Reactive Power Control Relay RM 2106/12: Operating Instructions
Reactive Power Control Relay RM 2106/12: Operating Instructions
0 65
400
3
150
2 2
,
I
A
= Response current to be set in A
Q = Capacitor stage rating of the lowest
stage in var
(not the overall power of the system)
U = Mains voltage in V (phase to phase)
k
i
= Current transformer ratio
(primary/ secondary current)
k
u
= Voltage transformer ratio
(primary/ secondary voltage)
(if any)
21
Response current-setting 400 VAC mains voltage
Current- Step size (= Rating of smallest stage kvar)
transformer
A /A 2,5 5 6,25 7,5 10 12,5 15 20 25 30 40 50 60 100
30 /5 0,40 0,80 0,98 1,20 1,60
40 /5 0,30 0,60 0,74 0,90 1,20 1,50
50 /5 0,24 0,48 0,59 0,72 0,96 1,20 1,44
60 /5 0,20 0,40 0,49 0,60 0,80 1,00 1,20 1,60
75 /5 0,16 0,32 0,39 0,48 0,64 0,80 0,96 1,28 1,60 1,92
100 /5 0,12 0,24 0,30 0,36 0,48 0,60 0,72 0,96 1,20 1,44 1,92
150 /5 0,08 0,16 0,20 0,24 0,32 0,40 0,48 0,64 0,80 0,96 1,28 1,60 1,92
200 /5 0,06 0,12 0,15 0,18 0,24 0,30 0,36 0,48 0,60 0,72 0,96 1,20 1,44
250 /5 0,05 0,10 0,12 0,14 0,19 0,24 0,29 0,38 0,48 0,58 0,77 0,96 1,15 1,92
300 /5 0,04 0,08 0,10 0,12 0,16 0,20 0,24 0,32 0,40 0,48 0,64 0,80 0,96 1,60
400 /5 0,03 0,06 0,08 0,09 0,12 0,15 0,18 0,24 0,30 0,36 0,48 0,60 0,72 1,20
500 /5 0,02 0,05 0,06 0,07 0,10 0,12 0,14 0,19 0,24 0,29 0,38 0,48 0,58 0,96
600 /5 0,04 0,05 0,06 0,08 0,10 0,12 0,16 0,20 0,24 0,32 0,40 0,48 0,80
750 /5 0,03 0,04 0,05 0,06 0,08 0,10 0,13 0,16 0,19 0,26 0,32 0,38 0,64
1000 /5 0,02 0,03 0,04 0,05 0,06 0,07 0,10 0,12 0,14 0,19 0,24 0,29 0,48
1500 /5 0,02 0,02 0,03 0,04 0,05 0,06 0,08 0,10 0,13 0,16 0,19 0,32
2000 /5
0,02 0,03 0,04 0,05 0,06 0,07 0,10 0,12 0,14 0,24
2500 /5
0,02 0,03 0,04 0,05 0,06 0,08 0,10 0,12 0,19
3000 /5
0,02 0,03 0,04 0,05 0,06 0,08 0,10 0,16
4000 /5
0,02 0,03 0,04 0,05 0,06 0,07 0,12
5000 /5
0,02 0,03 0,04 0,05 0,06 0,10
6000 /5
0,02 0,03 0,04 0,05 0,08
Table 2: Response current setting with 400 VAC mains voltage
If the step size, current transformer or nominal voltage of the power factor correction
system do not match the values in the table, then the formula 1 on page 20 must be
used to calculate the response current.
22
4.6 Relative value of the switch
outputs -6-
These values refer to the relative stage
ratings.
Example:
A system has the following stages:
Stage rating Relative value
6.2 kvar => 1.0
6.2 kvar => 1.0
12.5 kvar => 2.0
25 kvar => 4.0
25 kvar => 4.0
0 kvar => 0.0
Note:
To assure correct operation of the reac-
tive VA control system the following con-
ditions must be taken into account when
choosing stage ratings:
If all possible switching combinations are
sorted according to reactive power (ca-
pacity), then the power difference be-
tween two consecutive combinations may
not be more than 1.2 times the smallest
stage power.
When automatic response current identi-
fication is switched on (-4-), the relative
value is automatically determined by the
control relay. This can be read under
setup code -6- but not altered.
When automatic response current identi-
fication is switched off (-4-), the relative
value of the switch outputs must be pro-
grammed manually.
The flashing LED in the stage display (a)
indicate the switch output to which the
relative value refers. Pressing the Se-
lectkey (i) briefly allows you to skip to
the next relative value.
The switch outputs with the lowest ca-
pacity are assigned relative value 1.0.
The relative values for the bigger stages
are calculated as follows:
Formula 2:
Relative value
Stage power
Smallest stage power
=
Free switch outputs are assigned relative
value 0.0. Only whole numbers can be
entered as factors.
