CWT5010 Commands

This document contains commands for controlling a CWT5010 device. It lists basic parameters, alarm parameters, input/output parameters, control output commands, and interior temperature parameters. Commands include setting up communication ports, enabling alarms, configuring inputs/outputs, and controlling output states.

Uploaded by

Arieza Perdhana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
154 views

CWT5010 Commands

This document contains commands for controlling a CWT5010 device. It lists basic parameters, alarm parameters, input/output parameters, control output commands, and interior temperature parameters. Commands include setting up communication ports, enabling alarms, configuring inputs/outputs, and controlling output states.

Uploaded by

Arieza Perdhana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

1

CWT5010 Commands

CONTENTS
Setup control server phone .........................................................................................................................5
CS Setup Control server phone ..................................................................................................................5

CWT5010 COMMANDS

V3.2

Basic parameters .........................................................................................................................................6


UB Setup RTU com port0 BPS..................................................................................................................6
UP Setup RTU com port0 Parity ................................................................................................................6
SIGNALA Enable or Disable low signal Alarm ..........................................................................................6
RSILOW Setup the thread hold value of Signal Low Alarm.........................................................................6
DAS Enable or Disable Daily Report SMS at 10.pm everyday.....................................................................7
PRTCS Send proof time request SMS to first valid CS number when power up.............................................7
PRTSP Send proof time request SMS to SP when power up .........................................................................7
SP Setup the SP phone number ..................................................................................................................7
RPLSUC Reply SMS for successfully executed SMS command ..................................................................7
RPLERR Reply SMS for incorrect executed SMS command .......................................................................8
PW Setup RTU login Password .................................................................................................................8
ID Setup RTU Device ID ..........................................................................................................................8
PIN Setup RTU PIN code..........................................................................................................................8
PUK Setup RTU PUK code.......................................................................................................................8
SMSC Setup the SMS message center service number ................................................................................9
DESC Setup the RTU description information ............................................................................................9
Alarm parameters ......................................................................................................................................10
ARING Enable or Disable Alarm RING call function................................................................................10
ASC Enable or Disable Auto Answer Voice call from CS phones ...............................................................10
AWB Enable or Disable description in Alarm SMS ...................................................................................10
UARTEVENT Enable or Disable Export events from UART .....................................................................10
IOAT Setup alert sms resend times........................................................................................................... 11
DRPTID Enable or Disable ID information in daily report SMS ................................................................ 11
DRPDEF Enable or Disable ARM/DISARM information in daily report SMS ............................................ 11
DRPBAT Enable or Disable Power Supply information in daily report SMS............................................... 11
DRPMEM Enable or Disable description information in daily report SMS .................................................12
DRPRSI Enable or Disable GSM Signal information in daily report SMS ..................................................12
DRPDIN Enable or Disable Alarm Wired Inputs information in daily report SMS .......................................12
DRPTMP Enable or Disable build in temperature information in daily report SMS .....................................12
Input and output parameters ....................................................................................................................13
IOTP Setup all inputs and outputs type.....................................................................................................13
IOIP Disable inputs alarm .......................................................................................................................13
IOIC Enable inputs alarm........................................................................................................................13
DINURG Enable or Disable inputs 24 hours option .................................................................................14
DINSND Enable or Disable inputs sound alarm option ............................................................................14
IOAS Setup alarm sms limit interval........................................................................................................14
IOLS Setup sms resend interval when input is in alarm state......................................................................14
DINDLY Setup timer for ensuring inputs alarm ........................................................................................15
S Setup digital inputs alarm sms content ..................................................................................................15
S Setup digital inputs recover sms content................................................................................................15
I Setup inputs name ................................................................................................................................15
O Setup outputs name .............................................................................................................................16
IOIS Read inputs status...........................................................................................................................16
IOOS Read outputs status .......................................................................................................................16
IOOR Setup remember outputs status.........................................................................................................16
IOHT Setup Persist timespan of siren.........................................................................................................16
Control outputs commands........................................................................................................................17
IOOH Control outputs on........................................................................................................................17
IOOL Control outputs off........................................................................................................................17

