External Static Pressure Calculation: AHU-UB - 22 Hvac 27/27 M.M 4 June 2014 MA/CAL/27

This document contains calculations for the external static pressure and friction drop of air handling units serving the Al-Hazm Mall HVAC system. It includes duct sizes, lengths, fittings, and calculated values such as equivalent friction length, air velocity, and friction drop per 100 feet for 6 supply air duct sections and 3 fresh air duct sections. The total calculated friction drop for the supply and fresh air ducts and fittings is 1.168 inches water gauge.

Uploaded by

Engr.Mmosaad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views3 pages

External Static Pressure Calculation: AHU-UB - 22 Hvac 27/27 M.M 4 June 2014 MA/CAL/27

This document contains calculations for the external static pressure and friction drop of air handling units serving the Al-Hazm Mall HVAC system. It includes duct sizes, lengths, fittings, and calculated values such as equivalent friction length, air velocity, and friction drop per 100 feet for 6 supply air duct sections and 3 fresh air duct sections. The total calculated friction drop for the supply and fresh air ducts and fittings is 1.168 inches water gauge.

Uploaded by

Engr.Mmosaad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

MechaTronics Co.

External static pressure Calculation

AHU-UB_22
QTY.(2)
Al-Hazm Mall

HVAC

Project

Designed by

Project No.

M.M

Date

CFM

SIZE (MM)

LENGTH

DIA.

FT.

27/27

Circ:

MA/CAL/27

4 June 2014

DUCT
SECTION

Sheet

FT.

FT.

FITTINGS
Br
R
FT.

of

27
/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

10.0

40.0

57.1

823

0.04

0.025

AC SUPPLY DUCT
1

2,200

650

400

553.4

5.2

17.1

30.0

1,290

400

300

377.7

2.8

9.2

5.0

5.0

14.2

1036

0.10

0.015

860

400

200

304.7

2.3

7.5

5.0

5.0

12.5

1062

0.14

0.018

430

300

200

266.4

4.8

15.6

0.0

15.6

694

0.08

0.012

AC SUPPLY DUCTS & FITTINGS

0.070

AC FRESH AIR DUCT


4

600

400

200

304.7

1.9

6.2

15.0

15.0

21.2

741

0.07

0.016

600

400

200

304.7 11.0

36.1

15.0

15.0

51.1

741

0.07

0.038

600

400

200

304.7

13.1

5.0

18.1

741

0.07

0.013

4.0

5.0

AC FRESH AIR DUCTS & FITTINGS

0.067

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.070

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.067

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.062

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.106
1.168

25th Flr., Chatham House


116 Valero cor. Herrera Sts.
Salcedo Village, Makati City
1227 Philippines
Tel. (632) 887-1391
Fax (632) 887-1172
E-mail [email protected]

prepared by/ Engr.Mohamed Mosaad

prepared by/ Engr.Mohamed Mosaad