Voltage Transformer Test Report: Cty TNHH MTV CN Chung Tín

The document is a voltage transformer test report for customer INTEL. It details test results for 3 voltage transformers of type VRS2Bn/S1 and serial numbers 0840076 through 0840078 located in the BB03 panel at the ATM-CENTER substation. Insulation and winding resistance tests were performed and found the transformers to have insulation resistance of 2.5MΩ or higher and winding resistances within specification, indicating the transformers passed testing.

Uploaded by

Thức Võ
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views

Voltage Transformer Test Report: Cty TNHH MTV CN Chung Tín

The document is a voltage transformer test report for customer INTEL. It details test results for 3 voltage transformers of type VRS2Bn/S1 and serial numbers 0840076 through 0840078 located in the BB03 panel at the ATM-CENTER substation. Insulation and winding resistance tests were performed and found the transformers to have insulation resistance of 2.5MΩ or higher and winding resistances within specification, indicating the transformers passed testing.

Uploaded by

Thức Võ
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

CTY TNHH MTV CN CHUNG TN

Service Department

70,ng ch Khim,P14,Q11,H Ch Minh,Vit Nam


Tel; 0963 132 983
Fax: 38617442

Voltage Transformer Test Report

Customer: INTEL
Address: SHTP ,Dist 9 ,Ho Chi Minh City
Substation: ATM CENTER- (HTB)

Object/panel: BB03

Manufacturer:

SCHNEIDER

Serial:

0840076 - 0840077- 084008

Type:

VRS2Bn/S1

Specification:

22 0.11
/

KV
3
3

INSULATION MEGGER TEST :


Subject

Test voltage (kV)

Phase A

- 100VA

Test set used : KYORITSU3121


Result (M)

2.5

Pri. - Housing
N/A

Sec.1 - Housing
N/A

Sec.2 - Housing
N/A

Phase B

2.5

N/A

N/A

N/A

Phase C

2.5

N/A

N/A

N/A

WINDING RESISTANCE TEST:

Status

Test set used : FLUKE 87V


Status
Secondary winding
02 in Ohm
N/A
OK

Phase of test

Primary winding
in Ohm

Secondary winding
01 in Ohm

L1

N/A

0.5

L2

N/A

0.5

N/A

OK

L3

N/A

0.4

N/A

OK

REMARKS :

Done By:

DUONG VAN DONG

Date:

Witnessed By:

NGUYEN THUAN HOA

Date:

Voltage Transformer Test Report

10 DEC 2011

Page 1 of 1