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

CWT5010 Commands

IOOP
IOPO
IOOP
IOOF

Control outputs pulse.....................................................................................................................17


Setup pulse interval.......................................................................................................................17
Control outputs pulse with time ......................................................................................................17
Control all outputs by a command ..................................................................................................18

Interior temperature parameters...............................................................................................................19


TMPH Setup high point of interior temperature normal range ....................................................................19
TMPL Setup low point of interior temperature normal range .....................................................................19
TMPB Setup temperature adjustments value.............................................................................................19
TMPAS Setup the timespan of twice alarm sms ........................................................................................19
TMPLS Setup timespan of resend alarm sms ............................................................................................20
TMPNDLY Setup timespan of ensure alarm status ....................................................................................20
TMPOS Setup lags of temperature alarm range.........................................................................................20
TMPON Enable temperature sensor alarm................................................................................................20
TMPOFF Disable temperature sensor alarm .............................................................................................20
TMPURG Setup temperature sensor alarm is urgency 24 hours..................................................................21
TMPSND Setup temperature sensor sound alarm......................................................................................21
TMPIH Setup interlock output pin of high point .......................................................................................21
TMPIL Setup interlock output pin of low point .........................................................................................21
TMPR Query temperature normal range...................................................................................................21
TMPC Query current temperature value...................................................................................................22

The instructions of SMS COMMANDS


You can use this sms commands to remote control and configure RTU
SMS commands is valid when RTU is in working mode
You can execute this sms commands through RS232. But the point is that when the input command is
made through RS232, the % has to be input ahead, while if it is sent via sms, no % or < CR > is
needed.
Type

Format

Note

Config commands

%command<value><enter>

Return OK or ERROR

Inquire commands

%command<?><enter>

Return the result or ERROR

Interior battery parameters .......................................................................................................................23


BATEN Enable or disable power lost alarm..............................................................................................23
POWDLY Setup time of ensure power alarm............................................................................................23
POW Query power status........................................................................................................................23
Interlock parameters .................................................................................................................................24
IOOC Setup outputs action......................................................................................................................24
IOOA Setup link with .............................................................................................................................24
Setup timers...............................................................................................................................................25
mtimer Setup system timers ....................................................................................................................25
mspan Setup minutes timers ....................................................................................................................25
sspan Setup second timers .......................................................................................................................25
mdate Setup week timers ........................................................................................................................25
Setup User command ................................................................................................................................27
U Setup the User defined commands........................................................................................................27
Y Setup the User defined commands mapped RTU commands...................................................................27
System operation commands ....................................................................................................................28
PW Setup system password .....................................................................................................................28
DAYRP Query the RTU status (Daily report SMS) ...................................................................................28
ARM/BF Arm the RTU system ...............................................................................................................28
DISARM/CF Disarm the RTU system......................................................................................................28
RST Reset the RTU power ......................................................................................................................28
LOADF Load factory settings .................................................................................................................28

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

CWT5010 Commands

Setup control server phone

Basic parameters

CS Setup Control server phone

UB Setup RTU com port0 BPS

Write
Command

Write
Command

CS<n>=[phone]

Parameters:
<n>: CS phone index, form 0~9
[phone]: a valid phone number or null
string to delete

Read
Command

Query all CS phone number

Example:
CS0=138000000000

Parameters
<BPS>: 300-115200
Default BPS is 9600BPS

Example:
UB=9600

Parameters
<Parity>:
0: None (default)
1: Odd Parity
2: Even Parity
3: 0 Parity
4: 1 Parity

Example:
UP=0

UB=<BPS>
Read
Command
UB=?

CS?

