) yard adjacent to transmission switching station Transmission switching station has microwave tower for Primary relaying channel, SCADA, and internal voice communications Copper leased entrance cable, with isolation, at Transmission control house Transmission control house has PRIMARY and SECONDARY rooms Communications racks and telco isolation equipment in PRIMARY room PA System in place to cover the switchyard (copper connections to yard corners)
40
Years of Service
1969 2009
Wireless communications for Smart Grid Requires lightning protection @ top Proper bonding along feedline route Bond @ antenna Bond prior to horizontal transition Bond prior to CH entry Center conductor protection just inside CH Driven rods @ tower & feedline entrance
40
Years of Service
1969 2009
40
Years of Service
1969 2009
40
Years of Service
1969 2009
40
Years of Service
1969 2009
Key Design Features: Single Point Ground Bus (no ground loops) Discrete (insulated preferred) home-run bonding connections to all equipment connections: Cable tray & rack taps AC System Neutral @ AC Panel Telecom Reference Ground point Substation ground grid connection Building steel Microwave feedlines Departure From Telecom Practice Racks directly bolted to floor and each other without isolation Cable trays may not be bonded across joints Grounding conductors not insulated
40
Years of Service
1969 2009
A Few Images
Smart Recloser
Master Tower
Halo Ground
Insulated Stand-Off
Feedline Entrance
Producers and Absorbers Separated Clear separation of power, grounding, and data cables
Cable Management
Low Voltage Serial Connections: RS-232/485, GPS Ethernet Fiber Optic Entrance and Patch Cables
Non-Substation Hardened Equipment Security (card access, surveillance, etc.) Working with teams outside Transmission Engineering
Summary
Communications Grounding-Bonding practices require safety, but also reliability Control House equipment connects to a single point ground bus bar to which all metallic elements are bonded Soft radius bends for all grounding and bonding connections Minimize or eliminate ground loops
THE ROAD TO THE FUTURE IS BRIGHT FOR POWER AND SMART GRID COMMUNICATIONS Are you ready?