Contoh Beton

The document shows a plan and details for building 2 level 2 concrete structure. It includes a general arrangement plan showing slab layout and reinforcement, a reinforcement plan showing rebar layout and schedules, and column and edge beam details.

Uploaded by

naffian2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
187 views

Contoh Beton

The document shows a plan and details for building 2 level 2 concrete structure. It includes a general arrangement plan showing slab layout and reinforcement, a reinforcement plan showing rebar layout and schedules, and column and edge beam details.

Uploaded by

naffian2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

AA

AB

AC

AD

AE

AF

AG

AH

AJ

AK

BUILDING 5
BUILDING 4

4
B2

C2
-C
2
B

900 x 300

1
CC
B2

900 x 300
1
CC
B2

BUILDING 2
900 x 300

C2
-C
2
B

900 x 300

A9

7
CC
B2

C2
-C
2
B

900 x 300

A10

1
CC

900 x 300

SR-B

1
CC
B2

A8

SR-B

C2
-C
2
B

SR-B

C3
-C
2
B

SR-B

C3
-C
2
B

SR-B

2
CC
B2

250

KEYPLAN

7
CC
B2

SR-B

900 x 300

900 x 300

250

C2
-C
2
B

1
CC
B2

B2-ST1

SR-B
1
CC
B2

50

C2
-C
2
B

900 x 300

900 x 300

C2
-C
2
B

900 x 300

SR-B

900 x 300

C2
-C
2
B

CONSTRUCTION JOINT
900 x 300

A5

11

CONSTRUCTION JOINT

900 x 300

1
CC
B2

C2
-C
2
B

S333

900 x 300

A6

SR-B

11

900 x 300

900 x 300

C2
-C
2
B
C2
-C
2
B

A4

SR-B

900 x 300

900 x 300

1
CC
B2
900 x 300

7
CC
B2

C2
-C
2
B

DELAYED POUR

50

2
CC
B2

900 x 300

A7

SR-B

900 x 300

C2
-C
2
B

C1
-C
2
B

C2
-C
2
B

900 x 300

1
CC
B2

C1
-C
2
B

C2
-C
2
B

STRIP

B2-ST1

900 x 300

900 x 300

900 x 300

1
CC
B2

C2
-C
2
B

SR-B
250

C3
-C
2
B

SR-A

C3
-C
2
B

SR-B

C3
-C
2
B

C2
-C
2
B

SR-B

SR-A

C3
-C
2
B

SR-A

C3
-C
2
B

C2
-C
2
B

B2-ST2

250

900 x 300

A3

SR-B

900 x 300

900 x 300

900 x 300

900 x 300

A1

1
CC
B2

900 x 300

BUILDING 2 - LEVEL 2 GENERAL ARRANGEMENT PLAN


SCALE: 1 : 100

NOTES:

FOR GENERAL NOTES REFER TO DRAWINGS S-2002 & S-2003

180

DENOTES SLAB THICKNESS

CONCRETE STRENGTH TO BE f'c = 40 MPa


REFER TO ARCHITECT'S DRAWINGS FOR EXTENTS OF HOBS, SETDOWNS,
FALLS AND GRADES ETC
WHERE ARCHITECT'S DRAWINGS INDICATES FALLS IN SLABS STRUCTURAL
SIZES SHOWN ARE THE MINIMUM ALLOWABLE THICKNESS
ALL EXTERNAL SLABS TO BE MEMBRANED / WATERPROOFED REFER TO
ARCHITECT'S DETAILS UNO
900 x 300
DENOTES BEAM IN SLAB (DEPTH x WIDTH)

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

SR-A

1
CC
B2

2
CC
B2

2
CC
B2

900 x 300

A2

900 x 300

2
CC
B2

1
CC
B2

2
CC
B2

2
CC
B2

900 x 300

900 x 300

2
CC
B2

3
CC
B2

2
CC
B2

900 x 300

BUILDING 2 - CONCRETE COLUMN SCHEDULE


MARK

SIZE

B2-CC1
B2-CC2
B2-CC3
B2-CC4
B2-CC5
B2-CC6
B2-CC7

300
350
400
450
500
550
600

4
3
2
1
REV

17-11-14
22-10-14
15-10-14
15-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

DENOTES COLUMN SHEAR RAIL TYPE


REFER DRG S-2501 FOR DETAILS
PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - LEVEL 2 GENERAL


ARRANGEMENT PLAN
PROJECT No.

P13378

DRAWING No.

REV.

S-2121

4
BG&E Pty Limited

AA

AB

AC

AD

AE

AF

AG

AH

AJ

AK

2200
B2-EB08
D (4)

D (4)

2200

2200

2200

D (4)

D (4)
B (2,3)
B (2,3)

D (4)

B (1,4) B (2,3)
B (1,4)
D (3)

D (3)

D (4)

D (4)

D (1,4)

D (3)

D (3)

N12-200 U BARS
1750 LONG
B (1,4)

D (3)

A6

2200

B2-EB04

D (4)

N16-200
U BARS

D (4)

B2-EB05

1750

2200

B2-EB03

2200

B (2,3)

D (4)

D (4)

D (4)

D (3)

D (3)

D (4)

D (3)

D (3)

2200

2200

D (3)

B2-EB01

B2-EB01
D (3)

2200
TYP

D (3)

2200
TYP

D (4)

2200

2200

2200

2200
TYP

D (4)

D (4)

2200

N12-200 U BARS
1750 LONG

2200

D (4)

D (3)

D (2)

N10-300

1750

A1

2200
TYP

D (3)

D (4)

2200
TYP

D (3)

2300

D (3)

2200
TYP

B2-EB01

2200

D (4)

B2-EB02

D (2,3)

D (3)

D (4)

D (3)

2200

D (3)

A2

2200

2200

D (3)

2200

2200
TYP

2200

B (4)

D (4)

1000
TYP

D (2,3)

B
(1)

D (3)

D (3)

D (4)

D (3)

2-N16 T & B

2200

300

2200
TYP

D (4)

D (3)
2200

B (1,4)

D (4)

D (4)

2-N20 T & B

B (2,3)

D (3)

2200

D (3)
2200

D (3)

D (3)

2200

B (1,4)

D (4)

D (3)

B (2,3)

N12-200 U BARS
1750 LONG

B2-EB02

N12-300 U
BARS 1200
LONG

D (4)

D (1,4)

B2-EB02

B (1,4)

J (1)
B (4)

2200
TYP

2200

D (3)

A4

B2-EB02

B (2,3)

D (4)

D (4)

J (3)

D (3)

2 N16 (2,3)
EXTRA

D (4)

2200

N12-200
U BARS
2-N16
T&B

2200

2200

B2-EB08

D (3)

2200

800

N12-200 U BARS
1750 LONG

2200

B
J(1)
(4)

D (4)

D (2,3)

N12-200 U
BARS 1750 LONG
D (1,4)

J (2)

D (3)
2200

D (3)

D (4)

N12-200 U
BARS 1750 LONG

D (4)

