HMI and PLC Connecting Guide
HMI and PLC Connecting Guide
CONTENTS
MT5000/4000 SERIES HMI AND PLC CONNECTING GUIDE ........................................................- 1 1 SERIAL COMMUNICATION PIN DEFINITION ............................................................................................- 1 2 PRINTER CONNECTING CABLE DIAGRAM .............................................................................................- 3 2.1 Serial Interface Printer Cable ........................................................................................................- 3 2.2 Recommend Optional printer ........................................................................................................- 5 3 DOWNLOAD CABLE DIAGRAM ..............................................................................................................- 6 3.1 Download by Serial Port ...............................................................................................................- 6 3.2 Download by USB ........................................................................................................................- 6 3.3 Download by Network Ethernet....................................................................................................- 6 4 COMMUNICATION SETTINGS AND GUIDE OF HMI CONNECTING WITH CONTROLLER ............................- 8 4.1 ABB Corporation...........................................................................................................................- 8 4.2 Allen-Bradley ..............................................................................................................................- 12 4.3 ACS-Tech80 Motion Controller ..................................................................................................- 24 4.4 ADAM.........................................................................................................................................- 26 4.5 AysjNet ........................................................................................................................................- 28 4.6 BACnet MS/TP ...........................................................................................................................- 29 4.7 Baldor NextMove ES (Motion Controller)..................................................................................- 34 4.8 Barcode .......................................................................................................................................- 36 4.9 Baumuller ....................................................................................................................................- 37 4.10 Bosch Rexroth KVFC+ (Inverter).............................................................................................- 38 4.11 Bosch Rexroth ...........................................................................................................................- 40 4.12 Bosch Rexroth Ethernet.............................................................................................................- 48 4.13 CANOpen Node Slave ..............................................................................................................- 54 4.14 Cimon ........................................................................................................................................- 61 4.15 Danfoss Inverter ........................................................................................................................- 63 4.16 Delta Corporation......................................................................................................................- 69 4.17 Delta (Temperature Controller) .................................................................................................- 72 4.18 ENDA........................................................................................................................................- 79 4.19 Emerson NetWork Power ..........................................................................................................- 80 4.20 Epower ......................................................................................................................................- 84 4.21 Facon Corporation.....................................................................................................................- 86 4.22 Fuji SPB ....................................................................................................................................- 92 4.23 GE Fanuc Automation Inc.........................................................................................................- 94 4.24 HAIWELL...............................................................................................................................- 103 4.25 HanG .......................................................................................................................................- 105 4.26 Hitachi Inverter .......................................................................................................................- 106 4.27 Hitachi IES Co., Ltd ................................................................................................................- 108 4.28 Hollysys Corporation ..............................................................................................................- 115 4.29 HuaDA HD-JZ06.....................................................................................................................- 118 4.30 IDEC Corporation ...................................................................................................................- 120 4.31 Inovance Electric Corporation.................................................................................................- 122 -
4.32 Invt ..........................................................................................................................................- 126 4.33 KDN Corporation ....................................................................................................................- 129 4.34 Kinco Corporation...................................................................................................................- 131 4.35 Kinco EB-MOD2P-01(Kinco Bus Bridge) .............................................................................- 134 4.36 Kinco Servo Series ..................................................................................................................- 140 4.37 Kinco Master & Kinco Slave(Master/Slave Protocol Connection).........................................- 143 4.38 Keyence Corporation...............................................................................................................- 144 4.39 Koyo Corporation....................................................................................................................- 150 4.40 KTC Srdlink ............................................................................................................................- 154 4.41 KYL Slave...............................................................................................................................- 156 4.42 LENZE Inverter.......................................................................................................................- 157 4.43 LS Industrial SystemsLG ................................................................................................- 159 4.44 LUST.......................................................................................................................................- 180 4.45 Memory map ...........................................................................................................................- 185 4.46 MEGMEET .............................................................................................................................- 186 4.47 Mikom .....................................................................................................................................- 190 4.48 Millenium3 ..............................................................................................................................- 192 4.49 Mitsubishi Electric Corporation ..............................................................................................- 194 4.50 MKS controller........................................................................................................................- 226 4.51 Modbus....................................................................................................................................- 227 4.52 MODROL................................................................................................................................- 234 4.53 OE MAX .................................................................................................................................- 235 4.54 Omron Corporation .................................................................................................................- 237 4.55 OMRON E5EZ-R3(Temperature Controller)..........................................................................- 255 4.56 OPTO 22 .................................................................................................................................- 257 4.57 Panasonic Electric Corporation ...............................................................................................- 260 4.58 Parker AutomationServo Controller ................................................................................- 264 4.59 PMAC Motion Controller .......................................................................................................- 271 4.60 Power-one AURORA Wind Inverter .......................................................................................- 272 4.61 Profibus DP Slave ...................................................................................................................- 274 4.62 RF-IC (Card Reader) ...............................................................................................................- 278 4.63 RKC Instrument INC. .............................................................................................................- 279 4.64 Saia-Burgess............................................................................................................................- 282 4.65 Sailsors D9 (Temperature Controller) .....................................................................................- 284 4.66 Schneider Electric, Ltd. ...........................................................................................................- 285 4.67 SHIMADEN FP23 ..................................................................................................................- 294 4.68 SIEMENS................................................................................................................................- 297 4.69 SIKO AG05 SIKONETZ5.......................................................................................................- 325 4.70 Sinocon Sc1n...........................................................................................................................- 326 4.71 TAIAN.....................................................................................................................................- 328 4.72 TMCM_303.............................................................................................................................- 330 4.73 THINGET Controller ..............................................................................................................- 332 4.74 Toledo DLoadCell ...................................................................................................................- 334 4.75 Toshiba ....................................................................................................................................- 335 -
4.76 Trio motion controller .............................................................................................................- 339 4.77 Unitronics ................................................................................................................................- 343 4.78 Universal ASCII Slave ............................................................................................................- 347 4.79 Vigor Corporation....................................................................................................................- 348 4.80 XiLin Inverter..........................................................................................................................- 350 4.81 Yamatake Corporation .............................................................................................................- 351 4.82 Yaskawa Electric Corporation .................................................................................................- 356 4.83 Yokogawa Electric Corporation ..............................................................................................- 367 4.84 YuDian AI................................................................................................................................- 373 4.85 ZiGuang Ethernet ....................................................................................................................- 378 -
Pin
Function
Signal
RS-232C
RS-485
RS-422A
RX-(B)
--
RS485B
Receive data
RXD
Receive data
--
--
TXD
Transmit data
--
--
TX-
--
--
Transmit data
SG
RX+(A)
--
RS485A
Receive data
NC
--
--
--
NC
--
--
--
TX+
--
--
Transmit data
Signal ground
Pin
Function
Signal
RS-232C
RS-485
RS-422A
RX-(B)
--
RS485B
Receive data
RXD
Receive data
--
--
TXD
Transmit data
--
--
TX-
--
--
Transmit data
SG
RX+(A)
--
RS485A
Receive data
CTS
Clear transmit
--
--
RTS
Request
transmit
--
--
TX+
--
--
Transmit data
8
9
Signal ground
Pin
Signal
NC
--
NC
--
NC
--1-
RS-232C
NC
--
SG
Signal ground
NC
--
RXD
Receive data
TXD
Transmit data
NC
--
The COM2 can be used to download and upload HMI program, and connect to PLC via RS232 as
well.COM2.
-2-
-3-
TXD
RXD
19
18
BUSY
17
16
GND
15
g. WH-C13RA9-00E82B support printing of 384 dots width, and with automatic cutting function.
Serial port printing mode via RS232 level, short circuit as follows:
-4-
Printer model
Interface
Print Structure
Print format
WH-A52Z20-30E125
serial
240 dots/line
WH-A52Z20-40E125
serial
240 dots/line
WH-E202Z20-50E0022T55
serial
240 dots/line
WH-A62R10-41E725
Serial
thermal
192 dots/line
WH-A93RG0-00E725
Serial
thermal
192 dots/line
WH-E173R90-00E11720GA
Serial
thermal
192 dots/line
WH-A93RG0-00E825
Serial
thermal
384 dots/line
WH-T2AR10-30E82B
Serial
Thermal POS
384 dots/line
WH-E191RB0-00E1182055
WH-E191RB0-00E1182055
Serial
thermal
576 dots/line
Siupo SP-M, D, E, F
SP-E4004SK
Serial
240 dots/line
MY-POS80K
MY-POS80K
Serial
thermal POS
240 dots/line
Pictbridge
USB slave
Ink-jet
A4
EPSON ColorioPX-G5300
USB slave
Ink-jet
A4
HP 8500A/8500A Plus
USB slave
Ink-jet
A4
WH4008A31-053
WH-A62R10
WH-A93RG0-00E825
-5-
1 TX+
(orange,white)
2 TX3 RX+
4 BD4+
5 BD46 RX7 BD3+
8 BD3-
orange)
(green,white)
(blue)
(blue,white)
(green)
(brown,white)
(brown)
3 RX+ green,white
6 RX- green
1 TX+orange,white
4 BD4+blue
5 BD4- blue,white
2 TX- orange
7 BD3+ (brown,white)
8 BD3- brown
-6-
1 TX+
2 TX3 RX+
4 BD4+
5 BD46 RX7 BD3+
8 BD3-
(orange,white)
( orange)
(green,white)
(bule)
(bule,white)
(green)
(brown,white)
(brown)
1 RX+orange,white
2 RX- orange
3 TX+ green,white
4 BD4+ bule
5 BD4- bule,white
6 TXgreen
7 BD3brown,white
8 BD3- brown
-7-
CPU
Link Module
ABB AC31
O7KR51-V3.6
ABB AC500
PM571
PM581
PM591
Driver
Network Communication
Series
CPU
ABB AC500
Link Module
PM583
CPU Direct
Driver
ABB AC500 Modbus TCP Slave
System configuration
Series
CPU
ABB AC31
O7KR51-V3.6
ABB AC500
PM571
PM581
PM591
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485
RS485-2
Setting
RS232
Setting
RS232
Setting
CPU
PM583
Link Module
CPU Direct
Connect Type
Parameter
Ethernet
Setting
-8-
Cable
Your owner cable
RS485-2
-9-
PLC Settings
Related parameters settings refer to the communication equipment specifications
PLC
IP setting can use control builder plus orpanel settingspecific reference to ABB help
Supported Device
ABB AC31
Device
Bit Address
Word Address
Format
Input bit
I00.00-624.15
------
DD.DD
Output bit
O00.00-624.15
------
DD.DD
M(0.0--99.15)U(233.00-255.15)
------
DDD.DD
S000.00-624.15
------
DDD.DD
Input Register
------
IW00.00-624.15
DD.DD
Output Register
------
OW00.00-624.15
DD.DD
Internal Register
------
MW(0.0--99.15)U(233.00-255.15)
DDD.DD
Indirect Register
------
KW01.00-624.15
DD.DD
Internal Register
(Double words)
------
MD0.00-624.15
D.DD
Indirect Register
(Double words)
------
KD0.00-624.15
D.DD
Internal Relay
Link Relay
- 10 -
ABB AC500
Device
PLC Register
Internal Register
Internal Register
(Double words)
Bit Address
Word Address
Format
MB0.012499.7
------
DDDD.O
------
MW0.03.01695
D.DDDDD
------
MD0.06.01695
D.DDDDD
Note
1Select MODBUS mode in the ABB AC500 programming software;
2If selecting COM1 MODBUS, serial communication setting must be slave in the 15th
Operation mode. Other parameters match the touch-screen.
3Example: MB address: 0.0.1, please input 0.1 in the HMI.
Cable Diagram
ABB AC31 RS232
- 11 -
HMI terminal
9pin D-SUB female/male
com0/com1 com2
2 RX
7 RX
2 TXD
3 TX
8 TX
7 RXD
5 GND
5 GND
5 GND
4.2 Allen-Bradley
Serial Communication
Series
MicroLogix
CPU
Link Module
Channel 1
MicroLogix 1000
MicroLogix 1200
MicroLogix 1500
(1764-LSP,1764-LRP)
Channel 0
MicroLogix 1400
(1766-L32BWAA)
Channel 0
Driver
AIC+
Advanced
Interface Converter
1761-NET-AIC
Channel 2
Channel 0
SLC500
SLC 5/03
SLC 5/04
SLC 5/05
1770-KF3
2760-RB
1775-KA
5130-RM
AB SLC500/PLC5/MicroLogix
Series(DF1)*1
1771-KGM
PLC-5
PLC-5/11
PLC-5/20
PLC-5/30
PLC-5/40
PLC-5/40L
PLC-5/60
PLC-5/60L
Channel 0
CompactLogix
1769-L20
1769-L30
1769-L31
1769-L32E
1769-L35E
Channel 0
Channel 1
ControlLogix
1756-L61
1756-L63
CPU Direct
- 12 -
AB
CompactLogix/ControlLogix
Series(DF1)*2
MicroLogix
CPU
Link Module
MicroLogix 1100
MicroLogix 1400
MicroLogix 1000
MicroLogix 1100
MicroLogix 1200
MicroLogix 1400
MicroLogix 1500
1761-NET-ENI
AB
SLC500/PLC5/MicroLogix
CPU Direct (channel Series Ethernet(TCP Slave)
SLC5/05
SLC500
PLC-5
CompactLogix
Driver
*1
1)
SLC5/03
SLC5/04
SLC5/05
1761-NET-ENI
1761-NET-ENI
1769-L30ER
1769-L32E
1769-L35E
CPU Direct
AB
CompactLogix/ControlLogix
Series Ethernet(TCP Slave)
1761-NET-ENI
*2
CPU
1500 (1764-LRP)
MicroLogix
MicroLogix 1000
MicroLogix 1200
MicroLogix 1500
MicroLogix 1400
SLC500
SLC 5/03
SLC 5/04
SLC 5/05
Link Module
Channel 1
COMM Type
Parameter
Cable
RS232C
Setting
RS232C
Setting
RS232C
Setting
RS232C
Setting
RS232C
Setting
Channel 0
AIC+
Advanced
Interface Converter
1761-NET-AIC
Channel 0
Channel 2
Channel 0
1770-KF3
2760-RB
1775-KA
5130-RM
1771-KGM
PLC-5
PLC-5/11
PLC-5/20
PLC-5/30
Channel 0
- 13 -
PLC-5/40
PLC-5/40L
PLC-5/60
PLC-5/60L
CompactLogix
ControlLogix
1769-L20
1769-L30
1769-L31
1769-L32E
1769-L35E
1756L61
Channel 0
RS232C
Setting
RS232C
Setting
Connect Type
Parameter
Cable
Ethernet
Setting
Ethernet
Setting
Channel 1
CPU Direct
MicroLogix
SLC500
PLC-5
CompactLogix
CPU
Link Module
MicroLogix 1100
MicroLogix 1400
CPU Direct
(channel 1)
MicroLogix 1000
MicroLogix 1100
MicroLogix 1200
MicroLogix 1500
1761-NET-ENI
SLC5/05
CPU Direct
(channel 1)
SLC5/03
SLC5/04
SLC5/05
1761-NET-ENI
ALL
CPUs
that
support the link I/F on
the right
1761-NET-ENI
1769-L30ER
1769-L32E
1769-L35E
CPU Direct
1761-NET-ENI
- 14 -
PLC Setting
RSLogix500 software setting
NOTE:
- 15 -
PLC Setting
RSLogix5000 software setting
NOTE: Protocol: DF1 Point to Point; Error Detection: CRC; Enable Duplicate Detection: Disabled.
1Set the communication parameters: Controller properties
- 16 -
NOTE: Define the new device in the RSLogix5000 before using the register in the HMI.
(2) Define Tags and Data type: Select Controller Tags right-clickNew Tag, set up tag:
NOTE:
1. The controller registers that HMI needs to visit should be defined in the RSLogix5000 in advance.
2. Controller Tags are suitable for all routines in controller, they are global, so the tag should be built in
Controller Tags
(3) Tag Name and File Number mapping: Select LogicMap PLC/SLC Messages.Note: the
software should be in offline mode
- 17 -
Example
Build a new tag whose name is a, the Data Type is INT:
Note:
1. For the Data Typethe CompactLogix/ControlLogix supports the INT, BOOL, REAL data type only.
2. This driver does not support Multi-dimensional array, so you can define the range of Dim0 only.
3. In this driver, the INT range is 0~254; REAL range is 0~254, and the BOOL range is 0~999.
Besides, build two new tags whose Names are b and c, Data Type are REAL and BOOL.
The BOOL variable address range is 0~1024 in PLC, but this driver only supports 0~999. So the HMI can
only visit the BOOL register from to 999.
After the tags are defined, map the Name to the File Number:
- 18 -
Note:
1. The File Number is unique, a same File Number cannot map to different Names
2. The range of File Number in this driver is 0~254.
The HMI mapping addresses are as follows:
Tag Name
Data Type
Support Range
Mapping File
Number
INT[255]
0~254
INT 000000~000254
BOOL
000.0~254.15
N_BOOL 000000.00~000254.15
REAL[255]
0~254
REAL 001000~001254
BOOL[1024]
0~999
254
B_BOOL 254000~254999
PLC Setting
- 19 -
PLC Setting
Supported Device
AB SLC500/PLC5/MicroLogix Series(DF1)
Device
Bit Address
Word Address
Format
B30.0-255.15
------
DDD.DD
B100.0-255.15
------
DDD.DD
B110.0-255.15
------
DDD.DD
B120.0-255.15
------
DDD.DD
B130.0-255.15
------
DDD.DD
- 20 -
Notes
O00.0-255.15
------
DD.DD
I10.0-255.15
------
DD.DD
------
N150-255
DDD
------
N140-255
DDD
------
N130-255
DDD
------
N120-255
DDD
------
N110-255
DDD
------
N100-255
DDD
------
N70-255
DDD
------
F80-255
DDD
------
C5PV0-255
DDD
------
C5SV0-255
DDD
------
T4PV0-255
DDD
------
T4SV0-255
DDD
Note:
The format of I/O address is I/O e.s/b, and the e is slot number, s is variable number and b is bit number.
For example:
The PLC address is O0 0.0/11, mapping address in HMI is O0 0.11;
The PLC address is O0 0.1/8, mapping address in HMI is O0 1.8.
The I/O address in HMI is continuous when different AB CPU use the I/O modules.
Take Micrologix 1400 + output module 1762-OW16 for example, O0 1.3/3 maps the O0 6.3 in HMI.
AB CompactLogix/ControlLogix Series(DF1)
Device
Bit Address
Word Address
Format
N_BOOL000000.00~254254.15
------
DDDDDD.DD*1
B_BOOL000000~254991
------
DDDDDD*1
------
REAL000000~254254
DDDDDD*1
------
INT000000~254254
DDDDDD*1
------
DINT000000~254254
DDDDDD*1
- 21 -
Note:
*1 Variable less than three address the need to fill the former 0
The correct format example as follow: file number is 112, variable address is 87.12, format is 112087.12.
2. Users can define the File Number.
AB SLC500/PLC5/MicroLogix Series Ethernet(TCP Slave)
Device
Bit Address
Word Address
Format
Notes
B130.0-255.15
------
DDD.DD
B120.0-255.15
------
DDD.DD
B110.0-255.15
------
DDD.DD
B100.0-255.15
------
DDD.DD
B30.0-255.15
------
DDD.DD
Bf:n0.0-255255.15
------
DDDDDD.DD
O00.0-255.15
------
DD.DD
I10.0-255.15
------
DD.DD
------
OW00-255
DDD
------
IW10-255
DDD
------
N150-255
DDD
------
N140-255
DDD
------
N130-255
DDD
------
N120-255
DDD
------
N110-255
DDD
------
N100-255
DDD
------
N70-255
DDD
------
Nf:n0-255255
DDDDDD
------
F80-255
DDD
------
Ff:n0-255255
DDDDDD
------
C5PV0-255
DDD
------
C5SV0-255
DDD
------
T4PV0-255
DDD
------
T4SV0-255
DDD
*1
*1
*1
Note:
*1 Variable less than three address the need to fill the former 0
The correct format example as follow:
Bf:n 113087.12, file number is 113, variable address is 87.12, and mapping address in PLC is B113: 87/12;
Ff:n 9002, file number 9, variable address 2, and mapping address in PLC is F9:2.
AB CompactLogix/ControlLogix Series Ethernet(TCP Slave)
Device
Bit Address
Word Address
Format
N_BOOL000000.00~254255.15
------
DDDDDD.DD*1
B_BOOL000000~254999
------
DDDDDD*1
------
REAL000000~254255
DDDDDD*1
- 22 -
------
INT000000~254255
DDDDDD*1
------
DINT000000~254255
DDDDDD*1
NOTE:
1. Variable less than three address the need to fill the former 0
The correct format example as follow: file number is 112, variable address is 87.12, format is 112087.12.
2. Users can define the File Number.
Cable Diagram
MicroLogix RS232 cable diagram
1. Cable made by AB Corporation
- 23 -
Ethernet cable
Connecting PC and HMI use cross-ruling; communicating with hub or switch use cross-over cable or
cross-ruling.
Refer to 3.3 Download by Network Ethernet for method of making connection cable.
CPU
Link Module
Driver
SA2103
SB214SA
ACS-Tech80
System configuration
Series
CPU
Link Module
COM Type
SA2103
SB214SA
RS232
Communication Setting
RS232 communication
- 24 -
Parameter
Setting
Cable
Your owner cable
Supported Device
Device
Bit Address
Word Address
Format
Notes
LD 0~3
R/W
Linear Acceleration(LA)
-----------
LA 0~3
R/W
Linear Velocity(LV)
------
LV 0~3
R/W
------
AP 0~3
R/W
------
MM 0~3
R/W
Functions Avail.(FA.1)
------
FA.1 0~3
Read Only
Array Offset(AO)
------
AO 0~3
R/W
------
UI 0~3
R/W
------
LI 0~3
R/W
Path Gen.mode(PG)
------
PG 0~3
R/W
Motor enabled(MO)
MO 0~3
------
Write Only
CLEAR
CLEAR 0
------
RESET
RESET 0
------
B 0~3
------
Linear DecelerationLD
Cable Diagram
RS232 communication cable
- 25 -
Write Only
4.4 ADAM
Serial Communication
Series
ADAM
CPU
Link Module
Driver
ADAM-4017
ADMA-4015
ADAM-4017
ADMA-4015
System configuration
Series
ADAM
CPU
Link Module
COMM Type
Parameter
Cable
ADAM-4017
RS485
Setting
ADMA-4015
RS485
Setting
Communication Setting
HMI Setting
ADAM-4017 default communication: 9600, 8, none, 1; station: 255
- 26 -
PLC Setting
Connect INIT with GND, and reset the device, then set the communication of ADMA-4015.
Supported Device
ADAM-4017
Device
Bit Address
Word Address
Format
------
S_Channel 0-65535
DDDDD
------
A_Channel 0-7
Configuration Status
------
Status 0-65535
DDDDD
------
M_channel 0-65535
DDDDD
------
Channel_Status 0-65535
DDDDD
- 27 -
------
Read Version
Version 0-65535
DDDDD
Name 0-65535
DDDDD
1 Data type of S_Channel and A_Channel is signed integer. Decimal digits is 2 when the power
supply is 500mv or 150mv, other conditions is 3.
2 Data type of other registers is HEXING
3M_channel$AA5VVAt the same time allow multiplexing.
Enter the decimal value in the range of 0 to 255, mapping hexadecimal (00-FF)
ADAM-4015
Device
Bit Address
Word Address
Format
Notes
Channel
------
Channel 0-5
Floating
Cable Diagram
HMI terminal
9pin D-SUB female/male
Controller
RS485 terminal
com0/com1
1 RX-
DATA-
6 RX+
DATA+
4.5 AysjNet
Serial Communication
Series
CPU
Link Module
Driver
Compressor Controller
KYK3-K
RS485 on port
AysjNet
System configuration
Series
CPU
Link Module
Compressor
Controller
KYK3-K
RS485 on port
COMM Type
RS485
- 28 -
Parameter
Cable
Setting
Communication Setting
Supported Device
Device
Bit Address
Word Address
Format
Notes
control
CTL 0~5&128&150
------
DDD
Write only
set
------
SET (0~51)&128
DDD
state
------
STATUS 0.0~17.2
DD.D
Read only
Cable Diagram
CPU
Link Module
Driver
BACnet MS/TP
VLC-660R
Johnson FC BUS
BACnet MS/TP
BACnet MS/TP
Extend
ALERTON
VLC-660R
Ethernet Communication
Series
CPU
Link Module
- 29 -
Driver
BACnet IP
BACnet IP
CPU
Link Module
COM Type
Parameter
Cable
BACnet MS/TP
VLC-660R
Johnson FC BUS
CPU Direct
RS485
Setting
ALERTON
VLC-660R
Port on CPU
unit
RS485-2
Setting
BACnet MS/TP
Extend
BACnet IP
CPU
Link Module
COMM Type
Parameter
Cable
Ethernet
Setting
NOTE
- 30 -
PLC Setting
Please refer to the communication equipment related documentation to set the parameter
Note:
Lable one:
a.PLC Communication Time Out:255 stands for HMIs ID number;
b.005 stands for HMIs MAC address,Range is 0~127And it must be different from
others which one in the token-ring
Lable three:
a.Protocol Time Out 2:16 stands for register read and writer priority,range is 1~16;
b.9999 stands for offset address;Range is 0~4194303;
c.PLCs ID number=Offset address+The setting in [PLC Attribute]-[Station No.];
- 31 -
PLC Setting
Please refer to the communication equipment related documentation to set the parameter.
BACnet IP protocol
HMI Setting
NOTE
PLC Setting
Please refer to the communication equipment related documentation to set the parameter.
Supported Device
BACnet MS/TP Protocol
Device
Bit Address
Word Address
Format
Binary Input
BI 0-65535
------
DDDDD
Binary Output
BO 0-65535
------
DDDDD
Binary Value
BV 0-65535
------
DDDDD
- 32 -
Notes
Analog Input
------
AI 0-65535
DDDDD
Float
Analog Output
------
AO 0-65535
DDDDD
Float
Analog Value
------
AV 0-65535
DDDDD
Float
------
MI 0-65535
DDDDD
Float
------
MO 0-65535
DDDDD
Float
------
MV 0-65535
DDDDD
Float
Bit Address
Word Address
Format
Notes
AI
------
0-65535
DDDDD
Float
AO
------
0-65535
DDDDD
Float
AV
------
0-65535
DDDDD
Float
BI
0-65535
------
DDDDD
BO
0-65535
------
DDDDD
BV
0-65535
------
DDDDD
MI
------
0-65535
DDDDD
MO
------
0-65535
DDDDD
MV
------
0-65535
DDDDD
Note
BACnet IP Protocol
Device
Bit Address
Word Address
Format
Binary Input
BI 0-65535
------
DDDDD
Binary Output
BO 0-65535
------
DDDDD
Binary Value
BV 0-65535
------
DDDDD
Analog Input
------
AI 0-65535
DDDDD
Analog Output
------
AO 0-65535
DDDDD
Analog Value
------
AV 0-65535
DDDDD
------
MI 0-65535
DDDDD
------
MO 0-65535
DDDDD
------
MV 0-65535
DDDDD
Cable Diagram
RS485-2
- 33 -
Notes
Ethernet cable
Connecting PC and HMI use cross-ruling; communicating with hub or switch use cross-over cable or
cross-ruling.
Refer to 3.3 Download by Network Ethernet for method of making connection cable.
CPU
Link Module
Driver
NextMove ES
NextMove ES
Baldor NextMove ES
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
NextMove ES
NextMove ES
RS232
Setting
Communication Setting
HMI Setting
PLC Setting
Use the guide of the Workbench software
- 34 -
Supported Device
- 35 -
Only data of comms can be monitored, some address greater than or equal to 100 are read only. Please
pay attention to matching the controller software configuration.
Device
Bit Address
Float
---------
1-255
DDD
Notes
Float Data type
Cable Diagram
RS232 communication cable of HMI connecting to controller
4.8 Barcode
Serial Communication
Series
CPU
Link Module
Driver
RS232
Barcode
3800LTP-12E
Barcode
MLJ-MS9590
SYMBOL LS4208-SR200007 ZZR
Flashcode LS3042
System configuration
Series
CPU
Link
Module
COMM
Type
Parameter
Cable
RS232
RS232
Setting
3800LTP-12E
Barcode
MLJ-MS9590
SYMBOL LS4208-SR200007 ZZR
Flashcode LS3042
Communication Setting
- 36 -
Supported Device
Device
Bit Address
Word Address
Format
Word
--------
LW 8900-8999
DDDD
Bit
--------
LB 8999
DDDD
Notes
NOTE:
1. LW 8900-8999: the character after scanning, text and note book parts can display it.
2. LB 8999: the state of barcode is received or not. LB 8999=1 means the data is received.
Cable Diagram
Connect the scanner and the COM port of HMI directly.
4.9 Baumuller
Serial Communication
Series
CPU
Link Module
Driver
Baumuller
BM4413-ST0-02200-03
Baumuller
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
Baumuller
BM4413-ST0-02200-03
RS485
Setting
Your owner
cable
Communication Setting
- 37 -
Supported Device
Device
Bit Address
Word Address
Format
Bit type
DB_BIT000-255F
------
DDD.H
Word type
------
DB0-255
DDD
Notes
Cable Diagram
RS485-4 communication cable
CPU
KVFC+
Link Module
Driver
RS485
System configuration
Series
KVFC+
CPU
Link Module
COMM Type
Parameter
Cable
RS485
Setting
- 38 -
Communication Setting
Supported Device
Device
Bit Address
Word Address
Format
Start/Stop
STW0~3
------
Set frequency
------
HSW 0
------
B 0~41
DD
Deviation alarm
------
E 0~41
DD
------
P 0~37
DD
------
H 0~38
DD
D array
------
D 0~6
Programmable control
function array
Cable Diagram
- 39 -
Notes
STW0 open, start.
STW0 close, stop.
STW1 close, positive rotation.
STW1 open, negative rotation.
STW2 REV inching turning.
STW3 FWD inching turning.
B16 acceleration time.
B17 deceleration time.
CPU
PPC-R
PPC-R22.1 13VRS
Link Module
Driver
L40
L20
Bosch Rexroth
System configuration
Series
CPU
PPC-R
PPC-R22.1 13VRS
L40
L20
Link Module
COMM Type
Parameter
Cable
RS232C
Setting
RS485
Setting
RS232C
Setting
Communication Setting
PPC-R communication setting
RS232 communication: 19200, 8, even, 1; station number: 128
RS485 communication
- 40 -
NOTE: To communicate with the touch screen, declare variable firstly in the Rexroth software.
NOTE: To communicate with the touch screen, declare variable firstly in the Rexroth software.
