Components and Cladding

1. This document performs a wind load analysis for a building located in Palawan, Philippines. 2. Key parameters are extracted from wind load tables and figures, including the basic wind speed, various exposure factors, and external pressure coefficients. 3. The building is divided into zones, and the wind pressure and load are calculated for each zone based on the zone's area and the external pressure coefficients.

Uploaded by

Claudio Lopera
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views

Components and Cladding

1. This document performs a wind load analysis for a building located in Palawan, Philippines. 2. Key parameters are extracted from wind load tables and figures, including the basic wind speed, various exposure factors, and external pressure coefficients. 3. The building is divided into zones, and the wind pressure and load are calculated for each zone based on the zone's area and the external pressure coefficients.

Uploaded by

Claudio Lopera
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Kent Gem O.

Betita
BSCE-VB
WIND LOAD ANALYSIS
1. V = 150 kph, zone 3A (Palawan; table 207-11)
2. Kd = 0.85; Building (Main wind force resisting system) Table 207 -2
Iw = 1.15; Essential Occupancy (commercial bldg. more than 1 storey );
Table 207 3
3.
4.
5.
6.

Kz = 0.89; z (21m); (Exposure B); Case 1


Kzt = 1; Section 207.5.7
G=0.85
Enclosed Building; Section 207.5.9.
7. Internal pressure coefficient GCpi = 0.18; Fig. 207-5
8. External pressure coefficients GCp ; Components and Cladding; Figure
207 -11c

3 2

8.71

126

14.6984

2
36

126

12.3564

1
17.5000

10.0625

2
3 2

54

29.2651

40.0000

Zone 3 = 2.75 x 2.75 = 7.5625 x 4 = 30.25m ; GCp = +3, -2


Zone 2 = (445.63-221.19) x 2 + (174.38-36) x 2 = 725.64m ; GCp= +3, -1.2
Zone 1 = (221.19 + 36) x 2 = 514.38m ; GCp = +3, -0.8

47.3 10 6

9. Velocity pressure qz = (
) (0.81 )(1)(0.85)(150)2(1.15)
Qz = 0.84265 kPa
10.
Low-Rise Buildings and Buildings with h < 18 m; Components
and Cladding. Design wind load p=
p qz (GC p ) (GC pi )

kPa

Zone 1, 2 & 3
P13=0.84265 ((+0.3) (0.18)) =+.101, +.404

(kpa)

Zone 1
P1 = 0.84265((-0.8) (0.18)) = -.8256, -0.5224

(kpa)

Zone 2
P =0.84265((-1.2) (0.18)) = -1.1629, -0.86

(kpa)

Zone 3
P3 = 0.84265((-2.0) (0.18)) = -1.837, -1.5336

(kpa)

2.7500
10.0000

Zone 3 = 2.75 x 2.75 = 7.5625 x 8 = 60.5m ; GCp = +3, -2


Zone 2 = (10 x 2.75) x 4 + (34.5 x 2.75) x 4 = 489.5m ; GCp= +3, -1.2
Zone 1 = (34.5 x 10) x 2 = 690.m ; GCp = +3, -0.8