2200

B2-EB04

2300

D (4)

CONSTRUCTION
JOINT

B (2)
B (3)

B2-EB01

B (2,3)

D (4)

B2-EB05

2200

D (4)
B (1,4)

B2-EB01

A3

B2-EB02

J (1)
D (4)

B2-EB01
CONSTRUCTION JOINT

A5

B2-EB04

2-N16 T & B

D (3)

D (3)

2200

D (4)
D (4)

2200

B(2) B(3)

N12-300 U
BARS 1200 LONG

800

2200

D (3)

2 N16 (2,3)
EXTRA

D (4)

B (2,3)

D (4)

B (1,4)

N12-200 U BARS

2200

A7

B (2,3)
B (1,4)
N12-300 U
BARS 1200 LONG
B(1) J(4)

500

2200

B2-EB05

D (1,4)

2300

B2-EB04

D (4)

N12-300 U BARS
D (3)

N12-300 U BARS

D (4)

B2-EB02

2200

N12-200 U BARS
1750 LONG

D (3)

D (3)

D (3)

2200

D (3)

2200

D (3)

A8

D (4)

D (4)

D (3)

2200

D (3)

2200

2200

D (3)

D (4)

D (4)

D (3)

D (3)

2200
D (3)

B2-EB02

2200

2200

A9

D (4)

D (3)

B2-EB02

A10

B2-EB08

D (4)

2200

D (4)

D (4)

B2-EB08

2200

BUILDING 2 - LEVEL 2 REINFORCEMENT PLAN


SCALE: 1 : 100

A
B
C
D
E
F
G
H
J
K
M
N
P
R
S
T
V
W
X
Y

REINFORCEMENT TABLE
N12-350
N12-300
N12-250
N12-200
N12-150
N16-350
N16-300
N16-250
N16-200
N16-150
N16-100
N20-350
N20-250
N20-200
N20-175
N20-150
N20-100
N24-250
N24-200
N24-150

3N12

(4)

3
2
1
REV

17-11-14
15-10-14
15-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS
CLIENT

(3)
1200

(2)
(1)

N12-200 L BAR
NOTE: TOP LAYER L BAR NOT
REQUIRED WHERE REINFORCEMENT
OVER COLUMN IS PRESENT

REINFORCEMENT LAYERING LEGEND

LAYER

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

EDGE BEAM

BUILDING 2 - TYPICAL EDGE REINFORCEMENT DETAIL


SCALE: 1 : 20

G (3)

PROJECT

REINFORCEMENT & SPACING

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

NOTES:

DATUM

RE-ENTRANT BARS NOT SHOWN ON PLAN FOR CLARITY.


REFER TYP. DETAILS.
REBATES IN EDGEBEAMS FOR PRE-CAST PANEL
CONNECTIONS NOT SHOWN ON PLAN, REFER TO PRE-CAST
PANEL ELEVATIONS AND ARCH. CONCRETE OUTLINE PLAN
FOR DETAILS AND LOCATIONS.
REFER TO S-2145 FOR TYPICAL EDGE BEAM ELEVATIONS.

DESIGNED

JP

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - LEVEL 2 REINFORCEMENT


PLAN
PROJECT No.

P13378

DRAWING No.

S-2122

REV.

3
BG&E Pty Limited

AA

AB

AC

AD
350

350
1550
125

AE
350

1550
125

1700
125

1700

350
1550

125

AF
350

1550

125

1700

350
1550

1700

1300

1350

1350

350
1300

140

140

140

1700

700

140

1675

140

AK

100

185

100

185

55

750

350
350

140

AJ

125

125
175

AH

350

125

A10

AG

A9
1750

A8

100

205

205

205

35

55

185

100

185

185
35

35

35

35

35

205

205

205

205

75

205

205

205

1750

350

100

35

1750

350

350

205

75

100

125
55

1825

350

125

125

125

125
125

205

100

100

125

1750

55

185
35

205
185

205

205

55

55

1100

55

185

170

185

125
55

850

205

205

350

205
205

35

1000

1100

205
125

700

1000

125

350

350

A7

125

100

100

185

100

185

75

100

75

125

185

1800

55

125
75

205

205
55

185

75

185

185

185

125

350

205
1350

125

125

205

205

205
185

55

1000

100

CONSTRUCTION
125 JOINT

185

125

150

125

185

350
1350

CONSTRUCTION
JOINT

185

1400

125

A5
350

205

205

55

A6

350

1000

125

55

1100

125

125

185

800
1250

205

205

205

125

125

55
125

1375
1650

55

185

100

185

125

185

75

185

55

175

125

1400

1350

1550

140

140

125

1700

1700

1550

125

1550

350

350
350

140

140

125

1700

1700

1550

1550

350
350

BUILDING 2 - LEVEL 2 POST TENSIONING LAYOUT PLAN


SCALE: 1 : 100

140

140

125

125

1700

1700

1550

1550
350

350
350

140

800

1000 350

1375

125

350

185

1825

125

1650

35

125

55

1600

55

125

35

185

1400

100

1350

35

185

125

35

35

75

1675

350

205

1650

205

125

A1

185

100

185

35

350

350

1750

100

55

75

125

A2

350

205

350
1750

205

350

350

A3

205

205

205

350

205

350

205

150

1750

100

55

75

185

75

100

75

1825

1750

125

35

35

35

1825

205

1750

1800

1750

205

185

205

140

1300

185

55
205

350

125

205

125

205

350

205

55

205

75

55

185

185

75

170
125

A4

75
185

75

185

35

125

350
1000

1100 775

1425

125

350

1700

1700

1550

1550

350
350

1700

1700

1550

1750

350
350

1700

1850

850 700 1250

1850
350

350
350

1850

350

350

3
2
1
REV

17-11-14
15-10-14
15-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS
CLIENT

LEGEND

NOTES:
1.
2.
3.
4.

5.
6.

DENOTES TENDON LIVE END

ALL TENDONS TO CONSIST OF 5 x 12.7mm STRANDS U.N.O.


REFER DRAWING S-2503 FOR TYPICAL DETAILS AND ADDITIONAL
REINFORCEMENT.
BEAM TIES MAY BE LOCALLY RELOCATED WHEN CONFLICT EXISTS
WITH POST TENSIONING DUCT LOCATION.
ENSURE 100mm MINIMUM COVER (HORIZONTAL) TO PENETRATIONS
AND 30mm MINIMUM TO CAST-IN SLEEVES FROM EDGE OF POST
TENSIONING DUCT U.N.O.
REMOVAL OF PROPPING TO BE APPROVED BY ENGINEER.
TAGGING OF TENDONS:

DENOTES TENDON DEAD END

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

DENOTES TENDON COUPLER

DENOTES TENDON LIVE END IN PAN

PROJECT

TENDONS TAGGED TOGETHER


SHALL HAVE THE SAME
VERTICAL PROFILE U.N.O.
DENOTES SLAB CONSTRUCTION JOINT

DENOTES DELAYED POUR STRIP


STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1 : 100

AT

A0 SIZE

TITLE

BUILDING 2 - LEVEL 2 POST


TENSIONING LAYOUT PLAN
PROJECT No.

