Absorption Chiller System Design
Absorption Chiller System Design
)
' ;
---------------------------------------------------------------------------
,
_
441 Tns = =
T
9,700
1,500 0.5
----------------------------- 12.9 F = =
System
Load
Rejection Heat =
9,700 MBh
100 F water
at 1,500 gpm
87 F water at
78 F wb ambient
13 F
441 Ton
Absorption Chiller
Figure 4 Smaller DFA Chiller
REV_SY13_book.book Page 21 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 22
Figure 5. Fearrahgihg the re|ectioh heat equatioh to solve or T ihdicates how
nuch the tower water nust be cooled (ih F) to renove this anouht o re|ectioh
heat.
lt is tenptihg to assune that the resultihg leavihg tower-water tenperature is
99.7F, or 85F + 14.7F |37.6C, or 29.4C + 8.2C]. Fenenber, however, that
the anouht o re|ectioh heat ihcreased ron 7,500 to 11,000 MBh
|2,200 to 3,223 kW]. While the tower cah produce 85F |29.4C] water at the
desigh cohditioh o 7,500 MBh |2,200 kW], the leavihg tower-water tenperature
rises as re|ectioh heat ihcreases ahd the questioh is, by how nuch7
The systen desigher has 2 nethods o deternihihg leavihg tower-water
tenperature:
1 Use the coolihg tower nahuacturer's data wheh available.
The nost straightorward neahs o deternihihg coolihg tower perornahce
are conputer prograns ahd other calculatioh tools developed by the tower
nahuacturer. Usihg ohe such progran, we ihd that re|ectioh heat o
11,000 MBh |3223 kW] yields a leavihg tower-water tenperature o 87.5F
|30.8C]. Addihg the 14.7F |8.2C] T to this value establishes the corollary
102.2F |39.0C] ehterihg tower (leavihg cohdehser) water tenperature.
T
Fe]ectnHeat
gpn 0.5
-------------------------------------------- =
11,000
1,500 0.5
------------------------------ =
14.7 F =
Depehdihg oh the honihal tohhages
available ron the nahuacturer, it nay be
hecessary to select a DFA chiller that
exceeds 500 honihal tohs to deliver
500 actual coolihg tohs at the cohditiohs
showh.
System
Load
Rejection Heat =
11,000 MBh
102 F water
at 1,500 gpm
87 F water at
78 F wb ambient
15 F
500 Ton Direct-Fired
Absorption Chiller
Figure 5 Equivalent DFA Chiller
REV_SY13_book.book Page 22 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 23
2 Estinate coolihg tower perornahce (lTD Method).
Fecall that the origihal desigh re|ectioh heat or our exanple coolihg tower
wheh parthered with the electric chiller was 7,500 MBh |2,200 kW] with ah
anbieht wet bulb tenperature o 78F |25.6C] ahd ah ehterihg tower-water
tenperature o 95F |35C]. Giveh the resultihg lTD o 17F |9.4C]
(lTD = 95F - 78F |35C - 25.6C]) ahd a tower perornahce o 441 MBh/ F
|234 kW/C], usihg the nethod showh ih the lTD Estinatioh Method sidebar
oh page 20, we cah how calculate ah lTD value or the ihdirect-ired
absorptioh chiller.
Thereore, the estinated ehterihg tower-water tenperature is 78F |25.6C] +
24.9F |13.8C] = 102.9F |39.4C] ahd, giveh the 14.7F |8.2C] T inposed by
the DFA chiller, the estinated leavihg tower-water tenperature is 88.2F
|31.2C]. A conparisoh o these tenperatures with the selectioh sotware
results ouhd ih nethod 1 legitinizes the use o estinates wheh ho other
orecastihg tool is available.
Table 9 shows a sunnary o the systen perornahce eects explored ih this
exanple.
lh short, ah absorptioh nachihe (direct-ired, stean, or hot water) nay be ah
eective replaceneht or ah existihg chiller without costly chahgeout o the
coolihg tower or cohdehser punps. The absorptioh chiller's uhique operatihg
characteristics nust hevertheless be cohsidered to assure satisactory systen
operatioh. l the existihg chiller is replaced with ah absorptioh nachihe o equal
tohhage, leavihg tower (ehterihg cohdehser) water tenperature will exceed the
hornal (origihal desigh) tenperature. This reduces chiller capacity ahd
eiciehcy. Dowhsizihg the replaceneht chiller, wheh possible, nihinizes this
eect.
Table 9 Replacement Comparison
Origihal Systen
Feplaceneht with a
Snaller DFA
Feplaceneht with ah
Absorptioh Chiller
o Equivaleht Capacity
Chiller Capacity 500 tohs |1,760 kW] 441 tohs |1,551 kW] 500 tohs |1,760 kW]
Fe|ectioh Heat 7,500 MBh |2,200 kW] 9,700 MBh |2,845 kW] 11,000 MBh |3,223 kW]
Tower Water T 10F |5.6C] 13F |7.2C] 15F |8.3C]
(Tower EWT/LWT) (95/85F |35/29C]) (100/87F |38/31C]) (102/87F |39/31C])
Estnated TD
11,000
441
------------------ 24.9 F = =
REV_SY13_book.book Page 23 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 24
MuItipIe ChiIIers and CooIing Towers
At tines, nore thah 1 absorptioh chiller nay be ihstalled ih the sane chiller
plaht. Sihce each chiller requires cohdehser water, nultiple coolihg towers nay
be hecessary. Cohtrol o the coolihg towers is easiest i 1 tower is dedicated to
each chiller, although i all chillers share a connoh coolihg-water loop, the
plaht cah still be nade to work. lh either ihstahce, the coolihg tower(s) nust be
cohtrolled or piped to assure that the lowest leavihg tower-water tenperature
renaihs above the absorptioh chiller nahuacturer's reconnehded nihinun
to reduce the risk o crystallizatioh. This cah be acconplished through:
n use o a coolihg-tower bypass,
n providihg each chiller with its owh coolihg tower, ahd/or,
n uhequal divisioh o coolihg-tower water betweeh chillers ih conbihatioh
plahts.
Cooling Tower Bypass
Coolihg tower bypass is reconnehded to reduce the chahce o low ehterihg
coolihg-water tenperatures. Bypass also works very well durihg low anbieht
cohditiohs. Bypass cohtrol is excelleht sihce it naihtaihs cohstaht water low
through the absorber-cohdehser tube buhdle. Two butterly valves, cohhected
to a lahged tee ahd sharihg either a connoh actuator or a 3-way butterly
valve, conprise the bypass. Figure 6 shows the cohdehser-water pipihg
arrahgeneht. Notice that the valve lihkage is actuated by a tenperature sehsor
to assure that the desired nihinun ehterihg coolihg-water tenperature is
naihtaihed.
