Generator Test Report

This generator test report summarizes test results for Generator #1 located in the Turbine House 12 meters. It includes measurements of nameplate specifications, insulation resistance of the stator winding, DC resistance of stator and rotor windings, impedance of the rotor winding, and DC leakage testing of the stator winding at various voltages. Testing was performed on December 20, 2008 and results were approved by representatives from PT. TRUBA JAYA ENGINEERING, CNTIC, PLN and JMK.

Uploaded by

Erwin Sambas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
328 views

Generator Test Report

This generator test report summarizes test results for Generator #1 located in the Turbine House 12 meters. It includes measurements of nameplate specifications, insulation resistance of the stator winding, DC resistance of stator and rotor windings, impedance of the rotor winding, and DC leakage testing of the stator winding at various voltages. Testing was performed on December 20, 2008 and results were approved by representatives from PT. TRUBA JAYA ENGINEERING, CNTIC, PLN and JMK.

Uploaded by

Erwin Sambas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

GENERATOR TEST REPORT

Usage purpose

#1 Generator

Installation location

#1 Turbine house 12 meters

1.Nameplate:
Type

Active Power

Apparent Power

Power Factor

Rated Voltage

Rated Current

Rated Speed

Frequency

Rated Exciting Current

Rated Exciting Voltage

Stator Resistance 15

Rotor Resistance 15

Rated Hydrogen Pressure

State connection

Serial No.

Date of Release

Manufacturer
2. Test Insulation Resistance of Stator Winding:
Windings

Insulation ResistanceM
R15

R60

A-B C & E
B-A C & E
C-A B & E

Applied instrument:
3. Test DC Resistance of Stator Winding:
Windings

A-X

B-Y

C-Z

Resistance ()

Applied instrument:
4. Test DC Resistance and Insulation Resistance of Rotor Winding: 2008.12.20 t = 30 RH = 75%
Item

DC Resistance ()

Applied instrument:

Page 1 of 2

Insulation Resistance (M)

GENERATOR TEST REPORT


#1 Generator

Usage purpose

Installation location

#1 Turbine house 12 meters

5. Impedance measurement for Rotor Winding:


Out of the
chamber
2008.12.20
t=30

Voltage (V)

20

40

60

80

100

120

140

160

180

Current(A)
Impedance ()
Power(W)
Frequency (Hz)

In the
chamber

Applied instrument:
6. DC Leakage test of stator winding:
Phase

Supply Voltage
10kV

Leakage
Current (uA)

20kV

30kV

40kV

A-B C E
B-A C E
C-A B E

Applied instrument:
7.Test Conclusion:

Date:
Tested By:

PT.TRUBA JAYA ENGINEERING

Date:
Approved By:

CNTIC

Page 2 of 2

Date:
Witnessed By:

PLN / JMK