P13378

DRAWING No.

S-2123

REV.

3
BG&E Pty Limited

AA

AB

AC

AD

AE

AF

AG

AH

AJ

AK

BUILDING 5
BUILDING 4

4
C1
-C
2
B

C1
-C
2
B

1
CC
B2

900 x 300

1
CC
B2

900 x 300

A10

C1
-C
2
B

900 x 300

900 x 300

KEYPLAN

900 x 300

A9

C1
-C
2
B

900 x 300

1
CC
B2

BUILDING 2

1
CC
B2

A8

SR-B

1
CC
B2

SR-B

2
CC
B2

2
CC
B2

SR-B

SR-B

2
CC
B2
1
CC
B2

C1
-C
2
B

A7

SR-B

900 x 300

900 x 300

250

C1
-C
2
B

B2-ST1

C1
-C
2
B

900 x 300

C1
-C
2
B

C1
-C
2
B

900 x 300

900 x 300

S333

11

CONSTRUCTION JOINT

CONSTRUCTION JOINT
900 x 300

1 900 x 300
CC
B2

1
CC
B2

11

900 x 300

900 x 300

900 x 300

1
CC
B2
1
CC
B2

A4

SR-B

1
CC
B2

1
CC
B2

B2-ST1

DELAYED POUR

900 x 300

SR-B

A5

1
CC
B2

900 x 300

900 x 300

A6

SR-B

900 x 300

1
CC
B2
900 x 300

STRIP
900 x 300

900 x 300

1
CC
B2

SR-B

C2
-C
2
B

400 x 2400

SR-A

C2
-C
2
B

C1
-C
2
B

SR-B

SR-A

SR-A

B2-ST2

230

650 x 1200

C1
-C
2
B

1
CC
B2

A2

SR-B

C2
-C
2
B

650 x 1200

900 x 300

A3

SR-B

C1
-C
2
B

650 x 1200

1
CC
B2

900 x 300

250

900 x 300

500 x 1200

450 x 1200

1
CC
B2

1
CC
B2

1
CC
B2

1
CC
B2

1
CC
B2

A1

900 x 300

900 x 300

250
900 x 300

BUILDING 2 - LEVEL 3 GENERAL ARRANGEMENT PLAN


SCALE: 1 : 100

NOTES:

FOR GENERAL NOTES REFER TO DRAWINGS S-2002 & S-2003

180

DENOTES SLAB THICKNESS

CONCRETE STRENGTH TO BE f'c = 40 MPa


REFER TO ARCHITECT'S DRAWINGS FOR EXTENTS OF HOBS, SETDOWNS,
FALLS AND GRADES ETC
WHERE ARCHITECT'S DRAWINGS INDICATES FALLS IN SLABS STRUCTURAL
SIZES SHOWN ARE THE MINIMUM ALLOWABLE THICKNESS
ALL EXTERNAL SLABS TO BE MEMBRANED / WATERPROOFED REFER TO
ARCHITECT'S DETAILS UNO
900 x 300
DENOTES BEAM IN SLAB (DEPTH x WIDTH)

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

SR-A

DENOTES COLUMN SHEAR RAIL TYPE


REFER DRG S-2501 FOR DETAILS

900 x 300

900 x 300

BUILDING 2 - CONCRETE COLUMN SCHEDULE


MARK

SIZE

B2-CC1
B2-CC2
B2-CC3
B2-CC4
B2-CC5
B2-CC6
B2-CC7

300
350
400
450
500
550
600

4
3
2
1
REV

17-11-14
22-10-14
15-10-14
15-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - LEVEL 3 GENERAL


ARRANGEMENT PLAN
PROJECT No.

P13378

DRAWING No.

REV.

S-2131

4
BG&E Pty Limited

AB

AC

AD

AE

AF

AG

2200

D (4)

D (4)

2200

2200

D (4)

D (4)
B (2,3)
B (2,3)

D (4)

B (1,4) B (2,3)
B (1,4)
D (3)

D (3)

D (4)

D (4)

D (1,4)

D (3)

D (3)

N12-200 U BARS
1750 LONG
B (1,4)

D (3)

A6

B2-EB04

D (4)

CONSTRUCTION
JOINT

B (1,4)

B (1)

D (3)

300
2200
TYP

2200

2200

N10-300

1000
TYP

2-N20 T & B

B (2,3)

2200
TYP

1750

2200

TYP.

D (3)

D (3)

1750

D (3)

D (3)

D (3)

D (4)

D (4)

D (4)

B2-EB08

D (3)

TYP.

2200

D (4)

D (3)

2200

B (2,3)

D (4)
B2-EB01

D (4)

2200

B2-EB02

D (4)

2200

2200

500

2200

500

B2-EB05
2200

1750

B2-EB01

D (4)

B2-CB01

500

D (3)

TYP.

D (3)

500

2200

2200

2200
TYP

B2-CB01

500

D (4)

D (4)
2200

D (3)

2200

D (4)

500

D (4)

D (4)

D (3)

500

2200

D (4)

2200

A1

2200

500

B2-CB03
D (3)

2300

D (4)

B2-EB02

2200

B2-CB02

A2

D (4)

D (4)

2200

D (3)

2200

D (3)

D (4)

2200
TYP

D (4)
D (4)

D (4)
D (4)

D (3)

D (4)

B2-CB01

D (4)

D (3)

2200
TYP

J (3)

D (3)

D (3)

D (3)

N12-200 U BARS
1750 LONG

D (3)

A3

2200

B (4)
D (4)

2200

2200

2200

D (3)

2-N16 T & B

2200

2200

D (1,4)

2200

2200

B (2,3)

2200

D (3)

D (4)

B2-EB04

N12-300 U
BARS 1200
LONG

D (3)

B2-EB02

2200

B (2)
B (3)

B (1,4)

J (1)
B (4)

D (4)

D (2,3)

2200

B2-EB05

D (3)

A4

D (4)

D (4)
B (1,4)

B2-EB02

B (2,3)

D (4)

D (4)

2200

N12-200 U
BARS 1750 LONG

2200

D (3)

D (3)

D (3)

2200

2 N16 (2,3)
EXTRA

2200

B2-EB08

D (4)

N12-200
U BARS
2-N16
T&B

D (3)

N12-200 U BARS
1750 LONG

2200

B
J(1)
(4)

D (4)

D (2,3)

N12-200 U
BARS 1750 LONG
D (1,4)

800

D (4)

2300

D (4)

2200

B2-EB04

2200

D (3)

D (4)

2200

D (3)

B (2,3)

D (3)

B2-EB01

A5

2200

J (1)
D (4)

B (1,4)

B2-EB01

2200

B2-EB02

B2-EB01
CONSTRUCTION JOINT

B2-EB04

2-N16 T & B

B2-EB02

J (2)

D (3)

2200

D (4)
D (4)

2200

B(2) B(3)

N12-300 U
BARS 1200 LONG

800

2200

D (3)

