0% found this document useful (0 votes)
92 views

Outagereport

This document summarizes transmission outages in India on May 30-31, 2014. It reports on planned outages for maintenance, forced outages due to issues like tower collapses, and lines opened manually due to high voltage. Key details include the transmission element, voltage level, owner, outage and revival times, and reason for outage. A total of 51 transmission elements experienced outages over this period due to planned maintenance, unplanned failures, or high voltage safety openings.

Uploaded by

csudha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
92 views

Outagereport

This document summarizes transmission outages in India on May 30-31, 2014. It reports on planned outages for maintenance, forced outages due to issues like tower collapses, and lines opened manually due to high voltage. Key details include the transmission element, voltage level, owner, outage and revival times, and reason for outage. A total of 51 transmission elements experienced outages over this period due to planned maintenance, unplanned failures, or high voltage safety openings.

Uploaded by

csudha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

6/1/2014 nrldc.org/Outagereport.

aspx
http://nrldc.org/Outagereport.aspx 1/3
Transmission Elements Outage Report for 31-05-2014
A. Details of Transmission Elements under Planned Outage:-
S.No Element Name Type
Voltage
Level
Owner
Outage Revival
Expected
Date of
Revival
Reason / Remarks
Date Time Date Time
1 Balia-Bhiwadi Pole 2 Line 500 kV HVDC PGCI L 31-05-2014 11:25 31-05-2014 19:14 - defective capacitor replacement of filters at bhiwadi end
2 FSC of Balia-I at Lucknow FSC 400 kV PGCI L 06-05-2013 11:00 * * NA For shifting to Sohawal (PG)
3 FSC of Balia-I I at Lucknow FSC 400 kV PGCI L 06-05-2013 11:00 * * NA For shifting to Sohawal (PG)
4 Kishenpur(PG)-Sarna(PSEB) 1 Line 220 kV PGCI L 30-05-2014 09:40 31-05-2014 14:40 - For over-hauling of CGL Make CBs at Sarna end
5 Kishenpur(PG)-Sarna(PSEB) 2 Line 220 kV PGCI L 30-05-2014 09:46 31-05-2014 14:40 - For replacement of damaged X-arm at loc. no.274(DA+3)
*-Line still under outage NA - Not Available
B. Details of Transmission Elements under Forced Outage:-
S.No Element Name Type
Voltage
Level
Owner
Outage Revival
Expected
Date of
Revival
Reason / Remarks
Date Time Date Time
1 Bhiwani-Jatikala Line 765 kV PGCI L 30-05-2014 16:27 * * NA Tower collapsedat loc.no.208,209,210
2 Bhiwani -Meerut Line 765 kV PGCI L 30-05-2014 16:28 * * NA Cross arm damaged at loc no.174
3 Fatehpur-Gaya Line 765 kV PGCI L 31-05-2014 02:10 * * NA
Tower collapsedin between loc.no.305 to 330 (total
15 tower)
4 Abdullapur(PG)-Bawana(DTL) 2 Line 400 kV PGCI L 30-05-2014 16:30 * * NA Tower collapsedat loc no. 418
5 Jhajjar CLP-Kabulpur 2 Line 400 kV HVPNL 30-05-2014 16:30 31-05-2014 01:26 - Phase to earth fault.
6 Dipalpur-Kabulpur 2 Line 400 kV HVPNL 30-05-2014 16:30 * * NA Tower collapsedat loc no. 134
7 Jhajjar CLP-Kabulpur 1 Line 400 kV HVPNL 30-05-2014 16:30 31-05-2014 01:07 - Phase to earth fault.
8 Dipalpur-Kabulpur 1 Line 400 kV HVPNL 30-05-2014 16:30 * * NA Tower collapsedat loc. no. 134
9 Bahadurgarh(PG)-Bawana(GT) Line 400 kV PGCI L 30-05-2014 16:30 * * NA I solator burnt at Bawana.
10 Mandola-Meerut 3 Line 400 kV PGCI L 30-05-2014 16:30 31-05-2014 17:22 - Phase to earth fault.
