Interactive Distributed Generation Interface For Flexible Micro-Grid Operation in Smart Distribution Systems
Interactive Distributed Generation Interface For Flexible Micro-Grid Operation in Smart Distribution Systems
2, APRIL 2012
295
AbstractThis paper presents an interactive distributed generation (DG) interface for flexible micro-grid operation in the
smart distribution system environment. Under the smart grid
environment, DG units should be included in the system operational control framework, where they can be used to enhance
system reliability by providing backup generation in isolated
mode, and to provide ancillary services (e.g. voltage support and
reactive power control) in the grid-connected mode. To meet
these requirements, the proposed flexible interface utilizes a fixed
powervoltagecurrent cascaded control structure to minimize
control function switching and is equipped with robust internal
model control structure to maximize the disturbance rejection
performance within the DG interface. The proposed control
system facilitates flexible and robust DG operational characteristics such as 1) active/reactive power (PQ) or active power/voltage
(PV) bus operation in the grid-connected mode, 2) regulated
power control in autonomous micro-grid mode, 3) smooth transition between autonomous mode and PV or PQ grid connected
modes and vice versa, 4) reduced voltage distortion under heavily
nonlinear loading conditions, and 5) robust control performance
under islanding detection delays. Evaluation results are presented
to demonstrate the flexibility and effectiveness of the proposed
controller.
Index TermsDistributed generation (DG), flexible control,
micro-grids, smart distribution systems.
I. INTRODUCTION
Manuscript received May 27, 2011; revised September 19, 2011; accepted
November 05, 2011. Date of current version March 21, 2012.
The authors are with the Department of Electrical and Computer Engineering, University of Alberta, Edmonton, T6G-2V4, Canada (e-mail:
[email protected]).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TSTE.2011.2178045
296
model is in line with the IEEE 1547 test load used in DG applications [17]. The nonlinear load is a three-phase diode rectifier with an
load at the dc-side. The addition of the
diode rectifier helps in assessing the effectiveness of the proposed controller in rejecting voltage harmonics associated with
nonlinear loading, and rejecting load-DG-unit-grid interactions
at harmonic frequencies. Power circuit and control parameters
of DG units are given in the Appendix.
The schematic diagram of a single DG unit as the building
block of the sample micro-grid system is also shown in Fig. 1.
When the DG unit is connected to the grid, the voltage and frequency at the point of common coupling are dominantly dictated by the grid. However, in case of weak grids, the voltage is
prone to voltage sags and disturbances. In this case, the DG unit
can be controlled to support the grid voltage. Therefore, both
PQ and PV operational modes can be adopted in the grid-connected mode. Subsequent to an islanding event, DG units can
form an autonomous micro-grid system to enhance the reliability of sensitive loads. This flexible operation requires robust
control infrastructure, which is essential for system operators
and supervisory controllers in the smart grid environment.
In both grid-connected and isolated modes, the state space
presentation of the DG interface dynamics can be given in the
natural frame by
(1)
where and are the filter inductance and capacitance,
is the inverter output voltage,
is the inverter output current,
is the voltage at the point of common coupling,
and
is the network-side current. Note that
,
,
and
are 3 1 vectors representing phase quantities
corresponding to each phase, and the filter-inductor resistance
297
the proposed design strategy, both external and internal disturbances can be eliminated or remarkably attenuated within the
DG interface. Moreover, the fixed control structure increases
the robustness of the control structure to islanding detection
delays. The voltage control is designed by considering an
augmented model that includes the
-filter active damping
and inner current control loop dynamics to ensure robustness
and coordinated control design. Theoretical analysis and design
procedure of the proposed control scheme are described in the
following sections.
B. Resonance Damping
is ignored. In order to decrease the number of differential equations and simplify system presentation, (1) can be rewritten in a
stationary
reference frame system by applying the following
to
transformation:
(2)
Using (2), the state space model of the system in the
is as follows:
frame
(3)
Fig. 2 depicts the block diagram representation of the differential equations derived in (3) where
models the exogenous disturbance caused by connecting the system to the utility
grid. The block diagram suggests that the output current (i.e.,
) can be regarded as an external disturbance caused by unknown load or grid behavior either in islanded or grid connected mode. Along with these exogenous disturbances, control
mode switching in conventional DG controllers (e.g., from current control to voltage control) generates internal disturbances
within the control structure.