2 N16 (2,3)
EXTRA

D (4)

B (2,3)

2200

B (1,4)

N12-200 U BARS

500

A7

B (2,3)
B (1,4)
N12-300 U
BARS 1200 LONG
B(1) J(4)

D (3)

2200

B2-EB05

D (1,4)

2300

B2-EB04

D (4)

N12-300 U BARS
D (3)

N12-300 U BARS

D (4)

B2-EB02

2200

N12-200 U BARS
1750 LONG

D (3)

D (3)

2200

D (3)

2200

D (3)

A8

D (4)

D (3)

D (3)

2200

D (3)

D (3)

2200

2200

2200

D (4)

D (4)

D (3)

2200

D (4)

D (3)

A9

D (3)

B2-EB02

2200

2200

AK

B2-EB08

D (4)
D (4)

D (3)

B2-EB02

A10

AJ

B2-EB08
D (4)

AH

2200

AA

2200
TYP.

BUILDING 2 - LEVEL 3 REINFORCEMENT PLAN

A2

AB

A3

AC

BEAM TIE SCHEDULE


MARK SIZE & SPACING

(2)
(1)

BT1

B2 L03

N12-400

BT1

7N20
N12-400 LIGS
IN SETS OF 2

N12-350

LAYER

SLAB (3)

4N16

4N16

4N16

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS

B2 L03
CLIENT

7N20

7N20

B2-CB02

7N20

BT2

B2-CB01

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

7N20

BEAM ELEVATION B2-CB01

BEAM ELEVATION B2-CB03

SCALE: 1 : 50

SCALE: 1 : 50

G (3)

A1

REINFORCEMENT & SPACING

4N16

SLAB (3)

A2

A3

A4

PROJECT

PT TENDON

11N20

6N20

B2-CC1

B2-CC1

B2-CC1

B2-CC1

4N16

6N20

B2 L03

SLAB (4)
SLAB (3)

11N20
B2 L03

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

BUILDING 2 - TYPICAL EDGE REINFORCEMENT DETAIL

BT1

BT1

BEAM ELEVATION B2-CB02

BEAM ELEVATION B2-CB04

SCALE: 1 : 50

SCALE: 1 : 50

11N16

BT1

11N16

BT1
B2-CC1

7N20

B2-CC2

BT1

BT1

7N20

B2-CC2

7N20

EDGE BEAM

SCALE: 1 : 20

4N16

11N20

SLAB (4)
SLAB (3)

B2-CC2

N12-200 L BAR
NOTE: TOP LAYER L BAR NOT
REQUIRED WHERE REINFORCEMENT
OVER COLUMN IS PRESENT

SLAB (4)

B2-CC1

RE-ENTRANT BARS NOT SHOWN ON PLAN FOR CLARITY.


REFER TYP. DETAILS.
REBATES IN EDGEBEAMS FOR PRE-CAST PANEL
CONNECTIONS NOT SHOWN ON PLAN, REFER TO PRE-CAST
PANEL ELEVATIONS AND ARCH. CONCRETE OUTLINE PLAN
FOR DETAILS AND LOCATIONS.
REFER TO S-2145 FOR TYPICAL EDGE BEAM ELEVATIONS.

A1

A2

3N12

NOTES:

PT DUCT

4N16
SLAB (3)

17-11-14
15-10-14
15-08-14
DATE

EQ EQ EQ

1200

4N16

7N20

BT1

PT DUCT

SLAB (3)

PT TENDON

DESCRIPTION
EQ EQ EQ

REINFORCEMENT LAYERING LEGEND

4N16

SLAB (4)

3
2
1
REV

B2-CC3

(3)

B2-CC2

A
B
C
D
E
F
G
H
J
K
M
N
P
R
S
T
V
W
X
Y

REINFORCEMENT TABLE
N12-350
N12-300
N12-250
N12-200
N12-150
N16-350
N16-300
N16-250
N16-200
N16-150
N16-100
N20-350
N20-250
N20-200
N20-175
N20-150
N20-100
N24-250
N24-200
N24-150

SLAB (4)

B2-CC1

(4)

B2-CC2

B2-CC1

SCALE: 1 : 100

B2-CC1

A1

DESIGNED

JP
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - LEVEL 3 REINFORCEMENT


PLAN
PROJECT No.

P13378

DRAWING No.

S-2132

REV.

3
BG&E Pty Limited

AA

AB

AC

AD

350

350

350
1450

1550
125

125

AE

1700
125

1700

1550
125

1700

1700

AG

350

350

1650

125

AF

350

350

350

1550

1300

1350

125

175

140

100

185

140

140

140

140

140

1675

350

350

100

185

55

750

125

125

35

1750

350

205

75

100

100

205

205

205

35

35

55

185

100

185

100

185

55

1825

125

35

35

35

35

205

205

205

205

75

350
1750

350

A9

125
125

125

125

AK

1500

125

A10

AJ

350

1300

1350

AH

205

205

205

205

1750

350

A8

100
125
55

185

350

205

205

1100

850

205

55

55

55

170

185

125
55
35

205

205

125

185

75

185

185

1000

125

185

55

1100

125
125

700

1100

1000

205

55

1000

205

35

3
185

205

205
350

125

205

185

A7

125

100

100

185

100

75

185

75

350
1750

75

100

125

185

1800

55

125

1350

205

205

125

125

125

150

100

185

55

1350

CONSTRUCTION
JOINT
125
125

205

205

CONSTRUCTION
125 JOINT

185

185

185

55

1000

205
350

350

A5

205

125

1400

350
350

A6

125

125

200
125

1300

185

55

205

35

75

205

205

75

75

35

35

35

205

465

35

50

1825

1800

1750

205

125

350

205
1825

205

1750

125

170
205

140
115

350

205

205

205

800

205 205

55

185

75

75

185

185

75

125
350
350

A4

185

55

75
35

1250

125

1000

1100 775

1425

125

150

100

1650
1650

55

185

125

185

75

185

55
55

55

185
185

200

140

200

140

140

125
115

200

140

500

415

350

1375

205
140

355
125

355

125

125

125

125

125

125

125

355

125

125

350

1650

55

185
185
185

250

350

A1

205

125

800

175

35

185

50

50

1925

350

35

100

205

35

100

35
185

205

170

100

185

100
205

185

1600
125

465

35

50

50

185 185

125

50

75

1400

185 185

1500

1350

280

185 185

1750

100

350

205

315

350

1750

55

185

100

185

125

1375

205

55

385

185

55

185
385
465

125
185

100

55

125

205
350
350

205

315
125

A2

205

205

1750

A3

350
350

465
205

100

385

185

100

185

1750

55

125

200

125

125

350

350

450
1400

1400

1600

1650

1650

1600

1450
350

350
350

350

BUILDING 2 - LEVEL 3 POST TENSIONING LAYOUT PLAN


SCALE: 1 : 100

1800

1650

1600

1600
350
350

1650

1650

450

1600
350
350

2050

1625

1625

1550

1550
350
350

1700

1700

1550

1750
350
350

1800

1750

1550
350
350

1250

1850

1850
350
350

3
2
1
REV

17-11-14
15-10-14
15-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS
CLIENT

LEGEND

NOTES:
1.
2.
3.
4.

