The document discusses the need for directional overcurrent protection in transmission and sub-transmission systems with multiple power sources. In such systems, non-directional overcurrent relays installed at both ends of a transmission line may operate incorrectly for faults on the line. For example, a relay at one end may operate unnecessarily for a fault located closer to the other end. This could result in loss of power to loads when the line is disconnected when it does not need to be. Directional overcurrent relays are necessary to distinguish the direction of fault current flow and ensure only the correct relays operate to isolate faults at either end of the line.
The document discusses the need for directional overcurrent protection in transmission and sub-transmission systems with multiple power sources. In such systems, non-directional overcurrent relays installed at both ends of a transmission line may operate incorrectly for faults on the line. For example, a relay at one end may operate unnecessarily for a fault located closer to the other end. This could result in loss of power to loads when the line is disconnected when it does not need to be. Directional overcurrent relays are necessary to distinguish the direction of fault current flow and ensure only the correct relays operate to isolate faults at either end of the line.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Module 5 : Directional Overcurrent Protection
Lecture 18 : Directional Overcurrent Relaying
18.1 Necessity
In the overcurrent protection scheme considered in previous lectures, we had implicitly assumed that, 1. System is radial. 2. There is a single source.
This is quite true for traditional distribution systems but it does not hold true for sub-transmission or transmission system with multiple sources. Fig 18.1 shows a system which is radial but it has two sources connected to it. If relays for protection are installed only at one end of transmission line say towards source A end, it is obvious that after opening of relay in red, the fault will continue to be fed from source B. Hence, relays are also installed at other end of line to detect fault and disconnect transmission line from the other end as well. Similar situation will exist even for a single source system if parallel paths exist (fig 18.2). Hence, system which have multiple paths to source require relays at both ends. However, installing relays at both ends does not provide a complete relaying solution. To understand the reason, consider the action of red relay in fig 18.1 with respect to two likely faults F 1 and F 2 .
If the fault is at F 1 then it is responsibility of red relays to open. If fault is at F 2 , then it is the green relays which should trip the line. However, it is quite likely that for fault F 2 , the circled red relay may trip before circled green relay opens to disconnect feed from the source B, the reason being that both relays are subjected to same fault current.
In other words, circled red relay competes with circled green relay to clear fault. Opening of circled red relay unnecessarily causes loss of service to load at bus P and it should be classified as wrong operation.