Telecom Manual English
Telecom Manual English
FIG - 1
38 MM TINNED
38 MM COPPER
38 MM COPPER
FIG - 2
CHAPTER XXIV
INSTRUCTIONS FOR PROTECTION TO STAFF
SECTION A - GENERAL
24.1 Scope of instructions-
The instructions in this chapter are not exhaustive. Any carelessness on the part of the
staff will not be absolved by the absence of instructions detailed in this chapter.
24.2 Handling by authorised personnel-
All equipments shall be handled only by duly authorised staff particularly in case of
wireless transmitters. All connections and alterations, other than the usual
manipulations or operation, are to be carried only by staff specially appointed for this
work.
SECTION B - PROTECTIVE AND SAFETY DEVICES
24.3 Periodical checking- The condition of the equipment and correct functioning of
protective and safety devices shall be checked once in a month by the authorised
personnel.
24.4 Checking under fault conditions-When the protective and safety devices have
operated under fault conditions, check shall be carried out on the devices for their
correct functioning before resetting them for use.
24.5 Altering and disconnecting safety devices-
The safety devices shall not be altered or disconnected, except for replacements
without specific approval of the competent authority.
SECTION C- FIRST AID
24.6 First aid-
Since electrical shock may result in the interruption of natural breathing, all staff shall
be familiar with the methods of artificial respiration. It is essential that staff are
equipped with the knowledge of first aid. Charts explaining such methods should be
exhibited in a prominent place where high voltages are incident. Names of staff
trained in first aid shall also be displayed.
24.7 First Aid Box-
First aid box shall be kept in wireless stations, first aid rooms in workshops, etc.
SECTION D - ACID
24.8 Battery rooms
a. Battery rooms shall be provided with good ventilation.
b. Acid-proof tiles shall be provided on the flooring where acid is handled. It shall be
ensured that the floor is kept dry and free from fallen acid.
24.9 Storage of acid-
Acid shall be kept in a cool dry place.
24.10 Diluting the acid
a. Acid should always be added to water, when dilution is needed.
b. Where acid is handled, board containing the legend DO NOT ADD WATER
TO ACID with a pictorial representation shall be hung at a suitable place.
c. While handling acid containers rubber gloves shall be used.
SECTION E FIRE
24.11 Ammonia and battery room-
A bottle of strong ammonia should be kept in the battery room at all times.
24.12 Safe working in battery room-
Breaking of the connection in a circuit in which current is being carried or the lighting
of naked light in the battery room must be avoided.
24.13 Training in fire fighting-
The personnel should be given training in fire fighting with the basic equipments
provided.
24.14 Preventive measures-
a. Waste material used in cleaning the equipments should not be allowed to
accumulate in a corner.
b. Dangerous growth of vegetation near the equipments or feeder lines or masts must
not be allowed.
c. The roofs of buildings must be kept clear of leaves or combustible materials.
d. Smoking should be prohibited in petrol storage rooms and battery rooms. No
Smoking sign with a Cigarette and red cross shall be displayed.
e. Oil, paints, etc. should not be stored near the equipments.
f. Petrol storage rooms should not have sparking equipments emitting sparks like
buzzers, relays, fuses, etc.
g. Handling of petrol such as filling in engine tanks, etc. should not be done while the
medium and high power transmitters are radiating in close proximity.
h. Lighting of fire for cooking etc. within compound walls shall be strictly prohibited.
i. Buckets filled with sand, water shall be hung at a convenient place.
24.15 Fire Extinguishers
1 TYPES OF FIRE :
(i) A Class :
Wood, charcoal, jute, cloth, etc. only water is used to extinguish the
fire.
(ii) B Class: Oil, petrol, grease, paints etc. only foam is used to extinguish
the fire.
(iii) C Class: electrical fire water is not used only CO2 is used.
2 (a) Basic fire fighting equipments should be kept in places with fire risk and
it shall be ensured that they are in good condition. Expiry date should be
clearly mentioned on them. Notices of instructions for using the fire
fighting equipments shall also be provided.
(b) All electrical installations shall be provided with gas type fire
extinguishers. Water should not be used to extinguish electrical fires..
(c) In confined places where even the minimum ventilation is not available,
vaporising liquid extinguishers should not be used since they may be
poisonous and cause harmful physiological effects.
24.16 Precautions during the time of fire.
(a) Alarm must be given in accordance with local regulations.
(b) All forced air-cooling devices must be stopped.
(c) Equipments involved must be disconnected immediately at the supply
source.
(d) Spreading of the fire should be avoided.
SECTION F- ELECTRICITY
24.17 Removal of fuses- Fuses shall be removed or replaced only after the
circuit has been completely de-energised. A non-conductive fuse
extractor shall be used to remove knife or cartridge type of fuses from
their holders.
24.18 Handing circuit breakers
(a) In the case of manually operated circuit breakers, the face shall be kept
turned away from the circuit breaker, while closing.
(b) While working on non-closed type of circuit breakers, the use of safety
goggles is recommended.
24.19 Provision of labels
(a) All switches and cut-outs from which power may possibly feed shall be
secured in open position and suitable label shall be provided. After
completion of the work, the label shall be removed only by the person
who originally put on the label..
(b) Sign boards warning danger with legends in appropriate languages may
be hung at suitable places where radio frequency voltage or high dc or ac
voltages are encountered.
(c) When more than one repair party is engaged, each party shall provide the
label which will be removed after completion of the work by the
respective party. If switch locking facilities are available; it shall be
locked in the open position and the key retained by the person incharge of
the work.
24.20 Working on live circuit:
(a) Wherever possible work on live circuits with voltages over 350V peak may be avoided.
(b) The following protective measures shall be taken while working on live parts:
(i) Provision of ample light for illumination.
(ii) Removal of loose clothes and metallic personal accessories.
(iii) Provision of insulation from earth such as provision of rubber floor mats near electrical
distribution boards used in battery rooms.
(iv) Use of only one hand where practicable, keeping the other hand free.
24.21 Safety guards and covers.
(a) Suitable protective guards and wire nets shall be provided to prevent staff from making
accidental contact at the dangerous voltage and radio frequency high power radiation.
(b) All covers used for protection against accidental contact with high voltages shall normally
be kept closed and opened for maintenance or repair only by authorised staff.
24.22 Safety design and installation practices
(a) Insulated current carrying parts in the equipment shall be located in such a manner that
they are not subjected to abrasion or mechanical damage.