UP Setup RTU com port0 Parity

Delete
Command

Write
Command

CS<n>

UP=<Parity>

Read
Command
UP=?
SIGNALA Enable or Disable low signal Alarm
Write
Command
SIGNALA=<En>
Read
Command

Parameters
<En>
0: Disable (default)
1: Enable

Example:
SIGNALA=1

SIGNALA=?
RSILOW

Setup the thread hold value of Signal Low Alarm

Write
Command
RSILOW=<Signal>
Read
Command

Parameters
<Signal>
Normal Signal range is 10-30
0 or 99 means no signal at all

Example:
RSILOW=11

When signal low, RTU will make a sound


alarm and try to send SMS

RSILOW =?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

CWT5010 Commands

DAS Enable or Disable Daily Report SMS at 10.pm everyday


Write
Parameters
Command
<En>
0: Disable
DAS=<En>
1: Enable (default)
Read
Command

RPLERR Reply SMS for incorrect executed SMS command


Example:
DAS=1

Write
Command
RPLERR=<En>
Read
Command

DAS =?

Parameters
<En>:
0:
1:

Example:
RPLERR=1
Disable
Enable (default)

RPLERR=?

PRTCS Send proof time request SMS to first valid CS number when power up
Write
Parameters
Command
<En>:
0: Disable
PRTCS=<En>
1: Enable (default)
Read
Command

PW Setup RTU login Password


Example:
PRTCS=1

Write
Command
PW=<psd>
Read
Command

PRTCS=?

Password is 6 characters string

Example:
PW=888888

Default password is 000000

PW=?

PRTSP Send proof time request SMS to SP when power up


Write
Parameters
Command
<En>:
0: Disable (default)
PRTSP=<En>
1: Enable
Read
Command

Example:
PRTSP=1

ID

Setup RTU Device ID

Write
Command

Device ID is a 8 characters string


Default ID is null

ID=<id>
Read
Command

ID is used in GPRS CWT_IO protocol

Example:
ID=00000001

PRTSP=?
ID=?
SP Setup the SP phone number
Write
Command
SP=<phone>
Read
Command
SP=?

SP phone number is a phone that can automatic reply a SMS to any


incoming SMS, RTU use it to update interior Clocker by the timestamp in
SMS, the SMS contents is not important

PIN

SP phone number can be RTUs simcard number. So it will send proof


time sms to itself when power up and RTU will receive this sms. So RTU
can take out the time stamp from the sms PDU.
Note: if the RTUs simcard is changed, you must change the SP also.

PIN=<code>
Read
Command

RPLSUC Reply SMS for successfully executed SMS command


Write
Parameters
Command
<En>:
0: Disable
RPLSUC=<En>
1: Enable (default)
Read
Command

Example:
RPLSUC=1

Setup RTU PIN code

Write
Command

PIN code is 4 number

Example:
PIN=1234

PUK code including 8 numbers

Example:
PUK=12345678

PIN=?
PUK Setup RTU PUK code
Write
Command
PUK=<code>
Read
Command

RPLSUC=?
PUK=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

CWT5010 Commands

SMSC

Setup the SMS message center service number

Alarm parameters

Write
Command
ARING
SMSC=<code>
Read

Default is NULL (can works well in most of

Command

area and country)

SMSC=?
DESC

Enable or Disable Alarm RING call function

Write
Command

Parameters
<En>:
0: Disable (default)

ARING=<En>

1: Enable
If enable RING call, any alert will cause a

Read
Command

Example:
ARING=1

voice call to CS phone numbers.

Setup the RTU description information

Write
Command

Example:
DESC=room1

ARING=?
ASC

DESC=<string>
Read
Command

Enable or Disable Auto Answer Voice call from CS phones

Write

Parameters

Description is basic information about the


device, etc, the address, the administrator and

Command

so on.

ASC=<En>

DESC=?