III. PROPOSED CONTROL SCHEME
Applying an
filter at the output stage introduces a resonance peak to the frequency response of the system, which
can limit the achievable bandwidth of the current controller in
a multiloop hierarchical control approach. Besides, as the filter
and grid parameters change, the corresponding resonance frequency also shifts, resulting in potential harmonic excitations at
low-order harmonics affecting system stability. Therefore, converter resonance damping is essential to maintain stability and
facilitate high bandwidth current control design. Active resonance damping can be a viable option, particularly in DG applications where losses associated with passive damping can
reduce the generation efficiency. A simple and effective technique to actively damp
filter resonance is to introduce a
damping voltage that is proportional to the capacitor current.
The dynamic equations corresponding to the actively damped
system can be given as follows:
(4)
where
represents the current-dependent voltage source injected in series with the original inverter output voltage and
is the virtual damping coefficient.
With the active damping voltage modeled as a current-controlled voltage source, the open loop transfer function of the
system of Fig. 1 is driven as
(5)
A. Control Structure
As indicated in Fig. 2, external disturbances will be imposed
on the DG interface during mode transition and network/load
disturbances. On the other hand, internal disturbances will be
generated due to control function switching between different
modes in the conventional hierarchical control structure. To
overcome these issues and to achieve a flexible and robust
operation of DG units under the smart grid environment while
maintaining the hierarchical control structure, the proposed
control scheme, shown in Fig. 3, utilizes a fixed hierarchical
powervoltagecurrent control structure in both grid-connected
and isolated modes. This will minimize the undesired voltage
transients generated by switching from a current-controlled interface to a voltage-controlled interface in conventional control
techniques. Further, the proposed power controller works under
grid-connected and isolated micro-grid modes; this feature
provides a flexible interface for the DG unit to be used in
different operational modes with minimal switching. Due to
298
regarded as an open loop system where the feed-forward compensator should be designed to ensure close tracking performance. On the other hand, disturbance rejection can be achieved
via the feedback compensator design. Since the tracking and
disturbance rejection performances can be designed independently, the IMC control scheme can be considered as a two-degree-of-freedom controller.
The sensitivity function
and the complementary sensitivity function
, which represent tracking and disturbance
rejection capabilities of the system, respectively, can be driven
as follows:
Fig. 4. Open loop frequency response of the actively damped system at dif.
ferent values of
(6)
and
such that
The design goal is then to propose
and
within a reasonably large range of frequencies of interest. This will assure both disturbance rejection and
tracking ability of the system. Assuming
and
, then the model following error
is zero and the
control scheme is reduced to an open loop one with
. In this case,
can provide a perfect
tracking performance. Stability constraints require
to be
minimum phase. Besides,
can be an improper transfer
function and cannot be realized practically. Therefore, a lowpass filter is used to yield a proper feed-forward compensator
(7)
where corresponds to the bandwidth of the filter, and is
an integer selected in such a way that
is a proper or
strictly proper function. The disturbance rejection is achieved
via
which produces a compensating input to cancel out
disturbances. To overcome the computational burden associated with frame transformations, the proposed controller is performed in Clarks
-frame. Proportional resonant controller
299
(8)
Fig. 6. Augmented plant model including active damping and inner current
control loops.
(9)
Fig. 8 depicts the proposed IMC-based multiloop voltage control structure. Considering the output/input relation calculated
(10)
300
Fig. 9. Frequency response for the (a) tracking and (b) disturbance rejection performances.
it more robust in the presence of voltage harmonics or unbalances [21]. On the other hand, during islanded operation, the
processor internal clock is used to generate the aforementioned
signal while
is assumed to be
.
Considering the voltage and reactive power controller, the
voltage amplitude can be either set to 1.0 p.u. for PV-bus operation, or it can be adjusted through a reactive power controller for
PQ-bus operation. In the grid-connected mode, a proportional
integral (PI) controller is adopted to provide the magnitude of
the output voltage
. Therefore, the voltage control signal can
be generated as follows:
(13)
301
Fig. 12. Dynamic response of the system to an active power command step change in grid connected mode and PQ operation. (a) Converter active power. (b)
Converter reactive power. (c) Output voltage magnitude. (d) Instantaneous phase-a output voltage.
where
are the proportional and integral gains, respectively,
is the reference reactive power, and is the actual
reactive power.
In islanded operation, however, a voltage droop function is
adopted to share the reactive power among different DG units.
Accordingly, the voltage magnitude is generated according to
micro-grid system employs two DG units, which can work parallel to the utility grid, or in isolated mode when the grid is not
available to serve sensitive loads.