4.7 Service -7-
The fundamental wave currents presently
flowing in the current path (j) of the con-
trol relay and be displayed under this
point.
The display for inductive or capacitive
operating status (b) can be used to de-
termine which current is displayed.
ind. and cap. off => active current
ind. or cap. off => reactive current
ind. and cap. on => apparent current
23
5. Functioning and operation
The control relay runs completely auto-
matically after it has been connected and
started. The current power factor appears
in the digital display (c). The ind and cap
LEDs (b) show whether the network is
loaded with capacitive or inductive reac-
tive power.
At the same time, the stage indicator (a)
shows the switched capacitor stages.
5.1 Automatic control mode
In automatic control mode the control
relay constantly measures the current
power factor in the network and com-
pares this with the target power factor. If
deviations are identified that are in ex-
cess of the tolerance range (control
band), the required target power factor is
restored by activating or deactivating
specific capacitor stages within the con-
trol relay delay time and in accordance
with the capacitor discharge time.
The control relay delay time is adapted to
the size of the deviation. The greater the
deviation, the shorter the reaction time. In
contrast, the capacitor discharge time is
fixed at one minute.
In addition, the control relay monitors the
overcurrent in the capacitors and checks
whether the connected capacitor power
is sufficient for compensation. If auto-
maticresponse current identification is
activated, the control relay also checks
the power of the capacitors connected.
The control relay issues an alarm in the
event of an error. (see section 6)
5.2 Displaying the total harmonic dis-
tortion factor
If the control relay is in automatic control
relay mode and if no historical or current
alarm is pending, then pressing the Volt-
age thd key (h) will display the current
total harmonic distortion factor (thd) of
the voltage in %.
5.3 Check System
Simultaneously pressing Voltage
thd(h) and Select(i) displays the cur-
rent relative value of stage 1. The value
displayed alternately with A1 in the dis-
play (see section 6.2.2). It is acknowl-
edged automatically for each stage after
about 15 seconds or can be acknowl-
edged earlier by pressing any key.
Simultaneously pressing Voltage
thd(h) and Select(i) for about 3 sec-
onds brings the control relay into check
system mode.
If automatic response current identifica-
tion (setup code -4-) is activated, then the
control relay behaves as described in
section 3.1 Initial start-up.
24
Note:
The check system mode defines the
present stage ratings as reference val-
ues for subsequent stage rating
checking.
(see section 3)
5.4 Manual mode
Pressing Select (i) for more than 3 sec-
onds switches the control relay to manual
mode. The Manual Mode LED (g)
lights up.
The Voltage thd key (h) can now be
used to select a switching output. The
flashing LED in the stage indicator (a)
shows which switching output is pres-
ently selected.
After a waiting period of about 10 sec-
onds the switching status of the selected
switch output is inverted. After switching
the control relay remains in manual
mode.
To quit manual mode, press the Select
key (i) for over 6 seconds until neither the
Manual Mode LED (g) nor the Setup
Mode LED (f) lights up.
Note:
No automatic switching activities are
carried out in manual mode. Manual
mode does not terminate automati-
cally.
Alarm signals E4 and E5 are also gener-
ated in manual mode, but do not lead to
any switching activities.
An exception to this is the alarm contact
when alarm output is activated on contact
6 of the RM 2106 device or contact 12 of
the RM 2112 device (setup code -3-).
25
6. Alarms and troubleshooting
The control relay has a number of ways
of identifying connection errors and func-
tional errors.
6.1 Connection errors
If automatic response current identifica-
tion has been activated on the control
relay (setup code -4-), the control relay
can identify the following errors after ini-
tial start-up or check system proce-
dure.
In all cases the connection of the power
factor correction system and the wiring of
the control relay are to be checked(see
connection diagrams 3 to 6).
6.1.1 E3 - No capacitors
This error message appears when the
control relay was able to measure a cur-
rent, but was unable to detect a change
in current when switching the capacitor
stages.
This can have the following causes:
control contacts (contactors) are not
connected or are not working correctly
the fuses of the capacitor stages have
not been installed
the current transformer is not located
between power supply and loads (in-
cluding PFC) (see connection dia-
grams 3 to 6).
6.1.2 E1 - Defect capacitor stages
Possible causes:
individual capacitor stages only have
2-phase connections to the mains
the defect capacitor stages do not
draw a symmetrical current from the
3 phases
6.1.3 E2 - Incorrect connection
Possible causes:
the entire power factor correction sys-
tem or all capacitors have only been
connected in 2-phase connections
the Meas terminal is unused and 2
phase conductors are connected be-
tween terminal N and L
the Meas terminal is connected to
the neutral conductor
the L terminal is connected to the
neutral conductor
6.1.4 I = 0 - No current in current path
It was not possible to measure a current
of more than 20 mA in the current path
when capacitor stages were either acti-
vated or deactivated.
