Ground Floor Load Schedule & Computations

This document contains load schedules and computations for the ground, third, and roof floors of a building. The ground floor schedule lists various lighting, appliance, and air conditioning loads totaling 16,237 watts. Computations determine the required wire size as 2 x 38 mm^2 copper wire rated for 100 amps. The third floor schedule is similar and requires 2 x 50 mm^2 copper wire rated for 120 amps. The roof schedule has smaller lighting and pump loads totaling 4,139 watts, requiring 2 x 8.0 mm^2 copper wire rated for 30 amps. Wire sizes and circuit protection devices are specified for each circuit.

Uploaded by

Gintoki Sakata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
582 views

Ground Floor Load Schedule & Computations

This document contains load schedules and computations for the ground, third, and roof floors of a building. The ground floor schedule lists various lighting, appliance, and air conditioning loads totaling 16,237 watts. Computations determine the required wire size as 2 x 38 mm^2 copper wire rated for 100 amps. The third floor schedule is similar and requires 2 x 50 mm^2 copper wire rated for 120 amps. The roof schedule has smaller lighting and pump loads totaling 4,139 watts, requiring 2 x 8.0 mm^2 copper wire rated for 30 amps. Wire sizes and circuit protection devices are specified for each circuit.

Uploaded by

Gintoki Sakata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

GROUND FLOOR LOAD SCHEDULE & COMPUTATIONS:

BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
LIGHTING LOAD
3
SMALL APP.
4
SMALL APP.
5
AIRCON
3 HP
6
AIRCON 1.5 HP
7
REFREGERATOR
8
SPARE
9
SPARE
10
TOTAL
COMPUTATIONS
I =

BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
SMALL APP.
3
SMALL APP.
4
AIRCON 1HP
5
AIRCON 1HP
6
SPARE
7
SPARE
8
TOTAL
COMPUTATIONS
I =

NO.
OUTLET
22
12
18
6
7
1
1
2
-----

VOLTS

WATTS

AMPERES

PHASE

230
230
230
230
230
230
230
230
-----

2200
1200
1800
2160
2520
2238
1119
3000
----16237

9.57
5.22
7.83
9.39
10.96
9.73
4.87
13.04348
-----

1
1
1
1
1
1
1
1
-----

[16237+(25% x 3000)]x 0.8 D.F.


230

NO.
OUTLET
23
22
14
12
6
6
-----

2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

-----

WATTS

AMPERES

PHASE

230
230
230
230
230
230
-----

2300
2200
5040
4320
4476
4476
----22812

10.00
9.57
21.91
18.78
19.46
19.46
-----

1
1
1
1
1
1
-----

83.24

Amp

PROTECTION

15 AT
15 AT
15 AT
20 AT
20 AT
30 AT
30 AT
20 AT
-----

USE 2 # 38 mm TW 100 AT

59.09 Amp

VOLTS

[22812+(25% x 4476)] x 0.8 D.F.


230

SIZE OF WIRE &


CONDUIT

SIZE OF WIRE &


CONDUIT
2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

-----

PROTECTION

15 AT
15 AT
30 AT
30 AT
30 AT
30 AT
-----

USE 2 # 50 mm TW 120AT

3RD FLOOR LOAD SCHEDULE & COMPUTATIONS:


BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
SMALL APP.
3
SMALL APP.
4
AIRCON 1HP
5
AIRCON 1HP
6
SPARE
7
SPARE
8
TOTAL
COMPUTATIONS
I =

NO.
OUTLET
23
22
14
12
6
6
-----

VOLTS

WATTS

AMPERES

PHASE

230
230
230
230
230
230
-----

2300
2200
5040
4320
4476
4476
----22812

10.00
9.57
21.91
18.78
19.46
19.46
-----

1
1
1
1
1
1
-----

[22812+(25% x 4476)] x 0.8 D.F.


230

SIZE OF WIRE &


CONDUIT

PROTECTION

15 AT
15 AT
30 AT
30 AT
30 AT
30 AT
-----

2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

-----

USE 2 # 50 mm TW 120 AT

= 83.24 Amp

ROOF TOP FLOOR LOAD SCHEDULE & COMPUTATIONS:


BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
SMALL APP.
3
WATER PUMP 1.5 HP
4
SPARE
5
SPARE
6
TOTAL
COMPUTATIONS
I =

NO.
OUTLET
12
11
2
1
-----

VOLTS

WATTS

AMPERES

PHASE

230
230
230
230
-----

1200
1100
720
1119
----4139

5.22
4.78
3.13
4.87
-----

1
1
1
1
-----

[4139+(25% x 1119)] x 0.8 D.F.


230

= 15.37 Amp

SIZE OF WIRE &


CONDUIT

PROTECTION

2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

----USE 2 # 8.0 mm TW 30 AT

15 AT
15 AT
20 AT
30 AT
-----