- 41 -
PLC Setting
PPC-R software setting
PLC connects with PC via crossover ethernet cable. If using cross-connection ethernet cable, you must add
a HUB (we usually use a cross-connection line to access the Internet)
Hardware configuration
- 42 -
4. Click online/login
- 43 -
- 44 -
At the same time, you will find that there automatically generate two variables in the global variable
- 45 -
- 46 -
NOTEThe PLC panel must be set up, press Enter, then press , until showed up RS232, and then
press Enter to enter COM SERV interfaces (not SERV, it must change to SERV)
In accordance with the above settings, the serial line access, EV5000 can be communicated with the
Rexroth Controller L40 by serial port.
Supported Device
Device
Bit Address
Word Address
Format
BYTE
B0000-9999
------
DDDD
WORD
------
W0-65535
DDDDD
INT
------
I0-65535
DDDDD
UINT
------
UI0-65535
DDDDD
DWORD
------
DW0-65535
DDDDD
DINT
------
DI0-65535
DDDDD
UDINT
------
UD0-65535
DDDDD
Cable Diagram
PPC-R RS232 communication cable
- 47 -
Notes
CPU
Link Module
Driver
IndraLogic
IndraMotion MLC
IndraControl L25
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
IndraLogic
ETH
Setting
IndraMotio
n MLC
IndraControl L25
ETH
Setting
Communication Setting
L40
HMI Setting
- 48 -
Network configurationNote: PLC port num. must be set 6042HMI port num. is optionaldefault
is 6042. In addition, the screen and plc must be set in the same network segment, the gateway of the screen
is better to set with the actual use of the network gateway .
NOTE: To communicate with the touch screen, declare variable firstly in the Rexroth software.
PLC Setting
PLC connect with PC by crossover network cableif using cross-connection network cable, you must
add a HUB (we usually use a cross-connection line to access the Internet)
1. After L40 equipped with software driver successfully, to set as follows:
- 49 -
At this time open indralogic -->online/communication parameter -->new and select TCP/IP
to modify valueset IP address the same as controller: 192.168.100.103
- 50 -
3. Click online/login
L25:
HMI Setting
- 51 -
PLC Setting
1. Modify the IP in the controller.
2. Declare variable in controller programmer software.
3. Software setting
1Create new project and select IndraMotion MLC L25librarydriver and controlIndraMotion MLC,
then drug the selected controller onto the project file.
- 52 -
properties
box,
set
the
Firmware
3Declare variable
Declare variable UD in [Application][PlcProg(PRG)],and declare the variable type.
- 53 -
release
4. Click online/login
Supported Device
Device
Bit Address
Word Address
Format
Notes
BYTE
B0000-9999
------
DDDD
WORD
------
W0-65535
DDDDD
INT
------
I0-65535
DDDDD
UINT
------
UI0-65535
DDDDD
DWORD
------
DW0-65535
DDDDD
DINT
------
DI0-65535
DDDDD
UDINT
------
UD0-65535
DDDDD
Cable Diagram
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to 4.3 Download by Network Ethernet for method of making connection cable.
CPU
Link Module
K4
Driver
CANOpen port
System configuration
Series
KINCO
CPU
K4
Link Module
Parameter
Setting
CAN port
Setting
Communication Setting
HMI Setting
- 54 -
Cable
Your
cable
owner
NOTE: Baud Rate and Station No. must be the same as the setting in the controller.
Parameters Setting
1. Predefined PDO mapping parameters
a. Default is yes, that is an effective predefined PDO mapping parameters. HMI now use the following
PDO communication parameters and mapping
Receive PDO Mapping
Send PDO Mapping
Note: TX_PDO using the event-triggered mode, that is, only when its mapping variable changes, it sends
the PDO.
- 55 -
b. If the "No", the main station or other equipment necessary to configure the PDO communication
parameters and mapping (configure only in the pre-operational status). After configured, you can send a
save command via USB-CAN or controller to save the current configuration (restart still valid).
Command:
COB-ID
0x600 + NodeID
0x600 + NodeID
0x00
0x00
DATA
0x23 0x10 0x10 0x01 0x73 0x61 0x76 0x65
0x23 0x11 0x10 0x01 0x6C 0x6F 0x61 0x64
0x01 NodeID
0x80 NodeID
PLC setting
Note: you can find MT5020.EDS in fieldbus file of EV5000 Installation Directory, or you can download
from www.kinco.cn.
Take MT6000 for example (we use MT6000 HMI to test, and use 3S CODESYS software to download
project)
1. Setup
Start Menu 3s Software->Codesys v2.3->installtarget
- 56 -
- 57 -
- 58 -
- 59 -
Supported Device
- 60 -
Device
Bit Address
Word Address
Format
LW8000~LW8999
DDDD
Notes
NOTE: We must make the setting of PD0, SD0 and LW the same as codesys
Cable Diagram
4.14 Cimon
Serial Communication
Series
CPU
Link Module
Driver
PLC-S
Cimon
CM3-SP16MDRV
Cimon CM3-SP16
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
PLC-S
Cimon
CM3-SP16MD
RV
RS232/RS485
Setting
Communication Setting
HMI setting
Default parameter9600bps8none1station number0
RS232
- 61 -
RS485
Supported Device
Device
Bit Address
Word Address
Format
Input
X 0.0-63.F
------
DD.F
Output
Y 0.0-63.F
------
DD.F
Sub Relay
M 0.0-511.F
------
DDD.F
Link Relay
L 0.0-255.F
------
DDD.F
Keep Relay
K 0.0-255.F
------
DDD.F
Timer
T 0-519
------
DDD
Counter
C 0-519
------
DDD
- 62 -
Notes
------
DDDD
Z Register
F 0-2047
------
Z 0-1029
DDDD
Timer
------
T 0-519
DDD
Counter
------
C 0-519
DDD
Data Device
------
D 0-9999
DDDD
Sub Relay
------
M 0-511
DDD
Output
------
Y 0-63
DD
Input
------
X 0-63
DD
Keep Relay
------
K 0-255
DDD
Link Relay
------
L 0-255
DDD
------
S 0-99
DD
Special Relay
Cable Diagram
RS232
RS485
CPU
Link Module
Driver
Danfoss
FC-300
Danfoss
Modbus RTU
System configuration
- 63 -
Series
CPU
Link Module
COMM Type
Parameter
Cable
Danfoss
FC-300
RS485-2
Setting
Modbus RTU
FC-300
RS485-2
Setting
Communication Setting
Danfoss Protocol:
NoteChange the value of 8-30 to 2 on the Danfoss inverter for modbus protocolChange the value of 8-30
to 0 for the Danfoss Protocol
Inverter
8-3* FC Port Setting
8-30 protocol
*[0] FC (danfoss protocol)
[2] Modbus (modbus protocol)
8-31 address
1 247 * 1 (HMI station No.)
- 64 -
Inverter setting
Please refer to the manual of Danfoss inverter for details
Supported Device
Danfoss Protocol:
Device
Bit Address
Word Address
Format
EPD0-7998.99999
DDDD.DDDDD
EEPROM Register
EPW0-7998.99999
DDDD.DDDDD
RMD0-7998.99999
DDDD.DDDDD
RAM Register
RMW0-7998.99999
DDDD.DDDDD
Note
1. D indicates decimal; the prefix of RMD\RMW\EPD\EPW is address parameter, the suffix is index
number.
2. Mapping of index address (adding radix point if having index address, index value follow radix point.
Otherwise theres no radix point):
RMW310.1 is to 3-10, please clicking Menu, to find 3-10 to check.
- 65 -
Control word RW1: While RW1=0x47C or 1148, it means start. While RW=0x0F03 or 3843, it
means stop.
- 66 -
Frequency of RW0 mapping : If input 2000 to RW0, frequency is 25HZ, and input 4000, frequency
is 50HZ, and so on.
Timer, send value of RW1 and RW0 to RWD8000.
Bit Address
Word Address
Format
Output bit
0X1-65535
------
DDDDD
1X1-65535
------
DDDDD
------
3X1-65535
DDDDD
Output Register
------
4X1-65535
DDDDD
Notes
Note
Mapping of address (same as *10 relationships):
2-01 is to 4X2010
3-02 is to 4X3020
So address 4X1300 is to 1-30 as following picture, here is double word address. To get more
information, please refer to danfoss manual.
In addition, to get mapping address of startup, you should set bit of 3, 4, 5, 6,7,11 coil on:
0x047C=0000 0100 0111 1100
Set 0X 3, 0X 4, 0X 5, 0X 6, 0X 7, 0X 11 all to 1 (if random one of these registers is 0,inverter will
stop.
- 67 -
loop
01
02
03
04
05
06
07
08
09
10
11
12
13
14
0
Preset reference value LSB
Preset reference value MSB
DC brake
Inertial stop
Quickly stop
locking frequency
Acc/Dec stop
Do not reset
Do not inching
Acc/Dec 1
valid data
Relay 1 close
Relay 2 close
Set LSB
15
Set MSB
16
Do not reverse
Transducer controller word (FC structure)
Do not DC brake
Do not Inertial stop
Do not Quickly stop
Do not locking frequency
start
reset
inching
Acc/Dec 2
invalid data
Relay 1 open
Relay 2 open
reverse
Set 0X 30X 40X 50X 60X 7 all to 1 via the method of setting on when window open; Change
the inverter status (start or stop) by control the status of 0X11.
0x2000=0010 0000 0000 0000(binary bit from the 17th to the 32nd), setting the 30th bit to 1 means
- 68 -
frequency is 25Hz, and 1 in the 29th bit means 12.5Hz, and so on. In short, the 0X17~0X32 is to control
frequency. The inverter will show the value after starting.
0X17~0X32 for controlling frequencymapping as follows:
0x4000 50Hz
0x2000 25Hz
0x1000 12.5Hz (approximate)
0x800 6Hz
And so on, about 80 times
Cable Diagram
CPU
Link Module
DVP
DVP14SS11R2
DVP 24
DVP 32
DVP 60ES00
DVP-XXES01
Driver
Delta DVP
RS485 on port
System configuration
Series
CPU
DVP
DVP14SS11R2
DVP 24
DVP 32
DVP 60ES00
DVP-XXES01
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485 on port
RS485-2
Setting
Communication Setting
DVP RS232 communication
- 69 -
Note: RS485 communication, we should change the value of D1120 in the PLC Software.
PLC setting
1. Wpl207->Auxiliary Editing->RS-485 Protocol Setting (D1120), you can set the value of D1120.
- 70 -
2. PLC connection with the Wpl207, monitoring changes in the value of D1120. for example, 9600, 7, even,
1. and then D1120=86HEX
Supported Device
Device
Bit Address
Word Address
Format
Input
X0-9999
------
OOOO
Output
Y0-9999
------
OOOO
Auxiliary Relay
M0-9999
------
DDDD
Step Relay
S0-9999
------
DDDD
Timer Relay
T0-9999
------
DDDD
Counter Relay
C0-9999
------
DDDD
Timer
------
TV0-9999
DDDD
Counter
------
CV0-127
DDD
------
CV2 232-255
DDD
Data Register
------
D0-9999
DDDD
Cable Diagram
DVP RS232 communication cable
- 71 -
Notes
CPU
Link Module
Driver
DVP
DTA4848
DTB9696VR
DTC1000
DTC2000
Delta DTA/DTB/DTC
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
DVP
DTA4848
DTB9696VR
DTC1000
DTC2000
RS485 on port
RS485-2
Setting
Communication Setting
RS485-2 communication
Supported Device
- 72 -
Device
Bit Address
Word Address
Format
Output bit
0X1-FFFF
------
HHHH
1X1-FFFF
------
HHHH
------
3X1-FFFF
HHHH
Output Register
------
4X1-FFFF
HHHH
Notes
Controller Setting
1. Set the communication parameter
Setting communication parameter in setting mode
(1)
(2)
(Baudrate)
(3)
(Data bit)
(4)
(Parity)
(5)
(Stop bit)
Content
4700H
4701H
4702H
Upper-limit alarm 1
Explanations
Lower-limit alarm 1
Upper-limit alarm 2
Lower-limit alarm 2
4707H
PB Proportional band
4709H
Ti Integral time
470AH
Td Derivative time
470BH
Heating/Cooling hysteresis
0~9999
4710H
4711H
Control method
mode
4712H
or
0%~100%
4714H
4715H
Alarm 1 type
In the setting mode
Please refer to the contents of the Alarm Outputs for detail.
4716H
Alarm 2 type
In the setting mode
4717H
Temperature
selection
unit
4718H
Heating/Cooling
Selection
4719H
471AH
Communication
selection
display
control
471BH
Software Version
4729H
AT Setting
- 74 -
4733H
CT monitor value
Content
Explanation
1000H
1001H
Unit is 0.1, oC or oF
The data content should not be higher than the
1002H
1003H
1004H
1005H
Control method
control. In the setting mode
0: Heating, 1: Cooling, 2: Heating/Cooling, 3:
1006H
1007H
1008H
1009H
PB Proportional band
100AH
Ti Integral time
100BH
Td Derivative time
100CH
Integration default
100DH
100EH
100FH
or
- 75 -
1010H
1011H
1012H
1013H
or
or
1014H
1015H
1016H
1017H
1018H
1019H
101AH
101BH
101CH
1020H
Alarm 1 type
1021H
Alarm 2 type
1022H
Alarm 3 type
1023H
- 76 -
1024H
Upper-limit alarm 1
1025H
Lower-limit alarm 1
1026H
Upper-limit alarm 2
1027H
Lower-limit alarm 2
1028H
Upper-limit alarm 3
1029H
Lower-limit alarm 3
102AH
102BH
unit: 0.1
102DH
CT read value
102FH
software version
1030H
(setting when it is
1050H~
1057H
1060H~
1067H
2000H~
203FH
2080H~
20BFH
0811H
0812H
AT setting
In the adjusting mode
0: STOP, 1: RUN (default).
0814H
0815H
0816H
0817H
0818H
Cable Diagram
DVP RS485-2 communication cable
- 78 -
4.18 ENDA
Serial Communication
Series
CPU
ENDA devices
Link Module
Driver
ELC
ETC
EUC
EPC
EDP
System configuration
Series
ENDA
devices
CPU
Link Module
COMM Type
ELC
RS485
ETC
RS485
EUC
RS485
EPC
RS485
EDP
RS485
Parameter
Setting
Cable
Communication Setting
ENDA Devices:Default communication:9600, 8, 1, none; station1
Supported Device
ENDA PLC Devices
Device
Bit Address
Word Address
Format
Output Relay
MB 0-65535
------
DDDDD
IP 0-65535
------
DDDDD
Output Register
------
MW 0-65535
DDDDD
------
IR 0-65535
DDDDD
Notes
Device
Bit Address
Word Address
Format
Coils
Coils 0-65535
------
DDDDD
DI 0-65535
------
DDDDD
Holding Registers
------
HR 0-65535
DDDDD
------
IR 0-65535
DDDDD
Notes
Cable Diagram
RS485 communication cable
CPU
Link Module
Driver
Emerson EC10
Ec10-1006BRA
Emerson EC10
Emerson EC20
Ec20-2012BRA
Ec20-3232BRA
Emerson EC20
System configuration
Series
CPU
Emerson
EC10
EC10-1006BRA
Emerson
EC20
EC20-2012BRA
EC20-3232BRA
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485 on port1
RS485-2
Setting
RS232
Setting
RS485 on port1
RS485-2
Setting
Communication Setting
Emerson EC10 RS232 communication
- 80 -
- 81 -
NOTE: Communication with port1, you must set the system configuration in the programming software
first.
Supported Device
Emerson EC10
Device
Bit Address
Word Address
Format
Input Relay
X000-377
------
OOO
Output Relay
Y000-377
------
OOO
- 82 -
Notes
Internal Relay
M0000-1999
------
DDDD
Special Relay
SM000-255
------
DDD
Step Relay
S000-991
------
DDD
Timer Relay
T000-255
------
DDD
Counter Relay
C000-255
DDD
DDDD
Data register
------
-----D0000-7999
Special Register
------
SD000-255
DDD
Index Register
------
Z00-15
DD
Timer
------
T000-255
DDD
Counter
------
C000-199
DDD
Counter(double word)
------
C_Double200-255
------
D_Double0000-7999
DDDD
------
SD_Double000-127
DDD
DDD
Emerson EC20
Device
Bit Address
Word Address
Format
Input Relay
X000-377
------
OOO
Output Relay
Y000-377
------
OOO
Internal Relay
M0000-1999
------
DDDD
Special Relay
SM000-255
------
DDD
Step Relay
S000-991
------
DDD
Timer
T000-255
------
DDD
Counter
C000-255
DDD
DDDD
Data register
------
-----D0000-7999
Special Register
------
SD000-255
DDD
Index Register
------
Z00-15
DD
Timer
------
T000-255
DDD
Counter
------
C000-199
DDD
Counter(double word)
------
C_Double200-255
DDD
------
D_Double0000-7999
DDDD
------
SD_Double000-125
DDD
Cable Diagram
Emerson RS232 communication
- 83 -
Notes
4.20 Epower
Serial Communication
Series
CPU
Link Module
Epower
Epower
CPU Direct
Driver
EPower
Epower Slave
System configuration
Series
CPU
Link Module
COMM Type
Epower
Epower
CPU Direct
RS232
Communication Setting
- 84 -
Parameter
Cable
Setting
Setting
Supported Device
Device
Bit Address
Word Address
Format
UPSSet
UPSSet1-6
------
DDDDD
UPSPanel
UPSPanel0-9
------
DDDDD
UPSData
------
UPSData0-70
DDDD
UPSDisp
------
UPSDisp0
DDDDD
UPSCommand
------
UPSCommand0-52
DDDDD
------
UPSText0-1
DDDDD
UPSText
Slave driver notes
- 85 -
Notes
1. Transmit the device value to LW, LB by timer; refer to the addr table for details.
2. UPSCommand must use with UPSSetmacro
3. UPSDisp must use with UPStexrUPSPanelmacro.
Epower HMI project notes
1. The project must have UPSData0 device, otherwise the data accuracy will be affected; Suggest to
put UPSData0 device in the public window.
2. LW.B indicates the bits of UPSData
Cable Diagram
COM0 connect to ups communication board
CPU
Link Module
RS232 on the CPU unit
FBs
FBs-10MA/MC
FBs-14MA/MC
FBs-20MA/MC
FBs-24MA/MC
FBs-32MA/MC
FBs-40MA/MC
FBs-60MA/MC
FBs-20MN
FBs-32MN
FBs-44MN
FBe-20MA
FBe-28MA
FBe-40MA
CPU unit
FBe/FBn
Driver
FBS-CB25-3
Port 0
FATEK FB
Port 1
Modbus RTU
Port 2
Port 0
- 86 -
FBe-20MC
FBe-28MC
FBe-40MC
FBn-19MCT
FBn-26MCT
FBn-36MCT
CPU unit
Port 0
Port 1
Port 2
FB-DTBR
FB-DTBR-E
Network communication
Series
CPU
Link Module
Driver
FBs
FBs-20MAT
FBs-CBE-3
FATEK FB Ethernet(TCP)
Series
FB MA
FB MC
FB MA
FB MC
CPU
FBs-20MAT
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS232
Setting
RS485
Setting
RS232
Setting
RS485
Setting
FBS-CB25-3
FBs-20MAT
FBS-CB25-3
CPU
Link Module
COMM Type
Parameter
Cable
FBs
FBs-20MAT
FBs-CBE-3
ETH
Setting
- 87 -
Note: The detailed communication configuration must be the same as the PLCs port setting.
- 88 -
PLC Setting
1 In ether cfg software, click [scan] to search the PLC information.
- 89 -
Supported Device
Device
Bit Address
Word Address
Format
Input
X0-9999
------
DDDD
Output
Y0-9999
------
DDDD
Internal Relay
M0-9999
------
DDDD
Step Relay
S0-9999
------
DDDD
Timer Relay
T0-9999
------
DDDD
Counter Relay
C0-9999
------
DDDD
Data Register
------
R-L 0-3839
DDDD
Data Register
------
R-H 3840-9999
DDDD
Data Register
------
D0-9999
DDDD
Timer
------
T0-9999
DDDD
Counter
------
C0-199
DDD
Cable Diagram
FB RS232 communication cable
- 90 -
Notes
HMI terminal
9pin D-SUB female/male
Controller terminal
15 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
2 TXD
3 TX
8 TX
1 RXD
5 GND
5 GND
6 GND
3 RTS
4 CTS
com0/com1
2RXD
3TXD
5GND
7RTS
8CTS
2TXD
3RXD
5SG
7CTS
8RTS
Ethernet cable
Connecting PC and HMI use cross-ruling; communicating with hub or switch use cross-over cable or
cross-ruling.
Refer to 4.3 Download by Network Ethernet for method of making connection cable.
- 91 -
CPU
Link Module
Driver
SPB
NW0P20T-31
NB
NB2U24R-11
Fuji SPB
System configuration
Series
SPB
NB
CPU
Link Module
NW0P20T-31
NB2U24R-11
Ethernet Type
Parameter
RS485-4
RS485-4
Setting
Cable
Your owner cable
Communication Setting
NOTEWhen PLC is protected by password, protocol time out 2 is 65535, and the register is read only. If
you want to make the register writable, you must let the protocol time out 2 equal the PLC password.
Example: PLC password is 1234, and then you make the protocol time out 2 to be 1234.
PLC password is 0010, and then you make the protocol time out 2 to be 10.
Supported Device
SPB
Device
Bit Address
Word Address
Format
Data register
D 0~6FF.F
------
HHH.H
Special relay
M_special 0~1FF
------
HHH
Counter contact
C 0~FF
------
HH
Timer contact
T 0~1FF
------
HHH
Keep relay
L 0~FFF
------
HHH
Auxiliary relay
M 0~FFF
------
HHH
Output relay
Y 0~3FF
------
HHH
Input relay
X 0~3FF
------
HHH
- 92 -
Notes
Timer contact
------
TW 0~3FF
HHH
Counter contac
------
CW 0~FF
HH
Data register
DW 0~6FF
HHH
Special register
-----------
DW_special 0~1FF
HHH
------
W0 0~7FF
HH
------
W1 0~7FF
HHH
------
W2 0~7FF
HHH
------
W3 0~7FF
HHH
------
W4 0~7FF
HHH
------
W5 0~7FF
HHH
------
W6 0~7FF
HHH
HHH
NB
Device
Bit Address
Word Address
Format
Data register
D 0~3F.F
------
HHH.H
Special relay
M_special 0~1FF
------
HHH
Counter contact
C 0~1F
------
HH
Timer contact
T 0~1F
------
HHH
Keep relay
L 0~1FF
------
HHH
Auxiliary relay
M 0~3FF
------
HHH
Output relay
Y 0~3F
------
HHH
Input relay
X 0~3F
------
HHH
Timer contact
------
TW 0~1F
HHH
Counter contact
------
CW 0~1F
HH
Data register
------
DW 0~3F
HHH
Special register
------
DW_special 0~1FF
HHH
Cable Diagram
- 93 -
Notes
Read only
CPU
Link Module
Driver
IC693CPU311
IC693CPU313
IC693CPU321
IC693CPU323
IC693CPU331
IC693CPU340
IC693CPU341
IC693CPU350
IC693CPU351
IC693CPU352
IC693CPU360
IC693CPU363
IC693CPU364
IC693CPU374
IC693CSE311
IC693CSE313
IC693CSE323
IC693CSE331
IC693CSE340
GE Fanuc Series
SNP
IC693CPU311
IC693CPU313
IC693CPU321
IC693CPU323
IC693CPU331
IC693CPU340
IC693CPU341
IC693CPU350
IC693CPU360
IC693CPU364
GE SNP-X
IC693CPU351
IC693CPU352
IC693CPU363
IC693CMM311
IC693CPU374
VersaMax Series
CPU001/002/005
CPUE05
RS232 on port1
RS485 on port2
- 94 -
PACSystems RX3i
IC200UAL004/005/006
IC200UDD110/120/212
IC200UDR005/006/010
IC200UAA007
IC200UAR028
IC695CPE310
IC695CPE320
RS232 on port1
RS485 on port2
RS232 on port1
RS485 on port2
GE Fanuc Series
SNP
Network communication
Series
CPU
Series90-30
PACSystem RX3i
VersMax Micro&Nano
VerMax
Link Module
CPU340
CPU341
CPU350
CPU351
CPU352
CPU360
CPU363
CSE311
CSE313
CSE323
CSE331
CSE340
Driver
IC693CMM321
CPU364
CPU374
IC695CPE305
IC695CPE310
IC695CPE 315
IC695CPE 320
IC695ETM001
IC200UDD020
IC200UDD040
IC200UDD064
IC200UDD120
IC200UDD164
IC200UDD220
IC200UDD240
IC200UDR020
IC200UDR040
IC200UDR064
IC200UDR120
IC200UDR140
IC200UDR164
IC200UDR440
IC200UEM001
CPUE05
- 95 -
GE IP Ethernet
TCP Slave
Modbus TCP
CPU311
CPU313
CPU323
CPU331
CPU340
CPU341
CPU350
CPU351
CPU352
CPU360
CPU363
CSE311
CSE313
CSE323
CSE331
CSE340
IC693CMM321
CPU364
CPU374
Series 90-70
CPU731
CPU771
CPU772
CPU780
CPU781
CPU782
CPU788
CPU789
CPM790
CPM915
CPM925
CSE784
CSE924
CSE925
CPX772
CPX782
CPX928
CPX935
CGR772
CGR935
IC697CMM742 (Type2)
PACSystem RX7i
CPE010
CPE020
CRE020
Series 90-30
CPU
Link Module
- 96 -
COMM
Parameter
Cable
Type
GE
Fanuc
Series 90-30
IC693CPU374
RS485 on the
CPU unit
IC693CMM311
RS232
Setting
RS485-4
Setting
RS232
Setting
RS485-4
Setting
VersaMax
Series
CPU001/002/005
CPUE05
RS232 on port1
RS232
Setting
RS485 on port2
RS485-4
Setting
RS232 on port1
RS232
Setting
VersaMax
Micro & Nano
Series
IC200UAL004/005/006
IC200UDD110/120/212
IC200UDR005/006/010
IC200UAA007
IC200UAR028
RS485 on port2
RS485-4
Setting
IC695CPE310
IC695CPE320
RS232 on port1
RS232
Setting
RS485 on port2
RS485-4
Setting
PACSystems
RX3i
Connect Type
Parameter
Series 90-30/
Versamax/
PACSystem RX3i/
Versamax
Mico&Nano
Ethernet
(GE IP Ethernet(TCP Slave))
Setting
Series 90-30/
PACSystem RX3i/
Versamax
Mico&Nano
Ethernet
(Modbus TCP Slave)
Cable
Setting
PLC Setting
RX3i
- 99 -
PLC:
GE IP EthernetTCP SlaveProtocol:
HMI:
PLC:
- 100 -
Supported Device
Device
Bit Address
Word Address
Format
System
SC01-32
------
DD
System
SB01-32
------
DD
System
SA01-32
------
DD
System
S01-32
------
DD
Temporary
T001-256
------
DDD
Internal
M0001-4096
------
DDDD
Genius Global
G0001-1280
------
DDDD
Output
Q0001-2048
------
DDDD
Input
I001-256
------
DDD
Analog Output
------
AQ001-512
DDD
Analog Input
------
AI0001-2048
DDDD
Register
------
R0001-9999
DDDD
Cable Diagram
90-30/VersaMax/RXi RS232 communication
- 101 -
Notes
HMI terminal
9pin D-SUB female/male
com0/com1 com2
2 RX
7 RX
3 TX
8 TX
2 TX
3 RX
5 GND
5 GND
5 GND
com0/com1
1 Rx6 Rx+
5 GND
4Tx9 Tx+
9 SDA
21 SDB
7 GND
13 RDA
25 RDB
10 RTSA
11 CTSA
12 TER CTS
22 RTSB
23 CTSB
- 102 -
4.24 HAIWELL
Serial Communication
Series
CPU
Link Module
E/S
HW-S16ZA220R
Driver
RS232 on com1
Haiwell
RS485 on com2
System configuration
Series
CPU
E/S
HW-S16ZA220R
Link Module
COM Type
Parameter
Cable
RS232 on com1
RS232
Setting
RS485 on com2
RS485
Setting
Communication Setting
Haiwell RS232 communication
- 103 -
Supported Device
Device
Bit Address
Word Address
Format
SM0215
-------
DDD
Counter Relay
C0127
-------
DDD
Timer Relay
T0127
-------
DDD
Internal Relay
M02047
-------
DDDD
Switch Output
Y0127
-------
DDD
Switch Input
-------
DDD
System register
X0127
-------
SV0-139
DDD
Counter(Current Value)
-------
CCV-16 0-47&80-127
DDD
-------
CCV-32 48-79
DD
Timer(Current Value)
-------
TCV0-127
DDD
Internal Register
-------
V0-2047
DDDD
Analog Output
-------
AQ0-31
DD
- 104 -
-------
Analog Input
AI0-31
DD
Cable Diagram
Haiwell RS232 communication cable
4.25 HanG
Serial Communication
Series
CPU
Link Module
Driver
HanG
DTS3338
HanG
System configuration
Series
CPU
Link Module
COMM Type
HanG
DTS3338
RS485
Communication Setting
- 105 -
Parameter
Setting
Cable
Your owner cable
Supported Device
Device
Bit Address
Word Address
Format
Password
------
APAS 0
Meter Number
------
ANUM C032
HHHH
Init Meter
------
ASTR 0
Register value
------
AMVD 9010
HHHH
Notes
NOTEUse text part to show meter number (ANUM). AMVD data type: signed integer
Cable Diagram
CPU
Hitachi Inverter
SJ300
Link Module
Driver
Hitachi SJ300
RS485-2
System configuration
Series
Hitachi Inverter
CPU
SJ300
Link Module
RS485-2
- 106 -
Parameter
Setting
Cable
Your owner cable
Communication Setting
HMI default communication parameter: 4800, 7, none, 1; station: 1
Name
description
A001
Frequency set
00(VR)/01(Terminal)/02(operator)/03(RS485)/04(OPT 1)/05(OPT 2)
A002
Run set
C71
Baudrate
C72
Station set
1~32
C73
Data bit
C74
Parity
00(none)/01(even)/02(odd)
C75
Stop bit
1(bit)/2(bit)
Supported Device
Device
Bit Address
------
DDD
------
DDDDD
-----------
DDDD
DDD
------
DDD
------
TerminalPoint State
Surveillance Data
Format
------
FWD/REW/STOP
FREQ SET
Word Address
------
Transducer State
Notes
DD
(00)FWD/REW/STOP 0
Write only
(01)FREQ SET 0
Write only
Write only
DD
Read only
Read only
DD
Read only
Write only
Trip Record
------
Revert
------
(08)Revert 0
- 107 -
------
Store EEPROM
------
Store EEPROM 0
NOTE(02)Terminal Point State 0~7 use text part
D
D
Cable Diagram
RS485-2 communication cable
CPU
Link Module
Driver
H-20
H-28
H-40
H-64
H-200(CPU-02H)
H-250(CPU21-02H)
H-252B(CPU22-02HB)
H-252C(CPU22-02HC)
H-300(CPU-03Ha)
H-302(CPU2-03H)
H-700(CPU-07Ha)
H-702(CPU2-07H)
H-2000(CPU-20Ha)
H-2002(CPU2-20H)
H-4010(CPU3-40H)
H-1002(CPU2-10H)
port on CPU
Hitachi
H-300(CPU-03Ha)
H-302(CPU2-03H)
H-700(CPU-07Ha)
H-702(CPU2-07H)
H-2000(CPU-20Ha)
H-2002(CPU2-20H)
H-4010(CPU3-40H)
COMM-H
COMM-2H
- 108 -
Write only
EH-150
MICRO-EH
H-1002(CPU2-10H)
COMM-2H
EH-150(EH-CPU104)
EH-150(EH-CPU104A)
EH-150(EH-CPU208)
EH-150(EH-CPU208A)
EH-150(EH-CPU308)
EH-150(EH-CPU308A)
EH-150(EH-CPU316)
EH-150(EH-CPU316A)
EH-150(EH-CPU448)
EH-150(EH-CPU448A)
EH-150(EH-CPU516)
EH-150(EH-CPU548)
EH-150(EH-CPU516)
EH-150(EH-CPU548)
Port 1 on EH-SIO
Port 2 on EH-SIO
MICRO-EH(EH-D10)
MICRO-EH(EH-A14)
MICRO-EH(EH-D14)
MICRO-EH(EH-A23)
MICRO-EH(EH-D23)
MICRO-EH(EH-A28)
MICRO-EH(EH-D28)
Port 1 on CPU
MICRO-EH(EH-A23)
MICRO-EH(EH-D23)
MICRO-EH(EH-A28)
MICRO-EH(EH-D28)
Port 2 on CPU
MICRO-EH(EH-A64)
MICRO-EH(EH-D64)
MICRO-EH(EH-A40)
MICRO-EH(EH-D40)
MICRO-EH(EH-A20)
MICRO-EH(EH-D20)
Port on CPU
EH-OB232
EH-OB485
Ethernet Communication
Series
CPU
Link Module
Driver
S10V
LQP510-Z
LQP520-Z
EHV
EHV-CPU32
CPU
Link Module
COMM Type
Parameter
Cable
H-20
RS232
Setting
EH-150
EH-150(EHCPU104)
MICRO-EH
EH-A23DR
Port 1 on CPU
RS232
Setting
Port 2 on CPU
RS485
Setting
CPU
S10V
LQP510-Z
EHV
EHV-CPU32
Link Module
Connect Type
Parameter
LQP520-Z
Ethernet
Setting
Ethernet
Setting
RS422 communication
- 110 -
Cable
Your owner cable
Supported Device
Hitachi EH-A23DR
Device
Bit Address
Word Address
Format
Notes
External Input
X 00.000-5A.095
------
HHH.DDD
Read Only
External Output
Y 00.000-5A.095
------
HHH.DDD
X 100.000-9FF.095
------
HHH.DDD
Y 100.000-9FF.095
------
HHH.DDD
Remote Input
Remote Output
- 111 -
Read Only
Internal Output
R 0000-FFFF
------
HHHH
Data Area
M 0000-FFFF
------
HHHH
L 00000-03FFF
------
HHHHH
L 10000-FFFFF
------
HHHHH
On Delay Timer
TD 00000-65535
------
------
DDDDD
WX 000.00-05A.09
HHH.DD
External Output
------
WY 000.00-05A.09
HHH.DD
Remote Input
------
WX 100.00-9FF.09
HHH.DD
Remote Output
------
WY 100.00-9FF.09
HHH.DD
------
WR 0000-C3FF
HHHH
------
WRF 000-FFFF
HHHH
Data Area
------
WM 0000- FFFF
HHHH
------
WL 0000-03FF
HHHH
------
WL 1000-FFFF
HHHH
External Input
Read Only
Read Only
TC 00000-65535
DDDDD
Timer Counter
-----NoteX0.015 in the HMI match x15 in the PLC,Y1.000 in the HMI match Y100,WX0.09 in the HMI
match WX9 in the Plicate effective address is deleted radix point and the first zero behind radix point.