(b) Where cables pass through metallic parts, insulating bushings shall be provided.
(c) External conductors connected to the equipment at points within the case shall be so
arranged that their terminals are not subject to strain when any outer covering is protected
from abrasion and that they are prevented from getting twisted.
(d) Guard interlocking switches shall be so arranged mechanically, that inadvertent operation
is impossible.
(e) The accessibility in equipments and guards shall be so designed that the operator shall
not have access to live parts other than those at extra low voltages.
(f) If the operator is required to have access to parts of equipment which are dangerous
while the equipment is in operation, the covers provided to guard such parts shall not be
removable with the equipment switched on or shall themselves switch the current off when
the covers are removed.
24.23 Earthing
(a) Accessible metallic parts including hinged components which might become live in the
event of a fault, shall be earthed on all equipments and shall be so constructed that these parts
are permanently and reliably connected to an earth terminal or contact.
(b) If the body of the earthing terminal is part of the metal frame or enclosure, a screw or
nut of brass or other metal less resistant to corrosion should be provided.
(c) It should not be possible to loosen the earth terminal screw without the aid of a tool.
(d) If the equipment or any components are connected by a plug and a socket device; while
inserting the plug in the socket, the earth contact shall make its circuit before the current
carrying contacts engage and when the plug is withdrawn from socket, it shall break its circuit
after the live contacts break their contacts.
(e) All tall metallic structures shall be suitably earthed strictly.
24.24 Handling electrical equipment:
(a) While isolating the equipment from the mains supply the disconnection shall be
done with the operation of the switches as well as by removal of the fuses.
(b) The disconnection shall be checked once again before commencing the work on
the equipment.
(c) Since the electrical charge retained by the electrical machinery, when switched
off, may cause a severe shock in some cases, the out put terminals shall be earthed, before the
mains are handled.
(d) To ensure that the capacitors are discharged rapidly, after their source of potential
has been switched off, or disconnected, their live terminations, shall, wherever practicable,
have a discharge path which is either permanent or is applied so that the capacitors are
discharged to a safe potential. Capacitors wired permanently across the mains supply shall be
shunted by a resistance so that the discharge time of the capacitor shall not be greater than 100
mili second.
24.25 Handling radio equipment:
(a) Breaking of energised radio frequency output circuits shall be avoided as far as
possible.
(b) While energising a radio transmitter, it shall be ensured that no one is at work on
the equipment or aerial system, no tools or testing equipment are left in or on the equipment,
and all testing apparatuses are removed.
(c) Where other equipment is used close by, measures shall be taken to prevent shock
or injury to staff due to radio frequency energy picked up from an adjacent aerial or
equipment.
(d) The aerial should be disconnected from the transmission line to prevent
introduction of any dangerous voltages due to aerial pick up. If this is not possible, other
precautions such as earth at several places may be resorted to. These earth connections shall
be very short when compared with the wave lengths.
(e) Staff shall not be permitted to go near the aerial installations, unless it is definite
that no danger exists.
(f) Transmitting equipment with frequency range of 30 MHz and below, and aerial
output power of 500 W and above may cause dangerous voltages to be induced in other
structures specially those structures protruding in the same plane as the radiating source.
(g) All areas in which radio frequency power density in excess of 0.01 watt per sq cm
is known, or suspected to exist must be considered as hazardous areas, and personnel shall be
prohibited from doing any work, while the set is energised.
(h) Direct visual examination from the radiation path of any microwave radiator
reflector, wave guide, horn or any highly concentrated beam or radiating system during the
period of transmission must be avoided.
(i) Staff who must remain in the microwave beam for any length of time shall be
provided with and required to wear devices for eye protection with a wire mesh spring.
(j) If more than one transmitter is working on a site, care should be taken to avoid
burns from radio frequency pickup from the working transmitters.
(k) All external conductors or metal parts carrying current where radio frequency
power may exceed 5 W peak envelope shall be deemed to be live, and shall be protected
accordingly. All external circuits and accessories fed with radio frequency where the power
may exceed 5W shall be made inaccessible as far as practicable. Where such circuits can not
be made inaccessible, warning devices shall be displayed.
24.26 Protective measures for Telecommunication lines entering 25KV substation/switching
posts.
When telecommunication lines enter 25KV sub-stations and switching posts (Feeding posts,
section and sub-sectioning posts), the following protection measure shall be taken to protect
the staff and the Telephone equipment against any fault occurring on the Traction side.
a) Each Telecommunication line before its connection to Telephone equipment shall be
provided with heavy duty lightning arrestors and fuses. The heavy duty lightning arrestors
shall be of rare gas type with normal flashing voltage of 300 volts. The fuses shall be of 250
volts, 3 amps type.
(b) A common earthing shall be used for earthing of the heavy lightning arrestors and all
metallic bodies of sub-stations/switching posts so that no potential difference may arise
between these bodies in case of a fault occurring on the Traction Side.
24.27 Precautions in ac electrified area
(a) Instructions issued from time to time by administrations dealing with electrifications must
be strictly followed.
(b) Precautions are required to be taken on account of the following:
((i)) Proximity of a live conductor
(ii) Pressure of return current in rails.
(iii) Induction in all metallic bodies situated close to overhead equipments.
(c) Any contact, direct or indirect, with the 25KV line is dangerous and shall be strictly
avoided.
(d) Whenever staff has to work on installations which are in direct or indirect contact with
the rails, they shall:
(i) Use tools (insulated and non-insulated) in the manner approved by the CSTE of the
Railway.
(ii) Observe the provisions of Chapter XX of the Way and Works Manual, supplemented by
Instructions for Railway Staff Working on Tracks Equipped with 25KV, 50 Hz ac traction
(see Annexure A).
(iii) The metallic body and supporting frame of the equipment shall be earthed and the
resistance of this earthing shall not exceed 10 ohms. There should not be any possibility of
simultaneous human contact with metallic bodies connected to different earth.
(iv) Any equipment and portion thereof including the supporting structure falling within 2
meters of the 25KV live contact wire or any metal part electrically connected to this
conductor shall be protected by an iron screening, of approved design, solidly connected to
the structural work. The iron screen shall be connected to an earth not exceeding 10 ohms in
resistance.
(e) Each time staff has to work on telecommunication circuits along the 25 KV ac line. the
following protective measures must be observed:
(i) They should be as a general rule use rubber gloves and use tools with insulated handles.
