Air System Sizing Summary For AHU-01G

This document provides an air system sizing summary for AHU-01G serving a 1-zone education college building with 899.2 square meters of floor area. Key details include: The central cooling coil is sized to handle a total load of 152.5 kW and sensible load of 126.6 kW at peak conditions in July. The design supply air temperature is 13.0°C. The supply fan is sized for a maximum airflow of 8228 L/s to serve the peak sensible load. The fan has a 18.39 BHP motor requiring 13.71 kW of power. Outdoor air is provided at a rate of 1420 L/s or 1.58 L/

Uploaded by

Farid Sedeky
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views1 page

Air System Sizing Summary For AHU-01G

This document provides an air system sizing summary for AHU-01G serving a 1-zone education college building with 899.2 square meters of floor area. Key details include: The central cooling coil is sized to handle a total load of 152.5 kW and sensible load of 126.6 kW at peak conditions in July. The design supply air temperature is 13.0°C. The supply fan is sized for a maximum airflow of 8228 L/s to serve the peak sensible load. The fan has a 18.39 BHP motor requiring 13.71 kW of power. Outdoor air is provided at a rate of 1420 L/s or 1.58 L/

Uploaded by

Farid Sedeky
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for AHU-01G

Project Name: EDUCATION COLLEGE


Prepared by: ame

10/01/2008
07:20

Air System Information


Air System Name .......................................... AHU-01G
Equipment Class ............................................ CW AHU
Air System Type ..................................................... VAV

Number of zones ............................................................. 1


Floor Area ................................................................. 899.2 m

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................... Peak zone sensible load
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 152.5
Sensible coil load ................................................. 126.6
Coil L/s at Jul 1500 ................................................ 6907
Max block L/s at Jul 1500 ...................................... 8228
Sum of peak zone L/s ........................................... 7816
Sensible heat ratio ............................................... 0.831
m/kW ....................................................................... 5.9
W/m ..................................................................... 169.5
Water flow @ 5.6 K rise ........................................ 6.57

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ..................................................... Jul 1500


OA DB / WB ...................................................... 44.5 / 24.7
Entering DB / WB ............................................. 27.7 / 17.6
Leaving DB / WB .............................................. 11.3 / 10.4
Coil ADP ....................................................................... 9.4
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 45
Design supply temp. ................................................... 13.0
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s at Jul 1500 .................................... 8228 L/s
Standard L/s .......................................................... 7613 L/s
Actual max L/(s-m) ................................................ 9.15 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ......................................................... 18.39 BHP


Fan motor kW ........................................................... 13.71 kW
Fan static ................................................................... 1000 Pa
l/s/person .................................................................. 10.00 l/s/person

Design airflow L/s .................................................. 1420 L/s


L/(s-m) ................................................................... 1.58 L/(s-m)

Hourly Analysis Program v.4.1

Page 1 of 1