The list of address correspondence
Bit Address
Word Address
PLC address
X 00.000-00.047
------
X 0000-0047
Y 01.000-01.031
------
Y 0100-0131
------
WX 000.00-000.03
WX 0000-0003
------
WY 001.00-Y001.01
WY 0010-0011
Notes
Note: The range of X, Y, WX, WY is according to the I/O assign. Make sure the I/O address before using
the register.
Note:
1. Communication setting
EH series, only port1 supports procedure 2.Switch DIP and change special Internal Input (WR) value to
select procedure.
EH150 seriesonly EHCPU***A/448/516/548 support procedure 2.
EH PLC connect with PC only by procedure 1.
2. CPU related actions
EH150
DIP 5 must be set on.
If DIP 5 is on, which procedure (1 or2) to use by judging the value of the WR F037.The highest bit of
WR F037 must be on, so that the other bits can be written in. The data keep on, when turn on the power
again.
o By entering 0x8000, turn on the power again and value of the address is 0x0000.After settings,
communication with procedure 1.
o By entering 0xC000, turn on the power again and value of the address is 0x4000.After settings,
- 112 -
Bit Address
Word Address
Format
S 0-BFF
------
HHH
Z 0-3FF
------
HHH
E 0-FFF
------
HHH
V 0-FFF
------
HHH
P 0-7F
------
HH
N 0-FF
------
HH
CCC
CCC 0-FF
------
HH
CR
CR 0-FF
------
HH
CD
CD 0-FF
------
HH
CU
CU 0-FF
------
HH
UUU
UUU 0-FF
------
HH
UU
UU 0-FF
------
HH
TTT
TTT 0-1FF
------
HHH
TT
TT 0-1FF
------
HHH
K 0-FFF
------
HHH
M 0-FFF
------
HHH
R 0-FFF
------
HHH
G 0-FFF
------
HHH
Q 0-FFF
------
HHH
Y 0-FFF
------
HHH
J 0-FFF
------
HHH
X 0-FFF
------
HHH
OW
------
OW 0-FFF
HHH
IW
------
IW 0-FFF
HHH
- 113 -
Notes
DW
------
DW 0-FFF
HHH
FW
------
FW 0-BFF
HHH
SW
------
SW 0-BF
HH
ZW
------
ZW 0-3F
HH
EW
------
EW 0-FF
HH
VW
------
VW 0-FF
HH
PW
------
PW 0-8
NW
------
NW 0-F
CW
------
CW 0-F
UW
------
UW 0-F
TW
------
TW 0-1F
HH
KW
------
KW 0-FF
HH
MW
------
MW 0-FF
HH
RW
------
RW 0-FF
HH
GW
------
GW 0-FF
HH
QW
------
QW 0-FF
HH
YW
------
YW 0-FF
HH
JW
------
JW 0-FF
HH
XW
------
XW 0-FF
HH
CC
------
CC 0-FF
HH
CS
------
CS 0-FF
HH
UC
------
UC 0-FF
HH
US
------
US 0-FF
HH
TC
------
TC 1FF
HHH
TS
------
TS 0-1FF
HHH
Bit Address
Word Address
Format
Timer
T 0-65535
------
DDDDD
M 0-FFFFF
------
HHHHH
L 0-73FFF
------
HHHHH
Internal output
R 0-FFFF
------
HHHH
External output
Y 0-65535
------
DDDDD
External input
X 0-65535
------
DDDDD
------
TC 0-65535
DDDDD
Internal output
------
WM 0-FFFF
HHHH
------
WL 0-FFFF
HHHH
Internal output
------
WR 0-FFFF
HHHH
External output
------
WY 0-65535
DDDDD
External input
------
WX 0-65535
DDDDD
Cable Diagram
- 114 -
Notes
Ethernet Cable
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to 4.3 Download by Network Ethernet for method of making connection cable.
CPU
Link Module
LM3109
LM3107
RS232 on CPU
Hollysys LK
Driver
RS232 on CPU
Hollysys
RTU
LM
Modbus
Ethernet Communication
Series
CPU
Link Module
Driver
Hollysys LK
LK210
Series
Hollysys LM
CPU
LM3109
LM3107
Hollysys LK
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485
Setting
RS232
Setting
RS232
Setting
CPU
Link Module
COMM Type
Parameter
Cable
Hollysys LK
LK210
ETH
Setting
RS485-2
HMI Setting
NoteIn the dual redundancy system, just set one of IP addresses in Network Device Setting
PLC Setting
Must set the PLC station in PLC program software.
Supported Device
LM
Device
Bit Address
Word Address
Format
I0.0-2.7
------
D.O
Q0.0-1.7
------
D.O
M100.0-7816.7
------
DDDD.O
Analog inputs
------
IW0
Analog outputs
------
QW0
Internal register
------
MW0-8190
DDDD
------
MD0-8188
DDDD
Notes
Bit Address
Word Address
Format
Outputs Relay
0X 1-65535
------
DDDDD
Inputs Relay
1X 1-65535
------
DDDDD
Analog inputs
------
3X 1-65535
DDDDD
Data Register
------
4X 1-65335
DDDDD
Data Register(DWord)
------
5X 1-65535
DDDDD
- 117 -
Notes
Cable Diagram
Hollysys LM RS232 communication cable
Ethernet Cable
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to 4.3 Download by Network Ethernet for method of making connection cable.
CPU
HD
HD-JZ06
Link Module
Driver
System configuration
Series
CPU
HD
HD-JZ06
Link Module
COMM Type
RS232
Setting
RS485
Setting
Communication Setting
RS232 communication
- 118 -
Parameter
Cable
RS485 communication
Supported Device
Device
Bit Address
Word Address
Format
------
DDDD
MCU Register
LB 0-4095
VB 0-4095
------
DDDD
------
LW 0-4094
DDDD
MCU Register
------
VW 0-4094
DDDD
Cable Diagram
RS232 Port
- 119 -
Notes
RS485 Port
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1
1 RX-
7 B-
6 RX+
6 A+
5 GND
5 GND
CPU
Link Module
Driver
IDEC MicroSmart
MICRO SMART
FC4A-C10R2
FC5A-C24R2
FT1A-H48SA
System configuration
Series
CPU
Link Module
COMM Type
MICRO
SMART
FC4A-C10R2
FC5A-C24R2
FT1A-H48SA
RS232
Setting
RS485
Setting
Communication Setting
- 120 -
Parameter
Cable
Supported Device
Device
Bit Address
Word Address
Format
Internal Relay
M0.0-127.7
------
DDD.O
Output
Q0.0-30.7
------
DD.O
Input
I0.0-30.7
------
DD.O
Data Register
------
D0-8199
DDDD
Counter(Current Value)
------
C_CV0-99
DD
Counter(Preset Value)
------
C_SV0-99
DD
Timer(Current Value)
------
T_CV0-99
DD
DD
Cable Diagram
Idec RS232 communication cable
FC4A
HMI terminal
9pin D-SUB female/male
com0/com1
1 RX6 RX+
8
3 TXD
2 RXD
4 TX5 GND
Controller terminal
8 pin Mini Din (male)
2
1
4 RXD
3 TXD
5
6 GND
7
FC5A
- 121 -
Notes
RS485
CPU
Link Module
Driver
H2U
H2U-3624MR
CPU direct
COM1
CPU direct
Modbus RTU*1
COM1
System configuration
Series
CPU
Driver
Link Module
COMM Type
Parameter
Cable
H2U
3624M
R
Inovance
H2u
RS232
Setting
RS485-4
Setting
RS485-2
Setting
RS485-2
Setting
RS485-2
Setting
RS485-2
Setting
Modbus
RTU
Communication Setting
Inovance H2u protocol
HMI Setting
HMI monitor protocol communication: 9600, 7, even, 1; station: 0
RS232
- 122 -
RS422
RS485
PLC Setting
- 123 -
PLC setting
COM0 setting: D8116=02h, modbus-RTU slave protocol; D8111=1, station: 1; D8110=81h,
communication parameter: 9600, 8, none, 1.
COM1 setting: D8126=02h, modbus-RTU slave protocol; D8121=1, station: 1; D8120=81h,
communication parameter: 9600, 8, none, 1.
Supported Device
- 124 -
Device
Bit Address
Word Address
Format
Input Relay
X 000-177
------
OOO
Output Relay
Y 000-177
------
OOO
Auxiliary Relay
M 0000-1535
------
DDDD
Timer Relay
T_bit 000-255
------
DDD
Counter Relay
C_bit 000-255
------
DDD
SM 8000-8255
------
DDDD
S 000-999
------
DDD
Status Relay
Timer
------
T 000-255
DDD
Counter
------
C 000-199
DDD
Data register
------
D 0000-7999
DDDD
------
SD 8000-8255
DDDD
Counter MemoryDWord
------
C_dword 200-255
Notes
DDD
Cable Diagram
COM0 port communication cable
RS232
Please uses the programming cable: SC-09
RS422
HMI terminal
9pin D-SUB female/male
com0/com1
1 RX-
4Tx-
6 RX+
7Tx+
5 GND
3GND
4 TX-
1Rx-
9 TX+
2Rx+
RS485
- 125 -
4.32 Invt
Serial Communication
Series
CPU
Link Module
Driver
INVT
IVC1
Invt IVC1
System configuration
Series
INVT
CPU
Link Module
IVC1
COM Type
Parameter
Cable
RS232
Setting
RS485
Setting
Communication Setting
HMI Setting
RS232 default communication: 9600, 8, none, 1; station number: 1
- 126 -
PLC Setting
1. The PLC has two ports: port0 and port1, port1 support RS232 and RS485
2. Port0 configuration as follow:
- 127 -
Supported Device
Device
Bit Address
Word Address
Format
C_bit
C_bit 0-255
------
DDD
T_bit
T_bit 0- 255
------
DDD
S 0-1023
------
DDDD
SM
SM 0-255
------
DDD
M 0-2047
------
DDDD
Y 0-177
------
OOO
X 0-177
------
OOO
SD_double
------
SD_double 0-127
DDD
D_double
------
D_double 0-7999
DDD
C_double
------
C_double 200-255
DDD
C_word
------
C_word 0-199
DDD
T_word
------
T_word 0-255
DDD
------
Z 0-15
DD
SD
------
SD 0-255
DDD
------
D 0-7999
DDDD
Cable Diagram
- 128 -
Notes
Controller port0
8 pin Mini Din (male)
com0/com1 com2
2 RX
7 RX
5 TXD
3 TX
8 TX
4 RXD
5 GND
5 GND
3 GND
HMI terminal
9pin D-SUB female/male
Controller port1
com0/com1 com2
2 RX
7 RX
3 TX
8 TX
5 GND
5 GND
TXD
RXD
GND
CPU
Link Module
Driver
KDN-K3
KDN-K304-14AR
KDN-K3
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
KDN-K3
K304-14AR
RS232
Setting
Supported Device
KDN-K3
Device
Bit Address
Word Address
Format
I0.0-7.7
------
D.O
Q0.0-7.7
------
D.O
M0.0-31.7
------
DD.O
- 129 -
Notes
Analog inputs
------
AIW0-30
DD
Analog outputs
------
AQW0-30
DD
Internal register
------
VW0-4094
DDDD
------
VD0-4092
DDDD
NOTE:
1 AIW, AQW, VW, VD address must be an even number.
2 AIW and I device read only.
3 The single floating VR of PLC corresponds with the VD of the Ev5000 (choose single floating).
Communication Setting
KDN-K3 RS232 communication
Cable Diagram
RS232 communication cable
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
- 130 -
CPU
Kinco
K304-14AT
K304-14AR
K304-14AX
K304EX-14AR
K306-24DT
K306-24DR
K306-24AT
K306-24AR
K306EX-24AT
K306EX-24AR
K308-40AR
K308-40AT
K308-40AX
Link Module
Driver
K504-14AT
K504-14AR
K504EX-14AT
K504EX-14AR
K506-24AT
K506-24AR
K506-24DT
K506-24DR
K506EA-30AT
K508-40AT
K508-40AX
K508-40AR
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
Kinco
K304-14AT
K304-14AR
K304-14AX
K304EX-14AR
RS232
Setting
- 131 -
K306-24DT
K306-24DR
K306-24AT
K306-24AR
K306EX-24AT
K306EX-24AR
K308-40AR
K308-40AT
K308-40AX
RS485
Setting
K504-14AT
K504-14AR
K504EX-14AT
K504EX-14AR
K506-24AT
K506-24AR
K506-24DT
K506-24DR
K506EA-30AT
K508-40AT
K508-40AX
K508-40AR
RS232
Setting
RS485
Setting
Communication Setting
RS232 communication
RS485 communication
- 132 -
Supported Device
Device
Bit Address
Word Address
Format
I0.0-31.7
------
D.O
Q0.0-31.7
------
D.O
M0.0-31.7
------
DD.O
Analog inputs
------
AIW0-62
DD
Analog outputs
------
AQW0-62
DD
Internal register
------
VW0-4094
DDDD
------
VD0-4092
DDDD
Notes
ERR 0~127*1
ERR
--------
ERR 128~255*2
ERR 256~383*3
DDDDD
ERR 384~511*4
NOTE:
1) AIW, AQW, VW, VD address must be an even number.
2) AIW and I device read only.
3) The single floating VR of PLC corresponds with the VD of the Ev5000 (choose single floating).
*1 ERR0~127 indicate the recent 128 common errors. ERR0 is the latest error, ERR1 is the later
error, and so on.
*2 ERR128~255 indicate the recent 128 serious errors. ERR128 is the latest error, ERR129 is the
later error, and so on.
*3 ERR256~383 indicate the last 128 common errors the last time PLC is powered on. ERR256 is
the last error, ERR257 is the previous error, and so on.
*4 ERR384~511 indicate the last 128 serious errors the last time PLC is powered on. ERR 384 is the
last error, ERR385 is the previous error, and so on.
Cable Diagram
RS232 communication cable
- 133 -
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
CPU304/CPU304EX/CPU306
RS485 communication cable
CPU306EX /308/504
RS485 communication cable
CPU506EA
RS485 communication cable
CPU
Link Module
Driver
FieldBus Bridge
EB-MOD2P-01
Kinco EB-MOD2P-01
Modbus RTU
System configuration
Series
FieldBus
Bridge
CPU
EB-MOD2P-01
Link Module
COMM Type
Parameter
RS232
Setting
RS422
Setting
RS485
Setting
Communication Setting
EB-MOD2P-01 RS232 communication
- 135 -
Cable
Supported Device
EB-MOD2P-01
Device
Bit Address
Word Address
Format
0X1-60
------
DDDDD
1X1-60
------
DDDDD
3X_bit1-60
------
DDDDD
4X_bit1-60
------
DDDDD
------
3X1-60
DDDDD
Data Register
------
4X1-60
DDDDD
Data Register
------
5X1-60
DDDDD
Data Register
------
6X1-60
DDDDD
Data Register
------
3X-DINV 1-60
DDDDD
Data Register
------
4X-DINV 1-60
DDDDD
Notes
NOTEThe correspondence between the device of EV5000 and the s7-300 software, as follows:
4X-DINV------------PID
e.g.4X-DINV1------------PID256
4X-DINV3------------PID260
3X-DINV------------PQD
e.g.3X-DINV1------------PQD256
3X-DINV3------------PQD260
4X -------------------PIW
e.g.4X1 --------------------PIW256
4X2--------------------PIW258
3X--------------------PQW
e.g.3X1---------------------PQW256 3X2---------------------PQW258
0X--------------------I
e.g.0X1--------------------I0.0
0X9--------------------I1.0
1X--------------------Q
e.g.1X1--------------------Q0.0
1X9--------------------Q1.0
4X_BIT -------------------PIWbinary
e.g.4X_BIT1.0~~1.15-------------------PIW256binary
3X_BIT--------------------PQWbinary
- 136 -
e.g. 3X_BIT1.0~~1.15--------------------PQW256binary
Project configuration
1Use the guide to set up projects in the s7-300 software.
2Double click DP of "HW Config"->attribute->new
- 137 -
NOTE: the address of DP cant be the same as MPIs. Double click the address number to change.
4Double click GATEWAY"->"eview"->"B_MO1"to extend device.
NOTE: for project configuration of BRIDGE, you must configure DI/D0 resource of 12 bytes firstly.
AI/AO is optional.
5Must Use OB82,OB86,OB100,OB121,OB122 in the ladder program of the external device, otherwise
you need to manually operate the RUN switch of the external device as RUN,STOP,RUN in this order
upon restart the display or PLC. When you use those special OB block, the communication will be
automatically recovered even if you restart the display or PLC.
6Save and compile, and download to module, then the light of profibus is on.
7After configuration, and then you can program.
Bus Bridge setting:
- 138 -
1 Setting ID of Profibus by switching 8-bit Dip(DIP1 is lowest bit, DIP8 is highest bit),range is from 3
to 125;
ID must be the same as its configuration in Siemens software. As above picture for example, setting is 3,
that the switch DIP1 and DIP2 on the panel of profibus are set ON, others are OFF.
2Profibus support baudrate as follows: 9.6Kbit/s, 19.2Kbit/s, 45.45Kbit/s, 93.75Kbit/s, 187.5Kbit/s,
0.5Mbit/s, 1.5Mbit/s, 3Mbit/s, 6Mbit/, 12Mbit/sand interface is automatically adaptive.
3A cable (purple),connect DP interface of s7-300 and bus bridge of profibus. Two sides have active
terminal resistors; Switch on the s7-300 PLC is off, on the busbridge is on.
4 Setting baudrate of modbus by switching DIP1-3 of modbus ID port, support 8 kinds of
baudrate .Setting as follows:
1
Baud
OFF
OFF
OFF
1200
ON
OFF
OFF
2400
OFF
ON
OFF
4800
ON
ON
OFF
9600
OFF
OFF
ON
19200
ON
OFF
ON
38400
OFF
ON
ON
57600
ON
ON
ON
115200
5Setting station number of modbus by switching DIP4-8 of modbus ID port ,support 1 to 30 kinds of
station number(DIP4 is lowest bit,DIP8 is highest bit, if DIP4 is on and DIP5~8 is off, it means station
number is 00001,that is No. 1 station).
Cable Diagram
RS232 communication cable
- 139 -
CPU
ED
ED100
ED430
ED620
ED630
CD
CD420
CD430
CD620
Link Module
Driver
System configuration
Series
CPU
ED
ED100
ED430
ED620
ED630
CD
CD420
CD430
CD620
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485 on port
RS485-2
Setting
RS232
Setting
Communication Setting
Default communication: 9600, 8, none, 1; staion: 1
RS232 communication
- 140 -
NOTE: If the servo controller to modify the station number, the servo power needed to restart, the station
number to take effect, otherwise the communication is incorrect.
RS485 communication
Supported Device
Device
Bit Address
Word Address
Range
word
20
word
10
word
Notes
NOTE: Use the touch screen, pay attention to the rules addressing. The specific reference to the following
description.
Touch-screen type of address: according to the number of bits to the servo. Can only be 20, 10, 8.
Address of the touch screen: master address, and sub address
For example, kinco servo drive manual on page 117, the address 2509, sub-address 06, median 20,
addressing the touch screen as shown:
- 141 -
Cable Diagram
ED Series
RS232 communication cable
Controller terminal
9 pin D-SUB (male)
com0/com1
1 RX-
7Rx8Tx5 GND
2Rx+
3Tx+
5 GND
6 RX+
CD Series
RS232 communication cable
- 142 -
CPU
Link Module
Driver
Kinco Master
Kinco Master
Kinco Slave
Kinco Slave
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
Kinco Master
Setting
Kinco Slave
Setting
Supported Device
Device
Bit Address
Word Address
Format
B0 - 8999
------
DDDD
------
W0 - 8999
DDDD
Communication Setting
Kinco Master
Kinco Slave
- 143 -
Notes
Cable Diagram
HMI terminal
9pin D-SUB female/male
Controller terminal
9pin D-SUB female
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
CPU
Link Module
Driver
KV-16DT
KV-16DT
CPU Direct
KV-1000
KV-1000
CPU Direct
KV-3000
KV-3000
CPU Direct
Keyence KV-16DT
Keyence KV-1000
Keyence KV-3000
KV-Nano Series
KV-N60AT
CPU Direct
Keyence KV-N60AT
Network communication
Series
KV-5000
CPU
KV-5000
Link Module
Driver
CPU Direct
CPU
Link Module
COMM Type
Parameter
Cable
KV-16DT
KV-16DT
CPU Direct
RS232
Setting
KV-1000
KV-1000
CPU Direct
RS232
Setting
KV-3000
KV-3000
CPU Direct
RS232
Setting
KV-Nano Series
KV-N60AT
CPU Direct
RS232
Setting
- 144 -
CPU
KV-5000
KV-5000
Link Module
CPU Direct
Connect Type
Ethernet
Parameter
Setting
Cable
Your owner cable
- 145 -
RS232
PLC setting
1. In the [Confirm unit setting information] dialog box click [Yes], and the [Unit
Editor] window will display. On the [Select unit] tab, from the displayed list of
units select KV-N60, then drag &drop to the unit placement area. Configure
the setup items as follows.
Operation Mode: KV STUDIO mode; Baud Rate: 9600 bps.
Note: 1. Timer and counter register must be programmed in the KV STUDIO software before it be used in
the HMI.
2. If the communication is slower, you can change the baud rate and the Protocol time out 1(ms)
PLC configuration
1. "Editor" window, click [Configure unit] in the "[0] KV-5000 R30000" to modify the IP address of
the PLC, PLC and PC in the same segment, modify the IP address of the test shown, click [confirm] to save
the modifications
2. Switch to the "Monitor" window to see the changes of the figure will pop up window, Click [PLC
transfer -> Monitor mode (T)], pop-up "transmission program [communication goals: KV-5000 path:
USB]", Click [implementation], content writing, once again view the "[0] KV-5000 R30000" in the PLC's
IP address in the "Monitor" window [unit configuration], This indicates that the address has been modified
over.
Supported Device
KV-16DT
Device
Bit Address
Word Address
Format
Counter_contact0- 59915
------
DDDDD
Timer_contact0- 65535
------
DDDDD
CTH_contact0- 511
------
DDD
CTC_contact0- 511
------
DDD
------
DDDDD
Counter current
Relay0- 32766
------
Counter_current0- 3915
DDDD
Counter preset
------
Counter_preset0- 65535
DDDDD
Timer current
------
Timer_current0- 65534
DDDDD
Timer preset
------
Timer_preset0- 11998
DDDDD
Counter Relay
Timer Relay
Relay
- 147 -
------
CTH_current0- 65534
DDDDD
------
CTH_preset0- 32766
DDDDD
------
CTC_current0-65534
DDDDD
------
CTC_preset0- 32766
DDDDD
Data memory
------
DM0- 32766
DDDDD
TM0- 32766
DDDDD
KV-1000
Device
Bit Address
Word Address
Format
Relay
R0-59915
------
DDDDD
Control Relay
CR0-3915
------
DDDD
MR0-65535
------
DDDDD
Latch Relay
LR0-65535
------
------
DDDDD
DM0-65534
DDDDD
Control Memory
------
CM0-11998
DDDDD
------
TM0-511
DDD
------
EM0-65534
DDDDD
------
FM0-32766
DDDDD
Data Memory
Notes
KV-3000
Device
Bit Address
Word Address
Format
Relay
R0-999.15
------
DDD.DD
Control Relay
CR0-39.15
------
DD.DD
MR0-999.15
------
DDD.DD
Latch Relay
LR0-999.15
------
DDD.DD
Data Memory
------
DM0-65534
DDDDD
Control Memory
------
CM0-5999
DDDD
------
TM0-511
DDD
------
EM0-65534
DDDDD
Notes
-----FM0-32767
DDDDD
Extended Data memory
Note: PLC bit address without a decimal point in the distinction, in fact, the last two addresses
corresponding to the fractional part, makes a distinction between the touch screen.
- 148 -
Example, PLC which corresponds to R009, the touch screen address is R0.09; PLC which corresponds to
R015, the touch screen address is R0.15.
KV-5000
Device
Bit Address
Word Address
Format
Relay
R0-3744.11
------
DDDD.DD
Control Relay
CR0-244.11
------
DDD.DD
MR0-4095.15
------
DDDD.DD
Latch Relay
LR0-4095.15
------
DDDD.DD
Data Memory
------
DM0-65534
DDDDD
Control Memory
------
CM0-11998
DDDDD
------
TM0-511
DDD
------
EM0-65534
DDDDD
Notes
-----FM0-32767
DDDDD
Extended Data memory
Note: PLC bit address without a decimal point in the distinction, in fact, the last two addresses
corresponding to the fractional part, makes a distinction between the touch screen.
KV-N60AT
Device
Bit Address
Word Address
Format
Relay
R0-599.15
------
DDD.DD
Control Relay
CR0-89.15
------
DD.DD
- 149 -
Notes
MR0-599.15
------
DDD.DD
Latch Relay
LR0-199.15
------
DDD.DD
Link Relay
B0-1FFF
------
HHHH
Work Relay
VB0-1FFF
-------
HHHH
Counter
------
C0-255
DDD
Timer
------
T0-511
DDD
Data Memory
------
DM0-32767
DDDDD
Control Memory
------
CM0-8999
DDDD
------
TM0-511
DDD
Link register
------
W0-3FFF
HHHH
Working memory
------
VW0-9999
DDDDD
Cable Diagram
KV Series RS232 communication cable
KOYO
DIRECT
CPU
Link Module
SM24-T
DL06
DL105
DL230
DL240
DL250
DL350
DL450
Driver
Koyo Direct
RS232\RS422 on the port2
System configuration
- 150 -
Series
KOYO
DIRECT
CPU
Link Module
SM24-T
DL05
DL06
DL105
DL230
DL240
DL250
DL350
DL450
COMM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
RS232
Setting
RS232
Setting
RS485-4
Setting
Supported Device
Device
Bit Address
Word Address
Format
Input
I(X)0-477
------
OOO
Output
Q(Y)0-477
------
OOO
variable
M(C)0-377
------
OOO
Timer Status
T(T)0-177
------
OOO
Counter Status
C(CT)0-177
------
OOO
Data Register
------
R(V)0-7777
OOOO
Communication Setting
KOYO series RS232 communication setting
Notes
Cable Diagram
KOYO SM24-T series RS232 communication cable
- 152 -
HMI terminal
9pin D-SUB female/male
Controller PORT2
15 pin SVGA terminal
(male)
com0/com1 com2
8 TX
3 TX
2 RX
7 RX
5 GND
5 GND
3 RX
2 TX
7 GND
4 RTS
5 CTS
- 153 -
CPU
SRD
SRD2211
COM
Link Module
Driver
KTC SRDLINK
COM2023
System configuration
Series
CPU
SRD
SRD2211
COM
COM2023
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
RS232
Setting
RS485-2
Setting
Communication Setting
KTC RS232 communication
- 154 -
Supported Device
Please refer to the PLC manual for details.