(ii) When the work to be done is meticulous and rubber gloves cannot be used, special
precautions should be taken by splitting the circuit into sections by earthing them.
(iii) Before cutting the armour or the lead or the aluminium sheath of the cable or the wires in
the cable, establish as a general rule, an electrical connection of low ohmic resistance between
two parts of the armour and the sheathing and the wires that are to be separated by cutting.
(iv) Whenever the main telecommunication cable is tapped by derivation cables, the tapping
shall be through protective transformers to maintain physical separation between the main and
derivation cable conductors.
(v) When more than one repair party is engaged, each party shall provide the label which will
be removed after completion of the work by the respective party. If switch locking facilities
are available, it shall be locked in the open position and the key retained by the person
incharge of the work.
(v) While opening an underground telecommunication cable joint, the cable sheath and
armouring which may be at a higher potential than the earth should not be touched without
first connecting to a local earth installed temporarily for the purpose.
(vi) As the phantom circuit for block working is derived directly from the main cable,
through the plastic insulated conductors, the terminals in the derivation cable termination box
on which these plastic insulated conductors for block working are terminated, shall be painted
red. The maintenance staff should take necessary precautions while working on cable
termination boxes.
(vii) In VF repeater stations and cable huts, a caution board shall be displayed to indicate
that the maintenance staff must use rubber gloves and stand on rubber mats while working
on the cable termination and equipment. The issue of special instructions to the personnel
likely to have access to the cable conductors, sheath and terminations, of the cable sections
between sectionalising points, must be done. The marking of any accessible part of the
installations or apparatus connected to the line that may be raised to a dangerous potential
must be done.
(viii) While working on the telecommunication equipment installed on the overhead
equipment switching posts, maintenance staff should ensure that the lightning arresters and
the fuses connected in the line are in proper working condition before commencing the work.
24.28 Tools to be provided with insulating sleeves in 25 KV AC area.
(a) Tools which are used in signal and telecommunication circuits and on any current
carrying parts of signal and telecommunication equipment are required to be insulated to
protect the staff from ac induced voltages.
(b) The handles of these tools shall be provided with insulating sheath of rubber or
plastic materials of approved type sufficient to withstand 3000 V.
(c) The following tools shall invariably be insulated:
(i) Screw driver.
(ii) Pliers
(iii) Any other tools, whose handles are metallic and which are required for the
above purposes.
SECTION G - WORKSHOPS
24.29 Regulation of factories Act - All the safety regulations enjoined in Factories Act
shall be complied with.
SECTION H - HANDLING OF MATEIRALS, TOOLS AND METERS
24.30 Crane or hoist, handling materials - While materials are being handled by crane or
hoist or a winch, care shall be taken that the personnel are away from the danger zone.
24.31 Correct handling of tools - Wherever it is noticed that the tools are not properly
handled by the staff, the correct method should be taught so that the workmen do not injure
themselves by using wrong methods.
24.32 Voltage handling of tools - While making voltage tests on transmitters, the meter
must be insulated from the ground and the test leads shall be able to withstand the high
voltages.
SECTION I - TOOLS, GLOVES, BELTS AND HELMETS
24.33 Tools in wireless stations - The tools employed in a wireless station shall be as per
Para 24.28
24.34 Gloves
(a) Where high voltages are employed, suitable rubber gloves shall be provided, but
while working on radio frequency circuits, use of rubber gloves is prohibited.
(b) The gloves shall be designed such that they will not slip off during use, but shall
be easy to take off.
24.35 Belts - Safety belts of approved design may be provided for staff working on poles or
masts. The belts shall not be less than 7.5 cm wide and shall be made 5 mm thick, good
quality, non-fibrous leather.
24.36 Helmets - Helmets of approved design may be provided for staff liable to work in fire
fighting and in places of workshop where overhead cranes or hoists are working or where
small objects such as nuts, bolts, tools, stones, etc., are likely to fall from above.
ANNEXURE A
Para 24.27(d) (ii)
SUPPLEMENT TO CHAPTER XX OF THE WAY AND WORKS MANUAL
(Relevant Paras)
Instructions for Railway staff working on tracks equipped with 25KV single phase, 50
Hz ac traction overhead equipment and on or adjacent to such requirement.
1. The instructions lay down precautionary measures to be observed by railway personnel
working on the tracks equipped with 25 KV ac overhead equipment.
2. Precautions are required to be taken on account of the following:
2.1 Proximity of a live conductor - The risk of direct contact would occur while working
very close to a live conductor.
2.2 Pressure of return current in rails- The return current in the rails may cause a potential
difference :
- between rail and the surrounding mass of earth.
- between the two ends of a fractured rail.
- between the two rails at an insulated joint.
- between earth and any other metallic mass.
2.3 Induction in all metallic bodies situated close to overhead equipment- It is important to
note that induced voltage may appear at any instant in metallic masses in the vicinity of
traction conductors .
3. The precautions laid down must be followed under all circumstances in sections equipped
for 25KV single phase, 50Hz ac traction in addition to those in para 2003
3. (a) No work shall be done within a distance of 2 meters from the live parts
of the overhead equipment without a on permit to work (see para 2003)
3.3 No fallen wire or wires shall be touched unless power is switched off and
the wire or wires suitably earthed. In case the wires drop at a level
crossing, the gatekeeper shall immediately make arrangements to stop
all road traffic, power is switched off and the wires duly earthed.
4. During maintenance or renewal of track, continuity of the rails serving
electrified tracks shall be maintained by provision of temporary metallic
jumpers of approved design for bridging the gap which would be caused
during removal of fishplates or rails.
7 Use of rails as foot path, a seat or for such other purposes is strictly
prohibited.
8 In electrified tracks the use of steel measuring tape or long metallic wires
shall be avoided.
N.B. Para references given here refer to paras of the Way and Works
Manual
CHAPTER XXV
FAULT CONTROL PROCEDURES
25.1 INTRODUCTION:
This chapter discusses the Fault Control Procedures for Railways Telecommunication
Network both at Zonal Level as well as Divisional Level.