Possible causes:
fault in the current transformer
connection
the current transformer is located in
the wrong place
the current transformer ratio is too high
26
6.2 Connection messages
In addition to the error messages, the
control relay also displays the results of
its automatic connection recognition.
Messages A1 and A2 can be acknowl-
edged by pressing any key or are auto-
matically acknowledged after a waiting
period of about 30 seconds.
6.2.1 A2 - Incorrect connection that
can be corrected internally
The connection has not been made in
accordance with connection diagrams 3
to 6. However, the problem has been
recognised as a simple confusion in the
phase conductors or in the connection of
the current transformer. The control relay
can continue to operate with this
connection.
6.2.2 A1 - Relative value of the
switch output
The value for the relevant switch output
is displayed while message A1 appears
on the display. Switch outputs at which
little or no capacitor rating has been
recognised are assigned switching
sequence factor 0.0. The user should
check whether the values displayed cor-
respond to the connected capacitor
stage. The connection must be checked
if deviations are extreme. The switching
sequence determined is also stored in
the setup mode (-6-).
6.3 Alarms in automatic control
operation
The Alarm LED (e) lights up for as long
as an alarm is active. If alarm output was
activated on contact 6 of the RM 2106
device or contact 12 of the RM 2112
device (setup code -3-), this contact also
closes. If the alarm status has ended, the
Alarm LED turns off and the alarm con-
tact opens again if in use. The message
continues to flash on the display. Press-
ing the Voltage thd key (h) enables the
cause of the alarm to be read out and the
alarm to be acknowledged during or after
the alarm .
6.3.1 E4 - Harmonic overcurrent in
the capacitor
The control relay issues this alarm if the
programmed limiting value for the har-
monic overcurrent (setup code -2-) is
exceeded for more than 1 minute. All ac-
tivated capacitor stages are deactivated.
After the overcurrent falls below the limit-
ing value, the control relay begins to acti-
vate the stages again after waiting about
5 minutes. The maximum overcurrent
factor (I
eff
./I
50/60Hz
) is recorded as the
cause of the alarm.
27
6.3.2 E5 - Target power factor not
reached
If the operating point of the control relay
is above the control band (see section
4.1) and if all available capacitor stages
have already been activated, the control
relay issues error message E5 after a
delay. The lowest measured power factor
during the alarm is recorded as the cause
of the alarm.
This alarm can be suppressed at setup
code -3-. ( see section 4.3 )
6.3.3 E1 - Defect capacitor stages
After initial start-up or check system
procedure, the determined stage ratings
are stored in a non-volatile memory (only
when automatic response current identi-
fication is active; setup code -4-).
If the control relay detects a drop in stage
rating during operation of more than 20%
or there is an extremely asymmetrical
current in the three phases of a capacitor
stage, it registers these stages as defect.
The defect stages can be read out as the
cause of the alarm.
Note:
This function only works if automatic
response current identification is
active.
6.3.4 U = 0 - No measuring voltage
This message indicates that the control
relay with connected Meas terminal has
been put into operation, however no volt-
age can be measured at this input at pre-
sent.
It is not possible to read the cause of the
alarm. Likewise this message can only
be acknowledged by eliminating the er-
ror.
6.4 I = 0 - No measuring current
If the current in the current measurement
path drops below 20 mA, the message
I=0 appears on the display.
The control relay deactivates a capacitor
stage after about 3 seconds. If this does
not result in a change in current, then the
stages still active are also deactivated.
This signal does not activate an alarm.
6.5 Other errors
Situations may arise due to the connec-
tion or special operating conditions that
cannot be identified by the control relay.
Table 3 below lists further sources of
errors.
28
7. Troubleshooting
Pos Fault Possible causes Necessary action
1 Control relay not work-
ing; no displays on the
front of the control relay.
No or the wrong voltage
has been applied to the
control relay.
Check that operating voltage
applied to the control relay is
at the right level.
2 The control relay does
not react to manual
switching despite
Delay time of about
10 seconds is not up.
If the required stage flashes in the
stage display (a) then wait until
the stage switches.
availability of power and
functioning indicators.
Manual mode is not
activated.
Hold down "Select" key until
"Manual Mode" LED (g) lights up.
3 Stage indicator (a) lights
up, however capacitor
contactors are not
Control circuit not
connected correctly or
no control voltage.
Check the control circuit in accor-
dance with the connection dia-
gram; check fuse.
switched on. No zero conductor at
contactors.
4 Control relay does not
terminate the automatic
measuring procedure.
Unstable mains supply
(strong power factor
variation).
Wait for more stable mains condi-
tions or enter the response cur-
rent and switching sequence
manually.
