Drainages Lined Drain

This document summarizes the design of a drainage system for a site in Kuantan, Pahang, Malaysia. It includes: 1) Calculations to determine the design flow rate of 5.21 m3/s for a 10-year average recurrence interval using rainfall intensity equations and site parameters. 2) Selection of a drain size with a minimum 0.4m depth and 0.6m width to convey the design flow based on Manning's equation. 3) Recommendation of a drain with 0.6m width and 0.4m depth, but noting the calculated flow velocity of 0.25 m/s is lower than required minimum of 0.6 m/s.

Uploaded by

Kazer Othman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
113 views2 pages

Drainages Lined Drain

This document summarizes the design of a drainage system for a site in Kuantan, Pahang, Malaysia. It includes: 1) Calculations to determine the design flow rate of 5.21 m3/s for a 10-year average recurrence interval using rainfall intensity equations and site parameters. 2) Selection of a drain size with a minimum 0.4m depth and 0.6m width to convey the design flow based on Manning's equation. 3) Recommendation of a drain with 0.6m width and 0.4m depth, but noting the calculated flow velocity of 0.25 m/s is lower than required minimum of 0.6 m/s.

Uploaded by

Kazer Othman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

No.

Project
pez
Drainage Design

Design:
calculation

ref.

Fana

Checked

date:
Sheet:
Rev:

Ir.Veera

output

Determine design flow for the drain:


Eqn 2.2

Table 1.1

i=k
(d + )
where :
i=
T=
d=
,k,, =

Appendix 2.B
Table 2.B2

i=
Eqn 2.3

The avarage rainfall intensity (mm/hr) for selected ARI (T) and storm duration (d);
average recurrence interval, ARI (years);
storm duration (hours); 0.20 < d < 72 and
fitting constants dependent on the raingauge location

Location &
Station ID

ARI,T
(years)

Storm
duration d

kuantan,
Pahang

10

0.333

45.999

126.73

Derived parameter
k

0.210

0.074

mm/h

0.590
=

126.73 mm/h

Q = C.I.A
360
where :
Q=
C=
I=
A=

peak flow (m3/s);


dimensionless runoff coefficient;
average rainfall intensity over time of concentration, tc (mm/hr); and
drainage area (ha).

Q5 = 76.4812880821
360

=
0.85
= 126.72956 mm/h
=
0.71
ha
=

0.21

Manning's n for concrete lining

0.015

Assuming:
Drain longitudinal slope
Width, B
Side slope, Z

=
=
=

0.2
0.6
0

m3/s

calculation size of lined drain section


Table 2.3

%(1 in 250)

No.Project
date:
Sheet:
Rev:
output

pez
Drainage Design
ref.

Design:
calculation

Zer

Checked

Ir.Veera

Q =vxA
where :

v = (1/n) So1/2 R2/3 ;


A = (B + ZD)D = 0.90D
P = B + 2D ( 1 + Z2)0.5 = 0.9 + 2D
D (m)
0.30
0.40
0.45
0.60
Q=

Section
14.2.4.2

A (m2)
0.180
0.240
0.270
0.360

P (m)
1.20
1.40
1.50
1.80

0.22 (m3/s)

R (m)
0.15
0.17
0.18
0.20
>

v (m/s)
0.84
0.92
0.95
1.02

Q (m3/s)
0.152
0.221
0.257
0.367

Q5

OK

Allowing a minimum freeboard

50

mm

Hence, required depth, Dminimum

0.4

Provided dimention of lined drain drain (refer to precast concrete manufacturers):


width, B
Depth,D
Velocity, v
Discharge,Q

=
=
=
=

0.6
0.4
0.25
0.3

m
m
m/s
m3/s

The drain dimensions are 0.60m wide X 0.40m deep, which is within the recommended limits.
Check flow velocity for lined drain, v

Depth between 0.6 and 1.2m, drain shall be covered.


services opening shall be provided along open drain with maximum internal spacing at every 100 m

0.25 m/s
(0.6 <v <2 m/s)
NOT OK