In a typical Railway Telecom Network scenario, following types of Telecom Network co-
exist :
Transmission
- Microwave/UHF Network
- Optical Fibre Cable Network
- RE Telecom Cable Control Network
- Railways Overhead Wire Control Network
- DOT owned Overhead Wire Control Network
Switching
- Electronic Telephone Exchanges
- Electro-Mechanical Telephone Exchanges
Others
- Single Channel Duplex UHF/VHF Radio System
- Multiple Access Radio Relay (MARR) Systems
- Pair Gain System
- VHF/UHF Simplex Trans-receivers
- Talk Back Systems for Major Yards
It is indeed very necessary to establish well defined Fault Control Procedures for
satisfactory maintenance of such diverse Railway Telecommunication Networks so as to meet
the demanding requirements of Indian Railways in the 21
st
Century.
FAULT CONTROL PROCEDURES
25.2 TYPICAL TELECOM FAULT CONTROL SET-UP ON A RAILWAY
Typical telecom fault control set-up on a Railway shall consist of the following:
1. ZONAL TELECOM FAULT CONTROL SET-UP
2. DIVISIONAL TELECOM FAULT CONTROL SET-UP
The Zonal Telecom Fault Control Set-up shall be one for the entire Zonal Railway.
The Divisional Telecom Fault Control Set-up shall be established in each Division of
the Zonal Railway.
25.3 ZONAL TELECOM FAULT CONTROL SET-UP
25.3.1 It shall be manned by Section Engineer (Telecom) in a general shift. Three Section
Engineers (Telecom) shall be earmarked and should man the Zonal Fault Control set-up
round-the-clock in case of emergencies. Following Telecom Network shall be monitored by
the Zonal Telecom Fault Control Room.
Microwave/UHF Network on the entire Zonal Railway
25.3.2 The Zonal Telecom Fault Control Room shall also function as an Emergency Telecom
Control Room in case of Emergencies requiring immediate telecom facilities/restoration. The
emergencies may consist of the following:
- Major Rail Accidents
- Cyclones
- Breaches
25.3.3 When the Zonal Telecom Fault Control Room functions as the Emergency Telecom
Control Room, the Divisional Telecom Fault Control Rooms of the affected Division(s) shall
report their positions to the Zonal Telecom Fault Control Room which in turn shall advise the
Telecom Officials at HQs of the latest developments.
25.3.4 The Zonal Telecom Fault Control Room shall function under the direct control of Dy.
Chief Signal & Telecom Engineer (Microwave) or any other officer designated by the Chief
Communication Engineer of the Railway.
25.4 DIVISIONAL TELECOM FAULT CONTROL SET-UP
25.4.1 The Divisional Telecom Fault Control Set-up shall have two components:
a) For monitoring all telecom networks other than Microwave/UHF called:
Divisional Telecom Fault Control Room.
b) For monitoring Microwave/UHF networks called: Divisional Microwave Fault
Control Room.
Each of these Control Rooms shall be headed by a Senior Section Engineer (Telecom)
in a general shift. Three Section Engineers (Telecom)/ Jr. Engineer (Telecom) shall man the
Fault Control Room round-the-clock.
25.4.2 Following Telecom Networks shall be monitored by the Divisional Telecom Fault
Control Room.
- Optical Fibre Cable Network
- RE Telecom Cable Control Network
- Railways Overhead Wire Control Network
- DOT owned Overhead Wire Control Network
- Electronic Telephone Exchanges
- Electro-Mechanical Telephone Exchanges
- Single Channel Duplex UHF/VHF Radio Systems
- Multiple Access Radio Relay (MARR) Systems
- Pair Gain Systems
- VHF/UHF Simplex Trans-receivers
- Talk Back Systems for Major Yards
- Any other new Telecom System
25.4.3 Following Telecom Networks shall be monitored by the Divisional Microwave Fault
Control Room.
- Microwave/UHF Network on the entire Division
25.5 OFFICE AIDS/TELECOM FACILITIES TO BE PROVIDED AT THE
ZONAL/DIVISIONAL TELECOM FAULT CONTROL ROOMS
Following Office Aids/Telecom Facilities shall be provided for satisfactory
functioning of the Telecom Fault Control Rooms
- Fax Machine on an exclusive Railway Telephone Line with STD Facility
- Fax Machine on an exclusive MTNL Telephone Line with STD Facility
- Computer System with Printer & Modem on an exclusive Railway Line with
STD facility
- E-Mail facility where-ever available
- Hotline Communication between various Telecom Fault Control Rooms
25.6 PROCEDURE FOR FAULT REPORTING TO ZONAL TELECOM FAULT
CONTROL ROOM & ITS FUNCTIONS
25.6.1 Each of the Divisional Microwave Fault Control Rooms shall report their daily
positions to the Zonal Telecom Fault Control Room by the following communication means:
- By Railway FAX
- By E-Mail where-ever available
25.6.2 Any unusual occurrences, any Microwave/UHF Radio link breakdowns or Channel
Interruptions of vital circuits e.g. PRS data circuits, Inter-Railway or Inter Division
Administrative Trunk Circuits, Control Hotlines from Zonal Hqs to Divisions, shall invariably
be reported to Zonal Telecom Fault Control Room immediately on their occurrence on
Telephone followed by FAX/E-Mail.
25.6.3 Monthly, Quarterly & Annual Communication System Performance Reports of the
Division shall be transmitted through Modems on Railway lines to the Zonal Telecom Fault
Control Room, as per specified proforma.
25.6.4 A uniform Application Program shall be loaded on the Computers in every Telecom
Fault Control Room at Zonal Levels. This shall ensure transparency of Data Transmission
between Fault Control Rooms of the Divisions.
25.6.5 The Zonal Fault Control Room shall compile Monthly, Quarterly & Annual
Communication System Performance Reports of the Railway as per specified proforma, for
transmission to Railway Board.
25.6.6 When during emergencies, the Zonal Telecom Fault Control Room functions as an
Emergency Telecom Control Room, following additional functions shall get automatically
assigned :
- Maintaining very close co-ordination with the Divisional Telecom Fault
Control Room.
- Liasioning with BSNL/MTNL Officials at Hqs, if required, for providing
additional telecom facilities e.g. Extra BSNL/MTNL Nos., STD Facility on way-side
Telephones with ASMs. For this, Telephone Nos. with Designations of concerned
BSNL/MTNL Officials shall be kept up-to-date in the Control Room.
- Mobilising additional telecom resources as per site requirements.
25.6.7 A Disaster Management Plan detailing out the action to be taken in Emergencies shall
be prominently displayed in the Control Room.
25.6.7 Fault Control should ensure that minimum telecom needs with divisions and zones are
provided at accident side in least time.