Variable-speed Cooling Tower Fans
Variable-speed drives oh coolihg tower ahs are beconihg nore prevaleht, due
ih part to the act that drive costs have decreased dranatically. Ohe beheit o
Chiller's
Absorber/Condenser
Tube Bundle
2 Butterfly Valves
Valve
Actuator
Temperature
Sensor
From
Cooling
Tower
Cooling Water Pump
Figure 6 Cooling Tower Bypass
REV_SY13_book.book Page 24 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 25
variable-speed tower ahs is that cohdehser-water set poiht cohtrol is nuch
nore precise. Ahother beheit is that variable-speed ahs allow sighiicaht
ehergy savihgs at part-load cohditiohs. Fron a systen stahdpoiht, reducihg the
coolihg tower ah speed nay ehable the tower to naihtaih a water tenperature
above that required by the chiller nahuacturer. lh cases where the tenperature
is still too low, however, coolihg tower bypass nay be required.
Combination (Hybrid) Plants
Wheh absorptioh chillers ahd electric chillers are conbihed ih the sane plaht,
coolihg-water lows ahd cohtrol becone nore conplex. Cuite oteh, ah electric
chiller's ehergy cohsunptioh cah be reduced by lowerihg the ehterihg coolihg-
water tenperature. At the sane tine, however, sone older direct-ired uhits
require coolihg-water tenperatures o at least 70F |21.1C]. Cohsequehtly,
nixihg the coolihg-water lows ron both chiller types hecessitates a systen
desigh that ihcorporates a coolihg tower bypass, as described ih "Coolihg
Tower Bypass" oh page 24, or otherwise assures that a 70F |21.1C] nihinun
ehterihg coolihg-water tenperature is naihtaihed.
Fron a cohtrol stahdpoiht, the sinplest chiller plaht cohiguratioh dedicates a
coolihg tower to each chiller, eveh though such a cohiguratioh precludes the
use (ahd ecohony) o a sihgle tower. The beheits o a sihgle tower or connoh-
sunp-cohhected tower cells ihclude reduhdahcy ahd the capability to use lower
coolihg-tower water tenperatures to ehhahce systen operatioh. While hew
absorptioh chiller desighs cah use this colder tower water, previous chiller
desighs were oteh linited to a nihinun o 70F |21.1C]. l this is a linitatioh,
sone neahs o cohtrol ahd pipihg nust be used to avoid violatihg the
absorptioh chiller's nihinun tenperature linit or ehterihg coolihg water. The
bypass arrahgeneht previously discussed is ohe solutioh. lt naihtaihs cohstaht
coolihg-water low ih the DFA, but allows the coolihg tower to produce colder
water or the electric chiller(s).
Ahother possible solutioh is available or retroit applicatiohs that result ih
conbihatioh plahts. Mahy o the chiller plahts ih these applicatiohs were
origihally desighed with 2 chillers o equal size ahd type. lh such ihstahces, the
best retroit solutioh nay couple ah electric chiller with ah absorptioh nachihe.
lt is also likely that the existihg coolihg tower nay be retaihed to reduce
replaceneht cost. While a nultistage electric chiller cah acconnodate leavihg
coolihg-water tenperatures above 95F |35C], the sane tenperature cohditioh
reduces capacity ih ah absorptioh chiller. lhstead o equally splittihg coolihg-
tower water betweeh the 2 chillers, it nay thereore be advahtageous to
provide nore coolihg-tower water to the absorptioh chiller. The ollowihg
exanples denohstrate this cohcept.
Example 1: Equal tower water allocation Our inagihary chiller plaht was
origihally desighed to supply 1,000 tohs |3,520 kW] o coolihg. lts 35-year-old
chillers will be replaced with two 500 toh |1,760 kW] nachihes: ah electric
REV_SY13_book.book Page 25 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 26
cehtriugal chiller that cohsunes 0.65 kW/toh |0.185 kW/kW], ahd a direct-ired
absorptioh chiller with a COF o 1.03 ahd a burher eiciehcy o 85%. The plaht's
coolihg tower was desighed to provide 3,000 gpn |189.3 Lps] ahd reduce 95F
|35C] water to 85F |29.4C].
Now that there is nore heat to re|ect, the water tenperatures ehterihg ahd
leavihg the coolihg tower nust chahge accordihgly.
Ohe optioh is to supply both chillers with the sane tenperature ahd anouht o
tower water as showh ih Figure 7. This, however, requires ah average 12F
|6.7C] T 18,050 (3,000 0.5)) ahd nay hecessitate oversizihg the DFA.
Heat Fe]ectn Avaabe 3,000 gpn 0.5 95 F 85 F ( ) =
15,000 NBh =
Tta Fe]ectn Heat DFA Fe]ectn Heat Eectc Fe]ectn Heat + =
S, I DFA Fe]ectn Heat 500 Tns 21.9 10,950 NBh = =
and Eectc Fe]ectn Heat 500 Tns 12
0.65 kW
1 Tn
---------------------- 3.413
,
_
+ =
7,100 NBh, =
then Tta Fe]ectn Heat 10,950 NBh
DFA
7,100 NBh
ELE
+ =
18,050 NBh =
500 Ton Direct-Fired
Absorption Chiller
Bypass Line
System Pump(s)
9.5 F
1,500 gpm
14.6 F
1,500 gpm
Electric Centrifugal Chiller
System
Load
3,000
gpm
Figure 7 Combination Plant (Equal Chiller Flows)
REV_SY13_book.book Page 26 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 27
Example 2: Unequal tower water allocation Ahother optioh is to avoid
DFA oversizihg by leveragihg the nultistage electric chiller's ability to operate
at elevated coolihg-water tenperatures. We cah acconplish this by ihcreasihg
the DFA's share o tower-water low ron 1/2 to 2/3.
This leaves 1,000 gpn |63 Lps] or the electric chiller, yieldihg a coolihg
tenperature dierehce o:
With this desigh strategy, the DFA suers ohly a slight loss o capacity, while
the electric chiller is ohly about 4% less eicieht. As ihdicated here ahd ih
Figure 8, uhderstahdihg the operatihg characteristics o both chiller types ahd
desighihg to the strehgths o each nihinizes the potehtially hegative inpact o
coolihg-tower water oh overall systen capacity ahd eiciehcy.
Botton lihe, desighers nust recoghize that the anouht o tower water allocated
to each chiller is hot predeternihed. lhstead, it is ahother variable that cah be
used to optinize chiller plaht desigh. Sihce each |ob is diereht, optinizatioh
DFA T
10,950 NBh
0.5 2,000 gpn
-------------------------------------------- 11F = =
Eectc T
7,100 NBh
0.5 1,000 gpn
-------------------------------------------- 14.2F = =
500 Ton Direct-Fired
Absorption Chiller
Bypass Line
System Pump(s)
14.2 F
1,000 gpm
11 F
2,000 gpm
Electric Centrifugal Chiller
System
Load
3,000
gpm
Figure S Combination Plant (Unequal Chiller Flows)
REV_SY13_book.book Page 27 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 28
nay be oh perornahce, cost, or other actors. The desigher nust be coghizaht
o which criteria are nost inportaht to the owher ahd satisy these
requirenehts or the chiller plaht's desigh usihg the optiohs available.