Cable Diagram
KTC RS232 communication cable
Direct connect (cable by KTC Corporation)
- 155 -
CPU
Link Module
Driver
KYL Slave
KYL
KYL Slave
System configuration
Series
CPU
Link Module
COM Type
Parameter
Cable
KYL Slave
KYL
RS232
Setting
Communication Setting
RS232
Supported Device
Device
Bit Address
Word Address
Format
LB0
------
DD
LB1
------
DD
LB2
------
DD
LB3
------
DD
LB4
------
DD
LB8
------
DD
LB9
------
DD
LB10
------
DD
LB11
------
DD
LB12
------
DD
LB13
------
DD
LB14
------
DD
- 156 -
Notes
Station:1; LB
address
LB15
------
DD
LB17
------
DD
LB18
------
DD
LB19
------
DD
LB20
------
DD
LB24
------
DD
LB25
------
DD
LB26
------
DD
LB27
------
DD
LB28
------
DD
LB29
------
DD
LB30
------
DD
LB31
------
DD
Staion:2, LB
address(LB is on
the base of
1station+16)
Cable Diagram
RS232
CPU
Link Module
Driver
EVF9323-EV
Lenze Lecom_AB
System configuration
Series
Lenze
Lecom A/B
CPU
EVF9323-EV
Link Module
COM Type
Parameter
Cable
RS232
Setting
RS485
Setting
Communication Setting
Lecom AB RS232 communication
- 157 -
Supported Device
Refer to the PLC software for detailsGlobal drive control
Notecode_H: Data type is HEX
code_F: Data type is Floating
code_D: Data type is Decimal
Cable Diagram
Lecom AB RS232 communication cable
- 158 -
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
Master-K
XGT
Type
CPU
Link Module
Driver
K120S
K7M-DR10UE
K7M-DR20U
K7M-DT30U
K7M-DT40U
K7M-DT60U
K200S
K3P-07AS
XGB
XBC-DN64H
XBC-DR32H
Built-in RS-232C/RS-485
XEC-DN20SU
G6L-CUEB
G6L-CUEC
GM
LS GLOFA Cnet
G7L-CUEB
G7L-CUEC
Inverter
iG5A
SV008iG5A-2
LS iG5A
The difference of LS Master-K CPU DirectLS Master-K CnetLS Master-K Modbus RTU
Protocol
LS
Master-K
PLC Setting
Communication Mode
Multi-station
Baud(bps)
RS232/RS485
support
9600/19200
- 159 -
Cnet
/38400
LS Master-K
MODBUS RTU
RS232/RS485
support
9600/19200
/38400
LS
Master-K
CPU Direct
RS232
non-support
38400
Ethernet communication
Series
CPU
Link Module
Driver
GLOFA
GM6-CPUA
G6L-EUTP
LS GLOFA FEnet
XGT
XGK-CPUE
XGL-EFMT
LS XGT Ethernet
CPU
K7M-DR10UE
K120S
K7M-DR20U
K200S
K3P-07AS
XGB
XBC-DN64H
XBC-DR32H
XEC-DN20SU
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
RS232
Setting
RS485-2
Setting
RS232
Setting
RS232
Setting
Built-in RS-232C
RS232
Setting
Built-in RS-485
RS485-2
Setting
RS232
Setting
RS232
Setting
RS422/RS485
Setting
RS232
Setting
G7L-CUEC
RS422/RS485
Setting
RS485-2
Setting
G6L-CUEB
G6L-CUEC
GLOFA
GM7
iG5A
SV008iG5A-2
CPU
Link Module
COMM Type
Parameter
GLOFA
GM6-CPUA
ETH
Setting
XGK-CPUE
XGL-EFMT
ETH
Setting
XGT
- 160 -
Cable
Your owner cable
RS485 communication
PLC setting
If click Connect+Write+Run+Monitor Start, it will give a Cannot Change PLC Mode. Need to let the
run light go out by manual control, and then download. After download, let the run light keep on.
- 161 -
PLC Setting
- 162 -
If click Connect+Write+Run+Monitor Start, it will give a Cannot Change PLC Mode. Need to let the
run light go out by manual control, and then download. After download, let the run light keep on.
NOTE: Only support 115200 baud rate for the protocol; station number disable.
LS XGT Cnet protocol
Default communication: 9600, 8, none, 1; station: 0
HMI Setting
RS232 communication
- 163 -
RS485-2 communication
PLC Setting
1. Tools---Network Manager set communication
- 164 -
NOTE:Only support 115200 baud rate for the protocol; station number disable.
- 165 -
RS485-4 communication
PLC Setting
1. Set the parameters of CPU module
Open GMWIN, ParametersBasic Parameters set Communication:
- 166 -
As G6L-CUEC is RS422/485 module, the channel should be selected RS422 side. After set the
parameters, click OnlineConnect, and then click OnlineWrite after the communication is built,
pay attention to choose the correct Slot No..
- 167 -
The Slot No. is the I/O slot position where the communication module is. For example, G6L-CUEC is
plugged in the I/O 1, the Slot No. should be selected SLOT 1.
NOTE: Be sure to put the switch of the module to 9 (ON-LINE) position when communicating.
LS ig5A Protocol
HMI Setting
Default communication: 9600bps,8,none,1;PLC station:1
PLC Setting
Settings
paneldisplay
I59
Parameter
Addr
A43B
directions
Protocol
Modbus RTU
LS BUS
I60
A43C
Station
1-250
I61
A43D
BaudRate
1200[bps]
2400[bps]
4800[bps]
9600[bps]
19200[bps]
nonestop bit:1
nonestop bit:2
evenstop bit:1
oddstop bit:1
I65
A441
ParityCheck
The controller also supports the standard Modbus RTU protocol , set the agreement with
LS ig5A.
HMI Setting
PLC Setting
1. Modify the parameters of PLC: ToolsEnet Frame Editor, set the type as FENET:
NOTE: Modify the IP address only via serial communication, and in the offline.
2. On the Enet Editor and select Edit, set the PLC series and IP address
3. On the Option and select COM Port, set the serial port of PC
- 169 -
4. Download: OnlineConnectWrite
XGK-CPUE Setting
HMI setting
PLC setting
1. PLC parameter settings: [Tools] - [ network management ] , in the pop-up window XG-PD ,
create a new file , select the correct CPU kind .
- 170 -
2. Double click the [ base 00 ], in the pop-up window [communication module Settings], select
the category FEnet .
3. Double click the FEnet, in the pop-up window [ Standard Settings] to set the IP address and
drive .
- 171 -
Supported Device
LS Master-K CPU Direct
Device
Bit Address
Word Address
Format
I/O Relay
P 0.0-255.F
------
DDD.H
Auxiliary Relay
M 0.0-255.F
------
DDD.H
Link Relay
L 0.0-255.F
------
DDD.H
Keep Relay
K 0.0-255.F
------
DDD.H
Special Relay
F 0.0-255.F
------
DDD.H
Counter
C 0-255
------
DDD
Timer
T 0-255
------
DDD
I/O Relay
------
P 0-255
DDD
Auxiliary Relay
------
M 0-255
Link Relay
------
L 0-255
Keep Relay
------
K 0-255
Special Relay
------
F 0-255
------
S 0-255
Timer
------
T 0-255
DDDD
Counter
------
C 0-256
DDDD
Data Register
------
D 0-9999
DDDD
Notes
LS Master K-cnet
Device
Bit Address
Word Address
Format
I/O Relay
P 0.0-255.F
------
DDD.H
Auxiliary Relay
M 0.0-255.F
------
DDD.H
Link Relay
L 0.0-255.F
------
DDD.H
Keep Relay
K 0.0-255.F
------
DDD.H
Special Relay
F 0.0-255.F
------
DDD.H
Counter
C 0-255
------
DDD
Timer
T 0-255
------
DDD
I/O Relay
------
P 0-255
DDD
Auxiliary Relay
------
M 0-255
DDD
Link Relay
------
L 0-255
DDD
Keep Relay
------
K 0-255
DDD
Special Relay
------
F 0-255
DDD
------
S 0-255
DDD
Timer
------
T 0-255
DDDD
Counter
------
C 0-256
DDDD
Data Register
------
D 0-9999
DDDD
Device
Bit Address
Word Address
Format
I/O Relay
P 0.0-1023.F
------
DDD.H
Auxiliary Relay
M 0.0-1023.F
------
DDD.H
Link Relay
L 0.0-2047.F
------
DDD.H
Keep Relay
K 0.0-4095.F
------
DDD.H
Special Relay
F 0.0-1023.F
------
DDD.H
Timer
------
T 0-255
DDD
Counter
------
C 0-255
DDD
Data Register
------
D 0-9999
DDDD
Notes
LS Modbus RTU
Notes
LS XGT_Cnet
Device
Bit Address
Word Address
Format
File Relay
R_bit 0.0-10239.F
------
DDDDD.H
Data Relay
D_bit 0.0-10239.F
------
DDDDD.H
Communication Relay
N_bit 0.0-5119.F
------
DDDD.H
Link Relay
L_bit 0.0-2047.F
------
DDDD.H
Index Relay
Z_bit 0.0-624.F
------
DDD.H
C_bit 0-9999
------
DDDD
- 173 -
T_bit 0-9999
------
DDDD
Special Relay
F_bit 0.0-1023.F
------
DDDD.H
Keep Relay
K_bit 0.0-4095.F
------
DDDD.H
Auxiliary Relay
M_bit 0.0-1023.F
------
DDDD.H
I/O Relay
P_bit 0.0-1023.F
------
DDDD.H
File Register
------
R_word 0-10239
DDDDD
Data Register
------
D_ word 0-10239
DDDDD
Communication Register
------
N_ word 0-9999
DDDD
Link Register
------
L_ word 0-9999
DDDD
------
S_ word 0-9999
DDDD
Index Register
------
Z_ word 0-9999
DDDD
Counter
------
C_ word 0-9999
DDDD
Timer
------
T_ word 0-9999
DDDD
Special Register
------
F_ word 0-9999
DDDD
Keep Register
------
K_ word 0-9999
DDDD
Auxiliary Register
------
M_ word 0-9999
DDDD
I/O Register
------
P_ word 0-9999
DDDD
Bit Address
Word Address
Format
File Relay
R_bit 0.0-10239.F
------
DDDDD.H
Data Relay
D_bit 0.0-10239.F
------
DDDDD.H
Communication Relay
N_bit 0.0-5119.F
------
DDDD.H
Link Relay
L_bit 0.0-2047.F
------
DDDD.H
Index Relay
Z_bit 0.0-624.F
------
DDD.H
ZR_bit 0.0-10239.F
------
DDDDD.H
C_bit 0-9999
------
DDDD
T_bit 0-9999
------
DDDD
Special Relay
F_bit 0.0-1023.F
------
DDDD.H
Keep Relay
K_bit 0.0-4095.F
------
DDDD.H
Auxiliary Relay
M_bit 0.0-1023.F
------
DDDD.H
I/O Relay
P_bit 0.0-1023.F
------
DDDD.H
File Register
------
R 0-10239
DDDDD
Data Register
------
D 0-10239
DDDDD
Communication Register
------
N 0-9999
DDDD
Link Register
------
L 0-9999
DDDD
------
S 0-9999
DDDD
- 174 -
Index Register
------
Z 0-9999
DDDD
------
ZR 0-10239
DDDDD
------
C_ SV 0-9999
DDDD
------
T_ SV 0-9999
DDDD
------
C_ CV 0-9999
DDDD
------
T_ CV 0-9999
DDDD
Special Register
------
F 0-9999
DDDD
Keep Register
------
K 0-9999
DDDD
Auxiliary Register
------
M 0-9999
DDDD
I/O Register
------
P 0-9999
DDDD
Bit Address
Word Address
Format
A_Bit 0.0-8191.F
-------
DDDD.H
F_Bit 0.0-1023.F
-------
DDDD.H
W_Bit 0.0-10239.F
-------
DDDDD.H
R_Bit 0.0-10239.F
-------
DDDDD.H
U_Bit 0.0-511.F
-------
DDD.H
Keep Relay
K_Bit 0.0-4095.F
-------
DDDD.H
Link Relay
L_Bit 0.0-2047.F
-------
DDDD.H
Auxiliary Relay
M_Bit 0.0-4095.F
-------
DDDD.H
Output Relay
Q_Bit 0.0-1023.F
-------
DDDD.H
Input Relay
I_Bit 0.0-1023.F
-------
DDDD.H
-------
A 0-8191
DDDD
-------
F 0-1023
DDDD
-------
W 0-10239
DDDDD
File Register
-------
R 0-10239
DDDDD
-------
U 0-511
DDD
Keep Register
-------
K 0-4095
DDDD
Link Register
-------
L 0-2047
DDDD
Auxiliary Reguster
-------
M 0-4095
DDDD
Output Register
-------
Q 0-1023
DDDD
Input Register
-------
I 0-1023
DDDD
Special Relay
File Relay
Special Register
LS GLOFA Cnet
Device
Bit Address
Word Address
Format
Buffer Memory(Bit)
MX0-32767
------
DDDDD
Output(Bit)
QX0-1763
------
DDDD
Input(Bit)
IX0-1763
------
DDDD
Buffer Memory(Dword)
------
MD0-16368
DDDDD
- 175 -
Notes
Output(Dword)
------
QD0.0-17.1
DD.D
Input(Dword)
------
ID0.0-17.1
DD.D
Buffer Memory(Word)
------
MW0-32767
DDDDD
Output(Word)
------
QW0.0-17.3
DD.D
Input(Word)
------
IW0.0-17.3
DD.D
Device
Bit Address
Word Address
Format
Buffer Memory(Bit)
MX0-131056
------
DDDDD
Output(Bit)
QX0-1763
------
DDDD
Input(Bit)
IX0-1763
------
DDDD
Buffer Memory(Dword)
------
MD0-4095
DDDD
Output(Dword)
------
QD0.0-17.1
DD.D
Input(Dword)
------
ID0.0-17.1
DD.D
Buffer Memory(Word)
------
MW0-8191
DDDD
Output(Word)
------
QW0.0-17.3
DD.D
Input(Word)
------
IW0.0-17.3
DD.D
LS GLOFA FEnet
Notes
NOTE:
1. The address format of %QX\IX is DD.D.DD (00.0.00~63.7.63) in the PLC, it correspond to DD D DD
(0~63763) in the HMI; Note that put 0 before the address if the address is less than two bits.
For example,
Internal address : %QX\IX 0.3.1 in the PLC correspond to QX\IX 301 in the HMI;
Internal address : %QX\IX 1.4.63 in the PLC correspond to QX\IX 1463 in the HMI;
2. The address format of %QD\ID is D.D.D (0.0.0~1.7.1) in the PLC, it correspond to D D.D (0.0~17.1) in
the HMI;
For example,
Internal address : %QD\ID 0.3.1 in the PLC correspond to QD\ID 3.1 in the HMI;
Internal address : %QD\ID 1.5.1 in the PLC correspond to QD\ID 15.1 in the HMI;
3. The address format of %QW\IW is D.D.D (0.0.0~1.7.3) in the PLC, it correspond to D D.D (0.0~17.3) in
the HMI;
For example,
Internal address : %QW\IW 0.3.1 in the PLC correspond to QW\IW 3.1 in the HMI;
Internal address : %QW\IW 1.5.3 in the PLC correspond to QW\IW 15.3 in the HMI;
LS iG5A protocol
Device
Bits
Words
Bit Address
Word Address
Format
AB 0.0-65535.F
-------
DDDDD
-------
AW 0-65535
DDDDD
2Register more than eight consecutive addresses will not be properly read.
3Some address may affect the surrounding register read, should used separately
H8andH10H42andH44,do not show put together
H20H30H36H37H42H50H51H52H70H90
F30F37F60I27I57
Bit Address
Word Address
Format
-------
3X 1-65535
DDDDD
-------
4X 1-65535
DDDDD
NOTE:
Inverter address converted to decimal, the address of the function list A100
corresponds AW41216.
Modbus 1 0000
Cable Diagram
LS Master-K Cnet/ LS Master-K Modbus RTU protocol
RS232 communication cable
- 177 -
- 178 -
NOTE: Be sure to put the switch of the module to 9 (ON-LINE) position when communicating.
LS iG5A protocol
Ethernet Cable
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to 4.3 Download by Network Ethernet for method of making connection cable.
- 179 -
4.44 LUST
Serial Communication
Series
CPU
Link Module
Driver
CDE34.008
CDE34.008
LustBus
CPU
Link Module
Driver
ServoOne junior
Lust
CPU
Link Module
COM Type
CDE34.008
RS232
Parameter
Setting
Cable
Your owner cable
CPU
Link Module
COMM Type
Parameter
Cable
ServoOne junior
Lust
ETH
Setting
- 180 -
- 181 -
Parameter
Initial IP
Modified IP
b3
b2
b1
b0
int
192
168
39
hex
C0
A8
27
05
int
192
168
100
240
hex
C0
A8
64
F0
b3
b2
b1
b0
int
192
168
39
hex
C0
A8
27
05
int
192
168
100
240
hex
C0
A8
64
F0
Parameter
Initial IP
Modified IP
D2
5.
1.
D2
D2
D1
D2
D2
D2
D2
Press T1, respectively, and T2, you can adjust the value of b0, After release, while at T1 and T2 key until
the display or can be, Then press and T1 and T2, also show b0, then press the key T1 of about 1s,can switch
to b2, empathy can be modified the value of b2, b3, b4, modify the good, the same press T1 and T2 until
display or (where press T1 and T2 at the same time is the key to save and exit).
Well, after the change, restart the power, and then ping.
Supported Device
- 183 -
CDE34.008
Refer to the Controller software for details: DriveManager for c-line drives
ServoOne junior
Device
Bit Address
Word Address
Format
Array_DWord32
0.00000-32767.65535
DDDDD.DDDDD
Array_DWord16
0.00000-32767.65535
DDDDD.DDDDD
DWord32
0-32767
DDDDD
Word16
0-32767
DDDDD
Notes
Note: Array_DWord32/Array_DWord16 the address format is the primary address + decimal point +
sub-address, such as the address for the save as shown below, the main address is 11, sub-address is 0, the
data type is int16, then the touch screen corresponding to the address is Array_DWord16 11.00000.
The primary address is 11, sub-address is 1, the data type is int16, then the touch screen corresponding to
the address is Array_DWord16 11.00001. In addition, INT8 address, select Word16, but also through the
conversion can be displayed, as should show -3, while the display 253, which can be done in the macro
data conversion, so 253-256 = -3, that is in need of special address type conversion .
Cable Diagram
Lustbus RS232 communication cable
- 184 -
CPU
Link Module
Driver
BMS005A-MC11
BMS005A-MC11
MemoryMap(Master-Slave)
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
BMS005A-MC11
BMS005A-MC11
RS422
Setting
Your owner
cable
Communication Setting
HMI Setting
Default communication: 57600, 8, none, 1; station: 1
PLC Setting
Please refer to the manual of PLC for the configuration.
Supported Device
- 185 -
Device
Bit Address
Word Address
Format
LW.B 8000.0-8999.15
--------
DDDD.DD
--------
LW8000-8999
DDDD
Cable Diagram
4.46 MEGMEET
Serial Communication
Series
CPU
Link Module
Driver
MEGMEET MC280
MC280-1616BTA4
MEGMEET MC Series
CPU
Link Module
COMM Type
Parameter
Cable
MEGMEET
MC280
MC280-1616
BTA4
RS232/RS485
Setting
RS232
- 186 -
RS485
PLC Setting
1.Open X_builder,New projectselect PLC typeMC280
- 187 -
1Port0 settingRS232
2Port1andPort2 settingRS485
- 188 -
Supported Device
Device
Bit Address
Word Address
Format
Notes
Input Relay
X 0-377
------
OOO
Output Relay
Y 0-377
------
OOO
Internal Relay
M 0-10239
------
DDDDD
Special Relay
SM 0-511
------
DDD
Step Relay
S 0-4095
------
DDDD
Timer Relay
T_BIT 0-511
------
DDD
Counter Relay
C_BIT 0-306
------
DDD
D 0-7999
DDDD
Special Register
-----------
SD 0-511
DDD
Index Register
------
Z 0-15
DD
Timer
------
T_Word 0-511
DDD
Counter
------
C_Word 0-199
DDD
Counter(double word)
------
C_DWord 200-306
DDD
------
R 0-32767
DDDDD
------
R_DWord 0-32767
DDDDD
------
SD_DWord 0-511
DDD
------
D_DWord 0-7999
DDDD
Data register
Cables Production
RS232
- 189 -
RS485
4.47 Mikom
Serial Communication
Series
CPU
Link Module
MX2H
MX2H-3232M
Driver
Mikom MXxh
RS485 on port
System configuration
Series
CPU
MX2H
MX2H-3232M
Link Module
COMM Type
Parameter
Cable
Port 0
RS232
Setting
Port 1
RS485-2
Setting
Communication Setting
HMI Setting
Default communication parameters 19200, 7, 1, evenStation1
- 190 -
PLC Setting
Supported Device
Device
Bit Address
Word Address
Format
Input Relay
X 0-777
OOO
Output Relay
Y 0-777
OOO
Counter
C_bit 0-511
DDD
Timer
T_bit 0-511
DDD
Status Relay
S 0-1535
DDDD
Special Relay
SM 0-511
DDD
Internal Relay
M 0-4095
DDDD
Data register
D 0-7999
DDDD
SD 0-511
DDD
Z 0-255
DDD
Timer
T_word 0-255
DDD
Counter
C_word 0-199
DDD
Index Register
NOTE:
The PLC MODBUS protocol does not support double-word data type, so the protocol
does not support the bulk of the word read and write .
- 191 -
Cable Diagram
RS232 Communication
RS485-2 Communication
4.48 Millenium3
Serial Communication
Series
CPU
Link Module
Millenium 3
Millenium 3
Driver
Millenium 3
System configuration
Series
CPU
Millenium 3
Millenium 3
Link Module
COM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
Communication Setting
HMI Setting
Default communication parameters 115200, 7, 1, evenStation1
RS232 Communication:
- 192 -
RS485-2 Communication
Supported Device
Device
Bit Address
Word Address
Format
Notes
Register
------
Register 0~23
DD
Write only
Register
------
Register 24~47
DD
Read only
Cable Diagram
RS232
- 193 -
Users need to make the communication cable for M3 and HMI (region of red marquee as shown above)
M3 communicate with COM0 of HMI, the cable connection is as follow:
RS485-2
CPU
FX1S
FX0N
FX1N
Link Module
Driver
CPU Direct
FX-422-BD*3
Mitsubishi FX1S*2
FX-485-BD *3
FX-485-ADP*3
Mitsubishi FX1S*2
Mitsubishi
(Multi-station) *1
CPU Direct
Mitsubishi FX0N/1N/2N/3G*2
- 194 -
FX-485ADP/485BD/232BD
FX1NC
FX2N
FX2NC
FX2N-10GM
FX2N-20GM
FX-422-BD*3
FX-485-BD*3
FX-485-ADP*3
FX-232-BD*3
Mitsubishi FX0N/1N/2N/3G*2
Mitsubishi
FX-485ADP/485BD/232BD
1
(Multi-station) *
CPU Direct
Mitsubishi FX2N_10GM/20GM
CPU Direct
FX3U
FX3UC
FX-485-BD*3
FX-485-ADP*3
FX-232-BD*
FX3G
Q00jCPU
Mitsubishi FX3U*2
FX-422-BD*3
Mitsubishi FX3U*2
Mitsubishi
(Multi-station) *1
FX-485ADP/485BD/232BD
CPU Direct
Mitsubishi FX0N/1N/2N/3G*2
QJ71C24
QJ71C24-R2
QJ71C24N
QJ71C24N-R2
QJ71C24N-R4
QCPU
Q01UCPU
Q03UDCPU
Q06UDHCPU
QJ71C24
QJ71C24-R2
QJ71C24N
QJ71C24N-R2
QJ71C24N-R4
Q12HCPU
Mitsubishi Q06Hv2*4
Q00UJCPU
Q02UCPU
Mitsubishi Melsec Q
Q06HCPU
Mitsubishi Q06H
Mitsubishi Q06Hv2*4
L02CPU
LJ71C24-CM
Q02CPU
Q02HCPU
Q25HCPU
LCPU
QJ71C24
QJ71C24-R2
QJ71C24N
QJ71C24N-R2
QJ71C24N-R4
- 195 -
CPU
Link Module
FX3GE-24M
FX3U-32M
FX3U-ENET-L
Q00CPU
Q00JCPU
Q01CPU
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q03UDECPU
Q04UDEHCPU
Q06UDEHCPU
Q13UDEHCPU
Q26UDEHCPU
QJ71E71
QJ71E71-B2
QJ71E71-B5
QJ71E71-100
Q02UCPU
Q03UDCPU
Q04UDHCPU
Q06UDHCPU
Q13UDHCPU
Q26UDHCPU
QJ71E71
QJ71E71-B2
QJ71E71-B5
QJ71E71-100
LCPU
L02CPU
L26CPU-BT
QCPU
Q03UDECPU
Q26UDV CPU
FXCPU
QCPU
Driver
Mitsubishi FX Series Ethernet(TCP
Slave)
CPU
FX1S
FX0N
FX1N
FX1NC
FX2N
Link Module
COMM
Type
Parameter
Cable
RS232
Setting
RS485-4
Setting
RS485-4
Setting
RS232
Setting
RS485-4
Setting
FX-485-BD
RS485-4
Setting
- 196 -
FX2NC
FX-485-ADP
FX-232-BD
RS232
Setting
RS232
Setting
RS485-4
Setting
RS232
Setting
RS485-4
Setting
RS232
Setting
RS485-4
Setting
FX-485-BD
FX-485-ADP
RS485-4
Setting
FX-232-BD
RS232
Setting
Q00jCPU
RS232
Setting
Q00CPU
Q01CPU
RS232
Setting
Q00jCPU
Q00CPU
Q01CPU
Q02CPU
Q02HCPU
Q03UDCPU
Q25HCPU
QJ71C24
QJ71C24-R2
QJ71C24N
QJ71C24N-R2
RS232
Setting
QJ71C24
QJ71C24N
QJ71C24N-R4
RS485-4
Setting
Q00UJCPU
RS232
Setting
Q02CPU
Q02HCPU
Q01UCPU
Q02UCPU
Q03UDCPU
Q06HCPU
Q06UDHPU
Q25HCPU
RS232
Setting
Q06HCPU
Q12HCPU
RS232
Setting
L02CPU
LJ71C24-CM
Setting
FX2N-10GM
FX2N-20GM
FX3G
FX3UC
FX3U
Melsec Q
LCPU
RS232
RS485-4
CPU
Link Module
Connect Type
Parameter
Cable
FXCPU
FX3GE-24M
Ethernet
Setting
FX3U-32M
FX3U-ENET-L
Ethernet
Setting
Melsec Q
Q00CPU
Q00JCPU
Q01CPU
QJ71E71
QJ71E71-B2
QJ71E71-B5
- 197 -
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q03UDECPU
Q04UDEHCPU
Q06UDEHCPU
Q13UDEHCPU
Q26UDEHCPU
MELSEC L
QCPU
QJ71E71-100
Q02UCPU
Q03UDCPU
Q04UDHCPU
Q06UDHCPU
Q13UDHCPU
Q26UDHCPU
QJ71E71
QJ71E71-B2
QJ71E71-B5
QJ71E71-100
Ethernet
Setting
L02CPU
L26CPU-BT
Ethernet
Setting
Q26UDV CPU
Q03UDECPU
Ethernet
Setting
RS422 communication
- 198 -
HMI Setting
When using the Mitsubishi FX1SMitsubishi FX0N/1N/2N/3GMitsubishi FX3U protocol, PLC
configuration is as follow:
Dont select Operate communication setting, and click default
NOTE:
1. If you do not use the multi-station when using communication module, you can choose the protocol of
Mitsubishi FX1SMitsubishi FX0N/1N/2N/3GMitsubishi FX3U etc. according to the PLC model
2. Make sure that the value of D8120 is 0 when using the communication module
- 199 -
PLC Setting
Select the Operate communication setting
NOTE:
1. FX0N series dont support the Operate communication setting, but the communication parameters can
be modified by setting the value of D8120D8121D8129
2. If series of PLC is FX3U/3UC, you must select CH1
3. Select the Dedicated protocol and check Sum check option, Transmission control procedure must be
Form4
4. If you use the FX-232-BD module, set H/W type to Regular/RS-232C; if you use the FX
-485-BD/FX-485-ADP module, set H/W type to RS-485
The communication parameters can be modified by setting the value of D8120/D8121/D8129
Special register
Description
- 200 -
D8120
Communication format
D8121
Station number
D8129
Overtime
For example
The communication parameters of PLC as follow:
Communication format: 9600bps, 7, even, 2;
Station No.:1;
H/W type: RS485;
Time out: 1
Set the value of D8120/D8121/D8129:
D8120=0xE08E
D8121=1
D8129=1
NOTE: Restart the PLC after setting the value of D8120.
FX2N-10G/20GM protocol
Default communication: 9600, 8, even, 1; station: 0
RS232 communication
RS422 communication
- 201 -
RS232 communication
NOTE
1 If communication baudrate is error, HMI automatically set PLC baudrate for the HMI baudrate. It
is not necessary to consider whether the PLC communications baudrate being true.
2 This drives support password protection model Q00J.
RS232 communication
NOTE: If communication baudrate is error, HMI automatically set PLC baudrate for the HMI baudrate. It
is not necessary to consider whether the PLC communications baudrate being true.
HMI Setting
Default parameters :115200, 8, odd, 1 ; Station No. : 0(Non-support station number, only one HMI connect
to one PLC)
RS232 communication
NOTE: If communication baudrate is error, HMI automatically set PLC baudrate for the HMI baudrate. It
is not necessary to consider whether the PLC communications baudrate being true.
RS232 communication
RS422 communication
- 203 -
HMI Setting
1. CPU port communication
- 204 -
- 205 -
content
example
Switch1
0BEEH
115Kbps
8 bit
1 bit
even
Switch2
CH1:communication protocol
0005H
Switch3
0BEEH
Switch4
CH2:communication protocol
0005H
Switch5
0~31
0000H
If the communication parameters of CH2 485 is 19200/8/odd/1, station:0, set as follows switch setting
in PLC parameters and I/O assignment.
- 206 -
If the communcation parameters of CH1 232 is 19200/8/odd/1, station:0, set as follows switch setting in
PLC parameters and I/O assignment.