25.7 PROCEDURE FOR FAULT REPORTING TO DIVISIONAL TELECOM
FAULT CONTROL ROOM & ITS FUNCTIONS
25.7.1 Various Telecom Installations on the Division shall report their periodic , daily or
unusual occurrence report to the Divisional Control Room on Telephone.
25.7.2 The Divisional Telecom Fault Control Room shall compile the Monthly, Quarterly &
Annual Communication System Performance Reports of the Division as per specified
proforma for transmission to the Zonal Control Room.
25.7.3 Liasioning with BSNL/MTNL Officials at Divisional level, if required, for providing
additional telecom facilities e.g. Extra BSNL/MTNL Nos., STD Facility on wayside
Telephones with ASMs. For this Telephone Nos. with Designations of concerned BSNL
/MTNL Officials, shall be kept uptodate in the Control Room.
25.7.4 Mobilising additional telecom resources as per site requirements in case of
emergencies.
25.7.5 A uniform Application Program shall be loaded on the Computers in every Telecom
Fault Control Room at Divisional Level. This shall ensure transparency of Data
Transmission between Fault Control Rooms.
25.7.6 A disaster Management Plan detailing out the action to be taken in Emergencies shall
be prominently displayed in the Control Room.
25.7.7 Fault Control should ensure that minimum telecom needs with divisions and zones are
provided at accident side in least time.
25.8 PROCEDURE FOR FAULT REPORTING TO DIVISIONAL MICROWAVE
FAULT CONTROL ROOM & ITS FUNCTIONS
25.8.1 The Microwave/UHF Stations on the Division shall report their periodic daily or
unusual occurrence report to the Divisional Microwave Fault Control Room on Telephone.
25.8.2 The Divisional Microwave Fault Control Room shall compile the Monthly, Quarterly
& Annual Communication System Performance Reports of the Division as per specified
proforma for transmission to the Zonal Telecom Control Room.
25.8.3 Liasioning with BSNL Microwave Officials at Divisional level, if required, for
providing additional telecom Channels/restoration of Channels in case of failures. For this,
Telephone Nos. with Designations of concerned BSNL Officials, shall be kept uptodate in
the Control Room.
25.8.4 Mobilising required Spare Modules/Fixtures as per site requirements in case of
emergencies.
25.8.5 A uniform Application Program shall be loaded on the Computers in every Microwave
Fault Control Room at Divisional Level. This shall ensure transparency of Data Transmission
between Fault Control Rooms.
25.8.6 A Disaster Management Plan detailing out the action to be taken in Emergencies shall
be prominently displayed in the Control Room.
--------------------------------------
CHAPTER XXVI
INSPECTION
26.1 ANNUAL INSPECTION PROGRAMME
The divisional and extra divisional officers should compile the inspection programme of their
respective jurisdiction and send it to the Head Quarter for approval.
26.2 ADHEARENCE TO ANNUAL INSPECTION SCHEDULE
The annual inspection schedule should be strictly adhered to. Any deviation should be
reported to the higher authority explaining the circumstances which necessitated the
deviation.
26.3 INSPECTION REPORT
Each inspection conducted by the Officers shall be followed by an inspection report.
The report should indicate the state of working of the installation, efficiency of the services
rendered, any specific problems along with suggestions for the improvement of services.
26.4 SUBMISSION OF INSPECTION REPORT
The inspection report of the Officers should be submitted to the next higher authority.
The inspection report should be submitted within one months time.
26.5 MONITORING THE INSPECTION WORK
A watch should be kept on adherence to annual inspection schedule by the concerned
divisional and head quarter Officers. For this purpose an inspection register should be
maintained indicating the installation inspected, actual date of inspection, date of submission
of report.
26.6 COMPLIANCE REPORT
Strict action should be taken to ensure prompt compliance of the points noted in the
inspection reports. Such a compliance report should be submitted as a matter of course within
one month of inspection and ordinarily all action should be completed within three months
time.
26.7 REVIEW OF EARLIER INSPECTIONS
During surprise/scheduled inspections, the progress of compliance of earlier
inspection reports should be checked by the inspecting officer. The inspecting officer may
carry with him earlier inspection report on similar installation to serve as a guideline.
26.8 LOCATING WEAK POINTS
The inspection should be meaningful and the inspecting officers should cover all
points affecting the efficiency of the services and should particularly inspect to locate weak
points before they can rise to any failure or complaint.
26.9 ANNUAL SCHEDULE OF INSPECTION
The annual schedule of inspection which shall be conducted by officers are given in
Annexure-A.
26.10 QUALITY OF INSPECTION
The report of the inspections carried out by the Officers will be reviewed by the next
higher authorities. If it is felt by the reviewing officer that the report is inadequate or
inspection has not been carried out properly covering all the important aspects, the reviewing
officers will send his comments immediately to the inspecting officers concerned. In extreme
cases he may even ask the inspecting officer to carry out the supplementary inspection to
cover the remaining points .
26.11 INSPECTION REGISTER
Every installation shall maintain inspection register duly bind and page numbered.
This will be kept as important permanent document. All the report of inspections/formal
visits will be filed in the inspection book if possible by way of coloured charts. Remarks of
any surprise/casual visit will be recorded by the visiting officer on the space in the inspection
register. The compliance report of the points noted in the register shall be sent to the
inspecting officers for record.