The proposed flexible control structure, shown in Fig. 3,
makes it possible for the DG unit to support the grid in different scenarios. Different scenarios are tested. Key results are
presented as follows.
(14)
A. Grid-Connected Mode
where
Fig. 12 shows the control performance under PQ-bus operation mode for one of the DG units. The inductive load and
the capacitor bank are activated in this scenario. The reactive
power command is set to zero, whereas the active power command experiences a step change from 5 to 10 kW at
s.
Fig. 12(a) and (b) shows the active and reactive powers generated by the unit. Close active power tracking performance is
yielded. On the other hand, the coupling between active and reactive power dynamics is minimal. Fig. 12(c) depicts how the
output voltage amplitude changes to maintain the unity power
factor condition while increasing the active power injection.
Voltage fluctuation in this mode is the natural result of the absence of voltage control at the point of common coupling. The
instantaneous phase- output voltage is shown in Fig. 12(d).
In addition to active power regulation, the DG unit can contribute to the voltage reliability at the point of common coupling
by allowing bus voltage control (i.e., PV mode). This mode can
be activated once voltage sags (e.g., due to upstream faults) are
detected. Under these conditions, the voltage control mode is activated to inject reactive power during the sag period to provide
fault-ride-through performance. Accordingly, the economic operation of the DG unit will not be compromised. On the other
hand, in long radial feeders and weak grids, existing DG units
can be used for continuous voltage support. Fig. 13 shows the
effectiveness of the proposed control strategy in terms of providing the DG unit with the fault-ride-through capability. The
302
Fig. 13. Dynamic response of the system under 10% grid voltage sag under PV-bus operation. (a) Instantaneous
and feeder voltage in p.u. (c) Converter reactive power.
Fig. 14. Dynamic response of the system when a nonlinear load is added in grid connected mode. (a) Phase- output voltage. (b) Phase- load current (c) PLL
output.
303
Fig. 15. Dynamic response of the two-DG micro-grid system due to an islanding event with DG units acting as PV buses. (a) Instantaneous phase- grid voltage
with and without proposed controller. (b) RMS feeder voltage with proposed controller. (c), (d) Active and reactive converter powers of each DG unit.
Fig. 16. Dynamic response of the two-DG micro-grid system due to an islanding event with DG units acting as PQ buses. (a) Instantaneous phase- grid voltage
with and without proposed controller. (b) RMS feeder voltage with proposed controller. (c), (d) Active and reactive converter powers of each DG unit.
304
Fig. 17. Dynamic response of the system when a nonlinear load is added in islanded mode. (a) Instantaneous phase- output voltage. (b) Phase- load current.
Instantaneous phase- grid current. (c), (d) Active and reactive converter powers for DG1. (e), (f) Active and reactive converter powers for DG2.
Fig. 18. Dynamic response of the two-DG micro-grid system when reconnecting to the utility as PQ buses. (a) Instantaneous phase- grid current. (b) Instantaneous phase- output voltage. (c), (d) Active and reactive converter powers for each DG unit.
Fig. 16(a) and (b), respectively. Close voltage control characteristics are yielded subsequent to the islanding event. Once again
the system response in the absence of the proposed scheme is
shown in Fig. 16(a), where the higher transient over-voltage is
obvious. The active and reactive power responses for DG units
are shown in Fig. 16(c) and (d), where the initial active power
generated by each DG is 6.0 kW at unity power factor. Subsequent to the islanding event, the generated active power decreases in order to meet the load demand.
Fig. 17 shows the load voltage and current responses of the
islanded system when the nonlinear load is added at
s.
Fig. 17(a) shows the load voltage, whereas Fig. 17(b) shows the
load current. It can be seen that the controller is well capable of
maintaining the output voltage quality despite the highly distorted current going through the load. The THD of the load
voltage is 2.7%. Fig. 17(c)(f) shows the active and reactive
power profiles of both DG units. Accurate power sharing performance is yielded even in the presence of harmonic loading,
which demands reactive power injection by both DG units.
Fig. 18 shows the grid current, the load voltage, and power
responses during a supply restoration scenario at
s.
Once the utility supply is restored, both DG units operate as a
PQ bus with unity power factor and with a power command of
3.0 kW for each unit. In spite of grid-current transients, the load
voltage is closely controlled to facilitate seamless restoration.
Similar to the micro-grid formation event, the proposed con-
305