<En>:
0: Disable
1: Enable (default)

Example:
ASC=1

Read
Command
ASC=?
AWB

Enable or Disable description in Alarm SMS

Write
Command

Parameters
<En>:
0: Disable

AWB=<En>

1: Enable (default)
Add the description and timestamp with alert

Read
Command

Example:
AWB=1

sms

AWB=?
UARTEVENT

Enable or Disable Export events from UART

Write
Command

Parameters
<En>:

Example:
UARTEVENT=1

0: Disable (default)
UARTEVENT=<En>

1: Enable

Read
Command
UARTEVENT=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

10

11

CWT5010 Commands

DRPMEM Enable or Disable description information in daily report SMS


IOAT

Setup alert sms resend times

Write
Command

Write
Parameters

Example:

<n>:

IOAT=3
sms resend times

IOAT=<n>

Parameters

Command

<En>:

DRPMEM=1

0: Disable
DRPMEM=<En>

default is 1

Example:

1: Enable (default)

Read

Read

Command

Command
DRPMEM=?
IOAT=?
DRPRSI Enable or Disable GSM Signal information in daily report SMS
DRPTID

Enable or Disable ID information in daily report SMS

Write

Parameters

Command

<En>:

DRPTID=<En>

Write
Example:

Parameters

Command

<En>:

DRPTID=1

DRPRSI=1

0: Disable

0: Disable

DRPRSI=<En>

1: Enable (default)

Read

Read

Example:

1: Enable (default)

Command

Command
DRPRSI=?
DRPTID=?
DRPDIN
DRPDEF Enable or Disable ARM/DISARM information in daily report SMS
Write

Parameters

Command

<En>:

DRPDEF=<En>

Enable or Disable Alarm Wired Inputs information in daily report SMS

Write
Example:

Command

DRPDEF=1

<En>:

Example:
DRPDIN=1

0: Disable

0: Disable

DRPDIN=<En>

1: Enable (default)

Read

Read

Parameters

1: Enable (default)

Command

Command
DRPDIN=?
DRPDEF=?
DRPTMP Enable or Disable build in temperature information in daily report SMS
DRPBAT

Enable or Disable Power Supply information in daily report SMS

Write
Command

Parameters
<En>:
0: Disable

DRPBAT=<En>

1: Enable (default)

Read
Command

Write
Example:

Command

DRPBAT=1
DRPTMP=<En>

Parameters
<En>:
0: Disable

Example:
DRPTMP=1

1: Enable (default)

Read
Command
DRPTMP=?

DRPBAT=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

12

13

CWT5010 Commands

DINURG Enable or Disable inputs 24 hours option


Write
Command

Input and output parameters


IOTP Setup all inputs and outputs type
Setup all I/O channels type
Write
Command
IOTP=<I0I1I2I3><O0O1O2O3>
Setup single input type
Write
Command
IOTPI=<n>,<In>
Setup single output type
Write
Command
IOTPO=<n>,<On>
Read
Command

Parameters
<I0I1I2I3>
Inputs type:
0: DISABLE
1: TO OPEN ALARM (EDGE)
2: TO OPEN ALARM(LEVEL)
3: TO CLOSE ALARM (EDGE)(default)
4: TO CLOSE ALARM(LEVEL)
<O0O1O2O3>
Outputs type:
0: DISABLE
1: GENERAL OUTPUT (default)
2: BUZZER
3: SNAPSHOOT
4: SIREN
<n>: 0~3 (DI or DO index)

DINURG<n>,<En>
Example:
IOTP=33331000

Enable input0 24
hours option

DINURG=?
Example:
IOTPI=0,2

DINSND Enable or Disable inputs sound alarm option


Write
Command

Setup input0 type is 2


Example:
IOTPO=0,1

DINSND<n>,<En>

Setup output0 type is 1

Parameters
<n>:
0~3 (input index)
<En>:
0: Disable
1: Enable (default)

Example:
DINSND=1,0
Disable input1 sound
alarm option

Read
Command
DINSND=?

IOIP Disable inputs alarm

IOIP=<n/nn//nnnn>
Read
Command

Example:
DINURG0,1

Read
Command

IOTP=?

Write
Command

Parameters
<n>:
0~3 (input index)
<En>:
0: Disable (default)
1: Enable

Parameters
<n/nn//nnnn>:
1 digit to 4 digits
n: 0~3 (input index)

Example:
Disable input0 alarm
IOIP=0
Disable input2/3
IOIP=23

IOAS Setup alarm sms limit interval


Write
Parameters
Command
<n>:
03 (Inputs index)
IOAS<n>,<time>
<time>:
0~255 (min)
Read
Command

Example:
IOAS0,2

Default is 0

alarm
IOAS<n>?