ANNEXURE A
ANNUAL INSPECTION SCHEDULE OF OFFICERS
SN ITEM SR. DSTE(Tele)/DSTE
(Tele)/Incharge
DSTE/ASTE
1. MICROWAVE/UHF NETWORK 25% STNS/YEAR ALL STATIONS AT LEAST
ONCE IN A YEAR
2. TELEPHONE AND TRUNK
EXCHANGES
ALL EXCH. EXCEEDING
400 LINES ONCE IN A
YEAR
ALL EXCHANGES
ONCE IN A YEAR
3. CONTROL OFFICE & TEST ROOMS ALL CONTROL OFFICES
QUARTERLY
ALL CONTROL OFFICES
ONCE IN A MONTH
4. PA SYSTEMS AT RLY
STATIONS/TRAIN INDICATION
BOARDS & CLOCKS
ALL MAJOR STATIONS
IN A YEAR
ALL STATIONS ONCE IN
A YEAR
5. OFC/QUAD/RE CABLE SYSTEM
a)CABLE ROUTE
b)CABLE HUT/REPEATER
c)EMERGENCY SOCKETS
ONE INSPECTION IN
EACH CONTROL SECTION
YEARLY
a) INSPECTION OF
COMPLETE CABLE ROUTE
ONCE IN A YEAR
b) ALL HALF YEARLY
c) ALL BLOCK SECTIONS
IN A YEAR
6. REPAIR & MAINTENANCE
CENTRES
ONCE IN A YEAR ONCE IN A YEAR
7. ACCIDENT RELIEF TRAIN ONCE IN A YEAR ONCE IN A
QUARTER
8. OPTICAL FIBRE SYSTEM
a)OPTIC FIBRE STNS
b)CABLE ROUTE
a)10% OF STATIONS IN A
YEAR
b) ONE INSPECTION IN
EACH CONTROL SECTION
a)ALL STATIONS
IN A YEAR
b)INSPECTION OF COMPLETE
CABLE ROUTE ONCE IN
A YEAR
9. TRAIN RADIO SYSTEM 10% OF INSTALLATIONS
IN A YEAR
ALL INSTALLA-
TIONS IN A YEAR
10. FOOT PLATE INSPECTION OF O/H
ALIGNMENT
ONE SECTION
QUARTERLY
ALL SECTIONS IN
A YEAR
11. VIDEO SURVILLANCE SYSTEM ALL MAJOR STATIONS IN
A YEAR
ALL STATIONS HALF YEARLY
12. TELECOM EQUIPMENTS OF DATA
NETWORK FOR
UTS,PRS,FOIS,RAILNET ETC.
ALL MAJOR STATIONS IN
A YEAR
ALL STATIONS HALF YEARLY
CHAPTER XXVII
PAINTING
27.1 SECTION A- EQUIPMENT TO BE PAINTED
27.1.1 Items of equipment requiring painting
(a) The following are the main items of telecommunication equipment that need
regular painting :
(i) Antenna towers.
(ii) Emergency telephone socket posts and socket box.
(iii) Marking on OHE masts for the position of telecommunication cable joints.
(iv) Battery cupboards and shelves
(v) Selector cases
(vi) Telephone brackets
(vii) Train control telephone apparatus.
(viii) Trunk exchange and manual exchange boards.
(ix) Loudspeakers
(x) Electric clock casings.
(xi) CT box terminals on which the cable conductors are terminated.
(b) The following are the main items of telecommunication equipment that need
occasional painting.
(i) Line repeaters.
(ii) Control room equipment.
(iii) Way station control equipment.
(iv) VF equipment bays.
(v) Transformer bays.
(vi) 4 wire- 2 wire and 2 wire- 4 wire junction equipment.
27.1.2 Colouring scheme
(a) All wood work shall be finished with natural colour varnish.
(b) As far as possible the original colour scheme adopted by the manufacturers may
be followed in repainting. Where the same colours are not available, the repainting
must be done with paints having colours near about the original.
(c) Emergency telephone socket post shall be painted with alternatively black and
white paints for 15 cms length each.
(d) CT box terminals where cable conductors are terminated are to be painted red.
(e) Marking on OHE masts for position of telecommunication cable joints is to be of
red paint.
27.1.3 Interval of painting :
(a) The general principle for fixing intervals has been based on the following:
(i) All wood work polished once in year.
(ii) All outdoor equipment painted once in 3 years.
(iii) All indoor equipment painted once in 6 years.
(b) The above intervals may be suitably modified for any particular area after taking
into account the corrosive effect of atmosphere and weather conditions.
(c) The paintings on the emergency telephone socket posts and on OHE masts for
cable joints shall be done once in a year.
27.1.4 Painting programme
(a) Each SE/JE shall be responsible to see that the telecommunication equipment
under his charge is painted regularly.
(b) Each SE/JE shall draw out a schedule of painting for all the equipment under his
charge. The quantities required shall be worked out on the basis of scale of paints
to be fixed by the CSTE.
27.1.5 Requisitioning of paints Each SE/JE must requisition of paints in accordance with
the quantities worked out. To ensure timely supply, he must submit his requisition to
the DSTE sufficiently in advance.
27.1.6 Programme for painters Each SE/JE must draw out a programme of work for each
painter under his charge and give him definite instructions about the painting work to
be carried out. Each painter must be supplied with a diary for recording daily progress
of work. His programme must ordinarily be so arranged that he works on the line from
Monday to Friday and returns to the Headquarter on Saturday for instructions, to
receive supply for the next week and to carry out odd jobs at the headquarters station.
27.1.7 Painting register Each SE/JE must maintain a painting register, one page or more
being allotted to each equipment on his section. Record of the painting work done
with dates of commencing and completing the work must be regularly entered in this
register.
27.1.8 Inspection
(a) Each SE/JE must see that the painters are making satisfactory progress and that the
painting work is in accordance with the instructions.
(b) Each DSTE shall see that the painting programme is strictly adhered to and that it is
completed in due time. He shall, during the course of his inspection, also see that all
the equipment and apparatus is kept properly painted in accordance with the
instructions.
27.2 SECTION B- GENERAL INSTRUCTIONS
27.2.1 Precautions
(a) Paints shall be stored in a cool dry place away from flame or naked light.
(b) All containers should be kept securely closed when not in use to avoid loss of
material due to skinning and contamination. Paints, especially quick drying paints,
shall not be left open to the atmosphere.
27.2.2 Mixing of paints
(a) Paints from pigments and pastes must be prepared in accordance with standard
specifications.
(b) Linseed oil turpentine shall not be added to ready mixed paints. Mixing of kerosene
with paints is forbidden.
27.2.3 Painting of steel works
(a) The surface of metal should be clean and free from dirt, scale, deteriorated old paint
and rust and should be preferably dry before application of paint. Painting should
be done preferably during dry weather.
(b) For a new steel work, 3 coats of paints shall be applied. After the first two coats of
an approved primer, the third paint of the specific colour and quality shall be
applied. When repainting a structure, if the old paint does not show any signs of
blistering, scaling or cracking, it need not be scraped off. It may be used as a
foundation for the new coat.
(c) When there are patches of blistering, scaling or cracking, these patches should be
cleaned down to the steel and treated in a manner as recommended for a new
structure.
(d) The surface of metal should be cleaned by scrapping, chipping or scrubbing with
brickbats. No chemical of any kind must be used. Old paint may be burnt, if
necessary, and then scrapped off.
(e) Paint should be applied with brushes and spread evenly, smoothly and as thin as
possible. Rags or waste cotton should not be used for the application of paint.