5.
6.

DENOTES TENDON LIVE END

ALL TENDONS TO CONSIST OF 5 x 12.7mm STRANDS U.N.O.


REFER DRAWING S-2503 FOR TYPICAL DETAILS AND ADDITIONAL
REINFORCEMENT.
BEAM TIES MAY BE LOCALLY RELOCATED WHEN CONFLICT EXISTS
WITH POST TENSIONING DUCT LOCATION.
ENSURE 100mm MINIMUM COVER (HORIZONTAL) TO PENETRATIONS
AND 30mm MINIMUM TO CAST-IN SLEEVES FROM EDGE OF POST
TENSIONING DUCT U.N.O.
REMOVAL OF PROPPING TO BE APPROVED BY ENGINEER.
TAGGING OF TENDONS:

DENOTES TENDON DEAD END

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

DENOTES TENDON COUPLER

DENOTES TENDON LIVE END IN PAN


TENDONS TAGGED TOGETHER
SHALL HAVE THE SAME
VERTICAL PROFILE U.N.O.

PROJECT

DENOTES SLAB CONSTRUCTION JOINT

DENOTES DELAYED POUR STRIP


STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

JP
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1 : 100

AT

A0 SIZE

TITLE

BUILDING 2 - LEVEL 3 POST


TENSIONING PLAN
PROJECT No.

P13378

DRAWING No.

S-2133

REV.

3
BG&E Pty Limited

STEEL FRAMING SCHEDULE


AA

AB

AC

AD

AE

AF

AG

AH

AJ

A1

AK

A2

A3

A4

A5

A6

A7

A8

A9

A10

FACADE FRAMES TYPE B


FACADE FRAMES TYPE B

FACADE FRAMES
TYPE A

AJ

AH

EAST ELEVATION

SCALE 1:200

SCALE 1:200

AG

AF

AE

AD

AC

AB

A10

AA

FACADE FRAMES TYPE B

FACADE
FRAMES
TYPE B

A9

A8

A7

A6

A5

FACADE FRAMES TYPE B

A4

A3

A2

SIZE

COMMENT

C309
PC01
PC02
PC03
PC04
PC05
PC09
PC10
R327
S304
S320
S328
S330
S333
UA07
UA08
UB04
UB06
UB07
UB08
UB09
UB10
UB14
UC05
UC07
UC08

139.7 x 3.5 CHS(C350)


75 PFC
100 PFC
125 PFC
150 PFC
180 PFC
300 PFC
380 PFC
200 x 100 x 6.0 RHS
50 x 4.0 SHS
100 x 5.0 SHS
150 x 6.0 SHS
200 x 5.0 SHS
250 x 6.0 SHS
100 x 75 x 6 UA
100 x 75 x 8 UA
180 UB 18
200 UB 18
200 UB 22
200 UB 25
200 UB 30
250 UB 26
310 UB 40
200 UC 46
200 UC 60
250 UC 73

A1

FACADE FRAMES TYPE B


FACADE
FRAMES
TYPE B

NORTH ELEVATION

WEST ELEVATION

SCALE 1:200

SCALE 1:200

WELDED FRAME

L04

S333

S308

155 BT 20.2

L04

PROVIDE 12 THICK BASEPLATE TO


S333 FRAMES. FIX TO CONCRETE
WITH 4M16 HILTI HIT-RE500
ANCHORS. 110 EMBEDMENT,
80 MIN EDGE DISTANCE.
(TYP)

SHS OUTRIGGERS AND BT


VERTICAL MEMBERS LOCATED
AT EACH END OF CLADDING
PANEL AND TO SUIT PANELS
(1200 MAX. CENTRES)
BETWEEN. TYPICAL

S-2171
L03
S308

REFER SECTION 2 FOR


CONNECTION DETAILS

EA17

S-2171

EA17

50

REFER SECTION 2 FOR


CONNECTION DETAILS

11

20

11

155 BT 20.2

S333

COVER
MIN.

N12 x 600 LONG


LACER BAR TO
EACH LUG COG

L03

S308 OUTRIGGER

S308 OUTRIGGER

125x125x12 CAST-IN
PLATE WITH 2N12
LUGS AT 150 CENTRES

L02
4 No 19 DIA x 150 LONG
SHEAR STUDS PLUG WELD
TO 16 PLATE EXTERNAL
FACE 6CFW INTERNAL FACE

11

11

CONCRETE UPSTAND

PRECAST
PANEL/SLAB EDGE

10 DEG WHERE CASTINTO PRE-CAST PANEL

TYPICAL S308 OUTRIGGER DETAIL - CAST IN OPTION


155 BT 20.2

S333

6 CFW (SITE WELD) ALL


AROUND OUTRIGGER TO
CAST-IN PLATE

155 BT 20.2

L02
S308

155 BT 20.2

--

350 x 350 x 16 THICK


CAST IN PLATE

(x 350)

350

(x 250)

10 PLATE 4M16 HIT-V 8.8/S,


HILTI RE-500 CHEMICAL
ANCHORS (110 EMBEDMENT
MIN, 80 EDGE DISTANCE MIN.)

PRECAST PANEL/SLAB EDGE

TYPICAL S308 OUTRIGGER DETAIL - POST-FIX OPTION

2
1
A
REV

17-11-14
22-10-14
09-04-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
SCHEMATIC DESIGN ISSUE
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS

S1

250

DETAIL

SCALE: 1 : 10

S-2171

CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

L01
S308

L01
S333
11

11

6mm CFW (SITE WELD)


TO CAST-IN PLATE
(TYP)

150

CD CLADDING PANEL

PROJECT

M16 8.8/S BOLTS


AT 600 CTS
10 PLATE 4M16
8.8/S BOLTS

BUILDING 2 - FACADE FRAME TYPE A - SECTION VIEW


SCALE: 1 : 50

EA17 EACH SIDE


S308

AK

SOUTH ELEVATION

MARK

155BT20.2

TYPICAL CAST-IN TYPE 11


SCALE 1:10

BUILDING 2 - FACADE FRAME TYPE B - SECTION VIEW

STATUS

ISSUED FOR CONSTRUCTION

SCALE: 1 : 50

DETAIL
SCALE: 1 : 10

A
S-2171

SECTION

SCALE 1:

1:10

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - FACADE ELEVATIONS


AND DETAILS
PROJECT No.

P13378

DRAWING No.

REV.