Low-IIow Absorption Systems
Wheh conparihg various air cohditiohihg systens, nahuacturers, systen
desigh ehgiheers, ahd buildihg owhers oteh orget ah inportaht cohcept: the
ehergy neters are oh the buildihg. Mahy tines the ocus is oh the largest
conpoheht ih the systen, the chiller, without regard or the other portiohs o
the systen. Nordeeh ahd Schwedler discuss a low-low absorptioh systen ih
Cntactng Busness, Novenber 1998. A shortehed versioh describihg how to
use this systen to reduce operatihg costs is presehted here.
The prinary ehergy cohsuners o a chilled-water systen are the
chilled-water punps, chiller, cohdehser-water punps, ahd coolihg
tower ahs. Fron a buildihg owher's perspective, reducihg the
operatihg costs o the systen (hot |ust the chiller) nakes sehse. The
ollowihg exanple shows how varyihg low rates through the
cohdehser reduces systen operatihg costs. lh this exanple, the ohly
systen chahge is to reduce the desigh cohdehser low rate ron
4.45 gpn/toh |0.08 Lps/kW] to 3.09 gpn/toh |0.055 Lps/kW]. While the
chiller nust work harder wheh the low rate is reduced, the power
reductiohs or the cohdehser-water punp ahd coolihg-tower ah nore
thah balahce the additiohal chiller work. lt cah be seeh, thereore, that
reducihg the cohdehser-water low rate cah reduce systen operatihg
costs. lt cah also reduce coolihg tower, cohdehser punp, ahd
cohdehser pipe size ahd cost. Systen desighers cah oteh provide
value to the buildihg owher by cohsiderihg systens with reduced low
rates as showh ih Table 10 oh page 29 ahd Figure 9 oh page 30.
REV_SY13_book.book Page 28 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 29
Table 10 Flow Rate Comparison
Cohvehtiohal
Desigh
(4.45 gpn/toh)
|0.08 Lps/kW]
Low-low Desigh
(3.09 gpn/toh)
|0.055 Lps/kW]
Absorptioh Chiller Conpoheht
Capacity ih tohs |kW] 437 |1536] 437 |1536]
COF 1.024 1.008
Full load gas cohsunptioh (therns) |kWh] 51.2 |1500] 52.0 |1523]
Cohdehser low rate (gpn) |Lps] 1945 |123] 1350 |85]
Leavihg CW tenperature (F) |C] 94.7 |34.8] 99.1|37.3]
Cohdehser head (eet o water) |kFa] 45 |135] 22.7 |67.9]
Coolihg Tower Conpoheht
Static head (eet o water) |kFa] 19 |57] 19 |57]
Nunber o cells 1 1
Fah hp per cell |kW per cell] 30 |22.4] 25 |18.6]
Total tower power |kW] 24.1 20.1
Cohdehser-water Funp Conpoheht
Fipihg/valve pressure drop (eet o water) |kFa] 20 |59.8] 9.6 |28.7]
Total head (eet o water) |kFa] 84 |251] 51.3 |153]
kW |kW] 44.1 |44.1] 18.7 |18.7]
Ahhual Operatihg Cost - Usihg TFACE
600
(Chiller + Coolihg Tower + CW Funp)
$31,802 $27,469
REV_SY13_book.book Page 29 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 30
Percent of Chiller Load
Full Load 75% 50% 25%
$0
$5
$10
$15
$20
$25
$30
4.45 gpm/ton
3.60 gpm/ton
3.09 gpm/ton
O
p
e
r
a
t
i
n
g
C
o
s
t
P
e
r
H
o
u
r
Figure 9 Flow Rates versus Operating Costs
REV_SY13_book.book Page 30 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 31
Absorption ChiIIer SpeciaI AppIications
Absorptioh chillers are used ih conort coolihg, process coolihg, ahd hybrid
systens-basically ahy systen where the lie-cycle ecohonics nake sehse. lh
additioh, absorptioh chillers it extrenely well ih several hiche applicatiohs.
While this sectioh deals with sone o these applicatiohs, there are others which
nay also it very well.
Heating Is AvaiIabIe
Absorptioh chillers that are hot direct-ired require a source o heat. lh nahy
ihdustrial applicatiohs, such sources o waste heat are available. These
circunstahces are ideal or ihstallatioh o absorptioh chillers. Speciic
applicatiohs ihclude those ih the ollowihg list.
n A hybrid systen where the electric chiller is ruhhihg ih a heat recovery
node: at a high ehough tenperature the electric chiller provides preheat to
the absorptioh chiller.
n lhdustrial processes with waste heat, such as stean turbihes or stean ron
sterilizatioh: sihce the stean nust be cohdehsed beore beihg reused,
absorptioh chillers cah be used to cohdehse it, thus greatly reducihg the
cost o providihg coolihg.
n Frocesses that ihclude gas-ehgihe-driveh chillers or gas ehgihes that
produce electricity: oteh these ehgihes have water |ackets to renove heat
ron the ehgihe casihg. Ohce agaih, this heat cah be used to reduce the cost
o providihg coolihg.
n Frocess loads that ruh cohstahtly: gas utility rates nay be extrenely
beheicial to those who cah provide a 24-hour-per-day load to the utility.
Turbine InIet CooIing
Utilities or large ihdustrial custoners nay use gas turbihes to produce
electricity. These turbihes becone nore eicieht as the dehsity o ehterihg air
ihcreases. Because air dehsity ihcreases as its tenperature is lowered, it is
oteh beheicial to cool the air. Absorptioh chillers cah be ideal, especially wheh
heat is available ron the turbihes to drive or ire the absorber.
Hot Air as an Energy Source
There are nahy applicatiohs where the ehergy source available at a acility is
hot air. This air is typically 300F to 800F |149C to 427C]. lh the past, sone
nahuacturers o direct-ired absorptioh chillers had desighs that could be ired
with this air source directly. Today we ihd that ahother path is connohly
choseh, ohe which ihvolves the use o a specialized heat exchahger to heat
REV_SY13_book.book Page 31 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 32
water or use with a sihgle-eect or double-eect absorptioh chiller, as ih
Figure 10. This type o heat exchahger cah develop water tenperatures ron
200F to 370F |93C to 188C]. The honihal requireneht or ihlet-water
tenperature ih a typical sihgle-eect absorber is 270F |132C], ahd ih a double-
eect absorber it is 350F |177C].
ControIs
The Importance oI ControIs
lnagihe pilotihg ah airplahe. The plahe is lyihg snoothly, but it's tine to lahd.
You look at the pahel arouhd you but there's ho altineter, ho air speed
ihdicator, ho oil pressure light, ho nohitor. lh short, ho cohtrols o ahy kihd!
Few would argue the hecessity or adequate cohtrols ih this situatioh.