NOTE: After setting the switches, reset the PLC or turn the power off and then back on again.
- 207 -
PLC Setting
FX3GE-24M
1. Double clickPLC ParametersselectBuilt-in Ethernet Port Settingsthe parameters
configuration as follow:
- 208 -
FX3U-ENET-L
1. OpenFX3U-ENET-L Configuration Toolthe parameters configuration as follow:
- 209 -
3.
- 210 -
PLC Setting
1. Network parameters
[network type] select "Ethernet"; [start I/O] is a hexadecimal number increments & H10, you can select "0";
[network number] range is 1-239, generally set at the network level, only a layer of the network, so set to
- 211 -
"1"; [Group number] range is 0-32, select "0"; [station number] range 1-64, 1 occupied by the computer
side, can be set to 2-64, the example is set to "2" ; [Model] Select "online". Next, click [operation], set the
IP address of the dialog box pops up, in part by the network to determine the first three, the fourth part of
the free use of the network number. One thing to note is that the figure of [the initial time setting] to choose
"Always wait to open" (stop when communication), or Ethernet port is not open external device. Click [end
set] button to save the settings.
2. Operational settings
3. Open settings
In line 1 [protocol] selection "UDP" protocol; and that [open in pairs] option select "pairs", system will be
prompted to
- 212 -
NOTE:
1. PLC station number must be 255
2. Data format of Port number is decimalism
PLC Setting
Double click PLC parameters, select Built-in Ethernet Port Settings
- 213 -
NOTE: Host Station Port No. will be set by the selected format.
Q03UDE CPU :
HMI Setting
- 214 -
NOTE:
1. PLC station number must be 255
2. Data format of Port number is decimalism
PLC Setting
- 215 -
NOTE: Host Station Port No. will be set by the selected format.
Supported Device
FX1S
Device
Bit Address
Word Address
Format
Input Relay
X 00-764
------
OOO
Output Relay
Y 00-764
------
OOO
Internal Relay
M 000-7999
------
DDDD
Timer Contact
T 00-511
------
DDD
Counter Contact
C 00-255
------
DDD
D_bit 0.0-7999.F
------
DDDD.H
S 000-4095
------
DDDD
Timer Value
------
T_word 00-511
DDD
Counter Value
------
C_word 00-199
DDD
Data Register
------
D_word 000-17999
DDDDD
------
SD_word 8000-8255
DDDD
Counter Value
------
C_dword 235-255
DDD
32 bit device
Notes
Data Contact
State
Notes
FX0N/FX1N/2N/3G
Device
Bit Address
Word Address
Format
Input Relay
X 000-377
------
OOO
Output Relay
Y 000-377
------
OOO
Internal Relay
M 0000-3071
------
DDDD
Timer Contact
T_bit 000-255
------
DDD
Counter Contact
C_bit 000-199
------
DDD
SM 8000-8255
------
DDDD
- 216 -
State
S 000-999
------
DDD
Timer Value
------
T_word 000-255
DDD
Counter Value
------
C_word 000-199
DDD
Data Register
------
D 0000-7999
DDDD
------
SD 8000-8255
DDDD
Counter Value
------
C_dword 200-255
DDD
32 bit device
Device
Bit Address
Word Address
Format
Notes
Input Relay
X 00-571
------
OO
*1
Output Relay
Y 00-571
------
OO
*1
Internal Relay
M 000-7999
------
DDD
*1
------
DDDD
*1
Data Register
SM9000-9999
------
D 0-7999
DDDD
*2
------
DDDD
*2
------
SD 9000-9999
FD 4000-4550
DDDD
*2
Current Position(System)
------
CP_unit 0-1
------
CP_puls 0-1
FX2N-10GM/20GM
Current Position(Pulse)
NOTE:
*1 Dont support batch
*2 Support batch
FX3UC
Device
Bit Address
Word Address
Format
Input Relay
X000-764
------
OOO
Output Relay
Y000-764
------
OOO
Timer Contact
T_bit 000-511
------
DDD
Counter Contact
C_bit 000-255
------
DDD
Data Contact
D_bit0.0-7999.F
------
DDDD.H
State
S0000-4095
------
DDDD
Internal Relay
M0000-7999
------
DDDD
SM8000-8511
------
DDDD
Timer Value
------
T_word 000-511
DDD
Counter Value
------
C_word 000-199
DDD
Data Register
------
D_word 0-17999
DDDDD
Extension Register
------
R0000-32767
DDDDD
------
SD8000-9999
DDDD
- 217 -
Notes
Counter Value
------
C_dword200-255
DDD
32 bit device
FX Series Ethernet
Device
Bit Address
Word Address
Format
State
S 0-4095
------
DDDD
Data Contact
D_bit0.0-7999.F
------
DDDD.H
SM8000-8511
------
DDDD
Counter Contact
C_bit0-255
------
DDDD
Timer Contact
T_bit0-511
------
DDDD
Internal Relay
M 0-7679
------
DDDD
Output Relay
Y 0-377
------
DDDD
Input Relay
X 0-377
------
DDDD
Extension Register
------
R 0-32767
DDDDD
------
SD 8000-8511
DDDD
Data Register
------
D_word0-7999
DDDD
Timer Value
------
T_word0-511
DDD
Counter Value
------
C_word0-199
DDD
Counter Value
------
C_dword200-255
DDD
Notes
Q00jCPU
Device
Bit Address
Word Address
Format
Counter Coil
CC0-1023
------
DDDD
Counter Contact
CS0-1023
------
DDDD
Timer Coil
TC0-2047
------
DDDD
Timer Contact
TS0-2047
------
DDDD
SB000-7FFF
------
HHHH
Link Relay
B0000-7FFF
------
HHHH
Step Relay
S0000-1FFF
------
HHHH
Edge Relay
V0000-32767
------
DDDDD
Annunciator
F0000-32767
------
DDDDD
Latch Relay
L0000-32767
------
DDDDD
SM0000-2047
------
DDDD
Internal Relay
M0000-32767
------
DDDDD
Output Relay
Y0000-1FFF
------
HHHH
Input Relay
X0000-1FFF
------
HHHH
File Register
------
R000-32767
DDDDD
------
SW0-7FF
HHH
Link Register
------
W000-291F
HHHH
- 218 -
Notes
------
SD0-2047
DDDD
Data Register
------
D0-25983
DDDDD
Counter Value
------
CN0-25983
DDDDD
------
SN0-2047
DDDD
Timer Value
------
TN0-25983
DDDDD
Melsec Q
Device
Bit Address
Direct output
DY 0-7FF
HHHH
Direct input
DX 0-7FF
HHHH
Step Relay
S 0-2047
SB 0-7FFF
Counter Coil
CC 0-511
------
DDDD
Counter Contact
CS 0-511
------
DDDD
Step Coil
SC 0-511
------
DDDD
Step Contact
SS 0-511
------
DDDD
Timer Coil
TC 0-511
------
DDDD
Timer Contact
TS 0-511
------
DDDD
Link Relay
B 0-7FF
Edge Relay
V 0-1023
------
DDDD
Annunciator
F 0-1023
------
DDDD
Latch Relay
L 0-2047
------
DDDD
Internal Relay
M 0-8191
------
DDDD
Output Relay
Y 0-7FF
------
HHHH
Input Relay
X 0-7FF
------
HHHH
File Register
------
ZR 0-65535
DDDDDD
File Register
------
R 0-32767
DDDDD
Index Register
------
Z 0-9
DD
Counter Value
------
CN 0-511
DDDD
SN 0-511
DDDD
Word Address
Format
------
Notes
DDDD
HHHH
HHHH
Timer Value
------
TN 0-511
DDDD
------
SW 0-3FF
HHH
Link Register
------
W 0-1FFF
HHHH
------
SD 0-2047
DDDD
Data Register
------
D 0-11135
DDDDD
Bit Address
- 219 -
Word Address
Format
SB 00000- 7FFF
------
HHHH
Link Relay
B 00000- 7FFF
------
HHHH
Edge relay
V 00000-32767
------
DDDDD
Annunciator
F 00000-32767
------
DDDDD
Latch relay
L 00000-32767
------
DDDDD
SM 0000-2047
------
DDDD
Internal Relay
M 00000-32767
------
DDDDD
Output Relay
Y 0000-1FFF
------
HHHH
Input Relay
X 0000-1FFF
------
HHHH
Link Register
------
W 00000- 291F
HHHH
Timer Value
------
TN 00000-23087
DDDDD
Counter Value
------
CN 00000-23087
DDDDD
File Register
------
R 00000-32767
DDDDD
------
SW 0000- 7FF
HHH
Data Register
------
D 00000-25983
DDDDD
------
SD 0000-2047
DDDD
Q_QnA(link port)
Device
Bit Address
Word Address
Format
SB000-7FFF
------
HHHH
Link Relay
B0000-7FFF
------
HHHH
Edge Relay
V0000-32767
------
DDDDD
Annunciator
F0000-32767
------
DDDDD
Latch Relay
L0000-32767
------
DDDDD
SM0000-2047
------
DDDD
Internal Relay
M0000-32767
------
DDDDD
Output Relay
Y0000-1FFF
------
HHHH
Input Relay
X0000-1FFF
------
HHHH
Link Register
------
W0000-291F
HHHH
Timer Value
------
TN0-23087
DDDDD
------
SN0-23087
DDDDD
Counter Value
------
CN0-23087
DDDDD
------
ZR00000-65535
DDDDD
File Register
------
R00000-32767
DDDDD
------
SW000-7FF
HHH
Data Register
------
D00000-25983
DDDDD
------
SD0000-2047
DDDD
- 220 -
Q06
Device
Bit Address
Word Address
Format
SB 0000- 7FFF
------
HHHH
Link Relay
B 0000- 7FFF
------
HHHH
Edge relay
V 00000-32767
------
DDDDD
Annunciator
F 00000-32767
------
DDDDD
Latch relay
L 00000-32767
------
DDDDD
SM 0000-2047
------
DDDD
Internal Relay
M 00000-32767
------
DDDDD
Output Relay
Y 0000-1FFF
------
HHHH
Input Relay
X 0000-1FFF
------
HHHH
Link Register
------
W 00000- 291F
HHHH
Timer Value
------
TN 00000-23087
DDDDD
Counter Value
------
CN 00000-23087
DDDDD
File Register
------
R 00000-32767
DDDDD
------
SW 0000- 7FF
HHH
Data Register
------
D 00000-25983
DDDDD
------
SD 0000-2047
DDDD
Bit Address
Word Address
Format
S 000-8191
------
DDDD
SB 000-7FFF
------
HHHH
Counter Coil
CC 0-23087
------
DDDDD
Counter Contact
CS 0-23087
------
DDDDD
Step Coil
SC 0-23087
------
DDDDD
Step Contact
SS 0-23087
------
DDDDD
Timer Coil
TC 0-23087
------
DDDDD
Timer Contact
TS 0-23087
------
DDDDD
Link Relay
B 0000-1FFF
------
HHHH
Edge Relay
V 0-32767
------
DDDDD
Annunciator
F 0-32767
------
DDDDD
Latch Relay
L 0-32767
------
DDDDD
SM 0-2047
------
DDDD
Internal Relay
M 0-32767
------
DDDD
Output Relay
Y 0-1FFF
------
HHHH
Input Relay
X 0-1FFF
------
HHHH
------
W 0-291F
HHHH
Step Relay
Link Register
- 221 -
Timer Value
------
TN 0-23087
DDDD
Counter Value
------
CN 0-23087
DDDDD
SN 0-23087
DDDDD
------
R 0-32767
DDDDD
------
ZR 0-1042431
DDDDDDD
------
SW 0-7FF
HHH
Data Register
------
D 0-25983
DDDDD
------
SD 0-2047
DDDD
Bit Address
Word Address
Format
Direct output
DY 0-1FFF
HHHH
Direct input
DX 0-1FFF
HHHH
Step Relay
S 0-8191
------
DDDD
SB 0-7FFF
SB 0-1FFF
HHHH
Counter Coil
CC 0-1023
------
DDDD
Counter Contact
CS 0-1023
------
DDDD
Step Coil
SC 0-2047
------
DDDD
Step Contact
SS 0-2047
------
DDDD
Timer Coil
TC 0-2047
------
DDDD
Timer Contact
TS 0-2047
------
DDDD
Link Relay
B 0-1FFF
B 0-1FFF
HHHH
Edge Relay
V 0-2047
------
DDDD
Annunciator
F 0-2047
------
DDDD
Latch Relay
L 0-8191
------
DDDD
SM 0-2047
------
DDDD
Internal Relay
M 0-8191
------
DDDD
Output Relay
Y 0-1FFF
Y 0-1FFF
HHHH
Input Relay
X 0-1FFF
X 0-1FFF
HHHH
File Register
------
ZR 0-393216
DDDDDD
File Register
------
R 0-32767
DDDDD
Index Register
------
Z 0-19
DD
Counter Value
------
CN 0-1023
DDDD
SN 0-2047
DDDD
------
TN 0-2047
DDDD
------
SW 0-7FF
HHH
W 0-1FFF
HHHH
SD 0-2047
DDDD
Link Register
Special Data Register
------ 222 -
Notes
Data Register
------
D 0-45055
DDDDD
Device
Bit Address
Word Address
Format
Direct output
DY 0-1FFF
HHHH
Direct input
DX 0-1FFF
HHHH
Step Relay
S 0-8191
------
DDDD
SB 0-7FF
SB 0-7F0
HHHH
Counter Coil
CC 0-1023
------
DDDD
Counter Contact
CS 0-1023
------
DDDD
Step Coil
SC 0-2047
------
DDDD
Step Contact
SS 0-2047
------
DDDD
Timer Coil
TC 0-2047
------
DDDD
Timer Contact
TS 0-2047
------
DDDD
Link Relay
B 0-1FFF
B 0-1FF0
HHHH
Edge Relay
V 0-2047
------
DDDD
Annunciator
F 0-2047
------
DDDD
Latch Relay
L 0-8191
------
DDDD
SM 0-2047
------
DDDD
Internal Relay
M 0-8191
------
DDDD
Output Relay
Y 0-1FFF
Y 0-1FF0
HHHH
Input Relay
X 0-1FFF
X 0-1FF0
HHHH
File Register
------
ZR 0-32767
DDDDDD
File Register
------
R 0-32767
DDDDD
Index Register
------
Z 0-19
DD
Counter Value
------
CN 0-1023
DDDD
------
SN 0-2047
DDDD
Timer Value
------
TN 0-2047
DDDD
------
SW 0-7FF
HHH
Link Register
------
W 0-1FFF
HHHH
------
SD 0-2047
DDDD
Data Register
------
D 0-12287
DDDDD
Q03UDE
Notes
Cable Diagram
FX Series RS232 Cable
1. CPU port communication
Please use the FX series SC - 09 serial programming cable communication, can also be made simple
programming cable
- 223 -
2. FX-232-BD communication
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
2. FX-485-BD communication
- 224 -
Controller terminal
9 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
1 DCD
4 DTR
6 DSR
7 RTS
8 CTS
CPU
Link Module
Driver
BY125
BY125
MKS
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
BY125
BY125
RS232
Setting
Communication Setting
Default communication: 9600, 7, even, 1; station: 11
Supported Device
Device
Bit Address
Word Address
Format
Notes
Relay
CB 00-FF
------
HH
Register
------
CD00-FF
HH
External Register
------
ERCD 0000.00-FFFF.FF
HHHH.HH
------
M1 0~9
Read only
------
M2 0~9
Read only
------
M3 0~9
Read only
NOTE:
1ERCD is Extended register, the four position before radix point are C1,C2,C3,C4.The two
positions after radix point are S1, S2.
2Parameter code corresponding with CD are C1,C2;
- 226 -
3Parameter code corresponding with CB set to 1;Eg:Bit State Setting part, addr type CB67, set
the state to 1.
4) M1 correspond to parameter ":"; M2 correspond to parameter";"; M3 correspond to parameter"<";
Cable Diagram
MKS controller RS232 communication cable
4.51 Modbus
Serial Communication
Series
CPU
Link Module
SIO type
Driver
Modbus RTU
Modbus RTU
Modbus ASCII
MODBUS
Compatible
External Device
Modbus ASCII
Modbus TCP
Ethernet
Modbus TCP
Ethernet
Modbus UDP
Ethernet
Modbus UDP
Ethernet
System configuration
Series
Modbus RTU
Modbus
Extend
RTU
CPU
Link Module
COMM Type
Parameter
Cable
MODBUS
Compatible
External
Device
RS232/485 on the
CPU unit
RS232/RS485
Setting
RS232/485 on the
CPU unit
RS232/RS485
Setting
RS232/RS485
Setting
RS232/485 on the
CPU unit
- 227 -
Modbus
RTU
MT500 compatible
RS232/485 on the
CPU unit
Modbus ASCII
RS232/485 on the
CPU unit
RS232/RS485
Setting
RS232/RS485
Setting
Modbus TCP
Ethernet
Ethernet
Modbus UDP
Ethernet
Ethernet
Connection Configuration
Connection Configuration
Communication Setting
Modbus RTU protocol
RS232 communication
Default communication parameters: 9600, 8, even, 1; station: 1
NOTE:
1. Modbus RTU protocol supports broadcasting station number, but the radio function only supports write
operations, with a reading of properties for the components, can not use the radio function;
2. Radio features are used in two ways: First, write-only properties with components (Bit state setting
device, "switch" method, except); multi-state setting device, "add value", "sub value", "JOG++", "JOG--"
method excluded); Second, the use of macros, the macro programming, on the radio station to write the
address number.
- 228 -
- 229 -
- 230 -
Supported Device
Modbus RTU
Device
Bit Address
Word Address
Format
Output Relay
0X1-65535
------
DDDDD
1X1-65535
------
DDDDD
------
3X1-65535
DDDDD
Output Register
------
4X1-65535
DDDDD
Notes
Device
Bit Address
Word Address
Format
Notes
Output Relay
0X1-65535
------
DDDDD
Input Relay
1X1-65535
------
DDDDD
read only
Input Relay
3X_bit 1.00-65535.15
------
DDDDD
read only
Output Relay
4X_bit 1.00-65535.15
------
DDDDD
6X_bit 1.00-65535.15
------
DDDDD.DD
Input Register
------
3X1-65535
DDDDD
Output Register
------
4X1-65535
DDDDD
4X Byte Swap
------
5X1-65535
DDDDD
------
6X1-65535
DDDDD
4X-DINV 1-65535
DDDDD
3X-DINV 1-65535
DDDDD
read only
NOTE:
5X is the byte counter; 4X-DINV, 3X-DINV is the word high and low-bit counter. The relation of them as
follow:
Word:
4X(1word)
4 H
byte swap
5X(1word)
2 H
Dword:
Text:
Bit Address
Word Address
Format
Notes
Output Relay
LB 0-9999
------
DDDDD
Mapping to 0X 1~9999
Data Register
------
LW 0-65535
DDDDD
Mapping to 4X 1~9999
- 232 -
Bit Address
Word Address
Format
Notes
Output Relay
0X 1-65535
------
DDDDD
Input Relay
1X 1-65535
------
DDDDD
read only
Input Relay
3X_bit 1.00-65535.15
------
DDDDD.DD
read only
Output Relay
4X_bit 1.00-65535.15
------
DDDDD.DD
Input Register
------
3X 1-65535
DDDDD
Output Register
------
4X 1-65535
DDDDD
read only
Modbus ASCII
Device
Bit Address
Word Address
Format
Output Relay
0X1-65535
------
DDDDD
1X1-65535
------
DDDDD
------
3X1-65535
DDDDD
Output Register
------
4X1-65535
DDDDD
Notes
Bit Address
Word Address
Format
Notes
Output Relay
0X 1-65535
------
DDDDD
Input Relay
1X 1-65535
------
DDDDD
read only
Input Relay
3X_bit 1.00-65535.15
------
DDDDD.DD
read only
Data relay
4X_bit 1.00-65535.15
------
DDDDD.DD
Input Register
------
3X 1-65535
DDDDD
Output Register
------
4X 1-65535
DDDDD
Data Register
------
4X-DINV 1-65535
DDDDD
Data Register
------
3X-DINV 1-65535
DDDDD
read only
Bit Address
Word Address
Format
Output Relay
0X1-65535
------
DDDDD
Input Relay
1X1-65535
------
DDDDD
read only
Input Register
------
3X1-65535
DDDDD
read only
Output Register
------
4X1-65535
DDDDD
Cable Diagram
RS232 communication cable
- 233 -
Notes
4.52 MODROL
Serial Communication
Series
CPU
Link Module
Driver
MODROL
IMS-GF3-4011E
MODROL
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
MODROL
IMS-GF3-4011E
RS485
Setting
Communication Setting
HMI Setting
Default communication: 9600, 8, none, 1; station: 1
- 234 -
Supported Device
Device
Bit Address
Word Address
Format
Notes
------
D_1 0-9999
DDDD
One byte
------
D_2 0-9999
DDDD
Two byte
------
D_3 0-9999
DDDD
Three byte
Cable Diagram
MODROL RS485
4.53 OE MAX
Serial Communication
Series
CPU
Link Module
Driver
NX7
NX7
OE MAX NX7
System configuration
- 235 -
Series
CPU
Link Module
COMM Type
Parameter
Cable
NX7
NX7
RS232
Setting
Communication Setting
Default communication: 19200, 8, none, 1; station: 1
Supported Device
Device
Bit Address
Word Address
Format
Input/Output Relay
R 0.0127.15
------
DDD.DD
General Relay
L 0.063.15
------
DD.DD
General Relay
M 0.0127.15
------
DDD.DD
Keep Relay
K 0.0127.15
------
DDD.DD
Timer Relay
TC 0255
------
DDD
Special Relay
F 0.015.15
------
DD.DD
Internal HSC
------
R_word 0-127
DDD
General Register
------
L_word 0-63
DD
General Register
------
M_word 0-127
DDD
Keep Register
------
K_word 0-127
DDD
General Register
------
F_word 0-15
DD
Timer/Counter Register
------
SV_word 0-255
DDD
Timer/Counter Register
------
PV_word 0-255
DDD
General Register
------
W_word 0-2047
DDDD
Special Register
------
SR_word 0-511
DDD
Cable Diagram
Oemax RS232 communication cable
- 236 -
Notes
CPU
Link Module
CP1H
CP1L
CP1E
C200H
C200H-LK202
C120-LK201-V1
C200HS
C200H-LK201
C200H-LK202
C120-LK201-V1
CP1W-CIF01
Driver
OMRON C Series Host Link
OMRON CP Series Host Link
CP1W-CIF11/CIF12
C120-LK201-V1
C120-LK202-V1
C500-LK201-V1
C500-LK203
C1000HF
C500-LK201-V1
C500-LK203
C20H/28H/40H
C20PF/28PF
C40PF/60PF
C120-LK201-V1
C120-LK202-V1
C120
C120F
C120-LK201-V1
C120-LK202-V1
CQM1-CPU11
CQM1-CPU21
CQM1-CPU41
CQM1-CPU42
CQM1-CPU43
CQM1-CPU44
CQM1-CPU41-V1
CQM1-CPU42-V1
- 237 -
CQM1-CPU43-V1
CQM1-CPU44-V1
CPM2C
CQM1H-CPU11
CQM1H-CPU21
CQM1H-CPU51
CQM1H-CPU61
CPM1
CPM1A
CPM1A-V1
CPM2AH
SYSMAC
CJ2
CJ2M-CPU13
SYSMAC
CJ
CJ1G-CPU45
CJ1G-CPU44
CJ1G-CPU45H
CJ1G-CPU44H
CJ1G-CPU43H
CJ1G-CPU42H
CJ1M-CPU23
CJ1M-CPU22
CJ1M-CPU21
CJ1M-CPU13
CJ1M-CPU12
CJ1M-CPU11
CJ1H-CPU66H
CJ1H-CPU65H
CJ1W-SCU41
- 238 -
SYSMAC
CS
CS1G-CPU45
CS1G-CPU44
CS1G-CPU43
CS1G-CPU42
CS1G-CPU45H
CS1G-CPU44H
CS1G-CPU43H
CS1G-CPU42H
CS1G-CPU45-V1
CS1G-CPU44-V1
CS1G-CPU43-V1
CS1G-CPU42-V1
CS1H-CPU67
CS1H-CPU66
CS1H-CPU65
CS1H-CPU64
CS1H-CPU63
CS1H-CPU67H
CS1H-CPU66H
CS1H-CPU65H
CS1H-CPU64H
CS1H-CPU63H
CS1H-CPU67-V1
CS1H-CPU66-V1
CS1H-CPU65-V1
CS1H-CPU64-V1
CS1H-CPU63-V1
CS1W-SCU21
CS1W-SCB21
CS1W-SCB41
Network Communication
Series
CPU
CJ2M-CPU35
Link Module
EtherNet/IP port on CPU Unit
CJ1W-ETN21
SYSMAC
CJ/CS
CJ2M-CPU3*
CS1H
CS1G
SYSMAC C
CS1W-ETN21/EIP21
CJ1W-ETN21/EIP21
NJ*01
CP1L-EM
CP1L-EL
EtherNet/IP port on CPU Unit
CP1H
CP1L
OMRON CJ Series
Ethernet(TCP Slave)
CJ2H-***-EIP
SYSMAC NJ
Driver
CP1W-CIF41
CPU
Link Module
- 239 -
COMM Type
Parameter
Cable
CP1H
CP1L
CP1E
RS232
Setting
CP1W-CIF11/CIF12
RS485-4
Setting
CPM2AH
RS232
SYSMAC
CJ2
CJ2M-CPU13
RS232
Setting
RS232
Setting
SYSMAC CJ
CJ1G-CPU45
CJ1G-CPU44
CJ1G-CPU45H
CJ1G-CPU44H
CJ1G-CPU43H
CJ1G-CPU42H
CJ1M-CPU23
CJ1M-CPU22
CJ1M-CPU21
CJ1M-CPU13
CJ1M-CPU12
CJ1M-CPU11
CJ1H-CPU66H
CJ1H-CPU65H
RS232
Setting
RS232
Setting
RS485-4
Setting
RS232
Setting
Peripheral port on
the CPU unit*1
RS232
Setting
CS1W-SCU21
RS232
Setting
CS1W-SCB21
RS232
Setting
CS1W-SCB41
RS232
Setting
SYSMAC C
SYSMAC
CS
CS1G-CPU45
CS1G-CPU44
CS1G-CPU43
CS1G-CPU42
CS1G-CPU45H
CS1G-CPU44H
CS1G-CPU43H
CS1G-CPU42H
CS1G-CPU45-V1
CS1G-CPU44-V1
CS1G-CPU43-V1
CS1G-CPU42-V1
CS1H-CPU67
CS1H-CPU66
CS1H-CPU65
CS1H-CPU64
CS1H-CPU63
CP1W-CIF01
Peripheral port on
the CPU unit*1
CJ1W-SCU41
- 240 -
Setting
Setting
CS1H-CPU67H
CS1H-CPU66H
CS1H-CPU65H
CS1H-CPU64H
CS1H-CPU63H
CS1H-CPU67-V1
CS1H-CPU66-V1
CS1H-CPU65-V1
CS1H-CPU64-V1
CS1H-CPU63-V1
RS485-4
Setting
Parameter
Cable
CPU
CJ2M-CPU35
Link Module
EtherNet/IP port
on CPU Unit
Connect Type
Ethernet(TCP
Slave)
Setting
Setting
Setting
CJ1W-ETN21
SYSMAC
CJ/CS
CJ2M-CPU3*
CS1H
CS1G
EtherNet/IP port
on CPU Unit
CS1W-ETN21/EIP
21
CJ1W-ETN21/EIP
21
EthernetUDP
Slave
CJ2H-***-EIP
SYSMAC
NJ
SYSMAC
C
NJ*01
EtherNet/IP port
on CPU Unit
CP1L-EM
CP1L-EL
EtherNet/IP port
on CPU Unit
CP1H
CP1L
EtherNet/IP port
on CPU Unit
CP1W-CIF41
RS232 communication
- 241 -
EthernetUDP
Slave
RS422 communication
NOTEMake sure that the switch DIP1~6 of PLC must be OFF when using OMRON CP Series Host Link
protocol.
NO.
Setup contents
default status
OFF
OFF
OFF: OFF(default)
OFF
OFF
OFF
OFF
RS232 communication
RS422 communication
- 243 -
NOTE: Select custom communication parameters (non-standard communication parameters), the switch of
PLC must be OFF.
NOTE1.CJ1M switch DIP: SW1, SW2, SW3, SW5, SW8 must be off, but SW4, SW6, SW7 are optional.
2. CJ1M switches DIP 1~8 are OFF (default).
RS485-4 Default communication: 9600, 7, even, 2; station: 0
- 244 -
PLC Setting
1. Double-click the IO table and the unit set, find the Ethernet communication module
- 245 -
Attention HMI and PLC must be set in the same networkwhile the node ID should be different.
- 246 -
PLC Setting
Please use CX-Integrator to modify
1. Choose the right type to get the PLC and its software connected
2. Set the PLC into programming mode
3. Read the data and show the connected device
4. Double click the device to modify the related parameterfor example IP Address
- 247 -
2You can change the Node ID by the switch on the deviceNODE No.
- 248 -
PLC Setting
Type in IE the IP addressexhttp://192.168.11.33/C00.HTMand the passwordex:ETHERNETthen
you entry this interface.Later,you can modify the parameter.