(f) Brushes should be thoroughly cleaned in proper driers after use.
27.3 SECTION -C PAINTING OF MICROWAVE TOWERS
(a) Microwave Towers are to be painted as per requirement of Civil Aviation
Regulations.
(b) Repainting of Towers should preferably be done every five years or earlier
depending on the conditions of the paints and climatic condition of the place.
Before repainting work is undertaken, previous paint are to be scrapped off taking
care that galvanization of the members does not get affected.
CHAPTER - XXVIII
DRAWINGS AND SPECIFICATIONS
SECTION A - STANDARD DRAWINGS
28.1 INDIAN RAILWAY STANDARD DRAWINGS
(a) Indian Railway Standard Drawings designated by the code word IRS have been
issued by Director General, Research Designs and Standards Organisation, Lucknow. The
telecommunication drawings are marked IRS (TC) - 'TC' stands for 'Telecommunication'.
The particulars of the drawings and their reference numbers are detailed in an Index of Indian
Railway Standard Signal and Telecommunication Drawings including advanced drawings
IRS (TC) issued by Research Designs and Standards Organisation. This index shows all the
IRS (TC) drawings arranged alphabetically as well as serially in the order of their numbers.
Each drawing number is either prefixed with the letters 'TCA' or letters 'TC'.
(Note - 'TCA' stands for a telecommunication equipment assembly and 'TC' stands for
a part of a telecommunication equipment assembly.)
(b) New designs and drawings which are accepted for adoption as standards have the
word 'Advance' suffixed to their number, e.g. TC.50 (Advance) pending their final adoption
as Indian Railway Standard Drawing. For such drawings the manufacturers shall have a
sample approved by the purchaser before undertaking the bulk manufacture.
28.2 Supply of drawings
(a) Standard drawings - A set of all IRS (TC) drawings must be supplied to each
Sr.DSTE, ASTE and to each Inspector as required. IRS drawings should not be traced by the
Railways. Copies should be obtained from the Director General (S&T), Research Designs
and Standards Organisation, Ministry of Railways, Lucknow.
(b) In addition to the standard drawings, each Sr.DSTE/DSTE office must have
copies of the following :
(i) Disposition charts of overhead lines for control telephones, block instruments,
administrative trunks, telegraph and other railway circuits.
(ii) Jurisdictions of overhead line maintenance staff, telecommunication equipment
maintenance staff and signal and interlocking supervisors.
(iii) Charts for maintenance staff of underground telecommunication cables and
repeater stations.
(iv) Charts showing distribution of section and deputy control telephones.
(v) Charts of overhead wires and underground cables for local telephone exchanges.
(vi) Telecommunication cable route plan on electrified sections.
(vii) A chart indicating the exact location of the emergency telephone socket post and
the jurisdiction of maintenance staff.
(viii) Route plan of microwave/UHF/VHF networks.
(ix) Route plan /locations of emergency VHF stations.
(x) Route plan of train radio or wireless emergency communication system, if any.
(xi) Optic fibre cable route plan, if any.
SECTION - B SPECIFICATIONS
28.3 INDIAN RAILWAY STANDARD SPECIFICATIONS: Specifications for material
and equipment used for telecommunication purposes have been drawn out by Director
General, Research Designs and Standard Organisation, Ministry of Railways, Lucknow and
are titled 'Indian Railway Standard Specifications'. These specifications are issued under
fixed serial number, e.g., TC.12-66 : the letter TC denoting 'Telecommunication', the number
'12' representing the serial number of the specification and the final number '66' indicating the
year of original adoption as standard, or in the case of revision, the year of last revision.
28.4 Other specifications - Specifications issued by the British Standards Institution and the
Indian Standards Institution have also been adopted for items of equipment used for
telecommunication purposes for which no IRS specification exists.
28.5 Supply of specifications - Each Sr. DSTE/DSTE office should have a copy of all Indian
Railway Standard (Telecommunication) specifications. Copies of such British Standard and
Indian Standard Specifications that are generally required may also be kept.
28.6 Availability
(a) Indian Railway Standard Specifications are obtainable from Director General,
Research Design and Standards Organisation, Manak Nagar, Lucknow-226011.
(b) British standard and Indian Standard Specification are obtainable from the
Director, Bureau of Indian Standard, Manak Bhavan, 9-Bahadur Shah Jafar Marg, New Delhi
- 110 002.
SECTION C - MAINTENANCE OF DRAWINGS AND SPECIFICATIONS
28.7 Folders - Standard drawing and specifications should be maintained in a block form
separately bound in suitable folders. New drawings and specifications should on receipt be
promptly added to the respective folders. Obsolete or cancelled drawings and specifications
must be destroyed. Torn or defaced drawings should be replaced.
28.8 Responsibility.
(a) Each Sr. Section Engineer shall be responsible for :
(i) The standard drawings are properly maintained and kept upto date in respect of
new drawings issued and old ones cancelled.
(ii) The staff working under him understand and carry out work in accordance with
standard drawings. Any mistake in drawings that may come to his notice should be promptly
intimated to the Sr. DSTE/DSTE for arranging correction.
(b) Each Sr. DSTE/DSTE shall be responsible to see that:
(i) The standard drawings and specifications in his custody are kept upto date and that
the obsolete and cancelled ones are destroyed.
(ii) All SSEs /SEs /JEs keep their standard drawings upto date.
(iii) The staff properly understand and carry out work in accordance with standard
drawing.
(iv) Any mistake in the standard drawings and specification, which comes to his
notice, is promptly intimated to the CSTE for arranging correction.
SECTION D - ADDENDA AND CORRIGENDA AND ACCOUNTAL
28.9 Addenda and Corrigenda
(a) British Standard Specifications - British Standard Year Book is published by the
British Standards Institution, Victoria Street, London SW1. It contains a list of upto date
British Standards in numerical order and also gives a brief description of each.
(b) Indian Standard Specifications - The ISI Hand Book of publications contains upto
date list of Indian Standards and is available from the Director, Bureau of Indian Standard,
Bahadur Shah Jafar Marg, New Delhi-110 002.
(c) Standard Drawings - Railway should publish list of standard drawings for the
information of the staff. Addenda and corrigenda slips should be issued to these lists
regularly once in six months incorporating particulars of drawings issued, modified or
cancelled.
28.10 Accountal of Standard Drawings and Specifications -
All Indian Railway Standard Drawings and specifications must be accounted for in
the same way as other books of reference.