Casualties, ahd the costly destructioh o the airplahe itsel, are alnost certaih to
result without then. Though aircrat are adnittedly conplex, the inportahce o
cohtrols is hot uhique to such equipneht applicatiohs. Virtually all types o
nachihes require sone orn o cohtrols or operatioh. lh a conort systen,
cohtrols are heeded at 2 levels:
n uhit cohtrols that regulate conpoheht operatioh ahd preveht equipneht
danage, ahd
n systen cohtrols that naihtaih the desired conort cohditiohs.
The rest o this sectioh discusses cohtrol cohsideratiohs uhique to conort
systens with absorptioh chillers.
Absorption Chiller
Hot Source Air Cooler Return Air Heating
Coil
Inlet to
Generator
Chilled-Water Loop
and Condenser-Water
Loop Are Not Shown
Figure 10 Hot Air as an Energy Source
REV_SY13_book.book Page 32 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 33
ControI Improvements at the Unit LeveI
Sihce the purpose o ah absorptioh chiller is to produce chilled water, cohtrols
are required to regulate this chilled-water supply ahd, at the sane tine,
saeguard the chiller ron detrinehtal operatihg cohditiohs that could lead to
costly equipneht dowhtine ahd repairs. The uhit-level cohtrols have chahged
substahtially ih the past 5 years. The na|or actor that allows today's
absorptioh chillers to outperorn their older couhterparts is the additioh o
nicroelectrohic cohtrols, or direct digital cohtrol (DDC). Absorptioh chillers
were previously cohtrolled with pheunatic cohtrollers, ahd although
pheunatics have beeh used or years with good reliability, they are hot able to
provide the level o cohtrol required to properly address the speciic
requirenehts o ah absorptioh chiller. With nicroelectrohic cohtrols, we are
how able to nohitor ahd cohtrol alnost every aspect o the cycle.
Cohcehtratioh levels, low rates, pressures, ahd tenperatures cah how be
nohitored ahd cohtrolled "oh the ly" to provide a cycle that is nuch nore
reliable ahd eicieht at part load. Sihce the uhit has a greater ability to cohtrol
the cycle, it is able to avoid operatihg at cohditiohs that could cause danage.
The nicroelectrohic cohtrols provide na|or inprovenehts to sehse, ahd react
quickly to, chahgihg cohditiohs. Sehsors are actory ihstalled ahd
connissiohed ih strategic locatiohs to provide ihornatioh ihput to the uhit-
level cohtrol. The uhit-level cohtrol conpares ahd ahalyzes this ihput based oh
established operatihg guidelihes, deternihihg i ahy neasured paraneters are
approachihg or outside o acceptable linits. The results o this ahalysis are
used alnost ihstahtaheously to cohtrol variable-speed punps ahd other
conpohehts withih the nachihe, saely reactihg to cohditiohs that would have
caused older, pheunatic cohtrols to shut the nachihe dowh or saety.
Sone o the problens averted by the hew uhit cohtrols, alohg with a geheral
descriptioh o how they work, are highlighted below. For ihornatioh oh
speciic nachihe operatioh, cohtact the chiller nahuacturer.
Response to Changing Conditions
Fapidly chahgihg cohditiohs were the bahe o past-geheratioh absorptioh
chillers. l the coolihg-tower water tenperature suddehly chahged 20 degrees
due to a ah ailure, the chiller shut dowh to protect itsel. l the load chahged
too rapidly, the chiller either shut dowh to avoid crystallizatioh or it crystallized.
While crystallizatioh wash't catastrophic to the nachihe, it certaihly kept the
chiller ron nakihg chilled water. A nyriad o cohditiohs could cause the chiller
to shut dowh. Fheunatic cohtrols could oteh cohtrol ohly the rate at which
heat ehtered the chiller. To protect the nachihe, the cohtrols shut it dowh.
Trahe's Horizoh chillers use sophisticated nicroconputer-based cohtrols (Trahe
reers to these as Adaptive Cohtrols) to vary the speed o punps ihside the
chiller. This allows close cohtrol o solutioh cohcehtratiohs ahd avoids
REV_SY13_book.book Page 33 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 34
crystallizatioh o that solutioh. lh respohse to rapidly chahgihg cohditiohs,
Trahe Adaptive Cohtrols will nake as nuch chilled water as possible while
keepihg the nachihe withih a sae ahd eicieht operatihg ehvelope. Wheh
these uhit cohtrols are cohhected to systen-level cohtrols, ah alarn cah be seht
to the systen operator statihg, or ihstahce, that the cohdehser-water
tenperature has suddehly ihcreased 20 degrees.
Air lnside the Machine
Absorptioh chillers operate at pressures below those exterhal to the nachihe.
Thereore, i there are ahy leaks, air will leak ihto the chiller. For older uhits,
sonethihg as basic as air gettihg ihto the nachihe could cause the nachihe to
shut dowh or crystallize. l the nachihe did hot shut dowh, it would nost likely
operate at a reduced capacity ahd eiciehcy ahd, at the sane tine, the lithiun
bronide ih the nachihe would react with the air ahd cause corrosioh ih the
ihterior o the nachihe.
Today, uhder that sane scehario, the chiller's purge systen will autonatically
turh oh to renove the air. This will hot ohly keep the nachihe ruhhihg at the
optinun capacity ahd eiciehcy, but nore inportahtly it will allow the nachihe
to cohtihue operatihg ahd provide chilled water while the air is autonatically
purged. lh additioh, the air has hot speht ehough tine ih the nachihe or the
corrosioh process to begih. With ah autonatic purge, the systen operator has
ah ihdicatioh that the purge is ruhhihg at a high level ahd that the nachihe
should be checked out. Wheh cohhected to systen-level cohtrols, ah excess
purgihg alarn could be seht to a naihtehahce persoh at a renote locatioh ahd
a service techhiciah could be dispatched to deternihe i there is a problen with
the nachihe.
Utilizing Variable Evaporator-water Flow
lh the last ew years, variable-low chilled-water plahts have gaihed ih
popularity, partly because variable chilled-water low results ih a reductioh o
systen punpihg cost. Fast-geheratioh absorptioh chillers were hot capable o
allowihg the evaporator (chilled-water) low rate to vary. Today, variable-speed
drives oh the solutioh punps cah nodulate to acconnodate chahgihg
cohditiohs. Cohtact the chiller nahuacturer to deternihe the allowable
nihinun ahd naxinun low rates as well as the allowable rate o chahge o
evaporator-water low.
ControIs at the System LeveI
Uhit cohtrol is hecessary to ehsure that each nachihe is operatihg withih its
linits ahd is able to satisy coolihg ahd/or heatihg loads. Wheh a uhit becones
part o a systen, ahother layer o cohtrol is heeded to coordihate its operatioh
with that o other equipneht perornihg related roles. Fuhctiohs required at the
systen level o cohtrol ihclude:
REV_SY13_book.book Page 34 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 35
n ehablihg (startihg) ahd disablihg (stoppihg) chillers ahd associated punps,
n resettihg chilled-water set poihts,
n loggihg data ron the systen, ahd,
n sehdihg diaghostics to the systen cohtroller.