Supported Device
- 249 -
Bit Address
Word Address
Format
Hold Relay
HR_bit 00.00-99.15
------
DD.DD
Data Relay
DM_bit 0000.00-6655.15
------
DDDD.DD
Link Relay
LR_bit 00.00-63.15
------
DD.DD
Auxiliary Relay
AR_bit 00.00-959.15
------
DD.DD
Channel I/O
CIO_IR_bit 000.00-511.15
------
DDD.DD
Counter Relay
------
CNT_word 000-511
DDD
Timer Relay
------
TIM_word 000-511
DDD
Hold Register
------
HR_word 00-99
DD
Data Register
------
DM_word 0000-6655
DDDD
Link Register
------
LR_word 00-63
DD
Auxiliary Register
------
AR_word 000-959
DDD
------
CIO_IR_word 000-511
DDD
Bit Address
Word Address
Format
Notes
Work Relay
W_bit 0.00-511.15
------
DDD.DD
Hold Relay
H_bit 0.00-1535.15
------
DDDD.DD
Data Relay
D_bit 0.00-32767.15
------
DDDDD.DD
Counter Relay
C flag 0.00-4095.15
------
DDDD.DD
Timer Relay
T flag 0.00-4095.15
------
DDDD.DD
Auxiliary Relay
A_bit 0.00-959.15
------
DDD.DD
Channel I/O
CIO_bit 0.00-6143.15
------
DDDD.DD
Work Register
------
W_word 0-511
DDD
Hold Register
------
H_word 0-1535
DDDD
Data Register
------
D_word 0-32767
DDDDD
Counter Register
------
C_word 0-4095
DDDD
Timer Register
------
T_word 0-4095
DDDD
Auxiliary Register
------
A_word 0-959
DDD
------
CIO_word 0-6143
DDDD
Bit Address
Word Address
Format
Hold Relay
HR 0.00-4095.15
------
DDDD.DD
Link Relay
LR 0.00-4095.15
------
DDDD.DD
Auxiliary Relay
AR 0.00-4095.15
------
DDDD.DD
Internal Relay
IR 0.00-4095.15
------
DDDD.DD
Timer/Counter Register
------
TC 0-255
DDD
Data Register
------
DM 0-9999
DDDD
Notes
Bit Address
- 250 -
Word Address
Format
Channel I/O
CIO 0000.00-6143.15
------
DDDD.DD
WR 000.00-511.15
------
DDD.DD
AR 000.00-959.15
------
DDD.DD
Latch Relay
HR 000.00-511.15
------
DDD.DD
TIM 0000-4095
------
DDDD
CNT 0000-4095
------
DDDD
Data Memory
DM 00000.00-32767.15
------
DDDDD.DD
E0 0.00-EC 32767.15
------
DDDDD.DD
------
E0 0-EC 32767
DDDDD
Channel I/O
------
CIO 0000-6143
DDDD
------
WR 000-511
DDD
------
AR 000-959
DDD
Latch Relay
------
HR 000-511
DDD
------
TIM 0000-4095
DDDD
------
CNT 0000-4095
DDDD
Data Memory
------
DM 00000-32767
DDDDD
Index Register
------
IR 00-15
DD
Data Register
------
DR 00-15
DD
Bit Address
Word Address
Format
Channel IO
CIO 0.00-6143.15
------
DDDD.DD
W 0.00-511.15
------
DDD.DD
A 0.0-959.15
------
DDD.DD
Latch Relay
H 0.0-511.15
------
DDD.DD
Timer Up Flag
T 0-4095
------
DDDD
Count Up Flag
C 0-4095
------
DDDD
TKB
TKB 0-31
------
DD
Channel IO
------
CIO 0-6142
DDDD
------
W 0-511
DDD
------
A 0-959
DDD
Latch Relay
------
H 0-511
DDD
------
T 0-4095
DDDD
------
C 0-4095
DDDD
------
E0-E18 0-32767
DDDDD
EM
------
EM 0-32767
DDDDD
Index Register
------
IR 0-15
DD
Data Register
------
DR 0-15
DD
Bit Address
Word Address
Format
CIO_bit
------
DDDD.DD
CIO_FORCE
------ 251 -
CIO_FORCE_RELEASE
------
CIO_RELEASE_STATUS
------
W_bit
------
W_FORCE
------
W_FORCE_RELEASE
------
W_RELEASE_STATUS
------
H_bit
------
H_FORCE
------
H_FORCE_RELEASE
------
H_RELEASE_STATUS
------
T_FLAG
------
T_FORCE
------
T_FORCE_RELEASE
------
T_RELEASE_STATUS
------
C_FLAG
------
C_FORCE
------
C_FORCE_RELEASE
------
C_RELEASE_STATUS
------
A 0.0-11535.15
------
DDDDD.DD
E0-9_bit
------
DDDDD.DD
EA-F_bit
------
DDDDD.DD
E10-18_bit
-------
DDDDD.DD
Data Memory
D_bit 0.00-32767.15
------
DDDDD.DD
TKB
TK_FLAG 0-127
------
DDD
Latch Relay
0.0-1535.15
Timer Up Flag
0-4095
Count Up Flag
0-4095
Special Auxiliary Relay
Extension Data Memory
0.00-32767.15
DDD.DD
DDDD.DD
DDDD
DDDD
Channel IO
------
CIO 0-6143
------
W 0-511
DDD
Latch Relay
------
H 0-1535
DDDD
------
T 0-4095
DDDD
------
C 0-4095
DDDD
------
A 0-11535
DDDDD
DDDDD
------
E0-E9 0-32767
EA-EF 0-32767
E10-E18 0-32767
EM 0-32767
Data Memory
------
D 0-32767
DDDDD
TK
------
TK0-127
DDD
Index Register
------
IR 0-15
DD
Data Register
------
DR 0-15
DD
DDDD
Bit Address
CIO_bit
- 252 -
Word Address
Format
------
DDDD.DD
0.00-6143.15
CIO_FORCE
------
CIO_FORCE_RELEASE
------
CIO_RELEASE_STATUS
------
W_bit
------
W_FORCE
------
W_FORCE_RELEASE
------
W_RELEASE_STATUS
------
H_bit
------
H_FORCE
------
H_FORCE_RELEASE
------
H_RELEASE_STATUS
------
T_FLAG
------
T_FORCE
------
T_FORCE_RELEASE
------
T_RELEASE_STATUS
------
C_FLAG
------
C_FORCE
------
C_FORCE_RELEASE
------
C_RELEASE_STATUS
------
A 0.0-959.15
------
DDDDD.DD
Data Memory
D_bit 0.00-32767.15
------
DDDDD.DD
TKB
TK_FLAG 0-31
------
DDD
Latch Relay
0.0-1535.15
Timer Up Flag
0-4095
Count Up Flag
0-4095
DDD.DD
DDDD.DD
DDDD
DDDD
Channel IO
------
CIO 0-6143
------
W 0-511
DDD
Latch Relay
------
H 0-1535
DDDD
------
T 0-4095
DDDD
------
C 0-4095
DDDD
------
A 0-959
DDDDD
Data Memory
------
D 00000-32767
DDDDD
TK
------
TK0-31
DDD
Index Register
------
IR 0-15
DD
Data Register
------
DR 0-15
DD
Cable Diagram
RS232 Communication Cable
1. RS232 on the CPU unit or CP1W-CIF01\CS1W-SCU21\CS1W-SCB21 etc. module
- 253 -
DDDD
2. CP1W-CIF11/CP1W-CIF12 module
NOTECP1W-CIF11 is without photoelectricity isolation, the maximum communication distance is 50
m. CP1W-CIF12 is with photoelectricity isolation, the maximum communication distance is 500 m. Other
parameters specification and DIP switch settings are the same.
DIP
1
CONTENT
ON
YesBoth sides
OFF
No
ON
2-wiresRS485
OFF
4-wiresRS422A
ON
2-wiresRS485
OFF
4-wiresRS422A
-----
-----
N/A
ON
With RS control
OFF
Without RS controlReceive
ON
With RS control
OFF
Without RS controlSend
2
3
- 254 -
NOTE: When PLC uses CP1W-CIF11 or CP1W-CIF12 module for communication, if it uses 1:1 and
RS422 communication, it need to set all the DIP Switch SW1~6 as OFF. If it uses 1:N and RS422
communication, it need to set DIP Switch SW1~5 as OFF and SW6 as ON.
NOTE: When PLC uses CP1W-CIF11 or CP1W-CIF12 module and RS485 communication, please make
sure the DIP Switch SW1 of CP1W-CIF11 or CP1W-CIF12 as OFF, and set SW2,SW3,SW5,SW6 as
ON.SW4 can be set as ON or OFF.
CPU
Link Module
E5EZ-R3
E5EZ-C3MT
Driver
Omron E5EZ-R3
System configuration
Series
CPU
Link Module
- 255 -
COMM Type
Parameter
Cable
OMRON
E5EZ-R3
OMRON
E5EZ-R3
RS485 on
CPU unit
the
RS485-2
Setting
Communication Setting
Default communication: 9600, 7, even, 2; station: 0
Supported Device
OMRON E5EZ-R3
Device
Bit Address
Word Address
Format
Notes
Variable
------
DDD.HH
1.0 1.2D
(C1)
2.0 2.5B
(C3)
Action Command
------
0-8
State
0-31
------
DD
Abnormal Input
------
command
content
00:OFFdisable
Communication write
Run/Stop
Multi-segment SP
01:ON enable
Notes
Before writing data, "Communication
write" command is "01 ON (enable)",
otherwise it writes disable
00Run
01Stop
00Setting value 0
01Setting value 1
- 256 -
02Setting value 2
cant write-in.
03Setting value 3
00stop
AT execute/stop
write-in mode
RAM storage
00
Soft reset
00
00
00
01AT execute
00save
01RAM
Make sure the setting value be the same as the plcs station No.
Must be the same as the station No. of HMI
Before writing data, "Communication write" command must is "01 ON (enable)", otherwise it
writes disable
Cable Diagram
RS485-2 communication cable
4.56 OPTO 22
Ethernet Communication (nonsupport Direct Online Simulation)
Series
CPU
Link Module
- 257 -
Driver
SNAP-UP1-ADS
OPTO 22
Ethernet
System configuration
Series
OPTO 22
CPU
Link Module
SNAP-UP1-ADS
Connect Type
Ethernet
Ethernet
Parameter
Setting
Cable
Your owner cable
Communication Setting
Supported Device
Device
Bit Address
Word Address
Format
Bit Table
B0-65535
DDDDD
Bit Table
BT0.000-65535.255
DDDDD.DDD
Integer 32
N32 0-65535
DDDDD
Float
FN0-65535
DDDDD
UP Timer
UTN0-65535
DDDDD
Down Timer
DTN0-65535
DDDDD
PID parameter
PIDSN0.00-32.06
DDDDD.DD
Integer 32 Table
NT0.000-65535.255
DDDDD.DDD
Float Table
FT0.000-65535.255
DDDDD.DDD
Double
FN
Float
DTN
Float
UTN
Float
PID
Input
Float
- 258 -
Type
SetPoint
Float
Output
Float
Gain
Float
Tune I
Float
Tune D
Float
Mode
Double
IN
BIT
QN
BIT
PIN
Float
PQN
Float
NT
Double
FT
Float
BT
NOTE
1 The configuration in OPTO 22 software must be the same as the configuration in EV5000
software
truee.g.: define Float in the OPTO 22 softwareF1
Select FN device in the EV5000 software, address: 1.
Communicate correctly
errore.g.: define Float in the OPTO 22 softwareF0001
Select FN device in the EV5000 software, address: 1.
Communicate error
2 PIDSN correspondence
If it set up PID1 in the OPTO 22 software, it can show the values of Input, SetPoint, Output, Gain,
Tune I, Tune D, and Mode.
In the Ev5000 software, PIDSN format DDDDD.DD, Address can be written in 1.**.( the main address
in front of decimal point corresponding to the OPTO 22 of PID1 1 ,sub-addr refer to the table. the table
as follows:
Sub AddressExample PID11 is sub address
Corresponding Value
1.00
Input
1.01
SetPoint
1.02
Output
1.03
Gain
1.04
Tune I
1.05
Tune D
1.06
Mode
Cable Diagram
Ethernet communication cable
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to 4.3 Download by Network Ethernet for method of making connection cable.
- 259 -
CPU
FP
FP
Link Module
Tool port on the Control unit
Driver
Panasonic FP
AFPG801
AFPG802
AFPG803
AFPG806
FP0
FP1
FP-M
FP2
FP2SH
FP3
FP-e
FP10SH
FP10S
FP-X
System configuration
Series
CPU
Link Module
COMM Type
Parameter
FP
AFPG801
FP
AFPG802
Setting
RS485(2 wire)
Setting
RS232C
Setting
RS232C
Setting
RS232C
Setting
AFPG806
AFPG803
AFPG806
FP0
Cable
FP1
FP-M
FP2
- 260 -
FP2SH
AFP2465
AFP2804
RS422(4 wire)
Setting
AFP2805
RS485(2 wire)
Setting
RS232C
Setting
AFP3463
RS422(4 wire)
Setting
RS232C
AFP3462
AFPE224300
FP-e
RS232C
AFPE214325
RS485(2 wire)
AFPE214322
FP-X
Setting
AFPE224305
AFPE224302
FP10SH
FP10S
Setting
Setting
RS232C
Setting
AFP3462
RS232C port on the Control unit
NOTE
1. Only FP0 (C10CRM/C10CRS/C14CRM/C14CRS/C16T/C16CP/C32CT/C32CP) has RS232C port.
2. Only FP1 (C24/C40/C56/C72) has RS232C port.
3. Only FP1(C20R/C20T/C32T)has RS232C port.
4. AFP245 is the communication Package of FP2/FP2SH. AFP2803, AFP2084 and AFP2085 are the
communications module of AFP2465.
Communication Setting
RS232 communication
RS485 communication
- 261 -
RS422 communication
Supported Device
FP Series
Device
Bit Address
Word Address
Format
Output Relay
X0.0~9999.F
------
DDDD.H
Input Relay
Y0.0~9999.F
------
DDDD.H
Timer
T0~9999
------
DDDD
Counter
C0~9999
------
DDDD
Link Relay
L0.0~32767.F
------
DDDDD.H
Internal Auxiliary/Relay
R0.0~32767.F
------
DDD.H
------
EV0~32767
DDDDD
------
SV0~9999
DDDD
Data Register
------
DT0~99999
DDDDD
Input Word
------
WX0~9999
DDDD
Output Word
------
WY0~9999
DDDD
Internal Auxiliary/Relay
------
WR0~32767
DDDDD
------
LD0~99999
DDDDD
- 262 -
Notes
Link Relay
------
WL0~32767
DDDDD
File Register
------
FL0~99999
DDDDD
NOTE
1. Example: X address: 01 in the PLC corresponds to 0.1 in the EV5000; X address: 1F in the PLC
corresponds to 1.F in the EV5000.Y\R register address, and so on.
2. EV registers in the range of addresses on the touch screen can be set to 32767, but only supports the
9999 agreement.
Cable Diagram
RS232 communication
Tool port:
CPU port:
COM port:
Communication module:
- 263 -
RS485 communication
RS422 communication
FP3 RS422 programming port:
CPU
Link Module
- 264 -
Driver
Parker Compax3
Parker Compax3
Compax3
SLVD 15NS
Parker 6k
6K4
Parker 6k
ACR9040
ACR9040-P3-B
Parker ACR9000
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
RS485-4
Setting
Parker
Compax3
Compax3
Parker SLVD
Series
SLVD
Series
RS485
Setting
Parker 6k
6K4
RS232
Setting
ACR9040
ACR904
0-P3-B
RS232
Setting
Communication Setting
Parker Compax3 protocol
HMI Setting
Default communication parameters: 115200, 8, none, 1; station: 1
RS232 Communication
RS485-2 Communication
- 265 -
PLC Setting
NOTE: RS-485 Settings can be made in the C3 Servo Manager under RS485 settings
RS485-2 setting:
RS485-4 setting:
- 266 -
Parker 6K protocol
Default communication parameters: 9600, 8, 1, none; station: 0
- 267 -
Supported Device
Parker Compax3
Device
Bit Address
Word Address
Format
R_Bit 0.0-9999999.31
------
DDDDDDD.DD
------
R_Float 0.0-9999.511
DDDD.DDD
------
R_Int 0.0-9999.511
DDDD.DDD
NOTE: R_Bit device is the bit format of R_Int device. The address of R_Bit device is DDDDDDD.DD,
the first seven position indicate the address of R_Int, the last two positon indicate 32-bit
SLVD Series
Device
Bit Address
Word Address
Format
Pr_Bit
0-9999.15
------
DDDD.DD
Pr_Byte
------
0-9999
DDDD
Pr_Word
------
0-9999
DDDD
Pr_DWord
------
0-9999
DDDD
Note
6k Series
Device
Bit in register
Bit Address
Word Address
Format
Notes
VARB_bit 1.00~125.31
------
DDD
Read only
KILL 0
------
S0
------
C0
------
PS 0
------
HALT 0
------
RUN 0
------ 268 -
TAS_Bit 1.01-2.32
------
TSS_Bit 1-32
------
TIN_Bit 1.01-3.32
------
TOUT_Bit 1.01-3.32
------
------
VARB 1~125
------
VAR_Int 1~225
------
VAR_Float 1~225
DDD
------
VAR 1~255
DDD
------
VARS 1~255
DDD
------
A 1~255
DDD
------
AD 1~255
DDD
------
V 1~255
DDD
------
DRIVE 1~255
DDD
------
TAS 1~2
------
TPC 1~255
DDD
------
TPE 1~255
DDD
------
TER 0
------
TSS 0
------
TIN 1~3
------
TOUT 1~3
DDD
Read only
DDDD
NOTE: VARB configuration software need to use hexadecimal data type, integer-bit to 8 bits.
ACR9000
Device
Bit Address
Word Address
Format
P_low16bit
0.0~99999.f
------
DDDDD.FF
P_high16bit
0.0~99999.f
------
DDDDD.FF
P_int32
------
0~99999
DDDDD
P_float
------
0~99999
DDDDD
Cable Diagram
Parker Compax3 Series
RS232 Communication Cable
Notes
Controller
RS485 terminal
com0/com1
1 RX6 RX+
4 Tx9 TX+
3 Tx7 Tx+
8 Rx2 Rx+
5 GND
5 GND
1 Enable
9 (+5V)
SLVD Series
RS485-2 Communication Cable
6k/9000 Series
RS232 Communication Cable
- 270 -
CPU
PC/104
PC/104
Link Module
Driver
PMAC series
System configuration
Series
CPU
PC/104
PC/104
Link Module
RS232 on the CPU unit
COMM Type
Parameter
RS232
Setting
Cable
Your owner cable
Communication Setting
HMI Setting
Default communication parameters: 38400bps, 8, none, 1; station: 0
Supported Device
Device
Bit Address
Word Address
Format
Notes
I variable
------
I 0-9999
DDDD
R/W
M variable
------
M 0-9999
DDDD
R/W
P variable
------
P 0-9999
DDDD
R/W
Q variable
------
Q 0-9999
DDDD
R/W
I variable
------
I_float 0-9999
DDDD
R/W
Float
------
P_float 0-9999
DDDD
R/W
Float
------
Q_float 0-9999
DDDD
R/W
------
POS 0
------
VEL 0
------
FER 0
------
ORD/JOG* 0-9999
DDDD
P variable
Q variable
Float
- 271 -
------
RUN 0-9999
DDDD
-----DDDD W
Halt program
HLT 0-9999
NOTESome addresses in I variable devices are on with hex number, when single float number on, all bits
which cant be transformed into hex numbers will be 0
Cable Diagram
RS232 Communication Cable
CPU
Link Module
- 272 -
Driver
AURORA
PVI-6000-OUTD-US-W
Aurora PV
System configuration
Series
AURO
RA
CPU
Link Module
PVI-6000-OUTD-US-W
COMM Type
Parameter
RS485
Setting
Cable
Your owner cable
Communication Setting
HMI Setting
Default communication parameters: 19200, 8, none, 1; station: 2
Supported Device
Device
Bit Address
Word Address
Format
------
Time 0-9999.7
DDDDD.0
------
Energy 0-9999.7
DDDDD.0
------
Measure 0-9999.7
DDDDD.0
------
Fireware 0-9999.7
DDDDD.0
------
Version 0-9999
DDDD
------
SN 0-9999
DDDD
------
PN 0-9999
DDDD
------
State 0-9999
DDDD
Cable Diagram
NOTE: AURORA Wind Inverter supports two connection modes, please refer to the manual of power-one
Corporation for details.
1. Connect with RS485 port
- 273 -
CPU
Link Module
PROFIBUS DP port
Driver
Profibus DP Slave
System configuration
Series
SIMATIC
S7-300/400
CPU
Link Module
Setting
PROFIBUS DP port
Setting
Communication Setting
HMI Setting
- 274 -
Parameter
SIP Type
Profibus
PLC Setting
NOTE: you can find kinco.gsd in the fieldbus file of EV5000 Installation Directory, or you can download
from www.kinco.cn.
1. Setup kinco.gsd file
Setup GSD file in the s7-300 software.
Process:
1. Closed all the station in HW Config
2.choose option > install GSD file.
3.Find out the folder of eview.gsd.
4.Choose eview.gsd, and then click the install button.
You can find the ico in PROFIBUS DP\MMI, after installing
2. configuration setting
(1) Make a new project in s7-300 through the guide
(2) We must use OB82OB86OB100OB121 and OB122 in BLOCK, or system will go wrong when PLC
is power-up.
(3) Double click HW Config, choose DP and right click add master station.
- 275 -
NOTE: the address No. of DP master station and slave can not be same.
(5) Input and output setting
- 276 -
(6) Profibus DP Slave has adaption functionyou can change the transmission rate of DP master station,
maximum is 12Mbps.
(7) Double click slave ico, then set User_Prm_Data (0) =01
- 277 -
Supported Device
Device
Bit Address
Word Address
Format
LW.B8500.0~8615.F
DDDD.H
LW.B8000.0~8115.F
Notes
DDDD.H
LW8500~8615
DDDD
correspond PIW
LW8000~8115
DDDD
correspond PQW
LW8500~8615(Data
width is dword)
DDDD
correspond PID
LW8000~8115(Data
width is dword)
DDDD
correspond PQD
NOTE: When use either PID or PQD, you must set User_Prm_Data (0) =1 if HMI communication with the
DP port of Siemens; Other company devices which support PROFIBUS DP Master, default
User_Prm_Data (0) =0.
Cable Diagram
A-type violet cable
Series
RF-IC
CPU
Link Module
RF-IC
Driver
RF-IC
System configuration
Series
RF-IC
CPU
RF-IC
Link Module
COMM Type
RS232
Parameter
Setting
Cable
Your owner cable
Communication Setting
Supported Device
Device
Bit Address
Word Address
Format
Bit
LB 8999
------
DDDD
------
LW 8900
DDDD
NOTE: LB8999 means bar code has received or not. LB8999=1 means data has received.
Cable Diagram
CPU
Link Module
Driver
RKC CH
CH402WK02-VV*AN-5N
CPU direct
RKC CH402
- 279 -
Notes
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
RKC
CH
CH402WK02-V
V*AN-5N
RS485
Setting
Communication Setting
HMI Setting
Default communication: 9600, 8, none, 1; station: 1
RS485 communication
PLC Setting
Press SET key and R/S key at one time,then press the SET key and select parameters:
Add
Address *1
bPS
Baudrate *2
bIT
data instruction *3
InT
transmission delay *4
*1: Two bits ASCII code. Example 23, instrument number must 23(32H 33H)
*2: Baudrate controlled by code as below; default value: 2
02400 bps
14800 bps
29600 bps
319200 bps
*3: data instruction controlled by code as below; default value: 0
ID
Data bit
parity
stop bit
0
8
none
1
1
8
none
2
2
7
odd
1
3
7
odd
2
- 280 -
4
5
7
7
even
even
1
2
Supported Device
Device
Bit Address
Word Address
Format
Notes
Alarm 1 status
AA: 0
------
Read only
Burnout
B1: 0
------
Read only
PID control/Autotuning
G1: 0
------
R/W
Alarm 2 status
AB: 0
------
Read only
RUN/STOP transfer
SR: 0
------
R/W
Self-tuning
G2:0
------
R/W
Measured value
------
M1: 0
Read only
------
M2: 0
Read only
------
M3: 0
Read only
Error code
------
ER: 0
Read only
Set value(SV1)
------
S1: 0
R/W
Alarm 1 setting
------
A1: 0
R/W
Alarm 2 setting
------
A2: 0
R/W
------
A3: 0
R/W
------
A4: 0
R/W
------
A5: 0
R/W
------
P1: 0
R/W
Integral time
------
I1: 0
R/W
Derivative time
------
D1: 0
R/W
Anti-reset windup
------
W1: 0
R/W
------
P2: 0
R/W
Overlap/deadband
------
V1: 0
R/W
------
T0: 0
R/W
------
T1: 0
R/W
PV bias
------
PB: 0
R/W
------
LK: 0
R/W
Cable Diagram
RS485 Communication Cable
4.64 Saia-Burgess
Serial Communication
Series
CPU
Link Module
PCS
PCS1.C8
PCD
PCD2.M110
PCD2.M120
PCD2.M150
PCD2.M170
PCD2.M480
Driver
Saia SBus
Systems Configuration
Series
CPU
PCS
PCS1.C8
PCD
PCD2.M110
Link Module
COMM Type
Parameter
RS232
Setting
RS485-4
Setting
RS232
Setting
Communication Setting
HMI Setting
Default communication: 9600, 8, none, 1; station: 80
RS232 communication
- 282 -
Cable
RS485 communication
Supported Device
Device
Bit Address
Word Address
Format
Input
I0-8091
------
DDDDD
Output
O0-8091
------
DDDDD
Flag
F0-8091
------
DDDD
Timer
------
T0-1599
DDDD
Counter
------
C0-1599
DDDD
Register
------
R0-4095
DDDD
------
R_Float0-4095
DDDD
Cable Diagram
PCS1.C8
RS232 communication cable
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1 com2
2 RX
7 RX
3 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
- 283 -
Notes
PCD2.M110
RS232 communication cable
CPU
Link Module
Driver
Swp-T16-80-08-N
Sailsors D9
System configuration
Series
CPU
Link Module
Sailsors D9
Swp-T16-80-08-N
COM Type
RS485
Communication Setting
HMI Setting
Default communication parameters: 9600, 8, none, 1; station: 80
RS485 communication
- 284 -
Parameter
Setting
Cable
Your owner cable
Supported Device
Device
Bit Address
Word Address
Format
------
CH 0~16
DD
Channel Indexing
------
SN 1~16
DD
Notes
Cable Diagram
RS485 communication cable
CPU
TSX3705001
TSX 37 05 028DR1
TSX 37 08 056DR1
TSX 37 10 128DT1
TSX 37 10 128DR1
TSX 37 10 128DTK1
TSX 37 10 164DTK1
TSX 37 10 028AR1
Link Module
- 285 -
Driver
TSX 37 10 028DR1
TSX 37 21 101
TSX 37 22 101
TSX 37 21 001
TSX 37 22 001
Premium
Nano
Twido
TSX 07 3L 28
TSX 07 30 10
TSX 07 31 16
TSX 07 31 24
TSX 07 32 28
TSX 07 33 28
System configuration
Series
CPU
Modicon
TSX
TSX3705001
TSX3705001
TSX 37 05 028DR1
TSX 37 08 056DR1
TSX 37 10 128DT1
TSX 37 10 128DR1
TSX 37 10 128DTK1
TSX 37 10 164DTK1
TSX 37 10 028AR1
TSX 37 10 028DR1
TSX 37 21 101
TSX 37 22 101
TSX 37 21 001
TSX 37 22 001
Link
Module
RS485 on
the CPU unit
Driver
Schneider
Modicon
Uni-TelWay
- 286 -
COMM
Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
TSX3705001
TSX3705001
TSX 37 05 028DR1
TSX 37 08 056DR1
TSX 37 10 128DT1
TSX 37 10 128DR1
TSX 37 10 128DTK1
TSX 37 10 164DTK1
TSX 37 10 028AR1
TSX 37 10 028DR1
TSX 37 21 101
TSX 37 22 101
TSX 37 21 001
TSX 37 22 001
Twido
RS485
on
the CPU unit
Modbus
RTU
RS232
Setting
RS485-2
Setting
RS232
Setting
RS485-2
Setting
Communication Setting
HMI Setting
Schneider Modicon Uni-TelWay protocol
Default communication9600, 8, odd, 1; station:1
RS232 communication
NOTE: Cable by Schneider Electric Industries, Rotary switch setting: 2(TER Direct)
RS485 communication
- 287 -
NOTE: Cable by Schneider Electric Industries, Rotary switch setting: 3(OTHER Direct)
RS485 communication
- 288 -
PLC Setting
PL7 software setting
1. Start menumodicum telemecanique XWAY Driver Manager to set communication parameter
4. And then click XWAY TestConnect, if the connection is successful, it will clue Connected
5. Open the PL7 softwareCreate new project click Hardware configurationdouble-click pop-up
window Comm
- 290 -
RS232 communication
- 291 -
RS485 communication
PLC Setting
1. Specify a large number for the internal word in the Controller Memory Use Edit and load the
configuration into the PLC to open the memory area for the words. If set the internal word 3000, you can
use address of MW before 3000.
- 292 -
2. You must program a coil with maximum address to open the memory area for the Bits. If you
program a coil with 127 addresses, then the address before 127 can be used.
Supported Device
Modicon TSX
Device
Bit Address
Word Address
Format
Internal Relay
S00000-32767
------
DDDDD
Auxiliary Relay
M00000-32767
------
DDDDD
MW.B0000-9999.F
------
DDDD.H
Data register
------
MW0000-7999
DDDD
------
MD0000-7999
DDDD
Notes
Twido
Device
Bit Address
Word Address
Format
Output Relay
0X 1-9999
------
DDDD
1X 1-9999
------
DDDD
------
3X 1-9999
DDDD
Notes
4X 1-9999
DDDD
Output Register
-----NOTE:
The M register in the software of TWIDO corresponds to 0X in the ev5000 software; MW corresponds
to 4X.The HMIs address must plus 1 to correspond with the address of PLC.
e.g.: M0 corresponds to 0X1.
Dont use 1X, 3X device, because there is no correspondence with the PLC.
Cable Diagram
Uni-TelWay protocol
RS232 communication cable
Cable recommended by Schneider Electric Industries, Rotary switch setting: 2(TER Direct)Add a direct
line
CPU
FP23
Link Module
FP23
Driver
SHIMADEN FP23
System configuration
Series
CPU
Link Module
COMM Type
Parameter
FP23
FP23
RS485
Setting
Communication Setting
Default communication parameters: 9600, 8, even, 1; station: 1
- 294 -
Cable
Your owner cable
Supported Device
Device
Bit Address
Word Address
Format
Ctrl_Write 184-252
------
HHH
------
------
Basic_Read 00-42
HH
OUT1_W,OUT2_W(Write Only)
------
Out_Write 0-1
PV1PV2Read Only
------
PV_Read 0-1
------
Reference 300-952
HHH
Parameter
R/W
Parameters mean
00H
PV_W
Read
Measurements
01H
SV_W
Read
Setting value
02H
OUT1_W
Read
Output1 value
03H
OUT2_W
Read
Output2 value
04H
EXE_FLG
Read
Execute_flagno execute=0
05H
EV_FLG
Read
06H
Reserve
Read
value:0000H
07H
EXE_PID
Read
Execute_PID No.
09H
HB_W
Read
0AH
HL_W
Read
0BH
DI_FLG
Read
DI status flag
10H
UNIT
Read
Measurement unit
11H
RANGE
Read
Measuring range
12H
CJ
Read
13H
DP
Read
- 295 -
14H
SC_L
Read
15H
SC_H
Read
16H
DPFLG
Read
0=show 1=cancel
20H
E_PRG
Read
21H
E_PTN
Read
22H
Reserve
Read
Reserve
23H
24H
E_RPT
Read
E_STP
Read
25H
E_TIM
Read
Step time
26H
E_PID
Read
29H
E_STPRPT
Read
Number of steps
42H
POSI
Read
Parameter
R/W
Parameters mean
184H
AT
write
18CH
COM
write
Parameter
R/W
300H
FIX_SV
R/W
Parameters mean
FIX mode SV: in the limit range of SV
R/W
PB21
ratio coefficient0.0 to 999.9(0.0=OFF)
460H
About device address details, please refer to the FP23 communication protocol.
