Bab4 PROTEKSI TRAFO
Bab4 PROTEKSI TRAFO
BAB IV
PROTEKSI TRAFO
1. Ragam proteksi tergantung KVA trafo :
o KVA kecil <10 kVA (trafo LV) cukup fuse
o KVA sedang 10 s.d. 5 MVA (LV, MV) fuse , overcurrent relay
o KVA besar >5 MVA (MV, HV) fuse, overcurrent, differential relay, dll.
2. Tipe gangguan :
o External fault : gangguan pada sisi luar trafo, sisi beban, dll
o Internal fault :
o Short circuit in winding & connection
o Incipient fault
3. Ragam perlindungan
o Percentage Differential Protection
o Overheating protection
o Protection against Magneting Inrush Current
o Buchholz relay
o Pressure relay
o Earth fault relay
o Protection of Earthing Transformer
PROTEKSI TRAFO
F1
L1
F2
T1
1000KVA 20KV/380V 50HZ D/Y 3 FASE 4W Dy5 ONAN Z=5%
PENJELASAN
1 DATA 1.000KVA ADALAN 100%PT
F3
PL 100%
L2 J IKA OL 25%
PL(OL) =125% PL
F4 HARUS MAMPU DITANGGUNG TRAFO
PL(OL) =100% PT
100%PL ADA PERSAMAAN 125%PL =100%PT
PL =(100%/125%) PT = 0,80 PT
LOAD
SUMBER
OL % Nilai PL THD PT
50 % PL =(100%/150%) PT = 0,67 PT 67 %PT
45 % PL =(100%/145%) PT = 0,69 PT 69 %PT
40 % PL =(100%/140%) PT = 0,71 PT 71 %PT
35 % PL =(100%/135%) PT = 0,74 PT 74 %PT
30 % PL =(100%/130%) PT = 0,77 PT 77 %PT
25 % PL =(100%/125%) PT = 0,80 PT 80 %PT
20 % PL =(100%/120%) PT = 0,83 PT 83 %PT
15 % PL =(100%/115%) PT = 0,87 PT 87 %PT
10 % PL =(100%/110%) PT = 0,91 PT 91 %PT
5 % PL =(100%/125%) PT = 0,95 PT 95 %PT
0 % PL =(100%/125%) PT = 1,00 PT 100 %PT
CONTOH
SETTING OL =25% PL =80 PT
0,8 * 1000 KVA = 800 KVA
ARUS BEBAN =P/(1,73*VLL) = 1217 A
In BEBAN 1217 A
SETTING F4 125% In BEBAN 1521 A 25 s
UKURAN L2 MINIMAL 150% In 1825 A
SETTING F3 125% In BEBAN 1521 A 30 s
2 DATA 20 KV/380V
DAPAT DIKETAHUI
ARUS NOMINAL SEKUNDER Ins =
Inp =P/(1,73*VLL = 100%
1000000/(1,73*380) = 1.521 A
ADL 125% I_overload BEBAN
ARUS NOMINAL PRIMER Inp
Inp =P/(1,73*VLL =
1000000/(1,73*20.000) = 29 A
SETTING F2 125% In TRAFO
125% * 29A 36 A 25 s
UKURAN L2 MINIMAL 150% In 54 A
SETTING F1 125% In BEBAN tergantung Z trafo
J IKA Z <6% iF1 =600% Inp 217 A
J ika 6%<z<10% iF1 =400% Inp 145 A
J ika z >10% iF1 =150%~125% Inp 45 A
z=5% maka iF1 =600% Inp iF1 217 A
sebagai setting isc
3 DATA 3PH D/Y 4W DY5
4W =R, S, T, N
DY5 FASE SEK TERGESER 150 DEG THD PRI
4 DATA ONAN
SISTEM PENDINGINAN
METODE : 1 ALAMI =NATURAL N
2 PAKSA =FORCED F
a FAN
b POMPA SIRKULASI
MEDIA : 1 UDARA =AIR A
2 MINYAK =OIL O
3 AIR =WATER W
150
DERAJ AD
N
R
S
T
T
R
S
IRp IRs
3X30=150 DEG
CARA PENULISAN
KODE
MEDIA METODE MEDIA METODE
EX.
1 UDARA NATURAL UDARA NATURAL
A N A N ANAN
(AN)
2 MINYAK NATURAL UDARA NATURAL
O N A N ONAN
3 MINYAK NATURAL UDARA FAN
O N A F ONAF
4 MINYAK POMPA UDARA FAN
O F A F OFAF
5 MINYAK NATURAL AIR NATURAL
O N W N ONWN
(OW)
5 DATA Z = 5%
SAAT NORMAL
In =V/(ZT +ZL)
PENDINGINAN BELITAN PENDINGINAN CASING
R
L
ZT
R
L
In
GB1 :
KEAD
NORMAL
Vn
SAAT ADA SC DI TERM SEK
Isc =Vn/ZT >>>In
Z =ZT =5% ARTINYA SAAT
ADA SC DI TERM SEK
J IKA V =5% Vn MAKA TRAFO MENYERAP In
Vn %Vn I =ARUS DISERAP TRAFO
20.000 V 5 1 In
10 2 In
15 3 In
... In
100 20 In =Isc
RUMUS ARUS SHORT CIRCUIT
Isc =(I/Z)*In
KESIMPULAN Iscp =(100/5)*29 580 A
DARI Z=5% Iscs =(100/5)*1217 24.340 A
SETTING If1 217 A (=6 In)
SETTING If3 5.800 A (MAX 10 In)
ZT
R
L
In
GB2 :
KEAD
ADA SC
DI TERM
SEK
%Vn
6 UKURAN FUSE = K*In
SIFAT PROTEKSI NILAI In K (=%)
untuk teg primer <600V
Proteksi Utama fuse (CB) <2 A max 300%
Proteksi Utama fuse (CB) 2 A<In<9A max 167%
Proteksi Utama fuse (CB) >9 A max 125%
Proteksi Back up
Tanpa Rele OCR (termis) MAX 250%
Dengan Rele OCR (termis) z<6% max 600%
6%<z<10% max 400%
>10% max 150%
untuk teg >600V
Tanpa Rele OCR (termis)
Primary fuse max 150%
Primary CB max 300%
Dengan Rele OCR (termis)
Primer >600V sekunder >600V sekunder <=600V
Fuse CB Fuse CB Fuse CB misal
z<6% 600% 300% 300% 150% 250% <250%167% (In>9A)
125% (In<9A)
6%<z<10% 400% 200% 250% 125% 250% 250% 167% (In>9A)
125% (In<9A)
rele termis,
atau
tanpa
Fuse
Proteksi
utama
Proteksi
Back up
Fuse, atau
CB
Proteksi
utama
rele termis,
atau
tanpa
Proteksi
utama
Proteksi
utama
Fuse, atau
CB
Proteksi
Back up
Fuse, atau
CB