IOIP=?
IOIC

Enable inputs alarm

Write
Command
IOIC=<n/nn//nnnn>
Read
Command

Parameters
<n/nn//nnnn>:
1 digit to 4 digits
n: 0~3 (input index)

IOIC=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

Example:
IOIC=1
IOIC=0123

IOLS Setup sms resend interval when input is in alarm state


Write
Parameters
Command
<n>:
03 (Inputs index)
IOLS<n>,<time>
<time>:
0~255 (min)
Read
Command

Example:
IOLS0,2

Default is 0

IOLS<n>?

www.mobq2000.com

14

15

CWT5010 Commands

DINDLY Setup timer for ensuring inputs alarm


Write
Command
DINDLY<n>,<time>

Parameters
<n>:
03 (Inputs index)
<time>:

O
Example:
DINDLY0,5

Setup outputs name

Write
Command
O<nn>=<string>

0~65535 (sec)
Read
Command

Parameters
<nn>:
0003 (outputs name index)
<string>:

Example:
O02=pump

Name

Default is 0

Read
Command

DINDLY<n>?

O<nn>=?

S Setup digital inputs alarm sms content


Write
Command
S<nn>=<string>

Parameters
<nn>:
0003 (inputs alarm sms index)
<string>:
Alarm sms

Example:
S00=sensor alarm

IOOS

Read outputs status

Read
Command

S<nn>=?
S Setup digital inputs recover sms content

S<nn>=<string>

Read
Command
IOIS

Read
Command

Write
Command

IOIS Read inputs status

Parameters
<nn>:
0407 (inputs recover sms index)
<string>:
Recover sms

Example:
S03=alarm recover

IOOS
IOOR Setup remember outputs status
Write
Command

Read
Command

IOOR=<En>

S<nn>=?

Read
Command

I Setup inputs name

IOOR=?

Write
Command
I<nn>=<string>

Parameters
<nn>:
0003 (inputs name index)
<string>:
Name

Read
Command

Example:
I02=sensor

Parameters
<En>:
0: Disable (default)
1: Enable

Example:
IOOR=1

IOHT Setup Persist timespan of siren


Write
Command

Parameters
<n>:
0255 (min)

Example:
IOHT=10

IOHT=<n>
Read
Command

Default is 15 minutes

I<nn>=?
IOHT=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

16

17

CWT5010 Commands

IOOF Control all outputs by a command

Control outputs commands

control
Command

IOOH Control outputs on


control
Command
IOOH<nnnn>

Parameters
<nnnn>:
1 digit to 4 digits
n: 0~3 (outputs index)

Example:
Control ouput0 on:
IOOH0

IOOF<S0S1S2S3>

Parameters
<S0S1S2S3>: 4 digits
Sn:
0: output off
1: output on

Example:
Control output1/2 off
and others on
IOOF1001

Control ouput0/2/3 on:


IOOH023
IOOL Control outputs off
control
Command
IOOL<nnnn>

Parameters
<nnnn>:
1 digit to 4 digits
n: 0~3 (outputs index)

Example:
IOOL0
IOOL0123

Parameters
<nnnn>:
1 digit to 4 digits
n: 0~3 (outputs index)
default pulse interval is 1 second, and the
interval can be set by command IOPO

Example:
IOOP0
IOOP0123

Parameters
<sec>:
0~65535 (second)

Example:
IOPO5

IOOP Control outputs pulse


control
Command
IOOP<nnnn>

IOPO

Setup pulse interval

Write
Command
IOPO<sec>
Read
Command
IOPO?