Followihg are applicatioh cohsideratiohs or 3 systen-level cohtrol uhctiohs o
particular relevahce or absorptioh equipneht: cohtrol o heatihg/coolihg
chahgeover, chilled-water reset, ahd ihteracihg with a buildihg autonatioh
systen.
Control of Heating/Cooling Changeover
Switchihg a direct-ired absorptioh nachihe ron sinultaheous heatihg/coolihg
to heatihg-ohly operatioh requires chahgihg its systen-water set poihts. lt also
neahs that the chiller nust be told that it is how to produce ohly heated water.
The nethod used to connuhicate this chahge varies ron ohe DFA desigh to
the hext. For sone desighs it nay require opehihg or closihg ron 1 to 3 valves.
Be sure to cohsult the nahuacturer's operatihg ihstructiohs to uhderstahd the
required steps.
Chilled-water Reset
Chilled-water reset nay or nay hot beheit a chilled-water systen that ihcludes
absorptioh nachihes. Chilled-water reset will reduce the nachihe's uel
cohsunptioh. Fenenber that as the leavihg chilled-water tenperature
ihcreases, the uel cohsunptioh (or the sane chiller) decreases. (As a rule o
thunb, the eiciehcy gaihed with each 1F |0.6C] o reset is 1% to 2%.) At part-
load cohditiohs, it is thereore beheicial to the chiller to produce warner
chilled water. This cah be acconplished by settihg the chilled-water
tenperature set poiht upward as the chiller load decreases.
Chilled-water reset nay ihcrease the punp ahd/or ah ehergy required by the
systen. Fenenber that the chiller is operatihg as part o a systen, ahd the
systen's task is to naihtaih conort cohditiohs or satisy process coolihg
requirenehts. Dehunidiicatioh capability decreases as chilled-water
tenperature rises, so ohe nust ehsure that the use o chilled-water reset does
hot |eopardize occupaht conort. By the sane tokeh, i a process requires a
naxinun o 46F |7.8C] chilled water, it is hot advisable to cohtrol operatioh
to 48F |8.9C].
Ahalysis prograns such as TFACE
600 or DOE-2, there are tines wheh a ull ehergy ahalysis is hot
warrahted. Such situatiohs ihclude:
n ih very prelinihary stages wheh there is a nihinun o ihornatioh about
buildihg desigh ahd use available,
n wheh the buildihg owher or developer wahts sone ahalysis, but is hot
willihg to pay or a ull ehergy ahalysis, ahd/or,
n wheh the ehgiheer is still tryihg to secure the |ob, wahts to perorn sone
ahalysis to highlight his or her irn's capabilities, but cah ohly spehd
30 nihutes to 1 hour to perorn the ahalysis.
REV_SY13_book.book Page 43 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 44
lh these ahd sinilar situatiohs, use o a scopihg tool is warrahted. Ohe such tool
is Systen Ahalyzer, a Wihdows
Fules-o-thunb or estinatihg
stoichionetric air
Fule 1 (Source: Gdn-Fatt Enegy
Gup)
Allow 1 cu t o air or every 100 Btu o
gross heatihg value, theh, ron that value,
subtract 0.5 cu t. For exanple, hatural gas
cohtaihs 1,000 Btu/cu t, thereore:
Stoichionetric Air Fequired = (1,000/100) -
0.5 = 9.5 cu t air/cu t hatural gas
Fule 2 (Source: 1997 ASHFAE
Fundanentas Handbk)
"Ahother requehtly used value or
estinatihg air requirenehts is that 0.9 cu t
|0.25 n] o air is required or 100 Btu
|1 MJ] o uel." For hatural gas, theh:
Stoichionetric Air Fequired = 1,000 x 0.9 =
9.0 cu t/cu t |9.6 n/n] hatural gas.
These exanples denohstrate the ihexact
hature o "rule-o-thunb" calculatiohs ahd
uhderscore the inportahce o applyihg
such rules ohly or hohcritical processes.
REV_SY13_book.book Page 50 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 51
be hazardous because o carboh nohoxide productioh, ahd cohtributes to air
pollutioh." Cohsequehtly, while stoichionetric conbustioh cah be achieved, it
should hot be the ob|ective o good burher desigh or ad|ustneht.
lh act, or ecohony ahd saety, sone surplus conbustioh air (excess air) is
heeded to conpehsate or uhcohtrollable variahces ih uel, air delivery, lihkage
ad|ustnehts, ahd equipneht operatihg ehvirohneht. Excess air is deihed as
the anouht o air, ih additioh to the ideal or stoichionetric quahtity, required or
conplete conbustioh. Typically it is at least 15%-30% o the stoichionetric air
value.
How nuch excess air to provide or a particular DFA ihstallatioh is deternihed
by such actors as expected variatiohs ih uel ahd air supplies, systen
applicatioh, burher desigh, ahd cohtrol requirenehts. Too little excess air cah
result ih ihconplete conbustioh, snoke, ahd the ornatioh o carboh
nohoxide (CO) ahd hitrogeh oxide (NO
x
) conpouhds, while too nuch cah
decrease burher eiciehcy.
VeriIying CompIete Combustion:
Testing FIue Gas Composition
l the burher o a direct-ired absorptioh chiller is properly desighed, ad|usted,
ahd operated, thereby eectihg conplete conbustioh, the resultihg lue gas
should cohtaih percehtages o oxygeh (O
2
), carboh dioxide (CO
2
), ahd carboh
nohoxide (CO) as showh ih Table 14.
Usually cohducted ohce every 6 nohths uhless otherwise reconnehded by the
chiller nahuacturer, lue gas ahalysis provides a neahs or veriyihg conplete
conbustioh ahd evaluatihg burher perornahce. lt cah be used to detect uhsae
cohditiohs ahd to ehsure conplete ahd proper nixihg o uel ahd air, as well as
to deternihe (ahd perhaps inprove) conbustioh eiciehcy.
Various tests cah be used to deternihe the conbustioh perornahce o uel-
burhihg equipneht. While Bacharach ahd Hays Orsat kits are connohly used
or this purpose, electrohic test gear is gaihihg popularity. All 3 ahalysis
nethods nohitor O
2
, CO
2
, ahd CO. lh additioh, electrohic gear checks stack
Table 14 Composition of Flue Gas
Fuel Type Oxygeh Carboh Dioxide Carboh Mohoxide
1
1
Feerehce the curreht ANSl stahdard or carboh nohoxide enissiohs.
Natural Gas 3%-4% 9.5%-10%
No. 2 Fuel Oil 3%-4% 12%-13%
As a rule o thunb, allot 1.2 cu t |0.34 n
3
]
o total air (stoichionetric air + excess air)
or every 100 Btu |105.5 kJ] o uel cohteht.
So, or each 1 cu t |0.028 n
3
] o hatural
gas (at 1,000 Btu/cu t|37.7 kJ/ n
3
]), about
12 cu t |0.34 n
3
] o air are heeded to
assure conplete conbustioh.
REV_SY13_book.book Page 51 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 52
tenperature, while Bacharach kits neasure stack tenperature ahd snoke
cohteht. Flue gas sanples are typically collected via a sanplihg tube port oh the
lue access duct cover.
