0% found this document useful (0 votes)
82 views

Multi 9: Protection in The Tertiary Sector

The document describes how to remotely trip and indicate the position of a residual current circuit-breaker. It discusses: 1) The S1 emergency pushbutton can be used to remotely open the ID circuit-breaker via its NC contact and undervoltage release. Reclosing occurs by pressing the ID toggle. 2) The OFS auxiliary contact indicates the open or closed position of the ID to remote indicator lights. The green H1 light indicates closed, and the red H2 light indicates open. 3) Accessories for the C60 circuit-breaker must be mounted within 54mm on its left side, including the OFS contact.

Uploaded by

WinSajeewa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views

Multi 9: Protection in The Tertiary Sector

The document describes how to remotely trip and indicate the position of a residual current circuit-breaker. It discusses: 1) The S1 emergency pushbutton can be used to remotely open the ID circuit-breaker via its NC contact and undervoltage release. Reclosing occurs by pressing the ID toggle. 2) The OFS auxiliary contact indicates the open or closed position of the ID to remote indicator lights. The green H1 light indicates closed, and the red H2 light indicates open. 3) Accessories for the C60 circuit-breaker must be mounted within 54mm on its left side, including the OFS contact.

Uploaded by

WinSajeewa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Merlin Gerin 96056CEN

electric circuit
9
6
0
5
6
.
D
X
F
additional
information
multi 9
protection in the tertiary sector
how to remotely trip and indicate the position of a residual
current circuit-breaker?
b the ID residual current circuit-breaker breaks a circuit either manually or automatically after
detection of a residual current resulting from an insulation fault between a live conductor and a
frame or the earth;
b the S1 emergency pushbutton, equipped with a NC contact, controls the MN undervoltage
release:
v action on S1 causes remote opening of the ID,
v reclosing occurs by action on the ID toggle;
b the OFS auxiliary contact, required to adapt the electrical auxiliaries on the ID, is equipped with
a changeover switch linked to the "open" or "closed" position of the ID; it controls remote
indication by indicator light:
v the H1 green indicator light indicates the "closed" position of the ID,
v the H2 red indicator light indicates the "open" position of the ID.
b the electrical auxiliaries of the C60 are mounted on the left-hand side of the ID within a
limit of 54 mm, including OFS;
b A power cut results in tripping of the ID. To eliminate brownouts or transient voltage
drops, an MNs delayed undervoltage release allows a 0.5 s time delay of ID tripping.
24 octobre 2003
products used qty. part no.
DPN 1
2P ID 1
MN 1 26960
OF.S 1 26923
products used qty. part no.
red indicator light 1 18320
green indicator light 1 18321