The test report summarizes the results of an assessment of a current transformer. The current transformer passed all automatic and manual tests. Test results show the current transformer has a ratio of 300:4.9805, a phase angle of 10.7 minutes at rated current, and meets the performance requirements for metering current transformers according to the applicable standard.

Uploaded by

Sukryadhi Syamri
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views

R Core 1

The test report summarizes the results of an assessment of a current transformer. The current transformer passed all automatic and manual tests. Test results show the current transformer has a ratio of 300:4.9805, a phase angle of 10.7 minutes at rated current, and meets the performance requirements for metering current transformers according to the applicable standard.

Uploaded by

Sukryadhi Syamri
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Test Report

Date/Time:

2015-01-06, 18:21:09 AM

Assessment

Auto

Manual

Passed

Location
Company:
Station:
Phase:

pt pln kendari
pltd wuawua
R

Country:
Feeder:
IEC-ID:

kendari
konda

CT Nameplate
Manufacturer:
Type:
Serial Number:

Ratio:
Frequency:
Nominal Burden:

current electric (PTY) ltd


BS 7626
33342.3

Tap:
Core Number:
Optional 1:

1s1_1s2
1

300:5
50Hz
22.5 VA

Core Type:
Class:
Operating Burden:

Metering CT
0.5 - FS 5 ext. 120% (IEC 60044-1)
22.5 VA

CT-Analyzer
HC874C

Software Version:
Hardware Version:

4.10 (11-07-06 14:34)


01/00/07/05/00/11

Equipment
Test Device:
Serial Number:

Test Settings:
min. VA at M-cores Isn 5A:
Primary Current I-pn:
Secondary Current I-sn:

300.0A
5.0A

Frequency:

50.0Hz

Applied Standard:
Class:
Rct:

FS:

Nominal Burden:
Operating Burden:

IEC 60044-1

Core Type:

5.0 ?

Ext:

Assessments:
Auto

Manual

Passed
Passed
Passed
Passed
Passed

Resistance
Secondary Winding:
R-meas:
R-ref:

307.4m
366.6m

Metering CT

0.367 ? (75.0C)

1.000

Delta compensation: Ratio 1


?
Value is automatically detected by CT Analyzer's guesser function

Class
...
...
FS
FSi

22.5VA ? cos : 0.8 ?


22.5VA ? cos : 0.8 ?

0.5 ? - FS 5 ext. 120% ?

Multiplying Factor for Ratio Assessment:

Parameter

3.75VA

T-meas:
T-ref:

25.0C
75.0C

120%

Ratio:

Results with nominal Burden:


Used Burden:
Used I-p:
Ratio:
Deviation:
-c:
RCF:
N:
Phase:
Polarity:

22.5 VA cos : 0.8


300.00A
300.0 : 4.9805
-0.390%
0.530%
1.00391
59.74
10.70min
OK

Burden

Current ratio error in % at % of rated current

Designation

VA / cos

1.0 %

5.0 %

10 %

20 %

50 %

100 %

120 %

200 %

22.50 / 0.8

-1.210

-0.771

-0.670

-0.581

-0.481

-0.390

-0.365

-0.284

11.25 / 0.8

-0.650

-0.309

-0.240

-0.189

-0.130

-0.090

-0.078

-0.040

5.625 / 0.8

-0.327

-0.061

-0.010

0.025

0.061

0.083

0.089

0.108

3.75 / 1.0

-0.011

0.131

0.160

0.178

0.192

0.198

0.200

0.204

Burden

Phase displacement in minutes at % of rated current

Designation

VA / cos

1.0 %

5.0 %

10 %

20 %

50 %

100 %

120 %

200 %

22.50 / 0.8

42.17

28.62

24.72

20.79

15.84

10.70

9.02

4.70

11.25 / 0.8

35.40

22.26

19.44

16.82

13.52

10.89

10.01

7.07

5.625 / 0.8

32.98

18.91

16.52

14.49

11.92

10.08

9.56

7.76

3.75 / 1.0

36.83

21.02

18.43

16.34

13.76

12.00

11.50

9.89

NOTE: Measurements with '!' have reduced accuracy. Accuracy only guaranteed on non-gapped
cores.

Excitation:
Used Standard:

IEC 60044-1

Results:
Kr:

Knee Points:

86%

Lm:

543.0mH

Ls:

291.3H

100%
Nom.Burden
50%
Nom.Burden
25%
Nom.Burden
3.75 VA

100%
Nom.Burden
50%
Nom.Burden
25%
Nom.Burden
3.75 VA

Standard

IEC 60044-1 21.83V 143.9mA


IEC 60044-6 20.32V 182.5mA
Results with nominal Burden:
Burden:
FS:
FSi:
Ts:
-i:

22.5 VA cos : 0.8


>4.76
4.47
0.4997s
>18.79% (@ FS = 5.0)

Results with operating burden:


Burden:
FS:
FSi:
Ts:
-i:

22.5 VA cos : 0.8


>4.76
4.47
0.4997s
>18.79% (@ FS = 5.0)

Excitation Table:

V/V

Actual Values
UCTrms

ICTrms

27.72V
27.45V
27.16V
26.88V
26.60V
26.30V
25.97V
25.59V
25.13V
23.97V
22.59V
21.08V
19.50V
17.94V
16.49V
15.16V
12.90V
7.120V
3.929V
2.168V
1.002V
0.660V
0.363V
0.200V
0.111V

4.265A
3.088A
2.210A
1.570A
1.129A
820.3mA
598.8mA
448.1mA
337.8mA
212.7mA
158.0mA
130.8mA
114.0mA
102.2mA
93.38mA
86.31mA
77.84mA
51.15mA
32.89mA
20.15mA
10.46mA
7.392mA
4.459mA
2.708mA
1.671mA

8.8mH
12.5mH
17.5mH
24.5mH
34.2mH
47.7mH
66.6mH
91.5mH
126.4mH
228.0mH
351.9mH
463.7mH
545.4mH
607.6mH
631.7mH
628.3mH
543.0mH
447.3mH
382.1mH
343.5mH
301.4mH
282.9mH
257.3mH
232.6mH
207.4mH

20
10
5

2
1
0 .5

0 .2

I /A

0 .1
1m

10 m

10 0m