11
Bawana(GT)-Bhiwani (PG)
Line 400 kV PGCI L 30-05-2014 16:30 * * NA Phase to earth fault.Y-ph
12 Mandola-Meerut 4 Line 400 kV PGCI L 30-05-2014 16:30 31-05-2014 16:52 - Phase to earth fault.
13
Bawana(DTL)-
Dipalpur(HVPNL)
Line 400 kV PGCI L 30-05-2014 16:40 * * NA Tower collapsedat loc no 418 and bend at 417
14 Bawana(DTL)-Mandola(PG) 1 Line 400 kV DTL 30-05-2014 16:45 31-05-2014 17:58 - Failure of LAat Bawana DTL
15 Dadri(NTPC)-Mandola(PG) 2 Line 400 kV PGCI L 30-05-2014 19:17 31-05-2014 00:59 - sparking in B-ph
16 Azamgarh-Sultanpur Line 400 kV UPPTCL 31-05-2014 00:32 31-05-2014 01:41 - Transient fault.
6/1/2014 nrldc.org/Outagereport.aspx
http://nrldc.org/Outagereport.aspx 2/3
17 Anpara-Sarnath 1 Line 400 kV UPPTCL 31-05-2014 02:37 31-05-2014 03:42 - Phase to phase fault.
18 Muradnagar-Panki Line 400 kV UPPTCL 31-05-2014 12:45 31-05-2014 16:54 - Phase to earth fault.
19
Mainpuri(PG)-
Paricha(UPPTCL) -2
Line 400 kV UPPTCL 31-05-2014 17:35 * * NA Phase to earth fault.B-ph
20
Mainpuri(PG)-
Paricha(UPPTCL) -1
Line 400 kV UPPTCL 31-05-2014 17:35 * * NA Phase to earth fault.Y&B-ph
21 Bareilly 50 MVAR B/R
Bus
Reactor
400 kV UPPTCL 05-08-2007 00:00 * * NA Failure of Reactor.
22 Sarnath 50 MVAR B/R
Bus
Reactor
400 kV UPPTCL 16-02-2009 06:14 * * NA Failure of Reactor.
23 Panipat 71.66 MVAR B/R
Bus
Reactor
400 kV BBMB 06-02-2012 00:11 * * 30-06-2014 Damaged and to be replaced by New .
24 FACT at BLB in Knp-BLB Line FACTS 400 kV PGCI L 30-04-2014 08:10 * * NA Low current & load in line.
25 Cbganj(UP)-Sitarganj(PG) Line 220 kV PGCI L 23-05-2014 23:31 * * NA Tower No.65 collapsed in LI LO portion.
26
Rai Bareilly(PG)-
Unchahar(NTPC) 3
Line 220 kV PGCI L 29-05-2014 11:56 * * NA Phase to earth fault.
27 Bhiwadi(PG)-Rewa SPL(HVPNL) Line 220 kV HVPNL 30-05-2014 07:09 31-05-2014 20:25 - Snaping of earth wire.
28 Bamnauli-Pappankanlan I 2 Line 220 kV DTL 30-05-2014 16:32 * * NA Phase to earth fault.
29 Bamnauli-Pappankanlan I 1 Line 220 kV DTL 30-05-2014 16:32 * * NA Tower collapsed.
30 Bawana-Rohini 1 Line 220 kV DTL 30-05-2014 16:32 * * NA Tower collapsed.
31 Bawana-Rohini 2 Line 220 kV DTL 30-05-2014 16:32 * * NA Tower collapsed.
32 Gopalpur(DTL)-Mandola(PG) 2 Line 220 kV DTL 30-05-2014 16:48 * * NA Tower collapsed.
33 Gopalpur(DTL)-Mandola(PG) 1 Line 220 kV DTL 30-05-2014 16:51 * * NA Tower collapsed.
34
Mandola(PG)-Wazirabad(DTL)
2
Line 220 kV DTL 30-05-2014 17:03 31-05-2014 19:59 - Tower collapsed.
35 Auraiya(NTPC)-Malanpur(PG) Line 220 kV PGCI L 31-05-2014 02:00 31-05-2014 02:43 - Phase to phase fault.
36 Mandola(PG)-Narela(DTL) 1 Line 220 kV DTL 31-05-2014 14:11 31-05-2014 20:40 - Phase to earth fault. R-ph
37
Mandola(PG)-Wazirabad(DTL)
4
Line 220 kV DTL 31-05-2014 14:11 31-05-2014 14:39 - SOTF operated.
*-Line still under outage NA - Not Available
C. Details of Transmission Elements Opened manually due to High Voltage:-
S.No Element Name Type
Voltage
Level
Owner
Outage Revival
Remarks
Date Time Date Time
1 Agra-Sikar 2 Line 400 kV PGCI L 30-05-2014 17:09 31-05-2014 10:19
2 Agra-Sikar 1 Line 400 kV PGCI L 31-05-2014 17:20 ** **
3 Jodhpur I I -Merta 1 Line 400 kV RRVPNL 31-05-2014 18:13 ** **
6/1/2014 nrldc.org/Outagereport.aspx
http://nrldc.org/Outagereport.aspx 3/3
4 Akal-Jodhpur I I Line 400 kV RRVPNL 31-05-2014 19:20 31-05-2014 21:34
** - Line shall be closed subject to voltage permissibility