Show: H indicates HEX
Note: 1Setting the parameters of ADDR address, the settings must be the same as the corresponding PLC
station.
2When Connecting multiple instruments, for distinguishing instruments, each instrument must be
set different ADDR value.
Cable Diagram
FP23 programmable PID regulator of 8 point and 10 point must be shorted or communications
failure
- 296 -
4.68 SIEMENS
Serial Communication
Series
CPU
Link Module
CPU212
CPU214
CPU215
CPU216
CPU221
CPU222
CPU224
CPU226
CPU224 XP CN
CPU226 XP CN
S7-200 SMART
CR40
SR20
S7-300
CPU312IFM
CPU313
CPU313C
CPU314
CPU314IFM
CPU315
CPU315-2 DP
CPU316
CPU316-2 DP
CPU318-2
S7-200
Driver
SIEMENS S7-200
SIEMENS
S7-300/400
Adapter Direct)
S7-400
CPU412-1
CPU412-2 DP
CPU412-3H
CPU413-1
CPU413-2 DP
CPU414-1
CPU414-2 DP
CPU414-3 DP
CPU416-1
CPU416-2 DP
CPU416-3 DP
CPU417-4
S7-300
CPU312IFM
CPU313
CPU313C
CPU314
SIEMENS
Direct) *1
- 297 -
S7-300/400
SIEMENS MPI*2
(PC
(MPI
CPU314IFM
CPU315
CPU315-2 DP
CPU316
CPU316-2 DP
CPU318-2
1. *1 :The protocol is suitable for the MT5020 series with MPI extended port. This
protocol supports multi HMI to multi PLC communication
2. *2 : The protocol is suitable for the MT4000 series HMI in 2013 November factory.
This protocol supports one HMI to one PLC communication
NOTE
CPU
Link Module
SIMATIC S7-200
CPU222
CPU224
CPU224 XP
CPU226
SMART S7-200
CR40
SR20
SIMATIC S7-1200
CPU1214C
CPU
CPU315-2DP
CP 343-1 IT
CP 343-1
SIMATIC S7-300
SIMATIC S7-400
CPU315-2 PN/DP
CPU317-2 PN/DP
CPU319-3 PN/DP
CP 243-1 IT
CP 243-1
CPU412-1
CPU412-2 DP
CPU412-3H
CPU413-1
CPU413-2 DP
CPU414-1
CPU414-2 DP
CPU414-3 DP
CPU416-1
CPU416-2 DP
CPU416-3 DP
CPU417-4
CPU414-3 PN/DP
CPU416-3 PN/DP
CP 443-1 IT
CP 443-1
CPU414-3 PN/DP
CPU416-3 PN/DP
Ethernet interface
on CPU
- 298 -
Driver
SIEMENS
S7-200
Ethernet (TCP Slave)
SIEMENS
S7-200
SMART Ethernet (TCP
Slave)
SIEMENS
S7-1200
Ethernet (TCP Slave)
SIEMENS
S7-300
Ethernet (TCP Slave)
SIEMENS
Ethernet
(TCP Slave)
S7-400
BUS Communication
Please refer to 4.59 Profibus DP Slave.
CPU
S7-200
CPU222
CPU224
CPU226
CPU224 XP CN
CPU226 XP CN
S7-200
SMART
CR40
SR20
S7-300
S7-400
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
RS485-2
Setting
CPU312IFM
CPU313
CPU313C
CPU314
CPU314IFM
CPU315
CPU315-2 DP
CPU316
CPU316-2 DP
CPU318-2
RS232
S7-300/400
(PC Adapter
Direct)
protocol
Setting
RS485
S7-300/400
(MPI Direct)
protocol
Setting
CPU412-1
CPU412-2 DP
CPU412-3H
CPU413-1
CPU413-2 DP
CPU414-1
CPU414-2 DP
CPU414-3 DP
CPU416-1
CPU416-2 DP
CPU416-3 DP
CPU417-4
RS485
SIEMENS
MPI protocol
Setting
RS232
S7-300/400
(PC Adapter
Direct)
protocol
Setting
RS485
S7-300/400
(MPI Direct)
protocol
Setting
Parameter
Cable
CPU
Link Module
- 299 -
Connect Type
SIMATIC S7-200
CPU222
CPU224
CPU224 XP
CPU226
CP 243-1 IT
CP 243-1
Ethernet
Setting
SIMATIC S7-200
SMART
CR40
SR20
Ethernet
interface
CPU
Ethernet
Setting
SIMATIC
S7-1200
CPU1214C
CPU
Ethernet
Setting
CPU315-2DP
CP 343-1 IT
CP 343-1
CPU315-2 PN/DP
CPU317-2 PN/DP
CPU319-3 PN/DP
Ethernet
interface
CPU
Ethernet
Setting
CPU412-3H
CP 443-1 IT
CP 443-1
Ethernet
Setting
SIMATIC S7-300
SIMATIC S7-400
on
on
RS485 communication
- 300 -
PLC Setting
- 301 -
NOTE:
1. If you use MT5-S7-300 adapter to communicate, the baudrate of PLC must be 187.5K, and HMI must be
19.2K
2. If we use PC adapter, PLC station No. is not necessary, so the communication is one-to-one.
3. DB block must be created, otherwise the relevant registers can not write (DB.DBX, DB.DBW, DB.DBD).
DBm.DBW, DBm.DBD address start must be an even number.
PLC Setting
1. Production of the adapter with KINCO, MPI transmission rate must be set 187.5K. 19.2K general users
of the transmission rate, if the S7-300 MPI-side transmission rate is 19.2K, you need to change it into the
Siemens adapter 187.5K (where changes in the hardware properties)
- 302 -
3. After the software change, downloaded to PLC, make sure the transmission rate of MPI is 187.5K, and
then in the options set PG / PC interface, select PC Adapter (MPI), MPI-side of the transfer rate will be
changed to 187.5K.
- 303 -
NOTE:
1. This protocol is suitable for MT5020 series with MPI extended port.
- 304 -
2. This protocol supports multi-station communication, and the MPI is RS485 port, so we can use this
protocol to communicate between many HMI and PLC, and then we must set the master station number.
3. HMI station No. can be 0~15, PLC station No. must be 0~15, the station No. of HMI and PLC can not be
the same number.
4. PLC baud rate can be 187.5K or 19.2K.
5. You must set DB first, or register cannot writeDB.DBX, DB.DBW, DB.DBD. The initial address of
DBm.DBW and DBm.DBD must be even number.
6. This protocol doesnt support direct simulation and indirect simulation.
PLC Setting
1. PLC station No. can be 0~15.
2. MPI baud rate can be 19.2k or 187.5k.
- 305 -
PLC setting
PLC station No. can be 2-15, MPI baud rate can be 19.2k or 187.5k
NOTE:
1. You should set DB block first, otherwise the registers as DB.DBX,DB.DBW and
DB.DBD cannot write.
2. This protocol supports one HMI to one PLC communication
- 306 -
PLC Setting
The settings for the CP 243-1 are defined in STEP 7 Micro/WIN via the Ethernet Wizard. For
assistance with all the information go to STEP 7 Micro/WIN Online Help via F1.
1. Starting the Ethernet Wizard
Open STEP 7 Micro/WIN
Start the Ethernet Wizard via Tools >Ethernet Wizard.
Click on Next
- 307 -
3. Specifying IP address
3.0 Define an IP address for the CP 243-1.
Caution:The IP address for this application may not be taken automatically from a server because the
panel requires a fixed reference partner (CP 243-1) for the Ethernet communication.
Note: The communication connection type for this module can be defined by the Automatic Setting.
4.0 Click on Next to continue.
- 308 -
5. Configuration connection
7.0 The configuration for connecting the CP 243-1 to the panel must be defined as in Fig..
8.0 Click OK to confirm the entries.
Warning: The TSAP must always be specified in four-digit format, with a leading zero (02.00).
- 309 -
7. Assigning memory
11.0 Specify a memory area for the configuration of the CP 243-1.
Recommend: If you click on Suggest address, the Wizard can identify a variable memory area.
Note: The register used in the panel must be out of the memory area for the configuration.
12.0 Click on Next.
- 310 -
9. Confirm message
13.0 Click Yes to confirm the message that appears.
- 311 -
PLC Setting
1. Modify the IP address
a. Setting IP in GeneralProfinet interface
b. After configuration, download device. Download in the first time, select the Extended download to
device, in the dialog to select show all accessible devices.
- 312 -
- 313 -
NOTE:
1. Make sure the data type of PLC same as the HMI when defining the data block. For example, if the data
type of PLC is REAL, then the data type of number input/display component must be float in HMI.
2. Make sure that the data block defined in PLC should be more than the data block used in HMI. For
example, if DB5.DBW32 is used in HMI, user cant define the data block up to DB5.DBW32, but up to
DB5.DBW34 or more.
PLC Setting
- 314 -
- 316 -
PLC Setting
1. In the hardware configuration, insert CP400 Ethernet module CP443-1
2. Open the Properties of CP443-1, set the IP address. No need to set MAC address.
Supported Device
S7-200
Device
Bit Address
Word Address
Format
S.B 0.0-31.7
------
DDD.O
SM.B 0.0-549.7
------
DDDD.O
Counter Relay
Cnt 0-255
------
DDD.O
Timer Relay
Tim 0-255
------
DDD.O
SCR
Special memory Relay
- 317 -
V Relay
V.B 0.0-10238.7
------
DDDDD.O
M.B 0.0-31.7
------
DDDDD.O
Q.B 0.0-15.7
------
DDDDD.O
I.B 0.0-15.7
------
DDDDD.O
AQW 0-62
DD
Analog Inputs
-----------
AIW 0-62
DD
------
SD 0-28
DD
SCR
------
SW 0-30
DD
------
SMD 0-546
DDD
Special memory
------
SMW 0-548
DDD
------
MD 0-28
DD
Internal memory
------
MW 0-30
DD
------
QD 0-12
DD
------
QW 0-14
DD
------
ID 0-12
DD
------
IW 0-14
DD
TimerCurrent Value
------
Cnt 0-255
DDD
CounterCurrent Value
------
Tim 0-255
DDD
------
VD 0-10236
DDDDD
V memory
NOTEVWVD address must be an even number
------
VW 0-10238
DDDDD
Analog Outputs
Bit Address
Word Address
Format
V.B 0.0-20479.7
------
DDDD.O
M.B 0.0-31.7
------
DD.O
Q.B 0.0-31.7
------
DD.O
I.B 0.0-31.7
SM.B 0.0-1535.7
-----------
DD.O
DDDD.O
S.B 0.0-31.7
------
DD.O
------
MD 0-28
DD
Internal memory
------
MW 0-30
DD
------
QD 0-28
DD
------
QW 0-30
DD
------
ID 0-28
DD
------
IW 0-30
DD
------
VD 0-20478
DDDD
V memory
------
VW 0-20476
DDDD
V Relay
SCR
- 318 -
Notes
Bit Address
Word Address
Format
Notes
I 0.0~511.7
------
DDDD.O
Q 0.0~511.7
------
DDDD.O
M 0.0~4095.7
------
DDDD.O
DBm.DBX
0~65535.7
------
DDDDD.O
m:10~60
------
DBm.DBW 0-65534
DDDDD
m:10~60
------
DBm.DBD 0-65532
DDDDD
m:10~60
Internal Relay
Internal Relay (32 bit)
------
MW 0~2046
DDDD
------
MD 0~2044
DDDD
------
QW 0~126
DDD
------
QD 0~124
DDD
------
IW 0~126
DDD
------
ID 0~124
DDD
NOTE:
1. The initial address of DBm.DBW and DBm.DBD must be even number.
2. Make sure that the data block defined in PLC should be more than the data block used in HMI. For
example, if DB5.DBW32 is used in HMI, user cant define the data block up to DB5.DBW32, but up to
DB5.DBW34 or more.
SIEMENS S7-300/400 (MPI Direct)
Device
Bit Address
Word Address
Format
Notes
I 0.0~255.7
------
DDDD.O
Q 0.0~255.7
------
DDDD.O
M 0.0~8191.7
------
DDDD.O
DBm.DBX 0.0~65533.7
------
DDDDD.O
m:1~60
DBn.DBX
100000.0~409665535.7
------
DDDDD.O
n:1~4096
Counter
------
C 0~2047
DDD
Timer
------
T 0~2047
DDD
Internal Relay
------
MW 0~8190
DDDD
------
QW 0~254
DDD
------
IW 0~254
DDD
Internal Relay
------
MD 0~8188
DDDD
------
QD 0~252
DDD
------
ID 0~252
DDD
------
DBm.DBW 0~65532
DDDDD
m:1~60
------
DBm.DBD 0~65532
DDDDD
m:1~60
- 319 -
*1
bit)
Data Register Relay
------
DBn_DBW
100000-409665534
DDDDDDDDD
n:1~4096
------
DBn_DBD
100000-409665532
DDDDDDDDD
n:1~4096
bit)
NOTE:
1. DBn_DBX, DBn_DBW, DBn_DBD is a custom block. First three data formats for data block number,
the address after the five, less than five former address zeros. To DB20.DBX23.4 example, EV5000
software addresses to DBn_DBX: 2000023.4
2. The initial address of DBm.DBW, DBm.DBD must be an even number.
3. *1 T/C registers are read only.
4. Make sure that the data block defined in PLC should be more than the data block used in HMI. For
example, if DB5.DBW32 is used in HMI, user cant define the data block up to DB5.DBW32, but up to
DB5.DBW34 or more.
SIEMENS S7-1200 Ethernet(TCP Slave)
Device
Bit Address
Word Address
Format
Notes
I 0.0~127.7
------
DDDD.O
Q 0.0~127.7
------
DDDD.O
M 0.0~2047.7
------
DDDD.O
DBn_DBX
100000.0~25565535.7
------
DDDDDDDD.O
DBm_DBX
0.0~65535.7
------
DDDDD.O
m:1~10
------
DBn_DBW
100000-25565534
DDDDDDDD
n:1~255
------
DBn_DBD
100000-25565532
DDDDDDDD
n:1~255
------
DBm_DBW
0-65534
DDDDD
------
DBm_DBD
0-65532
DDDDD
Internal Relay
Internal Relay (32 bit)
------
MW 0~2046
DDDD
------
MD 0~2044
DDDD
------
QW 0~126
DDD
------
QD 0~124
DDD
------
IW 0~126
DDD
------
ID 0~124
DDD
m:1~10
NOTE:
1. EV5000 in the DB register corresponds to the definition of S7-1200 software, the absolute address of DB,
rather than the global symbol DB.
- 320 -
2. DBn_DBX, DBn_DBW, DBn_DBD is a custom block. First three data formats for data block number,
the address after the five, less than five former address zeros. To DB20.DBX23.4 example, EV5000
software addresses to DBn_DBX: 2000023.4
3. The initial address of DBm.DBW, DBm.DBD must be an even number.
4. Make sure that the data block defined in PLC should be more than the data block used in HMI. For
example, if DB5.DBW32 is used in HMI, user cant define the data block up to DB5.DBW32, but up to
DB5.DBW34 or more.
SIEMENS S7-300 Ethernet(TCP Slave)
Device
Bit Address
Word Address
Format
Notes
I 0.0~2047.7
------
DDDD.O
Q 0.0~2047.7
------
DDDD.O
M 0.0~2047.7
------
DDDD.O
DBn_DBX
100000.0~25565535.7
------
DDDDDDDD.O
DBm_DBX
0.0~65535.7
------
DDDDD.O
m:1~10
------
DBn_DBW
100000-25565534
DDDDDDDD
n:1~255
------
DBn_DBD
100000-25565532
DDDDDDDD
n:1~255
------
DBm_DBW
0-65534
DDDDD
------
DBm_DBD
0-65532
DDDDD
Internal Relay
Internal Relay (32 bit)
------
MW 0~2046
DDDD
------
MD 0~2044
DDDD
------
QW 0~2046
DDD
------
QD 0~2044
DDD
------
IW 0~2046
DDD
------
ID 0~2044
DDD
m:1~10
NOTE:
1. DBn_DBX, DBn_DBW, DBn_DBD is a custom block. First three data formats for data block number,
the address after the five, less than five former address zeros. To DB20.DBX23.4 example, EV5000
software addresses to DBn_DBX: 2000023.4
2. The initial address of DBm.DBW, DBm.DBD must be an even number.
3. The data type of MB, IB, QB registers cant be set to signed int.
4. Make sure that the data block defined in PLC should be more than the data block used in HMI. For
example, if DB5.DBW32 is used in HMI, user cant define the data block up to DB5.DBW32, but up to
DB5.DBW34 or more.
SIEMENS S7-400 Ethernet(TCP Slave)
Device
Bit Address
Word Address
- 321 -
Format
Notes
I 0.0~255.7
------
DDD.O
Q 0.0~255.7
------
DDD.O
M 0.0~8191.7
------
DDDD.O
Data
Register
Relay
------
DDDDDDDD.O
node
Data
node
DBn_DBX
100000.0~25565535.7
Register
Relay
DBm_DBX
0.0~65535.7
------
DDDDD.O
------
DBn_DBW
100000-25565534
DDDDDDDD
------
DBn_DBD
100000-25565532
DDDDDDDD
------
DBm_DBW 0-65534
DDDDD
------
DBm_DBD 0-65532
DDDDD
m:1~10
m:1~10
bit)
Internal Relay
Internal Relay (32 bit)
------
MW 0~8190
DDDD
------
MD 0~8188
DDDD
------
QW 0~254
DDD
------
QD 0~252
DDD
------
IW 0~254
DDD
------
ID 0~252
DDD
NOTE:
1. DBn_DBX, DBn_DBW, DBn_DBD is a custom block. First three data formats for data block number,
the address after the five, less than five former address zeros. To DB20.DBX23.4 example, EV5000
software addresses to DBn_DBX: 2000023.4
2. The initial address of DBm.DBW, DBm.DBD must be an even number.
3. Make sure that the data block defined in PLC should be more than the data block used in HMI. For
example, if DB5.DBW32 is used in HMI, user cant define the data block up to DB5.DBW32, but up to
DB5.DBW34 or more.
Cable Diagram
SIEMENS S7-200 protocol
RS232 communication
Siemens models using standard serial PC / PPI cable . Cable Baud Rate DIP switch settings are as
follows:
1 ) with 5 DIP switch cable
- 322 -
Baud
SWITCH1=on
38400
000
19200
001
9600
010
4800
011
2400
100
1200
101
Baud
SWITCH1=on
115200
110
57600
111
38400
000
19200
001
9600
010
4800
011
2400
100
1200
101
Note: The switch 5 is set to 0 , the selected item Freeport;the switch 6,7,8 is set to 0.
- 323 -
PC / PPI cable on the baud rate DIP switch settings, you must set the baud rate with the PLC and
PC SET PG / PC Interface match the settings , Siemens S7-200 PLC baud rate can be programmed
via STEP7-Micro/WIN software settings.
RS485 communication
CPU
Link Module
Driver
Siko AG05
AG05
CPU
Link Module
COM Type
Parameter
Cable
Siko AG05
AG05
CPU Direct
RS485-2
Setting
Communication Setting
HMI Setting
Default parameter57600bps8none1station1
- 325 -
PLC Setting
Please reference to controller manual.
Supported Device
Device
Bit Address
Word Address
Format
Parameter No.
------
ID 0-FF
HH
SW
------
SW 0-0
CW
------
CW 0-0
Note
Notes
Cable Diagram
RS485-2
CPU
Link Module
Driver
SC1N
SC1N-30T-2AD2DA
Sinocon Sc1n
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
SC1N
SC1N-30T-2
AD2DA
RS232/RS485
Setting
Communication Setting
HMI setting
Default parameter9600bps7even1station1
RS232
- 326 -
RS485
Supported Device
Device
Bit Address
Word Address
Format
Input Relay
X 000-177
------
OOO
Output Relay
Y 000-177
------
OOO
Data Contact
D_bit 0.0-5998.F
------
DDDD.F
Internal Relay
M 0000-1535
------
DDDD
Timer Contact
T 000-255
------
DDD
Counter Contact
C 000-255
------
DDD
SM 8000-8255
------
DDDD
- 327 -
Notes
------
DDD
Timer Value
S 000-999
------
T_word 000-255
DDD
Counter Value
------
C_word 000-199
DDD
Data Register
------
D_word 0000-5998
DDDD
------
SD_word 8000-8255
DDDD
Counter Value
------
C_dword 200-255
DDD
State
32 bit device
Cable Diagram
RS232
RS485
HMI terminal
9pin D-SUB female/male
Controller
RS485 terminal
com0/com1
1 RX6 RX+
com2
1 B6 A+
5 GND
5 GND
4.71 TAIAN
Serial Communication
Series
CPU
Link Module
Taian
TOP3-30HR-A
Driver
Taian
System configuration
Series
CPU
Taian
TOP3-30HR-A
Link Module
COMM Type
Parameter
Cable
RS232
Setting
RS485
Setting
Communication Setting
HMI Setting
- 328 -
RS232 communication
RS485 communication
Supported Device
Device
Bit Address
Word Address
Format
X0-377
------
OOO
Output Relay
Y0-377
------
OOO
M0-7679& (8000-8511
------
DDDD
Step Relay
S0-4096
------
DDDD
Timer Relay
T0-511
------
DDD
Counter Relay
C0-255
DDD
Data Register
------
-----D0-8511
DDDD
Data Register
------
Z0-15
DD
Data Register
------
V0-15
DD
Timer(Current value
------
T_Current_Word 0-511
DDD
Auxiliary Relay
- 329 -
Counter(Current value
------
C_Current_Word 0-199
DDD
Counter
------
C_Current_Double 200-255
DDD
Timer(Preset value)
------
T_Preset_Word 0-511
DDD
Counter(Preset value)
------
C_Preset_Word 0-199
DDD
Counter
------
C_Preset_Double 200-255
DDD
NOTEZ, V is the turn of the write and read out. When testing a single word, max interval of word block
pack and max word block package size are changed to 1.
Cable Diagram
RS232 communication cable
4.72 TMCM_303
Serial Communication
Series
CPU
TMCM_303
Link Module
Driver
TMCM_303
System configuration
Series
TMCM_303
CPU
Link Module
COMM Type
Parameter
Cable
RS232
Setting
Communication Setting
HMI Setting
Default communication: 9600, 8, none, 1; station: 1
- 330 -
Supported Device
Please refer to TMCL Reference Manual for device details
TMCM_303
Device
Bit Address
Word Address
Format
Notes
ROR
------
0-2
Write Only
ROL
------
0-2
Write Only
MST
0-2
------
Write Only
MVP
------
0.0-2.7
DD.D
Write Only
SAP
0.008-0.013
1.008-1.013
2.008-2.013
0.0-2.213
DDDD.DDD
Write Only
GAP
0.008-0.013
1.008-1.013
2.008-2.013
0.0-2.213
DDDD.DDD
Read Only
STAP
0.0-2.213
------
DDDD.DDD
Write Only
RSAP
0.0-2.213
------
DDDD.DDD
Write Only
0.077
0.129
0.0-0.038
0.64-0.81
0.128-0.132
1.0-1.11
2.0-2.19
DDDD.DDD
Write Only
GGP
0.077
0.129
0.0-0.038
0.64-0.81
0.128-0.132
1.0-1.11
2.0-2.19
DDDD.DDD
Read Only
RFS
------
DWord 0.0-2.2
DD.D
Write Only
SIO
0-7
------
Write Only
SGP
- 331 -
GIO
0.0-0.10
2.0-2.07
1.0-1.7
DDD.DD
Read Only
CALC
------
0-9
Write Only
COMP
------
Write Only
JC
------
0-9
DD
Write Only
JA
------
Write Only
CSUB
------
Write Only
RSUB
------
Write Only
WAIT
------
0.0-4.7
DD.D
Write Only
STOP
------
Write Only
Cable Diagram
RS232 Communication Cable
CPU
Link Module
Driver
THINGET XC
XC3-32R-E
MODBUS RTU
THINGET Controller
System configuration
Series
Link Module
COM Type
Parameter
Cable
THINGET XC
RS232
Setting
Communication Setting
THINGET Controller protocol
HMI Setting
Default communication: 19200, 8, even, 1; station: 1
- 332 -
Supported Device
Device
Bit Address
Word Address
Format
Internal Relay
M0~M7999
------
DDDDD
Input Relay
X0.0~X51.1
------
OOOOOO.O
Output Relay
Y0.0~Y51.1
------
OOOOOO.O
State Relay
S0~S1023
------
DDDDD
Special Relay
M8000~M8511
------
DDDDD
Timer Relay
T0~T618
------
DDDDD
Counter Relay
C0~C634
------
DDDDD
Data register
------
D0~D7999
DDDDD
Timer
------
TD0~TD618
DDDDD
Counter
------
CD0~CD634
DDDDD
------
D8000~D8511
DDDDD
FlashROM Register
------
FD0~FD5000
DDDDD
------
FD8000~FD8511
DDDDD
Notes
NOTE
1. O indicates OCT, D indicates HEX.
2. Example: X\Y address: 1 in the controller corresponds with 0.1 in the HMIWare; X\Y address: 17 in the
controller correspond with 1.7 in the HMIWare.
MODBUS addrDecimal K
M0~M7999
0X 1~0X 8000
X0~X511
0X 16385~0X 16714
Y0~Y511
0X 18433~0X 18762
- 333 -
S0~S1023
0X 20481~0X 21504
M8000~M8511
0X 24577~0X 25088
T0~T618
0X 25601~0X 26219
C0~C634
0X 27649~0X 28283
words Addr
MODBUS addrDecimal K
D0~D7999
4X 1~4X8000
TD0~TD618
4X 12289~4X12907
CD0~CD634
4X 14337~4X 14971
D8000~D8511
4X 16385~4X 16896
FD0~FD1535
4X 18433~4X19968
FD8000~FD8511
4X 26625~4X 27136
Register Area
Cable Diagram
RS232 Communication
RS485 Communication
CPU
D3CellTM
D3CellTM
Link Module
RS422 on the CPU unit
Driver
DLoadCell
System configuration
Series
CPU
Link Module
COMM Type
- 334 -
Parameter
Cable
D3CellTM
D3CellTM
RS422
Setting
Supported Device
For detailed device, please refer to the PLC manual.
