MechaTronics Co.
External static pressure Calculation
AHU-UB_22
QTY.(2)
Al-Hazm Mall
HVAC
Project
Designed by
Project No.
M.M
Date
CFM
SIZE (MM)
LENGTH
DIA.
FT.
27/27
Circ:
MA/CAL/27
4 June 2014
DUCT
SECTION
Sheet
FT.
FT.
FITTINGS
Br
R
FT.
of
27
/File
TOTAL
EQUIV.
AIR
FRICTION
EQUIV.
VELOCITY
DROP/100 FT
FRICTION
DROP
FT.
LGTH. (FT.)
LGTH. (FT.)
fpm
IN W.G.
IN W.G.
10.0
40.0
57.1
823
0.04
0.025
AC SUPPLY DUCT
1
2,200
650
400
553.4
5.2
17.1
30.0
1,290
400
300
377.7
2.8
9.2
5.0
5.0
14.2
1036
0.10
0.015
860
400
200
304.7
2.3
7.5
5.0
5.0
12.5
1062
0.14
0.018
430
300
200
266.4
4.8
15.6
0.0
15.6
694
0.08
0.012
AC SUPPLY DUCTS & FITTINGS
0.070
AC FRESH AIR DUCT
4
600
400
200
304.7
1.9
6.2
15.0
15.0
21.2
741
0.07
0.016
600
400
200
304.7 11.0
36.1
15.0
15.0
51.1
741
0.07
0.038
600
400
200
304.7
13.1
5.0
18.1
741
0.07
0.013
4.0
5.0
AC FRESH AIR DUCTS & FITTINGS
0.067
Abbreviations:
E = Elbow Equivalenght Length
15 Ft.
AC SUPPLY DUCTS & FITTINGS
0.070
B = Branch Equivalenght Length
30 Ft.
VOLUME DAMPER ( x 3 )
0.375
Br = Branch Run Equivalenght Length
15 Ft.
SUPPLY AIR DIFFUSER
0.150
R = Reducer Equivalenght Length
5 Ft.
AC FRESH DUCTS & FITTINGS
0.067
FRESH AIR GRILLE
0.150
SOUND ATTENUATOR
0.250
SUB-TOTAL
1.062
ADD 10%
TOTAL FRICTION DROP IN WG
prepared by/ Engr.Mohamed Mosaad
0.106
1.168
25th Flr., Chatham House
116 Valero cor. Herrera Sts.
Salcedo Village, Makati City
1227 Philippines
Tel. (632) 887-1391
Fax (632) 887-1172
E-mail
[email protected]prepared by/ Engr.Mohamed Mosaad
prepared by/ Engr.Mohamed Mosaad