IOOP Control outputs pulse with time


control
Command
IOOP<nnnn>,<sec>

Parameters
<nnnn>:
1 digit to 4 digits
n: 0~3 (output index)
<sec>: 0~65535 (second)

Example:
Generate a 10 seconds
pulse on output0:
IOOP0,10
Generate a 3 seconds
pulse on output 0/2/3:
IOOP023,3

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

18

19

CWT5010 Commands

TMPLS Setup timespan of resend alarm sms


Write

Interior temperature parameters

Parameters

Command

<min>:

Example:
TMPLS=2

0~255 (min), default is 0


TMPLS=<min>

TMPH Setup high point of interior temperature normal range


Write
Command

Parameters
<Val>: -127~128

Example:
TMPH=30

0 means disable the function

Read
Command

TMPH=<Val>

TMPLS=?

Read
Command

TMPNDLY Setup timespan of ensure alarm status


Write

TMPH=?

Parameters

Command

<sec>:

Example:
TMPNDLY=2

0~255 (second), default is 0


TMPL Setup low point of interior temperature normal range
Write
Command

Parameters
<Val>: -127~128

TMPNDLY=<sec>
Example:
TMPL=10

TMPL=<Val>

Read
Command
TMPNDLY=?

Read
Command

TMPOS Setup lags of temperature alarm range


Write

TMPL=?

Parameters

Command

Parameters
<Val>: -127~128

<val>:

Example:
TMPOS=2

0~255

TMPB Setup temperature adjustments value


Write
Command

0 means disable the function

Example:
TMPB=2

TMPOS=<val>
Read
Command

TMPB=<Val>
TMPOS=?

Read
Command

TMPON

Enable temperature sensor alarm

Execution

TMPB=?

Command
TMPAS Setup the timespan of twice alarm sms
Write
Command
TMPAS=<min>

Parameters
<min>:

Example:

TMPON

TMPAS=2

0~255 (min), default is 0

TMPOFF Disable temperature sensor alarm

0 means disable the function

Execution

Read

Command

Command
TMPOFF
TMPAS=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

20

21

CWT5010 Commands

TMPURG

Setup temperature sensor alarm is urgency 24 hours

Write
Command
TMPURG=<En>
Read
Command

Parameters
<En>:
0: Disable
1: Enable

Example:
TMPURG=1

TMPC

Query current temperature value

Execution
Command
TMPC

TMPURG=?
TMPSND

Setup temperature sensor sound alarm

Write
Command
TMPSND=<En>
Read
Command

Parameters
<En>:
0: Disable
1: Enable

Example:
TMPSND=1

TMPSND=?
TMPIH Setup interlock output pin of high point
Write
Command
TMPIH=<DO>

Parameters
<DO>:
0~n (output index)
255 is none

Example:
TMPIH=0

Read
Command
TMPIH=?
TMPIL Setup interlock output pin of low point
Write
Command
TMPIL=<DO>

Parameters
<DO>:
0~n (output index)
255 is none

Example:
TMPIL=1

Read
Command
TMPIL=?
TMPR Query temperature normal range
Execution
Command
TMPR

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

22

23

CWT5010 Commands

Interior battery parameters


BATEN

Interlock parameters

Enable or disable power lost alarm

Write
Command

Parameters
<En>:

IOOC
Example:
BATEN=1

0: Disable
BATEN=<En>

Setup outputs action

Write
Command
IOOC=<nnnn><xxxx>

1: Enable

Read
Command
BATEN=?
POWDLY Setup time of ensure power alarm
Write
Command

Parameters
<sec>: 065535 seconds
Default is 5, 0 means disable the function

Example:

Parameters
<nnnn>: 0~3 Outputs action when alert by link with
<xxxx>: 0~3 Outputs action when recover by link with
n & x:
0: OPEN
1: CLOSE
2: CLOSE PULSE
3: CLOSE 300S
4: CLOSE 30S
5: CLOSE 60S
6: NONE

Read
Command

POWDLY=15
IOOC=?