SECTION E - INDIAN RAILWAY STANDARD EQUIPMENT
28.11 Indian Railway Standard Designs.
(a) Where Indian Railway Standard Designs exist, they should invariably be followed
for all new works and no modification of such designs should be introduced without the prior
approval of the Railway Board.
(b) Defects, if any, in standard designs noticed under service conditions or
modifications, which appear to be desirable should be brought to the notice of the Director
General, Research Designs and Standards Organisation, Ministry of Railway, Lucknow, for
examination in consultation with the telecommunication standard committee.
28.12 Requisitioning of materials.
(a) All materials and equipment must normally be indented in accordance with Indian
Railway Standard Drawings and Specifications. Indian Standard Specifications or British
Standard Specification should only be quoted for items for which an IRS Specification does
not exist.
(b) No alteration or modification to or divergence from IRS drawings shall be
permitted without the specific sanction in writing of the Director General, Research, Designs
and Standards Organisation, Ministry of Railways, Lucknow. In the case of deviations having
been decided upon before placing of an order whether direct or through the Director General,
Supplies & Disposals, the indenting authority concerned shall quote such sanction in the
order. When deviations are decided upon or desired after the placing of an order, the
necessary sanction shall be obtained in writing by the Inspectorate concerned in consultation
with the indenting authority.
(c) It shall be the responsibility of the DSTE, ASTE & SSE to see that reference of
correct drawings and specifications is given for all materials indented.
CHAPTER XXIX
BOOKS OF REFERENCE
29.1 BOOKS OF REFERENCE : Books of reference should be supplied to Officers,
Supervisors and Maintainers for their personal use, as well as for use in their offices.
A statement showing the various books and their distribution is at Annexure A. For
the officers, this list should be read in conjunction with Para 8.17 of Indian Railways
Signal Engineering Manual, Part 1 (1988 edition)
29.2 RESPONSIBILITY : All officials to whom books of reference have been
supplied shall be responsible for:
a. their safe custody and good order,
b. pasting all addenda and corrigenda slips promptly and seeing that these are up to
date to the last slip as notified from time to time, and
c. returning all books issued to them for personal use prior to retirement or
resignation or transfer from the railway service.
29.3 INSPECTION : Each Senior Divisional Signal & Telecommunication
Engineer/ Divisional Signal & Telecommunication Engineer shall make periodical checks to
see that Inspectors maintain their books of reference up to date and in good order. Each
Inspector shall, likewise, see that the staff under him maintain their books of reference up-to-
date and in good order.
29.4 ACCOUNTAL : All books of reference should be accounted for in the same way
as tools and plant items.
29.5 REPORTS OF TELECOMMUNICATION STANDARD COMMITTEE,
TECHNICAL PAPERS AND JOURNALS : Each Senior Divisional Signal &
Telecommunication Engineer / Divisional signal & Telecommunication Engineer
should arrange to have the under-mentioned technical literature in his office library :
a. Reports of Telecommunication Standards Committee Meetings.
b. Proceedings & Technical papers issued by Institution of Telecom Engineers,
India, Institute of Electronics & Telecommunication Engineers, Institution of
Railway Signal & Telecommunication Engineers.
c. All IRS Specifications pertaining to Telecommunication, relevant BSS, ISS &
DOT(TEC) specifications.
d. Quarterly Technical Bulletin and other technical papers on telecommunication
matters published by the Railway Board.
e. Technical books and journals of interest on telecommunications.
f. Copies of technical instructions and reports issued by RDSO on different items
of work relating to underground telecom cable installations, such as Technical
Instructions on balancing of VF cable, jointing of cables, installation of loading
coils, installation of VF repeater station equipment, cable laying practice for
optical fibre cables, testing of digital microwave equipments etc.,
29.6 RESPONSIBILITY OF DSTE : The Senior Divisional Signal & Telecommunication
Engineer / Divisional Signal & Telecommunication Engineer should encourage his
supervisors and other staff to study these reports, proceedings, papers and journals, so as to
enhance their knowledge and to keep themselves informed about the up-to-date
developments, methods and techniques in telecommunications. He should arrange to circulate
particulars of all new publications that are received from time to time for the information of
supervisors once every three months.
ANNEXURE -A
Para 29.1
STATEMENT SHWONG THE VARIOUS BOOKS OF REFERENCE AND
THEIR DISTRIBUTION AMONG STAFF
Item
No.
Publications Scale for
Office of Personal possession of
C
S
T
E
S
r
.
D
S
T
E
/
D
S
T
E
A
S
T
E
S
S
E
/
S
E
(
T
e
l
e
)
C
S
T
E
C
C
E
S
r
.
D
S
T
E
/
D
S
T
E
A
S
T
E
S
E
(
T
e
l
e
)
M
a
i
n
t
a
i
n
e
r
1 2 3 4 5 6 7 8 9 1
0
11 12
1. Telecommunication Engineering
Manual
1 1 1 1 1 1 1 1 1 1
2. General and Subsidiary Rules 1 1 1 1 1 1 1 1 1 1
3. Stores Manual 1 - - 1 - - - - - -
4. Pass Manual 1 1 - 1 - - - - - -
5. Safety First Manual 1 1 - 1 1 1 1 1 1 -
6. Schedule of dimensions 1 1 1 1 1 1 1 1 1 1
7. Telegraph Code 1 - 1 1 1 1 1 1 -
8. Payment of wages act with
notifications as issued.
1 1 - 1 - - - - - -
9. The hours of employment
regulations with notifications as
issued.
1 1 - 1 - - - - - -
10. Working Time table & Appendix
thereto
1 1 1 1 1 1 1 1 1 1
11. Catalogue of Stores 1 1 1 1 - - - - - -
12. Accident Manual 1 1 - 1 - - - -
13. IRS Drawings(Telecom) 1 1 1 1 - - - - - -
14. IRS specifications (of telecom items) 1 1 1 - - - - - - -
15. Railway Standard Drawings 1 1 1 1 - - - - - -
16. Indian Telegraph Act 1 1 - 1 - - - - - -
17. Indian Government Railway Code
for Engineering Department
1 - - - - - - - - -
18. CCIR Documents of the plenary
assembly
1 - - - - - - - - -
19. CCITT documents of the plenary
assembly
1 - - - - - - - - -
20. Indian Electricity Act 1 - - - - - - - - -
21. Electric Supply Rules 1 - - - - - - - - -
********