Electrical Science 2
Electrical Science 2
AC GENERATOR COMPONENTS
Field
The field in an AC generator consists of coils of conductors within the generator that receive a
voltage from a source (called excitation) and produce a magnetic flux. The magnetic flux in the
field cuts the armature to produce a voltage. This voltage is ultimately the output voltage of the
AC generator.
Armature
The armature is the part of an AC generator in which voltage is produced. This component
consists of many coils of wire that are large enough to carry the full-load current of the
generator.
Prime Mover
The prime mover is the component that is used to drive the AC generator. The prime mover may
be any type of rotating machine, such as a diesel engine, a steam turbine, or a motor.
Rotor
The rotor of an AC generator is the rotating component of the generator, as shown in Figure 1.
The rotor is driven by the generators prime mover, which may be a steam turbine, gas turbine,
or diesel engine. Depending on the type of generator, this component may be the armature or
the field. The rotor will be the armature if the voltage output is generated there; the rotor will
be the field if the field excitation is applied there.
Stator
The stator of an AC generator is the part that is stationary (refer to Figure 1). Like the rotor,
this component may be the armature or the field, depending on the type of generator. The stator
will be the armature if the voltage output is generated there; the stator will be the field if the
field excitation is applied there.
Slip Rings
Slip rings are electrical connections that are used to transfer power to and from the rotor of an
AC generator (refer to Figure 1). The slip ring consists of a circular conducting material that is
connected to the rotor windings and insulated from the shaft. Brushes ride on the slip ring as
the rotor rotates. The electrical connection to the rotor is made by connections to the brushes.
Slip rings are used in AC generators because the desired output of the generator is a sine wave.
In a DC generator, a commutator was used to provide an output whose current always flowed
in the positive direction, as shown in Figure 2. This is not necessary for an AC generator.
Therefore, an AC generator may use slip rings, which will allow the output current and voltage
to oscillate through positive and negative values. This oscillation of voltage and current takes
the shape of a sine wave.
Summary
The prime mover is the component that is used to drive the AC generator.
The rotor of an AC generator is the part that is driven by the prime mover
and that rotates.
Slip rings are electrical connections that are used to transfer power to and
from the rotor of an AC generator.
AC GENERATOR THEORY
Theory of Operation
The frequency of the generated voltage is dependent on the number of field poles and the speed
at which the generator is operated, as indicated in Equation (10-1).
NP
f = (10-1)
120
where
f = frequency (Hz)
P = total number of poles
N = rotor speed (rpm)
120 = conversion from minutes to seconds and from poles to pole pairs
The 120 in Equation (10-1) is derived by multiplying the following conversion factors.
60 seconds 2 poles
x
1 minute pole pair
Losses in an AC Generator
The load current flows through the armature in all AC generators. Like any coil, the armature
has some amount of resistance and inductive reactance. The combination of these make up what
is known as the internal resistance, which causes a loss in an AC generator. When the load
current flows, a voltage drop is developed across the internal resistance. This voltage drop
subtracts from the output voltage and, therefore, represents generated voltage and power that is
lost and not available to the load. The voltage drop in an AC generator can be found using
Equation (10-2).
where
Ia = armature current
Ra = armature resistance
XLa = armature inductive reactance
Hysteresis Losses
Hysteresis losses occur when iron cores in an AC generator are subject to effects from a
magnetic field. The magnetic domains of the cores are held in alignment with the field in
varying numbers, dependent upon field strength. The magnetic domains rotate, with respect to
the domains not held in alignment, one complete turn during each rotation of the rotor. This
rotation of magnetic domains in the iron causes friction and heat. The heat produced by this
friction is called magnetic hysteresis loss.
To reduce hysteresis losses, most AC armatures are constructed of heat-treated silicon steel,
which has an inherently low hysteresis loss. After the heat-treated silicon steel is formed to the
desired shape, the laminations are heated to a dull red and then allowed to cool. This process,
known as annealing, reduces hysteresis losses to a very low value.
Mechanical Losses
Rotational or mechanical losses can be caused by bearing friction, brush friction on the
commutator, and air friction (called windage), which is caused by the air turbulence due to
armature rotation. Careful maintenance can be instrumental in keeping bearing friction to a
minimum. Clean bearings and proper lubrication are essential to the reduction of bearing friction.
Brush friction is reduced by ensuring: proper brush seating, proper brush use, and maintenance
of proper brush tension. A smooth and clean commutator also aids in the reduction of brush
friction. In very large generators, hydrogen is used within the generator for cooling; hydrogen,
being less dense than air, causes less windage losses than air.