5 One stage is continu-
ously activated and de-
activated in automatic
Response current set too
low.
Set the response current correctly
in accordance with Table 1 or
Formula 1.
control relay mode. Strong load variation.
6 No stage activation in
automatic control relay
mode despite inductive
The response current has
been programmed
incorrectly.
Set the response current correctly
in accordance with Table 1 or
Formula 1.
load. Response current not
correctly identified despite
automatic response current
identification being set.
Check the control circuit accord-
ing to the connection diagram and
repeat the check system
procedure
Another measuring device
switched in parallel with the
control relay current path.
Current paths for different meas-
uring devices should always be
switched in series
Step size of capacitor is too
large.
Introduce capacitors with smaller
step size.
Table 3: Notes on troubleshooting
29
Pos Fault Possible causes Necessary action
7 "I=0" flashes on the
display.
Current transformer line
interrupted or short-
circuited.
Check current in current path using
ammeter (Imin 0.02 A).
8 Displayed power
factor is less than
Error in the control circuit. Check for the contactors
to be energized.
target power factor,
even though the
control relay has
activated all stages.
Error in the capacitor cur-
rent circuit.
Check fuses and contacts of
capacitor contactors as well as the
power consumption of the various
capacitor stages if necessary.
System too small. Add capacitors.
9 Control relay does
not switch off all
Response current is set too
high.
Set the response current correctly
according to Table 1 or Formula 1.
stages at light load
or standstill.
Control relay in manual
mode.
Press the "Select" key (i).
Table 3: Notes on troubleshooting
8. Technical data
Mode of connection:
As shown in connection diagrams 3 to 6.
Operating voltage:
Supply
voltage
Absolute permissible
threshold values
220 - 240 V 195 ... 264 V
Frequency:
50 Hz / 60 Hz (48 to 62 Hz)
Consumption of supply voltage:
Approx. 4 VA
Current path:
For current transformer ... /1A to ... /5A
Permissible maximum current: 6 A~
Consumption in current path:
Max. 0.5 VA at 5 A
Measuring voltage at terminal Meas:
Maximum 264 VAC at terminal N
Control contacts:
RM 2106 ....... 6 switching contacts
RM 2112 ..... 12 switching contacts
with potential binding to supply voltage
(terminal L)
Loading capacity of the control
contacts:
per contact max. ............................ 2 A
(only ohmic or inductive load)
total contact current, max. ............ 4 A
total contact load, max............. 950 VA
30
No-voltage trip
(undervoltage monitoring):
With voltage drops under 170 V for more
than 10 ms all capacitor stages con-
nected are switched off. After voltage is
restored the control relay switches the
required stages on.
Zero current trip:
For a current loss of longer than
3 seconds all capacitor stages connected
are switched off. After current is restored
the control relay switches the required
stages on.
Discharge time for the capacitors:
min. 1minute
Controls:
Keypad with 2 keys
Indicator elements:
RM2106: 12 LEDs
RM2112: 18 LEDs
3 character digital display
Operating temperature range:
-20 C to +65 C
Housing:
Plastic, black
flame-retardant as per UL-94 V0
Mounting:
From the front panel using a screwdriver
Front panel dimensions:
144 x 144 mm (DIN 43 700)
Panel hole size:
138 x 138 mm (DIN 43 700)
Installation depth:
40 mm
Weight:
approx. 0.8 kg
Installation position:
As required
Connections:
Terminal block
cable cross-section max. 1,5 mm
(AWG 16)
Protection class:
Terminals IP 20
Housing IP 54
(when the sealing ring is used)
Design as per:
DIN EN 61010-1 ( IEC 1010-1 )
Protection Class II (when insulated
mounting screws are used)
EMC:
EMC Immunity: DIN EN 61 000-6-2
EMC Emission: DIN EN 61 000-6-3
Fuse:
External, max. 4A specified
Accessories:
protection kit for protection class II / IP 54
...................................item no. 20-50014
31
Notes:
BA V1.11; ab SW V1.00
32
Power capacitors for low voltage
Power factor correction systems
Power factor correction systems with reactors
Modules for power factor correction systems
Active filters
Dynamic compensation of harmonics
Reactive power control relays
Maximum demand control systems
Mains monitoring instruments
Cost allocation
Energy management systems
Sales Programme
Reactive Power Control Relay Model RM 2106/12
Quality is our Motto
Quality has a Name
We are certified for
ISO 9001 and ISO 14001
F
R
A
K
O
5
5
-
0
5
5
3
1
/
1
0
/
0
7
/
X
X
X
X
/
a
b
V
1
.
0
0
/
V
1
.
1
1
S
u
b
j
e
c
t
t
o
t
e
c
h
n
i
c
a
l
a
l
t
e
r
a
t
i
o
n