6/14/02 Chapter 3: NEC CODE Rules and Design Practice 3/13

This document provides three examples of calculating circuit breaker sizes, wire sizes, and conduit fill requirements according to the National Electrical Code (NEC). The first example calculates a 20 amp breaker and #12 wire for a 15.6 amp load. The second calculates a 35 amp breaker and #10 wire for a 17 amp motor load. The third calculates a 45 amp breaker, #8 wire, and 1" conduit for a 25.1 amp unit heater load.

Uploaded by

man98_greyhoundz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views

6/14/02 Chapter 3: NEC CODE Rules and Design Practice 3/13

This document provides three examples of calculating circuit breaker sizes, wire sizes, and conduit fill requirements according to the National Electrical Code (NEC). The first example calculates a 20 amp breaker and #12 wire for a 15.6 amp load. The second calculates a 35 amp breaker and #10 wire for a 17 amp motor load. The third calculates a 45 amp breaker, #8 wire, and 1" conduit for a 25.1 amp unit heater load.

Uploaded by

man98_greyhoundz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NEC 310-16, THW, 75

C #12 = 20 Amp

Circuit breaker size = Load = 15.6 = 19.5
.8 .8
USE 20 Amp breaker
2 #12 in conduit Table 3A, 1/2" conduit will take up to 4 #12 THW
Example:
Load: Motor 3 HP, 1 phase, 230V run ground wire with all motors
I = 17A NEC 430=148

Wire Size = 17A = 21.5A
.8
NEC 310-16 #10 is next size wire good for 30 Amp CB = (I)(2 to
2.5) NEC 430-152
CB Size = (17 A) (2) = 34A USE 35A circuit breaker.
Conduit Size
3 #10, (2 power,1 ground), Table 3A, THW, 1/2" conduit will take 4 #10
Example
Load: Unit Heater 10 KW, 230V, 3 phase, find I, wire size, circuit breaker size
Conduit Size
I = 10 KW = 25.1 Amp
.23 KV 3
Wire Size- 25.1A = 31.3 Amp
.8
NEC 310-16 Use #8 good for 45 amp, 3 #8 + 1 #8 ground in 1" RGC Table 3A

Circuit Breaker = 25.1A = 31.3 Amp so use 35A
.8
Conduit Size if different size wires are used