Efficiency
Efficiency of an AC generator is the ratio of the useful power output to the total power input.
Because any mechanical process experiences some losses, no AC generators can be 100 percent
efficient. Efficiency of an AC generator can be calculated using Equation (10-3).
Output
Efficiency x 100 (10-3)
Input
Example: Given a 5 hp motor acting as the prime mover of a generator that has a load
demand of 2 kW, what is the efficiency of the generator?
Solution:
In order to calculate efficiency, the input and output power must be in the same
units. As described in Thermodynamics, the horsepower and the watt are
equivalent units of power.
ft lbf 1 kW 1000 w W
550 746
sec ft lbf 1 kW hp
737.6
1hp sec
W
Input Power = 5 hp x 746 3730 W
hp
Output 2000 W
Efficiency = 0.54 x 100 54%
Input 3730 W
Summary
AC GENERATOR OPERATION
Ratings
Paralleling AC Generators
Most electrical power grids and distribution systems have more than one AC generator operating
at one time. Normally, two or more generators are operated in parallel in order to increase the
available power. Three conditions must be met prior to paralleling (or synchronizing) AC
generators.
Their terminal voltages must be equal. If the voltages of the two AC generators are not
equal, one of the AC generators could be picked up as a reactive load to the other AC
generator. This causes high currents to be exchanged between the two machines, possibly
causing generator or distribution system damage.
Their output voltages must be in phase. A mismatch in the phases will cause large
opposing voltages to be developed. The worst case mismatch would be 180 out of
phase, resulting in an opposing voltage between the two generators of twice the output
voltage. This high voltage can cause damage to the generators and distribution system
due to high currents.
During paralleling operations, voltages of the two generators that are to be paralleled are
indicated through the use of voltmeters. Frequency matching is accomplished through the use
of output frequency meters. Phase matching is accomplished through the use of a synchroscope,
a device that senses the two frequencies and gives an indication of phase differences and a
relative comparison of frequency differences.
Types of AC Generators
As previously discussed, there are two types of
AC generators: the stationary field, rotating
armature; and the rotating field, stationary
armature.
This type of AC generator has several advantages over the stationary field, rotating armature AC
generator: (1) a load can be connected to the armature without moving contacts in the circuit;
(2) it is much easier to insulate stator fields than rotating fields; and (3) much higher voltages
and currents can be generated.
Three-Phase AC Generators
The principles of a three-phase generator are basically
the same as that of a single-phase generator, except
that there are three equally-spaced windings and three
output voltages that are all 120 out of phase with
one another. Physically adjacent loops (Figure 7) are
separated by 60 of rotation; however, the loops are
connected to the slip rings in such a manner that
there are 120 electrical degrees between phases.
AC Generator Connections
As shown in Figure 7, there are six leads from the
armature of a three-phase generator, and the output is
connected to an external load. In actual practice, the
windings are connected together, and only three leads are
brought out and connected to the external load.
An advantage of a wye-connected AC generator is that each phase only has to carry 57.7% of
line voltage and, therefore, can be used for high voltage generation.
Summary
The important information covered in this chapter is summarized below.
Power (kW) ratings of an AC generator are based on the ability of the prime
mover to overcome generation losses and the ability of the machine to dissipate
the heat generated internally. The current rating of an AC generator is based on
the insulation rating of the machine.
The disadvantage of a stationary field, rotating armature is that the slip-ring and
brush assembly is in series with the load circuits and, because of worn or dirty
components, may interrupt the flow of current.
A stationary armature, rotating field generator has several advantages: (1) a load
can be connected to the armature without moving contacts in the circuit; (2) it
is much easier to insulate stator fields than rotating fields; and (3) much higher
voltages and currents can be generated.
ELECTRICAL SCIENCE
Module 11
Voltage Regulators
Voltage Regulators TABLE OF CONTENTS
TABLE OF CONTENTS
LIST OF FIGURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
OBJECTIVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
VOLTAGE REGULATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Block Diagram Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Sensing Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Reference Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Comparison Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Amplification Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Signal Output Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Feedback Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Changing Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LIST OF FIGURES
LIST OF TABLES
NONE
REFERENCES
Academic Program for Nuclear Power Plant Personnel, Volume IV, Columbia, MD:
General Physics Corporation, Library of Congress Card #A 326517, 1982.
