Q5591 Is it possible to use the MELSECQ driver to

talk to a Mitsubishi Q03UDECPU PLCs and how do I


set this up?
ArticleID: Q5591
Created: 28/10/2009
Last Updated: 31/10/2009
Suggested By: Michel Latumaelissa

Applies To:
CitectSCADA
Summary:
I would like to use the MELSECQ driver to talk to a Mitsubishi Q03UDECPU PLCs is this possible and how do I set this up?
Solution:
It is possible to use the MELSECQ driver since the QnUDE(H) uses the QnA compatible 3E frame.
Follow the below screenshots as a reference for configuring this driver.
*Note: Make sure that the value of 255 is specified in the "Address" field of the IODevice.


Page 1 of 2 Q5591 Is it possible to use the MELSECQ driver to talk to a Mitsubishi Q03UDECPU PL...
10/28/2014 mk:@MSITStore:C:\d%20drive\Help%20Files\CitectSCADA%20KB%202013-05-28.ch...
Schneider Electric (Australia) Pty Ltd Disclaimer
Related Links
Attachments

The port no in Citect is entered in a decimal format and in hexadecimal in the PLC.
Keywords:
MELSECQ, Mitsubishi, Q03UDECPU