Foor burher perornahce (i.e., ihconplete ahd/or iheicieht conbustioh) is
ihdicated i the lue gas sanple cohtaihs carboh nohoxide (CO) or too little
oxygeh or carboh dioxide. Mahy cohditiohs cah result ih poor conbustioh,
sone o the nore connoh causes are detailed ih the ollowihg list.
n ihcorrect uel-to-air ratio
n inproper atonizatioh due to either uhsteady oil or air pressure, or a
plugged atonizer tip (liquid-uel burhers ohly)
n inpihgeneht o oil spray oh cold suraces (this cohditioh also produces
snoke)
n air ihiltratioh (air that bypasses the blower cah dilute conbustioh products)
n inproperly set oil tenperature or residual uels (ad|ustneht o oil
tenperature nay elinihate snoke ahd inprove the lue gas CO
2
level)
n poorly positiohed oil drawer (read|ustihg the oil drawer cah inprove
conbustioh eiciehcy ahd perornahce)
n uheveh overire drat (high luctuatiohs betweeh hegative ahd positive
burher pressures cah result ih drastic dierehces betweeh lue-gas ahalyses
ahd, ultinately, erroheous burher ad|ustnehts)
NO
x
Emissions
As showh ih the sidebar, hitrogeh oxides (NO
x
) are the conbustioh enissiohs
cohtaihihg hitrogeh ahd oxygeh ih direct-ired absorptioh chiller applicatiohs.
To nihinize their release, nahuacturers have developed low-NO
x
burhers.
These burher desighs use various nethods or reducihg NO
x
enissiohs. A cost-
eective nethod o achievihg low NO
x
enissiohs ih connercial ihstallatiohs is
lue-gas recirculatioh (FGF). lhduced by the conbustioh-air ah, FGF recycles
lue gases to lesseh NO
x
ornatioh by reducihg the lane tenperature ahd
oxygeh available or conbustioh.
lt is inportaht to hote that lue-gas recirculatioh requires ihstallatioh o ah
additiohal duct to trahsport gas ron the lue back to the burher. Figure 19 oh
page 53 depicts a typical FGF ihduced-drat pipihg ihstallatioh ahd outlihes the
associated ihstallatioh requirenehts.
A Little NO
x
Backgrouhd
Ntgen xdes ae pduced dung the
cnbustn pcess, ethe (1) by thena
Ixatn (eactn I ntgen and xygen
at hgh cnbustn tenpeatues), (2)
In Iue ntgen (xdatn I ganc
ntgen n Iue necues). UnItunatey,
hgh excess a and hgh Iane
tenpeatue technques I ensung
cnpete Iue cnbustn and, theeIe,
w enssns I ncnpete cnbustn
pducts, tend t pnte NC
x
Inatn.
j1997 ASHFAE Fundanentas Handbk,
Chapte 17. p. 15]
NO
x
collectively describes the conbustioh
enissiohs that cohtaih hitrogeh ahd
oxygeh: hitric oxide (NO), hitrogeh dioxide
(NO
2
), ahd hitrous oxide (N
2
O). At the lue
outlet, their relative cohcehtratiohs are
approxinately 97% NO, 2% NO
2
, ahd 1%
N
2
O. The Ehvirohnehtal Frotectioh
Agehcy (EFA) believes that N
2
O is a
precursor to the ornatioh o ozohe (O
3
)
which is, ih turh, recoghized as a health
risk ahd na|or cohstitueht o air pollutioh.
While study o the eects o NO
2
enissiohs is a relatively hew ield, N
2
O is
suspected to cohtribute to the depletioh o
stratospheric ozohe (which shields agaihst
ultraviolet light), ahd nay pronote the
greehhouse eect by absorbihg ihrared
radiatioh relected ron the earth's
surace. lt is also blaned or acid raih with
its attehdaht orest degradatioh ahd crop
destructioh.
lh light o these ehvirohnehtal cohcerhs,
sone local buildihg codes how call or low
NO
x
enissiohs.
The substahces that conprise NO
x
are
classiied as tenperature-depehdeht
thernal NO
x
, which ihcreases with higher
lane tenperatures, higher oxygeh
cohteht, ahd tine, conbustioh-depehdeht
pronpt NO
x
, whose productioh is lihked to
uels with CH radicals burhed ih oxygeh-
rich ehvirohnehts, ahd conpositioh-
depehdeht uel NO
x
which is produced by
uels cohtaihihg hohnolecular hitrogeh
conpouhds ahd cah be nihinized by
burhihg these uels ih a zohe with little or
ho oxygeh.
REV_SY13_book.book Page 52 Friday, May 28, 1999 11:42 AM
1999 Americah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 53
Flue Gas Intake
Flue Gas Ducting
Motorized FGR
Shutoff Valve
FGR Control Valve
Burner
Figure 19 Flue-gas Recirculation (FGR)
A typical flue-gas recirculation (FGR) system includes a stack flue-gas intake and associated
piping, as well as a shutoff valve and a control valve. (The latter is modulated via linkages with
the burner air/fuel control motor and is therefore usually factory mounted.) As referenced in the
illustration, basic installation (if not supplied as part of the DFA equipment) requires that the
installer do the following.
1 Modify the burner stack to accept the flue-gas intake. Position the intake at the center of the
stack inside diameter, either 3 to 5 stack diameters from the machine outlet or upstream of
an existing stack-outlet damper.
2 Run piping from the stack outlet to the inlet of the combustion air windbox. Steel tubing with
a wall thickness of 0.125" [3.175 mm] is typically suitable. Provide adequate mounting and
bracing throughout the run.
3 Use elbows with a radius-to-diameter (R/D) ratio > 2. Minimize the number of elbows to limit
pressure drop. Sectioned elbows, if used, must consist of multiple segments.
4 Insulate the ducting to minimize surface temperature and to comply with OSHA standards
and applicable codes.
5 Design all FGR piping runs to provide adequate clearance for machine inspection and
service.
REV_SY13_ch4.fm Page 53 Tuesday, June 1, 1999 10:41 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 54
Exhaust-gas Duct and FIue-stack Design
Design
The lue exhaust-gas duct ahd stack nust be desighed o naterial ih
conpliahce with nuhicipal, state, ahd ederal regulatiohs. The duct ahd stack
nust be heat-resistaht to accept tenperatures up to 675F |360C]. To avoid
eddy currehts or back pressure to the uhit, the duct, ahd the stack, sectiohal
areas should ihcrease ih dianeter ahd avoid sharp behds or steep chahges. l
behds are ihevitable due to the buildihg's cohstructioh, deternihe the height o
the stack with respect to the lehgth o the horizohtal lue gas duct usihg the
ollowihg ornula (i.e., provided the exhaust gas pressure at the stack outlet is
0 ih. to 0.2 ih. wg |0 to 50 Fa], ahd ih cohornahce with the sidebar at let).
Stack Opening
Desigh the stack outlet to preveht ehtry o raih, wihd, ahd show, ahd to
naihtaih a cohstaht drat.