Academic Program for Nuclear Power Plant Personnel, Volume II, Columbia, MD:
General Physics Corporation, Library of Congress Card #A 326517, 1982.
Nasar and Unnewehr, Electromechanics and Electric Machines, John Wiley and Sons.
Van Valkenburgh, Nooger, and Neville, Basic Electricity, Vol. 5, Hayden Book Company.
Lister, Eugene C., Electric Circuits and Machines, 5th Edition, McGraw-Hill.
Croft, Carr, Watt, and Summers, American Electricians Handbook, 10th Edition, McGraw-
Hill.
Mileaf, Harry, Electricity One - Seven, Revised 2nd Edition, Hayden Book Company.
Buban and Schmitt, Understanding Electricity and Electronics, 3rd Edition, McGraw-Hill.
TERMINAL OBJECTIVE
1.0 Given a block diagram, DESCRIBE the operation of a typical voltage regulator.
ENABLING OBJECTIVES
1.2 Given a block diagram of a typical voltage regulator, DESCRIBE the function of
each of the following components:
a. Sensing circuit
b. Reference circuit
c. Comparison circuit
d. Amplification circuit(s)
e. Signal output circuit
f. Feedback circuit
VOLTAGE REGULATORS
Because the voltage from an AC generator varies as the output load and power
factor change, a voltage regulator circuit is necessary to permit continuity of the
desired output voltage.
Purpose
The purpose of a voltage regulator is to maintain the output voltage of a generator at a desired
value. As load on an AC generator changes, the voltage will also tend to change. The main
reason for this change in voltage is the change in the voltage drop across the armature winding
caused by a change in load current. In an AC generator, there is an IR drop and an IXL drop
caused by the AC current flowing through the resistance and inductance of the windings. The
IR drop is dependent on the amount of the load change only. The IXL drop is dependent on not
only the load change, but also the power factor of the circuit. Therefore, the output voltage of
an AC generator varies with both changes in load (i.e., current) and changes in power factor.
Because of changes in voltage, due to changes in load and changes in power factor, AC
generators require some auxiliary means of regulating output voltage.
Figure 1 shows a typical block diagram of an AC generator voltage regulator. This regulator
consists of six basic circuits that together regulate the output voltage of an AC generator from
no-load to full-load.
Sensing Circuit
The sensing circuit senses output voltage of the AC generator. As the generator is loaded or
unloaded, the output voltage changes, and the sensing circuit provides a signal of these voltage
changes. This signal is proportional to output voltage and is sent to the comparison circuit.
Reference Circuit
The reference circuit maintains a constant output for reference. This reference is the desired
voltage output of the AC generator.
Comparison Circuit
The comparison circuit electrically compares the reference voltage to the sensed voltage and
provides an error signal. This error signal represents an increase or decrease in output voltage.
The signal is sent to the amplification circuit.
Amplification Circuit
The amplification circuit, which can be a magnetic amplifier or transistor amplifier, takes the
signal from the comparison circuit and amplifies the milliamp input to an amp output, which is
then sent to the signal output, or field, circuit.
The signal output circuit, which controls field excitation of the AC generator, increases or
decreases field excitation to either raise or lower the AC output voltage.
Feedback Circuit
The feedback circuit takes some of the output of the signal output circuit and feeds it back to the
amplification circuit. It does this to prevent overshooting or undershooting of the desired voltage
by slowing down the circuit response.
Let us consider an increase in generator load and, thereby, a drop in output voltage. First, the
sensing circuit senses the decrease in output voltage as compared to the reference and lowers its
input to the comparison circuit. Since the reference circuit is always a constant, the comparison
circuit will develop an error signal due to the difference between the sensed voltage and the
reference voltage. The error signal developed will be of a positive value with the magnitude of
the signal dependent on the difference between the sensed voltage and the reference voltage.
This output from the comparison circuit will then be amplified by the amplifier circuit and sent
to the signal output circuit. The signal output circuit then increases field excitation to the AC
generator. This increase in field excitation causes generated voltage to increase to the desired
output.
If the load on the generator were decreased, the voltage output of the machine would rise. The
actions of the voltage regulator would then be the opposite of that for a lowering output voltage.
In this case, the comparison circuit will develop a negative error signal whose magnitude is again
dependent on the difference between the sensed voltage and the reference voltage. As a result,
the signal output circuit will decrease field excitation to the AC generator, causing the generated
voltage to decrease to the desired output.
Summary
Amplification circuit(s) - takes the signal from the comparison circuit and
amplifies the milliamp input to an amp output