POWDLY=<sec>
Read
Command

IOOA Setup link with


Write
Command

POWDLY=?
IOOA=<n><index>
POW Query power status
Execution

Parameters
<n>: 0~3 output index
<index>: link with index
0: NONE

3: 2 input alert

6: system power down

1: 0 input alert
2: 1 input alert

4: 3 input alert
5: Interior temp alert

7: Server call
8: humidity sensor

Command
Read
POW

Command
IOOC=?
Example: config output0 on when input3 alert and output0 off when input3 recover
The sms command is:
IOOC16660666
IOOA04

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

24

25

CWT5010 Commands

Action index:

Setup timers

0: None

14: Pulse OC 3

28: Howl alarm

1: Disarm

15: Snapshoot

29: Clocker

2: Arm

16: daily report sms

30: Enable buzzer

3: Driver OC 0 (output0 on)

17: Export state by uart0

31: Disable buzzer

Example:
Setup send daily report
sms at 17:50 everyday

4: Driver OC 1 (output1 on)

18: Upload state by sms

32: Upload din by gprs

5: Driver OC 2 (output2 on)

19: Exec user cmd0

33: Upload dout by gprs

6: Driver OC 3 (output3 on)

20: Exec user cmd1

34: Upload ain by gprs

mtimer0=17,50,16

7: OC 0 off

21: Exec user cmd2

35: Upload modbus by gprs

8: OC 1 off

22: Exec user cmd3

36: Upload graycode by gprs

9: OC 2 off

23: Exec user cmd4

37: Save samples to flash

10: OC 3 off

24: Exec user cmd5

38: Upload din counter

11: Pulse OC 0

25: Exec user cmd6

39: Din counter reset

12: Pulse OC 1

26: Upload state by gprs

13: Pulse OC 2

27: Buzzer beep

mtimer Setup system timers


Write
Command
mtimer<n>=<HH>,<MM>,<action>

Parameters
<n>: 0~5 (mtimer index)
<HH>: 0~24 (hour)
<MM>: 0~60 (minute)
<action>: 0~39

Read
Command
mtimer=?
mspan Setup minutes timers
Write
Command
mspan<n>=<min>,<action>
Read
Command

Parameters
<n>: 0~5 (mspan index)
<min>: 0~65535 (minute)
<action>: 0~39

Example:
Setup send daily report
sms every 30 minutes
mspan0=30,16

Parameters
<n>: 0~5 (mspan index)
<min>: 0~65535 (second)
<action>: 0~39

Example:
Setup send daily report
sms every 30 seconds
sspan0=30,16

mspan=?
sspan Setup second timers
Write
Command
sspan<n>=<min>,<action>
Read
Command
sspan=?
mdate

Setup week timers

Write
Command
mdate<n>=<day>,<HH>,<MM>,<action>

Parameters
<n>: 0~6
<day>: 0~6 (week day)
<HH>: 0~24 (hour)
<MM>: 0~60 (minute)
<action>: 0~39

Example:
Setup
send
daily
report sms at 18:34
Monday
Mdate0=0,18,34,16

Read
Command
mdate=?

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

26

27

CWT5010 Commands

Setup User command

System operation commands

U Setup the User defined commands


Write
Command
U<nn>=<string>

PW Setup system password

Parameters
<nn>:
00: User defined command 0
01: User defined command 1

Example:
Use abc instead of
command IOOH0
U00=abc

05: User defined command 5


<string>:

PW=<pad>
Read
Command

Read
Command

U<nn>=?

DAYRP

Y Setup the User defined commands mapped RTU commands

Y<nn>=<string>

Example:
PW=123456

DAYRP Query the RTU status (Daily report SMS)

Read
Command

Command

Parameters
<psd>: 6 digits

PW=?

user defined command contents


max 24 characters

Write

Write
Command

Parameters
<nn>:
00: RTU command 0
01: RTU command 1

05: RTU command 5


<string>:
RTU command contents
max 24 characters

Read
Command

ARM/BF
Example:
Use abc instead of
command IOOH0

Execution
Command
ARM

Y00=IOOH0
DISARM/CF Disarm the RTU system
Execution
Command
DISARM
RST

Y<nn>=?

Arm the RTU system

Reset the RTU power

Execution
Command
RST
LOADF

Load factory settings

Execution
Command
LOADF

SHEN ZHEN YIKEHUDONG TECHNOLOGY TRADE LTD TEL+86-755-26719954

www.mobq2000.com

28