S-2171

2
BG&E Pty Limited

E4
S-2265

BA

BB

BC

BD

BE

BF

BG

RAMP UP
FROM GROUND

B4
-C
C1

B4
-C
C1

C1
-C
4
B

B4
-C
C1

B4
-C
C1

B8

B4
-C
C1

B4
-C
C1

BUILDING 5
BUILDING 4

250 THICK RAMP UP


TO LEVEL 2

BUILDING 2

B7

B4
-C
C1

B4
-C
C1

11
1
CC
B4

S-2251

KEYPLAN
SCALE: 1 : 1000

PC05

13
S-2251

B4
-C
C1

14

B4
-C
C1

B4
-C
C1

B4
-C
C1

PC05

12

S-2251

S-2251

PC05

B4
-C
C1

B6

B4
-C
C1

B4
-C
C1

06
UB

06
UB

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

SW1

B4
-C
C1

B5

B4
-C
C1

B4
-C
C1

PC05

RERER TO DRG. S-2265


FOR CLADDING SUPPORT
STEELWORK AND CRASH
BARRIER. TYPICAL ALL
AROUND

E1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4

S-2265

225

B4
-C
C1

B4
-C
C1

225

E3
PC05

S-2265

06
UB

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B3

B4
-C
C1

B4
-C
C1

PC05

S-2241

6
S-2241

PC05

MITRE CUT AND FSBW


AT CORNERS (TYP)

06
UB

5
S-2241

B4
-C
C1

PC10

B2

UB09

1
CC
B4

PC04

4
S-2241

PC04

S-2241

S-2241

S-2241

PC04

PC10

UB09

UB09
PC10
B4
-C
C1

B4
-C
C1

B4
-C
C1

S-2265
B4
-C
C1

B1

UB09
PC04

ALL CANOPY
CONNECTIONS
TO BE FULLY
WELDED U.N.O.

RAMP UP
250 THICK

B4
-C
C1

PC05

PURLINS TO BE Z15019
AT 600 CTS (TYP)

E2

STEEL MEMBER SCHEDULE

S-2265

MARK

BUILDING 4 - LEVEL 1 GENERAL ARRANGEMENT PLAN


SCALE: 1 : 100

NOTES:

180

DENOTES SLAB THICKNESS

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

MARK

SIZE

B4-CC1

300 x 450

FOR GENERAL NOTES REFER TO DRAWINGS S-2002 & S-2003

CONCRETE STRENGTH TO BE f'c = 40 MPa


REFER TO ARCHITECT'S DRAWINGS FOR EXTENTS OF HOBS, SETDOWNS,
FALLS AND GRADES ETC
WHERE ARCHITECT'S DRAWINGS INDICATES FALLS IN SLABS STRUCTURAL
SIZES SHOWN ARE THE MINIMUM ALLOWABLE THICKNESS
ALL EXTERNAL SLABS TO BE MEMBRANED / WATERPROOFED REFER TO
ARCHITECT'S DETAILS UNO
900 x 300
DENOTES BEAM IN SLAB (DEPTH x WIDTH)

BUILDING 4 - CONCRETE COLUMN SCHEDULE

SR-A

DENOTES COLUMN SHEAR RAIL TYPE


REFER DRG S-2501 FOR DETAILS

BUILDING 4 - SHEAR WALL SCHEDULE


MARK

DESCRIPTION

REINFORCEMENT

SW1

200 INSITU CONCRETE

N16-300 EF VERTICAL
N16-300 EF HORIZONTAL

C309
MC01
PC01
PC02
PC03
PC04
PC05
PC09
PC10
R326
R327
S304
S313
S320
S323
S324
S328
S330
S333
UA07
UA08
UB04
UB06
UB07
UB08
UB09
UB10
UB14
UC05
UC07
UC08

SIZE
Z15019
139.7 x 3.5 CHS(C350)
152.4 x 4.8 CHS(C350)
75 PFC
100 PFC
125 PFC
150 PFC
180 PFC
300 PFC
380 PFC
200 x 100 x 5.0 RHS
200 x 100 x 6.0 RHS
50 x 4.0 SHS
75 x 5.0 SHS
100 x 5.0 SHS
125 x 4.0 SHS
125 x 5.0 SHS
150 x 6.0 SHS
200 x 5.0 SHS
250 x 6.0 SHS
100 x 75 x 6 UA
100 x 75 x 8 UA
180 UB 18
200 UB 18
200 UB 22
200 UB 25
200 UB 30
250 UB 26
310 UB 40
200 UC 46
200 UC 60
250 UC 73

REMARKS

2
1
REV

17-11-14
13-08-14
DATE

ISSUED FOR CONSTRUCTION


BUILDING 4 - ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 4 - LEVEL 1 GENERAL


ARRANGEMENT PLAN
PROJECT No.

P13378

DRAWING No.

REV.

S-2211

2
BG&E Pty Limited

BE

BF

BA

BD

BE

BF

BG

1800
115

115

30

30
145

1100

1000
100

100

100

75

75

100

175

175

175

175

100

100

100

100

100

100

175

175

175

175

175

175

100

100

100

100

100

100

1850

300
300
300

1850
1850
175

175

100

100

100

75

1850

175

300

115

175
155

300

1850
1850

75

155

75
175
50

C (4)

175

175

155

C (4)

C (4)

50

1850
1850

300

115

75

C (4)

100

B4
300

B4

C (3)

C (3)

D (3)

C (3)

N12-200 U BARS
1750 LONG
N12-300 (1,4)
DISTRIBUTION

155

1850

C (4)

1850

C (4)

C (4)

175

1850

C (4)

300

1850
1850

B5
300

B5

1850

300

C (3)

C (3)

C (3)

C (3)

1850

100

1850

1850

C (4)

1850

C (4)

C (4)

175
175

300

1600

300

B6
300

B6

1600

100

C (3)

C (3)

C (3)

C (3)

D (3)

C (4)

1600

1600

D (2)

300
D (2)

145

175
115

N12-200 U BARS
1750 LONG

N12-200 U BARS
1200 LONG

N16-200 U BARS
1750 LONG

175
175

1700

1500

D (1)
D (4)

N16-200 U
BARS 1750 LONG

175

B7

1700

D (3)

C (4)

D (3)

D (2)

B7

50

J (4)

75

D (2)
J (3)

J (1)

300

C (3)

D (2)
J (3)

800 1000

1200

D (3)

1800

30

30

155

D (4)

D (4)

30

1000 (TYP)

D (2)

145

D (1)

1800

D (1)

D (3)

500

1800

115

1800

115

75

155

300

115

115

50

G (1)
D (4)

D (2)

REFER TO RAMP
REINFORCEMENT PLAN

1800

600

B8

50

N12-200 U BARS

B8
900

BC

400

N12-200 U BARS

1500

BB

155

N12-200 U BARS

BG

115

BD

75

BC

115

BB

300

BA

115
1850
175

175

175

175

100

100

30

30

30

30

100

100

1850

1200

1850
900

1000

115

1300
115

115

30

1300

115

75

50

115

115

50

145

115

115

155

145

155

50

145

145

50

D (4)
1500

900

900

175

300

175

300

175

145

D (1)

1500

1300

250

C (4)

J (3)
2100

1850
1850

1850

175

1300

2100

TENSION
LAP

30

1850

300

B2

1750

J (3)
J (2)
TENSION
LAP

J (3)

D (2)

D (1)

C (3)

D (3)
J (1)

J (3)

900

30

30

D (1)

1150

J (1)
D (2)

719

D (4)

1300

D (4)
D (4)

145

N12-200 U BAR
1500 LONG (1,4)

N16-200 U BARS
1750 LONG

J (4)

D (4)
D (1)

N12-200 U BARS
1750 LONG,
N12-300 (1,4)
DISTRIBUTION

D (3)

N12-200 U BAR
1500 LONG (2,3)

D (3)

2500

N12-150 U BAR
2500 LONG (1,4)

B2

D (2)

D (2)
D (3)

N16-200 U
BARS 1750 LONG

D (2)

1500

300

175

300

175

145

175

1850

300
C (4)

175

1300

C (4)

175
1850

C (4)

100

1850

C (4)

100

1850

300

C (3)

B3
2400
U.N.O.