Stack Location
Airlow arouhd buildihgs aects worker saety, process ahd buildihg equipneht
operatioh, protectioh o ihlets ron weather ahd pollutioh, ahd the ability to
cohtrol ihdoor air quality (i.e., tenperature, hunidity, air notioh, ahd
cohtanihahts). Wihd causes surace pressures that vary arouhd buildihgs,
chahgihg ihtake ahd exhaust systen low rates, hatural vehtilatioh, ihiltratioh
ahd exiltratioh, ahd ihterior pressure. Meah low patterhs ahd the turbulehce o
wihd passihg over a buildihg cah recirculate exhaust gases to air ihtakes.
Atnospheric cohditiohs, roo cohstructioh, ahd coolihg tower locatiohs nust
thereore be cohsidered wheh positiohihg the lue stack ahd other ihtake ahd
exhaust vehts, as showh ih Figure 20 ahd Figure 21 oh page 55.
For nore ihornatioh about low patterhs, wihd pressure estinatioh, air ihtake
cohtanihatioh, ahd problen-solvihg or wihd eects oh ihtakes, exhausts, ahd
equipneht, reer to these ASHFAE hahdbooks: 1997 Fundanentas (Chapter 15,
"Airlow Arouhd Buildihgs") ahd 1996 HVAC Systens and Equpnent
(Chapter 25, "lhdustrial Gas Cleahihg ahd Air Follutioh Cohtrol").
To assure sae ahd proper operatioh,
cohsult the chiller nahuacturer or
speciic burher pressure requirenehts ahd
stack desigh reconnehdatiohs.
Stack Heght 0.6 It pe 1 It Hznta Fun 4 It pe 90 Bend + =
0.2 n pe 0.3 n Hznta Fun 1.2 n pe 90 Bend + = [ ]
REV_SY13_book.book Page 54 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 55
Cooling Tower
Exhaust Gas
Vent
Flue Stack
Figure 20 Avoid Recirculation of Exhaust Gas
Direct-Fired
Absorption Chiller
Cooling Tower
Flue Stack
Vent
Flue Stack
Access Duct
Exhaust Duct
Figure 21 Typical Exhaust Duct lnstallation
REV_SY13_book.book Page 55 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 56
Construction
Sihce the duct or stack will be hot, it nust be cohstructed o heat-resistaht
naterial (i.e., cohcrete, plaster, nortar, or equivaleht hohlannable naterial) to
pernit ihstallatioh through a wall, ceilihg, or other buildihg structure. Other
cohstructioh cohsideratiohs ihclude the provisioh (ih the duct/stack) o
(a) supports that conpehsate or thernal expahsioh, (b) ihsulatioh to preveht
burhs ahd avoid elevatihg the equipneht roon tenperature, ahd (c) cleahihg
access doors or renovihg soot produced by the conbustioh process. Be sure
to conply with nuhicipal, state, ahd ederal codes. For naterial
reconnehdatiohs ahd/or proper danper positioh ahd lue pipihg, see
Chapter 30, "Chinhey, Gas Veht, ahd Fireplace Systens," ih the 1996 ASHFAE
HVAC Systens and Equpnent Handbk.
To avoid lighthihg-related problens, provide a lighthihg rod or good grouhd to
the lue stack.
MuItipIe-unit InstaIIations
l the sane lue stack is used or dischargihg exhaust ron nore thah 1 systen,
be sure to provide a danper, positiohed as ih Figure 22, to preveht exhaust
backlow ihto uhused uhit(s) ahd/or luctuatiohs ih static pressure. Always also
reerehce local codes or proper exhaust gas discharge ih your applicatioh.
Backflow Damper
Figure 22 Multiple-unit lnstallation
REV_SY13_book.book Page 56 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 57
ImpIications oI ASHPAE Standard 15-1994
lh 1994 ANSl/ASHFAE Stahdard 15, "Saety Code or Mechahical
Ferigeratioh," was adopted. "The purpose o this stahdard is to speciy the
sae desigh, cohstructioh, ihstallatioh, ahd operatioh o rerigeratihg systens."
lh geheral, absorptioh chillers are hot aected by the stahdard due to Sectioh
2.3 o the stahdard, which states:
Ths cde des nt appy whee wate s the pnay eIgeant.
Sectioh 8.13.6 does, however, aect absorptioh chillers. lt states:
N pen Ianes that use cnbustn a In the nachney n
sha be nstaed whee any eIgeant s used. The use I natches,
ghtes, hade eak detects, and sna devces shud nt be
cnsdeed a vatn I 8.13.6. Cnbustn equpnent sha nt be
nstaed n the sane nachney n wth eIgeant-cntanng
equpnent except unde ne I the Iwng cndtns:
(a) Cnbustn a s ducted In utsde the nachney n and
seaed n such a nanne as t pevent any eIgeant eakage In
enteng the cnbustn chanbe,
(b) A eIgeant vap detect s enpyed t autnatcay shut
dwn the cnbustn pcess n the event I eIgeant eakage.
Wheh rerigerahts are preseht durihg a conbustioh process, they cah break
dowh ihto products that are both harnul to hunahs ahd corrosive to
nachihery. The ihteht o Stahdard 15-1994 is to avoid both o these hazards by
prevehtihg rerigeraht exposure to ahy conbustioh process.
Thus, use o opeh-lane devices ih nachihery roons is strictly prohibited by
this sectioh uhless either Sectioh (a) or (b) is enployed.
Wheh a nachihery roon cohtaihs a boiler as well as a rerigeratioh systen,
Sectioh (a) allows conbustioh air be ducted to the boiler ron outside the
equipneht roon. This directive also applies to direct-ired absorptioh
equipneht sihce typical orced-drat conbustioh burhers applied with these
nachihes cohstitute opeh-lane devices. Ductihg o outside conbustioh air is
hecessary to preveht air (ahd rerigerahts) preseht ih the equipneht roon ron
ehterihg the lane. Mahy nachihery roons presehtly house both rerigeratioh
systens ahd boilers or direct-ired absorptioh nachihes. Usihg Sectioh (a)
thereore requires costly nachihery roon upgrades at owher expehse.
Alterhatively, Sectioh (b) allows a rerigeraht vapor detector to nohitor
rerigeraht levels ih the nachihery roon. l the detector neasures rerigeraht
levels above those allowable, a buildihg autonatioh systen that autonatically
shuts dowh the conbustioh process allows conpliahce with
Fortiohs o ASHFAE Stahdard 15 deal with
vehtilatioh requirenehts or equipneht
roons cohtaihihg rerigeratioh equipneht
usihg rerigerahts other thah water. The
begihhihg o this sectioh ("Conbustioh Air
Fequirenehts" oh page 50) addresses
requirenehts or delivery o air to the
burher o direct-ired absorptioh chillers.
Sihce this air will be used ih the
conbustioh process, it should be supplied
ih additioh to the vehtilatioh requirenehts
o Stahdard 15. The stahdard does hot
explicitly state this.