Communication Setting
Cable Diagram
RS485 Communication Cable
4.75 Toshiba
Network Communication
Series
CPU
Link Module
Driver
V30
TCXMAIN1
V-series
S2PU72A
CPU
Connect Type
Parameter
Cable
TCXMAIN1
Ethernet
Setting
S2PU72A
Ethernet
Setting
- 335 -
S2PU72A
PLC setting
- 336 -
Please refer to the communication equipment related documentation to set the parameter
Supported Device
TCXMAIN1
Device
Bit Address
Word Address
Format
0x00000000-0x0000FFFF
R00_B 0.00-FFFF.1F
------
HHHH.HH
0x01000000-0x0100FFFF
R01_B 0.00-FFFF.1F
------
HHHH.HH
0x02000000-0x02000FFF
R02_B 0.00-FFF.1F
------
HHH.HH
0x03000000-0x03000FFF
R03_B 0.00-FFF.1F
------
HHH.HH
0x04000000-0x04000FFF
R04_B 0.00-FFF.1F
------
HHH.HH
0x05000000-0x05000FFF
R05_B 0.00-FFF.1F
------
HHH.HH
0x06000000-0x06000FFF
R06_B 0.00-FFF.1F
------
HHH.HH
0x07000000-0x07000FFF
R07_B 0.00-FFF.1F
------
HHH.HH
0x08000000-0x0800FFFF
R08_B 0.00-FFFF.1F
------
HHHH.HH
0x09000000-0x09000FFF
R09_B 0.00-FFF.1F
------
HHH.HH
0x0A000000-0x0A000FFF
R0A_B 0.00-FFF.1F
------
HHH.HH
0x0B000000-0x0B00FFFF
R0B_B 0.00-FFFF.1F
------
HHHH.HH
0x0C000000-0x0C00FFFF
R0C_B 0.00-FFFF.1F
------
HHHH.HH
0x0D000000-0x0D000FFF
R0D_B 0.00-FFF.1F
------
HHH.HH
0x0E000000-0x0E000FFF
R0E_B 0.00-FFF.1F
------
HHH.HH
0x0F000000-0x0F000FFF
R0F_B 0.00-FFF.1F
------
HHH.HH
0x10000000-0x10000FFF
R10_B 0.00-FFF.1F
------
HHH.HH
0x11000000-0x11000FFF
R11_B 0.00-FFF.1F
------
HHH.HH
0x12000000-0x1200FFFF
R12_B 0.00-FFFF.1F
------
HHHH.HH
0x13000000-0x13000FFF
R13_B 0.00-FFF.1F
------
HHH.HH
0x14000000-0x14000FFF
R14_B 0.00-FFF.1F
------
HHH.HH
0x15000000-0x15000FFF
R15_B 0.00-FFF.1F
------
HHH.HH
0x17000000-0x17007FFF
R17_B 0.00-7FFF.1F
------
HHHH.HH
0x41000000-0x4100FFFF
R41_B 0.00-FFFF.1F
------
HHHH.HH
0x51000000-0x5100FFFF
R51_B 0.00-FFFF.1F
------
HHHH.HH
0x52000000-0x520000FF
R52_B 0.00-FF.1F
------
HH.HH
0x61000000-0x6107FFFF
R61_B 0.00-7FFF.1F
------
HHHH.HH
0x62000000-0x62003FFF
R62_B 0.00-3FFF.1F
------
HHHH.HH
0x63000000-0x63003FFF
R63_B 0.00-3FFF.1F
------
HHHH.HH
0x64000000-0x64003FFF
R64_B 0.00-3FFF.1F
------
HHHH.HH
0x65000000-0x65003FFF
R65_B 0.00-3FFF.1F
------
HHHH.HH
0x66000000-0x66003FFF
R66_B 0.00-3FFF.1F
------
HHHH.HH
0x67000000-0x67003FFF
R67_B 0.00-3FFF.1F
------
HHHH.HH
0x68000000-0x68003FFF
R68_B 0.00-3FFF.1F
------
HHHH.HH
0x69000000-0x69003FFF
R69_B 0.00-3FFF.1F
------
HHHH.HH
0x6A000000-0x6A003FFF
R6A_B 0.00-3FFF.1F
------
HHHH.HH
0x6B000000-0x6B003FFF
R6B_B 0.00-3FFF.1F
------
HHHH.HH
- 337 -
0x6C000000-0x6C003FFF
R6C_B 0.00-3FFF.1F
------
HHHH.HH
0x6D000000-0x6D003FFF
R6D_B 0.00-3FFF.1F
------
HHHH.HH
0x6E000000-0x6E003FFF
R6E_B 0.00-3FFF.1F
------
HHHH.HH
0x6F000000-0x6F000FFF
R6F_B 0.00-FFF.1F
------
HHH.HH
0x00000000-0x0000FFFF
------
R00 0-FFFF
HHHH
0x01000000-0x0100FFFF
------
R01 0-FFFF
HHHH
0x02000000-0x02000FFF
------
R02 0-FFF
HHH
0x03000000-0x03000FFF
------
R03 0-FFF
HHH
0x04000000-0x04000FFF
------
R04 0-FFF
HHH
0x05000000-0x05000FFF
------
R05 0-FFF
HHH
0x06000000-0x06000FFF
------
R06 0-FFF
HHH
0x07000000-0x07000FFF
------
R07 0-FFF
HHH
0x08000000-0x0800FFFF
------
R08 0-FFFF
HHHH
0x09000000-0x09000FFF
------
R09 0-FFF
HHH
0x0A000000-0x0A000FFF
------
R0A 0-FFF
HHH
0x0B000000-0x0B00FFFF
------
R0B 0-FFFF
HHHH
0x0C000000-0x0C00FFFF
------
R0C 0-FFFF
HHHH
0x0D000000-0x0D000FFF
------
R0D 0-FFF
HHH
0x0E000000-0x0E000FFF
------
R0E 0-FFF
HHH
0x0F000000-0x0F000FFF
------
R0F 0-FFF
HHH
0x10000000-0x10000FFF
------
R10 0-FFF
HHH
0x11000000-0x11000FFF
------
R11 0-FFF
HHH
0x12000000-0x1200FFFF
------
R12 0-FFFF
HHHH
0x13000000-0x13000FFF
------
R13 0-FFF
HHH
0x14000000-0x14000FFF
------
R14 0-FFF
HHH
0x15000000-0x15000FFF
------
R15 0-FFF
HHH
0x17000000-0x17007FFF
------
R17 0-7FFF
HHHH
0x41000000-0x4100FFFF
------
R41 0-FFFF
HHHH
0x51000000-0x5100FFFF
------
R51 0-FFFF
HHHH
0x52000000-0x520000FF
------
R52 0-FF
HH
0x61000000-0x6107FFFF
------
R61 0-7FFF
HHHH
0x62000000-0x62003FFF
------
R62 0-3FFF
HHHH
0x63000000-0x63003FFF
------
R63 0-3FFF
HHHH
0x64000000-0x64003FFF
------
R64 0-3FFF
HHHH
0x65000000-0x65003FFF
------
R65 0-3FFF
HHHH
0x66000000-0x66003FFF
------
R66 0-3FFF
HHHH
0x67000000-0x67003FFF
------
R67 0-3FFF
HHHH
0x68000000-0x68003FFF
------
R68 0-3FFF
HHHH
0x69000000-0x69003FFF
------
R69 0-3FFF
HHHH
- 338 -
0x6A000000-0x6A003FFF
------
R6A 0-3FFF
HHHH
0x6B000000-0x6B003FFF
------
R6B 0-3FFF
HHHH
0x6C000000-0x6C003FFF
------
R6C 0-3FFF
HHHH
0x6D000000-0x6D003FFF
------
R6D 0-3FFF
HHHH
0x6E000000-0x6E003FFF
------
R6E 0-3FFF
HHHH
0x6F000000-0x6F000FFF
------
R6F 0-FFF
HHH
S2PU72A
Device
Bit Address
Word Address
Format
XX
0.0-3071.F
------
DDDD.F
RR
0.0-4095.F
------
DDDD.F
SS
0.0-511.F
------
DDD.F
X_WORD
------
0-3071
DDDD
R_WORD
------
0-4095
DDDD
S_WORD
------
0-511
DDD
Cable Diagram
Refer to 4.3 Download by Network Ethernet
CPU
Link Module
Driver
Euro
Euro 205x
TRIO
Modbus RTU Extend
System configuration
Series
CPU
TRIO
Euro 205x
Modbus
RTU Extend
Euro 205x
Link Module
COMM
Type
Parameter
Cable
RS232
Setting
RS485-4
Setting
RS232
Setting
RS485-4
Setting
Communication Setting
TRIO protocol
HMI Setting
Default communication: 9600, 7, even, 2; station: 1
RS232 communication
- 339 -
RS485-4 communication
PLC Setting
Select the HOST LINK protocol in the PLC program software
1. Define HOST LINK slave node
HLS_NODE=1
2. Define HOST LINK slave model
HLS_MODEL=$FA
3. Set up HOST LINK slave for port2.
- 340 -
RS485-4 communication
RS232 communication
RS485-4 communication
PLC Setting
Modbus Protocol
- 341 -
ADDRESS=1
SETCOM9600,8,1,2,1,4
Supported Device
TRIO
Device
Bit Address
Word Address
Format
IR 0.0-4095.15
----------
DDDD.DD
Link Relay
LR 0.0-4095.15
----------
DDDD.DD
Assistant Relay
AR 0.0-4095.15
----------
DDDD.DD
Holding Relay
HR 0.0-4095.15
----------
DDDD.DD
Data Memory
----------
DM 0-30000
DDDDD
Timer/Counter
----------
TC 0-255
DDD
Notes
NOTE Address correspondence: IRn.m-->the m Trio VR (n); DMn->Table (n). Example IR1.02
corresponds to the 2nd bit of VR1.
Bit Address
Word Address
Format
4X_bit 0.0-1023.15
----------
DDDD.DD
Data register
----------
4X 0-1023
DDDDD
Notes
NOTEAddress correspondence: 4x corresponds to VR; 4x_bit corresponds to VRs bit. Address difference
between one position, e.g. 4x (501) corresponds to VR (500); 4x_bit (67.1) corresponds to the first bit of
VR (66).
Cable Diagram
NOTE: In the controller, A port is programming port, B port is communication port
Programming Cable
4.77 Unitronics
Serial Communication
Series
CPU
Link Module
Vision 130
V130-33-B1
Driver
Unitronics
Network Communication
Series
Vision 130
CPU
V130-33-B1
Link Module
Driver
CPU
Vision 130
V130-33-B1
Link Module
COM Type
Parameter
Cable
RS232
Setting
RS485-2
Setting
CPU
Link Module
Vision 130
V130-33-B1
Connect Type
Parameter
Ethernet
Setting
- 343 -
Cable
Your owner cable
PLC Setting
1. COM Initialize in the program software by RS485 communication.
- 344 -
- 345 -
Supported Device
Device
Bit Address
Word Address
Format
Notes
Inputs
I 0~999
------
DDD
Read only
Outputs
O 0~999
------
DDD
Memory Bits
MB 0~8191
------
DDDD
System Bits
SB 0~999
------
DDD
Timers
T 0~383
------
DDD
Read only
Counters
C 0~31
------
DD
Read only
Memory Integer
------
MI 0~4095
DDDD
Memory Longer
------
ML 0~511
DDD
Double Word
------
DW 0~255
DDD
Memory Float
------
MF 0~63
DD
System Integer
------
SI 0~999
DDD
System Longer
------
SL 0~199
DDD
------
SDW 0~199
DDD
Timers Preset
------
T_C 0~383
DDD
Read only
Timers Current
------
T_P 0~383
DDD
Read only
Counters Preset
------
C_C 0~31
DD
Read only
Counters Current
------
C_P 0~31
DD
Read only
Cable Diagram
RS232 communication cable
- 346 -
CPU
Link Module
Driver
System configuration
Series
CPU
Link Module
COM Type
Parameter
Cable
Universal ASCII
Slave
Universal ASCII
Slave
RS232 on the
CPU unit
RS232
Setting
Communication Setting
HMI Setting
Default communication: 57600, 8, 1, none; station: 1
Supported Device
- 347 -
Device
Bit Address
Word Address
Format
send
LB 0
------
clear
LB1
------
------
LW 0~99
DD
------
LW 100~199
DDD
send
LB2
------
clear
LB3
------
------
LW 200~299
DD
------
LW 300~399
DDD
send
LB 4
------
clear
LB5
------
------
LW400~499
DD
------
LW 500~599
DDD
Notes
Correspond to
COM0
Correspond to
COM1
Correspond to
COM2
Cable Diagram
RS232 communication cable
CPU
Link Module
Driver
VH
VH-14MR
VB0
VB0-14MR
Vigor
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
VH
VH-14MR
RS232
Setting
VB0
VB0-14MR
RS232
Setting
Communication Setting
Default communication: 19200, 7, even, 1; station: 0
- 348 -
Supported Device
Device
Bit Address
Word Address
Format
Input Relay
X 0-255
------
OOO
Output Relay
Y 0-255
------
OOO
Internal Relay
M 0-5119
------
DDDD
Special Relay
SM 9000-9255
------
DDDD
Timer Relay
T_bit 0-255
------
DDD
Counter Relay
C_bit 0-255
------
DDD
Timer
------
T_word 0-255
DDD
Counter
------
C_word 0-199
DDD
------
C_dword 200-255
DDD
Data Register
------
D 0-8191
DDDD
------
SD 90009255
DDDD
Cable Diagram
VH-14MR RS232 communication cable
1. Communication via USB programming port
Connection with HMI by programming cable of Vigor
Notes
CPU
Link Module
Driver
XiLin
EH600
XiLin EH600
System configuration
Series
CPU
Link Module
COM Type
Parameter
Cable
XiLin
EH600
RS485-2
Setting
Communication Setting
HMI Setting
Default Communication: 9600, 8, even, 1; station: 1
Supported Device
Device
Bit Address
Word Address
Format
------
Addr
HHHH
A FWD
------
A0
B REV
------
B0
- 350 -
Notes
C FJOG
------
C0
D RJOG
------
D0
E Free halt
------
E0
F Slow down
------
F0
G Reset failures
------
G0
PLC Setting
Please refer to XILIN frequency converter manual for details about device address.
Cable Diagram
CPU
Link Module
DCP30
P30A2
SDC35/36
C352
C354
C362
C364
DMC
DMC10D
DMC10S
Driver
Yamatake DCP30
Yamatake SDC/DMC
RS485 on the CPU unit
System configuration
Series
CPU
Link Module
COMM Type
Parameter
Cable
DCP30
P30A2
RS485
Setting
Your owner
cable
SDC35/36
C352
C354
C362
C364
RS485
Setting
Your owner
cable
DMC
DMC10D
RS485
Setting
DMC10S
Communication Setting
- 351 -
Your owner
cable
HMI Setting
Yamatake DCP30 protocol
Default communication: 9600, 8, even, 1; station: 1
DMC
Default communication: 19200, 8, even, 1; station: 6
- 352 -
PLC Setting
1. Set modbus RTU in the SLP-D10, and then download.
Supported Device
DCP30
Device
Bit Address
Format
RUN Status
------
1-26
DDD
PARA
------
1-33
DDD
EU
------
1-13
DDD
PID
------
1-80
DDD
SET
------
1-99
DDD
TBL
------
1-22
DDD
CNST
------
1-26
DDD
FO_R
1-19
------
DDD
FO_W
1-19
------
DDD
FC
1-19
------
DDD
FD
1-19
------
DDD
FBR1_R
------
1.0-30.22
DDD.DD
- 353 -
Notes
FBR2_R
------
1.0-30.22
DDD.DD
FBR3_R
------
1.0-30.22
DDD.DD
FBR4_R
------
1.0-30.22
DDD.DD
FBR5_R
------
1.0-30.22
DDD.DD
FBR6_R
------
1.0-30.22
DDD.DD
FBR7_R
------
1.0-30.22
DDD.DD
FBR8_R
------
1.0-30.22
DDD.DD
FBR9_R
------
1.0-30.22
DDD.DD
FBR10_R
------
1.0-30.22
DDD.DD
FBR11_R
------
1.0-30.22
DDD.DD
FBR12_R
------
1.0-30.22
DDD.DD
FBR13_R
------
1.0-30.22
DDD.DD
FBR14_R
------
1.0-30.22
DDD.DD
FBR15_R
------
1.0-30.22
DDD.DD
FBR16_R
------
1.0-30.22
DDD.DD
FBR17_R
------
1.0-30.22
DDD.DD
FBR18_R
------
1.0-30.22
DDD.DD
FBR19_R
------
1.0-30.22
DDD.DD
- 354 -
Parameter
Sub Addr
Parameter
.0
SP
.12
T2 2nd
.1
TM
.13
T3 1st
.2
NoneSkip
.14
T3 2nd
.3
EV1
.15
T4 1st
.4
Blank
.16
T4 2nd
.5
EV2
.17
T5 1st
.6
Blank
.18
T5 2nd
.7
EV3
.19
PID
.8
Blank
.20
NoneSkip
.9
T1 1st
.21
9.5.
.10
T1 2nd
.22
9.5.to
.11
T2 1st
Bit Address
Word Address
Format
Notes
Data Register
4X 0-65535
DDDDD
DMCPlease refer to the manual of DMC-SPL for details, in 10-8 communication parameters
Device
Bit Address
Word Address
Format
Data Register
4X 1002-65535
DDDDD
Cable Diagram
DCP 30 series
RS485 communication cable
- 355 -
Notes
Address add 1 to the
communication parameters
list
of
HMI terminal
9pin D-SUB female/male
Commutator terminal
9 pin D-SUB male
com0/com1 com2
2 RX
7 RX
2 TX
3 TX
8 TX
3 RX
5 GND
5 GND
5 GND
SDC36 series
RS485 communication cable
DMC series
RS485 communication cable
CPU
Link Module
Driver
VInverter
CIMR-JT
2A0001B
AA
MPMotion Controller
MP2200
MP2300
MP2310
MP2300S
Yaskawa MP2300
- 356 -
SGDM
/ PlusServo Controller
SGDV
Yaskawa SGDM
Yaskawa SGDV
CPU
MP series
MP2400
Link Module
ETH on the CPU unit
Driver
Yaskawa Ethernet(UDP Slave)
CPU
CIMR-JT2A
0001BAA
RS485-2
Setting
MP2300
RS232
Setting
RS232
Setting
RS485-4
Setting
RS232
Setting
RS485-4
Setting
Parameter
Cable
MP
/
Plus
SGDM
SGDV
Link Module
COM Type
Parameter
Cable
CPU
MP2400
Link Module
COMM Type
ETH
Setting
PLC Setting
20.0 change the inverter panel button up or down, adjustment to the parameter mode
21.0 then adjust to H5-01 by the button up or downaccording to the required parameter set
No.
Name
Scope
- 357 -
Parameter description
Setting
H5-01
Secondary station
address
0~FFH
Secondary station
number
1F
H5-02
0~5
01200bps
12400bps
24800bps
39600bps
419200bps
538400bps
H5-03
0~2
0no check
1even check
2odd check
RS232 communication
- 358 -
RS485-4 communication
PLC Setting
Related parameters Settings refer to the communication equipment description
HMI Setting
Default communication: 19200, 8, even, 1; station: 0
RS485-4 communication
- 359 -
NOTE: Station No. is a decimal number corresponding to axis address of servo controller.
PLC Setting
- 360 -
NOTE
1. axis address 0020H is the station number of PLChere is hexadecimalHMI is the decimal system;
2.if you change the axis address, Parameters will be displayed unless you restart
- 361 -
PLC Setting
1. Set the IPconnect with the MPE720 software
- 362 -
- 363 -
Supported Device
V inverter
Device
Bit Address
Word Address
Format
0X1-65535
------
DDDDD
1X1-65535
------
DDDDD
------
3X1-65535
DDDDD
data register
------
4X1-65535
DDDDD
Notes
NOTE:
1 this drive can not provide write batch of word part;
2 Address correspondence: MEMOBUS+1=4X
Eg: b1-01requency instruction selectionMEMOBUS register address is 080 H;the corresponding
screen is 4X 385
MP2300
Device
Bit Address
Word Address
Format
Coil
MB0.0-4095.F
------
DDDD.H
Input Relay
IB 0.0-FFF.F
------
HHHH.H
Hold Register
------
MW 0-65534
DDDDD
Input Register
------
IW 0-7FFF
HHHH
Notes
Bit Address
Word Address
Format
------
Pn000 Pn003
HHH
------
Pn100 Pn118
HHH
------
Pn200 Pn205
HHH
------
Pn300 Pn308
HHH
------
Pn400 Pn407
HHH
Sequence Reference
------
Pn500 Pn510
HHH
Other
------
Pn600 Pn601
HHH
Monitor mode
------
Un000 Un00D
HHH
- 364 -
Notes
SGDV
Device
Bit Address
Function
Selection
------------
Word Address
Format
Pn000~Pn002&Pn006~Pn009
HHH
Gain
------------
Pn121~Pn125&Pn131~Pn132& Pn135~Pn136
Pn139 & Pn13D&Pn140~Pn14B
HHH
------------
Speed
------------
HHH
HHH
Touque
------------
HHH
Sequential Control
------------
HHH
Pn550~Pn553&Pn560~Pn561&Pn600~Pn601
Input/Output signal
------------
Pn50A~Pn513&Pn515~Pn517
HHH
UDP
Device
Bit Address
Word Address
Format
IB0000.0-FFFF.F
------
HHHHH.H
OB0000.0-FFFF.F
------
HHHHH.H
MB00000.0-65534.F
------
DDDDD.H
Input register
------
IW0000-FFFF
HHHH
Output register
------
OW0000-FFFF
HHHH
Holding register
------
MW00000-65534
Notes
DDDDD
NOTEIn the HMIWare, bit address format is HHHH.H, but there is no point in the controller. E.g.: In the
EV5000 software, the bit address is MB65534.F, but there is no point in the controller, and it is MB65534F.
We set the I\O address as large as enough, and we found the big address cant be written, but it is the same
effect with the monitoring.
Cable Diagram
V series inverter
RS485-2 communication cable
- 365 -
MP2300
RS232 communication cable
HMI terminal
9pin D-SUB female/male
Controller terminal
9 pin D-SUB (male)
com0/com1
1 FG
1 FG
2 RD(RXD)
2 SD(TXD)
3 SD(TXD)
3 RD(RXD)
5 SG(GND)
7 SG(GND)
6 DR(DSR)
9 ER(DTR)
7 RS(RTS)
4 RS(RTS)
8 CS(CTS)
5 CS(CTS)
SGDM/SGDV
RS232 communication cable
- 366 -
FA-M3
CPU
Link Module
F3SP21-0N
F3SP25-2N
F3SP28-3N
F3SP35-5N
F3SP38-6N
F3SP53-4H
F3SP58-6H
F3SP28-3S
F3SP38-6S
F3SP53-4S
F3SP58-6S
F3SP59-7S
CPU Direct
F3SP20-0N
F3SP21-0N
F3SP25-2N
F3SP28-3N
F3SP30-0N
F3SP35-5N
F3SP38-6N
F3SP53-4H
F3SP58-6H
F3SP36-3N
F3SP28-3S
F3SP38-6S
F3SP53-4S
F3SP58-6S
F3SP59-7S
F3SP66-4S
F3SP67-6S
F3LC11-1N
F3LC11-1F
F3LC11-2F
F3LC12-1F
Driver
Yokogawa FA-M3
F3LC11-2N
CPU
Link Module
Driver
- 367 -
FA-M3
F3SP21-0N
F3SP25-2N
F3SP28-3N
F3SP35-5N
F3SP38-6N
F3SP53-4H
F3LE01-5T
F3LE11-0T
F3SP58-6H
F3SP28-3S
F3SP38-6S
F3SP53-4S
F3SP58-6S
F3SP59-7S
F3LE01-5T
F3LE11-0T
F3SP66-4S
F3SP67-6S
Yokogawa
Ethernet(TCP Slave)
FA-M3
FA-M3
CPU
F3SP21-0N
F3SP25-2N
F3SP28-3N
F3SP35-5N
F3SP38-6N
F3SP53-4H
F3SP58-6H
F3SP28-3S
F3SP38-6S
F3SP53-4S
F3SP58-6S
F3SP59-7S
F3SP20-0N
F3SP21-0N
F3SP25-2N
F3SP28-3N
F3SP30-0N
F3SP35-5N
Link Module
COM Type
Parameter
Cable
RS232
Setting
RS422
Setting
RS422/485(4Wire)
port on F3LCLL-2F
- 368 -
F3SP38-6N
F3SP53-4H
F3SP58-6H
F3SP36-3N
F3SP28-3S
F3SP38-6S
F3SP53-4S
F3SP58-6S
F3SP59-7S
F3SP66-4S
F3SP67-6S
RS422/485(2Wire)
port on F3LCLL-2F
RS485
Setting
FA-M3
CPU
Link Module
F3SP21-0N
F3SP25-2N
F3SP28-3N
F3SP35-5N
F3SP38-6N
F3SP53-4H
F3LE01-5T
F3LE11-0T
F3SP58-6H
F3SP28-3S
F3SP38-6S
F3SP53-4S
F3SP58-6S
F3SP59-7S
F3LE01-5T
F3LE11-0T
F3SP66-4S
F3SP67-6S
Ethernet I/F
on CPU Unit
Connect Type
Parameter
Cable
Ethernet
Setting
- 369 -
- 370 -
PLC Setting
RS485-4 communication configuration
Set the 485 communication module on the right as below.
1. Transmission Speed Setting Switch: SW1=7
2. Data Code Setting Switch: SW2
Bit
Settings
Setup Description
ON
Data Length
OFF
Parity Bit
OFF
--
OFF
Stop Bit
OFF
ON
Exist Terminator
OFF
Protect
OFF
Always OFF
Settings
Setup Description
ON
Data Length
OFF
Parity Bit
OFF
--
OFF
Stop Bit
OFF
ON
Exist Terminator
OFF
Protect
- 371 -
OFF
Always OFF
PLC setting
Use the swicthes on the right side of Ethernet module for setting the External Device.
1. Set all condition setup switch off.
2. Set IP Address: 192.168.100.230.
Supported Device
Device
Bit Address
Word Address
Format
Link Relay
L 1~256
------
DDD
Special Relay
M 1~256
------
DDD
Internal Relay
I 1~256
------
DDDD
Output Relay
Y (233~264)&(333~364
------
DDD
Input Relay
X (201~232)&( 301~332
------
DDD
Special Register
------
Z_word 1~256
DDDD
Link Register
------
W_word 1~256
DDD
- 372 -
Notes
Read only
Index Register
------
V_word 1~64
DD
File Register
------
B_word 1~256
DD
Data Register
------
D_word 1~256
DDD
Cable Diagram
RS232 communication cable
Yokogawa programming cable
HMI terminal
9pin D-SUB female/male
com0/com1 com2
Controller terminal
6 pin
2 RX
7 RX
1 TXD
3 TX
8 TX
2 RXD
5 GND
5 GND
5 GND
Controller
RS422 terminal
com0/com1
SDASDB+
FG
RDA-
1 RX6 RX+
5 GND
4 TX9 TX+
RDB+
4.84 YuDian AI
Serial Communication
Series
CPU
Link Module
- 373 -
Driver
AI
AI-518
AI-701
YuDian AI Single_Loop
AI-7048
YuDian AI 4_Loop
System configuration
Series
AI
CPU
Link Module
COMM Type
Parameter
Cable
AI-518
AI-701
RS485
Setting
AI-7048
RS485
Setting
Communication Setting
HMI Setting
Default communication: 9600, 8, none, 1; station: 1
Supported Device
YuDian AI Single_Loop
Device
Bit Address
Word Address
Format
Notes
HiAL
------
Read only
LoAL
------
Read only
dHAL
------
Read only
dLAL
------
Read only
orAL
------
Read only
AL1
------
Read only
AL2
------
Read only
PV
------
Read only
MV
------
SV
------
ALARM
------
Read only
Reference
------
86
DD
Address correspond to
AI parameters code
- 374 -
NOTE
1When setting the parameter of ADDR, it match the PLC Station Number .
2If connecting many devices, you should set different ADDR values.
YuDian AI 4_Loop
AI-7048
Device
Bit Address
Word Address
Format
Notes
HiAL
0.0-3.0
------
D.D
Read only
LoAL
0.0-3.0
------
D.D
Read only
dHAL
0.0-3.0
------
D.D
Read only
dLAL
0.0-3.0
------
D.D
Read only
orAL
0.0-3.0
------
D.D
Read only
AL1
0.0-3.0
------
D.D
Read only
AL2
0.0-3.0
------
D.D
Read only
PV
------
0.0-3.0
D.D
Read only
MV
------
0.0-3.0
D.D
SV
------
0.0-3.0
D.D
ALARM
------
0.0-3.0
D.D
Read only
Reference
------
0.0-3.086
D.DDD
Address correspond to AI
parameters code
NOTE:
1When setting the parameter of ADDR, it match the PLC Station Number.
2If connecting many devices, you should set different ADDR values.
3AI-7048 has 4 loops, so it occupies 4 address, For instance, Addr=5,address 5~8 were used by this
controller, other controller cant use address 5~8.
EXAMPLE
Take HIAL for example, look up table and then know that HIAL parameters code is 1, so HIAL for 4
channels correspond to address in HMI should be Reference0.01Reference1.01Reference2.01
Reference3.01.
If station number is 2, Reference0.01 is HIAL address of channel 2(station No. 2 + main address 0),
Reference1.01 is HIAL address of channel 2(station No. 2 + main address 1), and so on.
Thereinto the setting of station number is very important, it denotes start address of the controller (viz.
instrument address in instrument parameter), and main address just denotes 4 channels. When main address
is 0, it denotes channel (station number+0)
TABLE
Table 1
Parameter
Code
DEC
0
Adjustor
AI-518/708/808/518P/70
8P/808P
SV /SteP
Inspection instrument
AI-519/719/719P
SV /SteP
AI-501/701
N/A
- 375 -
AI-702M/704M/706M
N/A
HIAL
HIAL
HIAL
HIAL
LoAL
LoAL
LoAL
LoAL
dHAL
HdAL
HdAL
N/A
dLAL
LdAL
LdAL
N/A
dF
CHYS
AHYS
dF
Ctrl
Ctrl
N/A
N/A
M5
N/A
N/A
N/A
N/A
N/A
N/A
10
CtI
CtI
N/A
N/A
11
Sn
InP
InP
Sn
12
dIP
dPt
dPt
dIP
13
dIL
SCL
SCL
dIL
14
dIH
SCH
SCH
dIH
15
ALP
AOP
AOP
ALP
16
Sc
Scb
Scb
Sc
17
OP1
OPt
OPt
OPn
18
oPL
OPL
N/A
oPL
19
oPH
OPH
N/A
oPH
20
CF
AF
N/A
Cn
21
Feature codes
22
Add.R/W
Add.R/W
Add.R/W
Add.R/W
23
dL
FILt
FILt
dL
24
run
A-M
N/A
nonc
25
Loc
Loc
Loc
Loc
26
27
t01
t01
28
C02
C02
29
t02
t02
30
C03
C03
31
t03
t03
32
C04
C04
33
t04
t04
34
C05
C05
35
t05
t05
36
C06
C06
37
t06
t06
38
C07
C07
39
t07
t07
- 376 -
40
C08
C08
41
t08
t08
42
C09
C09
t09-C30
t09-C30
43-85
86
Run time
program
of
Table 2
Parameter Code
Flow totalizer
AI-301M
4 loop PID
adjustor
AI-708H/Y/808H
Frequency
measurement/switching value
AI-7048
DEC
HEX
00H
SV
SV
SP
01H
FHIA
HIAL
HIAL
02H
FloA
LoAL
LoAL
03H
SPE
dHAL
04H
Act
dLAL
05H
Sn
dF
AHYS
06H
FSc
CtrL
At
07H
PdIH
M5
08H
CSc
09H
CdIH
10
0AH
Cut
CtI
11
0BH
FdIH
Frd
InP
12
0CH
FdIP
dIP
dPt
13
0DH
PA
dIL
SCL
14
0EH
Po
dIH
SCH
15
0FH
Co
ALP
AOP
16
10H
Frd
switch state
Scb
17
11H
CF
oP1
18
12H
bC
OPL
19
13H
IoL
OPH
OPH
20
14H
FoH
CF
AF
21
15H
Feature codes
Feature codes
Feature codes
22
16H
Add.R/W
Add.R/W
Add.R/W
23
17H
IoH
dL
FILt
24
18H
FdL
run
Nonc
25
19H
Loc
Loc
Loc
26
1AH
N/A
MV
Cn
27
1BH
FdF
28
1CH
CHIA
29
1DH
CLoA
- 377 -
30
1EH
PHIA
31
1FH
PLoA
32
20H
ALP
33
21H
FSb
34
22H
CdIP
35
23H
PdIP
36
24H
PSc
37
25H
CLn
38
26H
FLJH
39
27H
FLJL
40
28H
EJH
41
29H
EJL
42
2AH
43-85
2BH-55H
86
56H
Cable Diagram
RS485 communication cable
CPU
Link Module
Driver
ZiGuang Ethernet
UNIS-600C
Ethernet
- 378 -
CPU
Link Module
COMM Type
Parameter
Cable
ZiGuang Ethernet
UNIS-600C
Ethernet
Ethernet
Setting
PLC Setting
1. Settings in the software as follows:
(1) System basic configuration: Set the controller number, IP address, and the PC IP address.
(2) Configuration of data tag: set the parameters according to the actual I/O card. The PLC register address
should be the same as the ID number of the data tag.
- 379 -
that needs to be
card.
Use
this
box
added or deleted.
This
box
displays
Card type
3Update and get configuration: After finish the system basic configuration and data tag configuration,
icon to update the configurations in
choose the Update Configuration in the Tool menu or click the
icon to get the
the controller. Choose the Get Configuration in the Tool menu or click the
configuration in the controller.
- 380 -
of
added
4Click
icon after updating controller configuration, then it will pop upWinEmu window, real-time
control of script debugging window and none-real time control of script debugging window.
WinEmu window monitors the internal data of controller, real-time control of script debugging window and
none-real time control of script debugging window provide environment for customer secondary
development.
Supported Device
Device
Bit Address
Word Address
Format
Notes
Bool_Read
Bool_Read 0-65535
------
DDDDD
Read only
Bool_Write
Bool_Write 0-65535
------
DDDDD
Write only
Float_Read
------
Float_Read 0-65535
DDDDD
Read only
Int_Read
------
Int_Read 0-65535
DDDDD
Read only
Float_Write
------
Float_Write 0-65535
DDDDD
Write only
Int_Write
------
Int_Write 0-65535
DDDDD
Write only
------
Time 0-2
NOTE: The name and address of registers in HMI must be same as register in Ziguang controller when
defining in HMI.
Cable Diagram
Ethernet communication protocol cable
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to 4.3 Download by Network Ethernet for method of making connection cable.