B3

100

145

100

1850

2400
U.N.O.

2400
U.N.O.

C (3)

D (3)

C (3)

2400
U.N.O.

1850

1850

115

115

1500

450

B1
J (3)
J (2)

115

B1

600 1288

1288

1000 350750 750

1667

1667

1667

1100
400

1325
400

1325 600

500 1400

400

600
350

BUILDING 4 - LEVEL 1 REINFORCEMENT PLAN


SCALE: 1 : 100

BUILDING 4 - LEVEL 1 PT LAYOUT PLAN

N12-200 U BARS

1900

400

1100
400

1667

1667

1667

1100
400

1408

1058

1058 600

400
2
1
REV

23-10-14
13-08-14
DATE

ISSUED FOR CONSTRUCTION


BUILDING 4 - ISSUED FOR CONSTRUCTION
DESCIPTION

REVISIONS

SCALE: 1 : 100

1200

BVL
BVL
RVD

CLIENT

(4)
(3)
Podium Level Central Park 152 - 158 St. Georges Terrace
Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

(2)
(1)

REINFORCEMENT LAYERING LEGEND

DISTRIBUTION BAR N12-200


TOP AND BOTTOM

BC

BD

BE

TYPICAL EDGE REINFORCEMENT DETAILS U.N.O.

B8
900

1900

1500

REINFORCEMENT & SPACING

LEVEL 1

G (3)

1500

PROJECT

GROUND
LEVEL

G (2)

G (3)

1500
G (3)

LAYER

J (3)

A
B
C
D
E
F
G
H
J
K
M
N
P
R
S
T
V
W
X
Y

REINFORCEMENT TABLE
N12-350
N12-300
N12-250
N12-200
N12-150
N16-350
N16-300
N16-250
N16-200
N16-150
N16-100
N20-350
N20-250
N20-200
N20-175
N20-150
N20-100
N24-250
N24-200
N24-150

J (4)

STATUS

ISSUED FOR CONSTRUCTION

J (1)
DRAWN

DESIGNED

JP

NOTES:

RE-ENTRANT BARS NOT SHOWN ON PLAN FOR CLARITY.


REFER TYP. DETAILS.
REBATES IN EDGEBEAMS FOR PRE-CAST PANEL
CONNECTIONS NOT SHOWN ON PLAN, REFER TO PRE-CAST
PANEL ELEVATIONS AND ARCH. CONCRETE OUTLINE PLAN
FOR DETAILS AND LOCATIONS.
REFER TO S-2145 FOR TYPICAL EDGE BEAM ELEVATIONS.

DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

RAMP REINFORCEMENT PLAN G-L1


SCALE: 1 : 100

AT

A0 SIZE

TITLE

BUILDING 4 - LEVEL 1 REINFORCEMENT


AND PT LAYOUT PLANS
PROJECT No.

P13378

DRAWING No.

S-2212

REV.

2
BG&E Pty Limited

E4
S-2265

BA

BB

BC

BD

BE

BF

BG
BUILDING 5
BUILDING 4

RAMP UP
FROM LEVEL 1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B8

250 THICK RAMP


UP TO LEVEL 3

BUILDING 2

PC05

UB
06

PC05

B4
-C
C1
B4
-C
C1

KEYPLAN

B4
-C
C1

B4
-C
C1
B4
-C
C1

B7

B4
-C
C1

B4
-C
C1

B4
-C
C1

UB
06

PC05

B4
-C
C1

B4
-C
C1

B6

PC05

RERER TO DRG. S-2265


FOR CLADDING SUPPORT
STEELWORK AND CRASH
BARRIER. TYPICAL ALL
AROUND

B4
-C
C1

SW1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B5

E1

225

225

S-2265

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

E3

B4
-C
C1

B4
PC05

S-2265

PC05

UB
06

S-2241

B3

B4
-C
C1

PC05

S-2241

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

PC05

S-2241

UB
06

B4
-C
C1

B2

RAMP - 250 THICK

B4
-C
C1

B4
-C
C1

B4
-C
C1

B4
-C
C1

B1

B4
-C
C1

E2
S-2265
2
1
REV

23-10-14
13-08-14
DATE

ISSUED FOR CONSTRUCTION


BUILDING 4 - ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

REVISIONS

BUILDING 4 - LEVEL 2 GENERAL ARRANGEMENT PLAN


SCALE: 1 : 100

CLIENT

BUILDING 4 - CONCRETE COLUMN SCHEDULE

NOTES:

MARK

SIZE

B4-CC1

300 x 450

FOR GENERAL NOTES REFER TO DRAWINGS S-2002 & S-2003

180

DENOTES SLAB THICKNESS

CONCRETE STRENGTH TO BE f'c = 40 MPa


REFER TO ARCHITECT'S DRAWINGS FOR EXTENTS OF HOBS, SETDOWNS,
FALLS AND GRADES ETC
WHERE ARCHITECT'S DRAWINGS INDICATES FALLS IN SLABS STRUCTURAL
SIZES SHOWN ARE THE MINIMUM ALLOWABLE THICKNESS
ALL EXTERNAL SLABS TO BE MEMBRANED / WATERPROOFED REFER TO
ARCHITECT'S DETAILS UNO
900 x 300
DENOTES BEAM IN SLAB (DEPTH x WIDTH)

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

SR-A

DENOTES COLUMN SHEAR RAIL TYPE


REFER DRG S-2501 FOR DETAILS

BUILDING 4 - SHEAR WALL SCHEDULE


MARK

DESCRIPTION

REINFORCEMENT

SW1

200 INSITU CONCRETE

N16-300 EF VERTICAL
N16-300 EF HORIZONTAL

STEEL MEMBER SCHEDULE


MARK
C309
MC01
PC01
PC02
PC03
PC05
PC09
PC10
R326
R327
S304
S313
S320
S323
S324
S328
S330
S333
UA07
UA08
UB04
UB06
UB07
UB08
UB10
UB14
UC05
UC07
UC08

SIZE
139.7 x 3.5 CHS(C350)
152.4 x 4.8 CHS(C350)
75 PFC
100 PFC
125 PFC
180 PFC
300 PFC
380 PFC
200 x 100 x 5.0 RHS
200 x 100 x 6.0 RHS
50 x 4.0 SHS
75 x 5.0 SHS
100 x 5.0 SHS
125 x 4.0 SHS
125 x 5.0 SHS
150 x 6.0 SHS
200 x 5.0 SHS
250 x 6.0 SHS
100 x 75 x 6 UA
100 x 75 x 8 UA
180 UB 18
200 UB 18
200 UB 22
200 UB 25
250 UB 26
310 UB 40
200 UC 46
200 UC 60
250 UC 73

REMARKS
Podium Level Central Park 152 - 158 St. Georges Terrace
Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION


DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 4 - LEVEL 2 GENERAL


ARRANGEMENT PLAN
PROJECT No.