REV_SY13_book.book Page 57 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 58
ASHFAE Stahdard 15-1994. Mahy buildihg owhers enploy Sectioh (b) ih
equipneht roons that either have direct-ired absorptioh chillers or boilers that
ire ihdirect-ired absorptioh equipneht.
InsuIation oI Hot and CoId Absorption
ChiIIer SurIaces
lt is inportaht to apply hohlannable ihsulatioh to the chiller's hot ahd cold
suraces ohce the uhit is ihstalled at the |ob site. lhsulatioh prevehts the chiller's
cold suraces ron sweatihg (which cah result ih water accunulatioh oh the
equipneht roon loor), it also reduces heat loss ahd protects operatihg
persohhel ron the chiller's hot suraces. Today, actory-ihstalled ihsulatioh o
the cold suraces is available ron sone nahuacturers. Sone nahuacturers
supply ihsulatioh or hot suraces but it nust be ield ihstalled. Conpohehts
typically requirihg either hot or cold ihsulatioh are idehtiied below.
n Hot lhsulatioh: Type ahd thickhess nust be suicieht to satisy OSHA saety
requirenehts or protectioh o operatihg persohhel. Feconnehded or
high-tenperature geherator ahd all cohhectihg pipes, ahd solutioh heat
exchahger(s).
n Cold lhsulatioh: May be warrahted to preveht sweatihg up to a dew poiht
ratihg o 74F |23.3C] ahd to withstahd a tenperature o 200F |93.3C]
durihg heatihg operatioh. Feconnehded or evaporator, evaporator water-
boxes, rerigeraht-punp housihg, rerigeraht spray-tree pipihg, evaporator
returh-pipihg, ahd evaporator storage-tahk.
The ihstaller nust nake sure that uhit cover plates ahd lahge parts are easily
detachable ater ihsulatihg ahd provide renovable ihsulatioh where speciied
by the chiller nahuacturer.
Machines Shipped DisassembIed
Sone absorptioh equipneht desighs pernit shippihg the nachihe ih 2 or nore
parts. This sinpliies riggihg the equipneht ihto linited-access buildihgs or
cohihed equipneht roons, though it nay inpact ihstallatioh costs ahd result
ih a greater potehtial or leaks thah actory-assenbled nachihes.
Typically the evaporator, absorber, cohdehser, ahd low-tenperature geherator
conpose ohe sectioh, while the high-tenperature (direct-ired) geherator
nakes up ahother. Each sectioh typically ships with a hitrogeh holdihg charge.
The sectiohs nust be ield cohhected (preerably by ah ASME-certiied welder)
ahd leak-tested beore the nachihe cah be charged with lithiun bronide.
Field ihstallatioh o the burher assenbly
nay be required whether the chiller ships
disassenbled or as a actory assenbly. l
shipped uhihstalled, the cost o burher
ihstallatioh should be actored ihto the
total ihstalled cost o the equipneht. l the
burher is gas ahd/or oil ired, reer to
Chapter 33, "Fipe Sizihg," o the 1997
ASHFAE Fundanentas Handbk or gas
ahd oil pipihg ihstallatioh cohsideratiohs.
REV_SY13_book.book Page 58 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 59
Froper ihstallatioh ahd naihtehahce are key to years o trouble-ree operatioh.
lnproper naihtehahce cohtihues to be the cause o nahy uhsatisactory
systens. lt is inportaht that owhers who nust naihtaih their systens, as well
as desighers ahd ihstallihg cohtractors, be aware o na|or cohsideratiohs ih
ihstallatioh ahd naihtehahce. Observatiohs nade ih this sectioh are typical or
absorptioh equipneht ahd are presehted or your cohvehiehce. Always cohsult
the nahuacturer or uhit-speciic ihornatioh.
ChiIIer Maintenance
Absorptioh chillers have very ew novihg parts sihce the absorptioh cycle uses
heat ehergy rather thah nechahical-conpressioh ehergy to drive the
rerigeratioh cycle. These uhits, cohsequehtly, are sub|ect to less wear ahd tear.
Ater ah absorptioh rerigeratioh systen is ihstalled ahd connissiohed, it
typically operates without the cohstaht attehtioh o ull-tine attehdahts. lh
nahy cases the nachihe starts ahd stops oh a tine clock or other exterhal
sighal, with day-to-day operator ihtervehtioh linited to loggihg preseht
operatihg cohditiohs.
Like all large rerigeratioh systens, absorptioh equipneht nust receive certaih
routihe naihtehahce ahd service to ehsure eicieht operatioh, extehd
equipneht lie, ahd nihinize dowhtine. Feer to "Frevehtive Maihtehahce
lhspectiohs or Absorptioh Chillers" oh page 63 or a suggested prevehtive
naihtehahce plah. Weekly ahd nohthly naihtehahce procedures are typically
perorned by buildihg naihtehahce persohhel, while specially traihed
techhiciahs hahdle sprihg/all chahgeovers ahd other techhical service
requirenehts, oteh as part o a chiller naihtehahce cohtract. See "Conparihg
Chiller Maihtehahce Costs" oh page 14. These procedures address the
nachihe's nechahical, heat trahser, solutioh, ahd cohtrols conpohehts.
MechanicaI Components
Absorptioh nachihes typically ihclude these nechahical conpohehts: punp(s)
to circulate rerigeraht ahd solutioh, a purge to renove hohcohdehsables ron
the systen, a burher (i directly ired), ahd ah ehergy cohtrol valve (i ihdirectly
ired).
Refrigerant and Solution Pumps
While seasohal bearihg ahd seal ihspectioh is hot required, exanihatioh o the
shat seals (i so equipped) or wear at 3-year ihtervals is usually suggested. Be
sure to cohsult the nahuacturer or speciic reconnehdatiohs.
A hunber o chiller systen optiohs (e.g.,
narihe water-boxes, tube naterial ahd
thickhess, ahd nicroelectrohic cohtrols)
are available to lower naihtehahce costs
ahd ehhahce systen eiciehcy. Exanihe
such alterhatives closely. Feducihg
naihtehahce costs (which ehhahces
systen reliability) or ihcreasihg systen
eiciehcy by eveh a snall percehtage cah
result ih a large payback over the lie o the
equipneht.
REV_SY13_book.book Page 59 Friday, May 28, 1999 11:42 AM
1999 Anericah Stahdard lhc. All rights reserved
SYS-AM-13 (May 1999) 60
Purge
Accunulatioh o air ahd other hohcohdehsable gases uhdernihes absorptioh
chiller eiciehcy ahd reliability. Fegular operatioh ahd naihtehahce o the
purge uhit is thereore required to naihtaih the chiller's desigh pressures (ahd,
thereore, tenperatures), preservihg its hernetic ihtegrity, ahd stabilizihg the
uhit vacuun. Today nost purges are ully autonatic ahd geherally require less
naihtehahce thah previous-geheratioh nahual purges.
lh Trahe absorptioh chillers, ah eductor systen noves the hohcohdehsables
ron the absorber to the cohdehser. The Furiier