P13378

DRAWING No.

S-2221

REV.

2
BG&E Pty Limited

400

N12-200 U BARS

BD

BE

BF

BG

400

1800

300
115

115

30

30

D (2)

100

100

75

75

100

175

100

100

100

100

175

175

175

175

100

100

100

100

175

100

300
300

100

1850

1850

N12-200 U BARS
1750 LONG
N12-300 (1,4)
DISTRIBUTION

300

100

1850

175

1850
175

1850

C (4)

175

1850

C (4)

C (4)

100

1850

C (4)

100

1850

B5
300

B5

100

1850

300

C (3)

C (3)

C (3)

C (3)

1850

1850

C (4)

1850

175

1850

C (4)

C (4)

175

1850

C (4)

175

175

300

B6
300

B6

1600

300

1600

100

C (3)

C (3)

C (3)

C (3)

D (3)

300

1100

1000

145
115

1600

100

145

175

1700

1600

175
175

N12-200 U BARS
1750 LONG

N12-200 U BARS
1200 LONG

N16-200 U BARS
1750 LONG

175

1700

1500

B7

D (1)
D (4)

N16-200 U
BARS 1750 LONG

D (2)

D (2)
D (3)

C (4)

D (3)

J (4)

B7

155

300

D (2)
J (3)

J (1)

300

C (3)

D (2)
J (3)

800 1000

1200

145

D (3)

1800

30

30

1000 (TYP)

D (4)

30

75

D (4)

D (2)

50

D (1)

1800

D (1)

D (3)

500

1800

115

1800

115

75

155

G (1)
D (4)

D (2)

REFER TO RAMP
REINFORCEMENT PLAN

1800

900

BC

50

B8

600

B8
1500

BB

115

N12-200 U BARS

BA

115

N12-200 U BARS

BG

50

BF

155

BE

115

BD

75

BC

115

BB

300

BA

175

175

100

100

100

75

155

300

1850

75

155

50

155
175

1850

175

115

300

175

75

C (4)

175

50

175

155

C (4)

C (4)

75

1850

300

B4
1850

C (4)

115

300

B4

C (3)

C (3)

D (3)

C (3)

115
1850

175

175

175

175

175

30

100

100

30

30

30

30

100

100

1850

1200

300

115
30

1300

115
30

30

450

1150

145

D (2)

B1
1500

115

J (3)
J (2)

115

B1

300

1850
900
1300
1300

75

155

50

115

115

50

145

115

115

115

D (1)

J (1)

145

155

50

145

1300

D (4)
D (4)

1000

250

D (4)
1500

D (1)

D (4)

1850

1850
300
1850

C (3)
1750

145
900

175

145

1300

2100

175

1300

D (1)

TENSION
LAP

C (4)

J (3)

J (3)

TENSION
LAP
2100

900

1500

D (1)
D (3)
D (2)

J (3)
J (2)

175

50

N12-200 U BAR
1500 LONG (1,4)

D (3)
J (1)

J (3)

D (2)

B2

175

750 900

D (4)

N16-200 U BARS
1750 LONG

J (4)

D (4)
D (1)

N12-200 U BARS
1750 LONG,
N12-300 (1,4)
DISTRIBUTION

D (3)

N12-200 U BAR
1500 LONG (2,3)

D (3)

2500

N12-150 U BAR
2500 LONG (1,4)

B2

D (2)

D (2)
D (3)

N16-200 U
BARS 1750 LONG

D (2)

1500

300

175

300

175

145

175

145

175

1850

C (4)

100

1850

C (4)

100

1850

C (4)

100

1850

C (4)

300

B3
2400
U.N.O.

B3

100

1850

300

C (3)

1850

2400
U.N.O.

2400
U.N.O.

C (3)

D (3)

C (3)

2400
U.N.O.

1850

1850

115

600 1288

1288

1000 350750 750

1667

1667

1667

1100

1500

400

400

1150 600

500 1400

400

600
350
400

BUILDING 4 - LEVEL 2 REINFORCEMENT PLAN

BUILDING 4 - LEVEL 2 PT LAYOUT PLAN

N12-200 U BARS
1200

SCALE: 1 : 100

1900

1100
400

1667

1667

1667

1100

1408

400

400

1058

1058 600

2
1
REV

23-10-14
13-08-14
DATE

ISSUED FOR CONSTRUCTION


BUILDING 4 - ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

REVISIONS
CLIENT

SCALE: 1 : 100
(4)
(3)
(2)
(1)

REINFORCEMENT LAYERING LEGEND

BC

BD

BE

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

DISTRIBUTION BAR N12-200


TOP AND BOTTOM

TYPICAL EDGE REINFORCEMENT DETAILS U.N.O.

B8

G (3)

2100

2100

D (3)

LAYER

TENSION
LAP
REINFORCEMENT & SPACING

J (3)

D (4)
J (3)

PROJECT

TENSION
LAP
J (1)
D (2)

A
B
C
D
E
F
G
H
J
K
M
N
P
R
S
T
V
W
X
Y

REINFORCEMENT TABLE
N12-350
N12-300
N12-250
N12-200
N12-150
N16-350
N16-300
N16-250
N16-200
N16-150
N16-100
N20-350
N20-250
N20-200
N20-175
N20-150
N20-100
N24-250
N24-200
N24-150

STATUS

ISSUED FOR CONSTRUCTION


DRAWN

DESIGNED

JP
DATUM

NOTES:

RE-ENTRANT BARS NOT SHOWN ON PLAN FOR CLARITY.


REFER TYP. DETAILS.
REBATES IN EDGEBEAMS FOR PRE-CAST PANEL
CONNECTIONS NOT SHOWN ON PLAN, REFER TO PRE-CAST
PANEL ELEVATIONS AND ARCH. CONCRETE OUTLINE PLAN
FOR DETAILS AND LOCATIONS.
REFER TO S-2145 FOR TYPICAL EDGE BEAM ELEVATIONS.

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

RAMP REINFORCEMENT PLAN L1 - L2


SCALE: 1 : 100

AT

A0 SIZE

TITLE

BUILDING 4 - LEVEL 2 REINFORCEMENT


AND PT LAYOUT PLANS
PROJECT No.

P13378

DRAWING No.

S-2222

REV.

2
BG&E Pty Limited

BB

N12-200 U BARS
300

300
1000
1150

75

115

1150
75

75

135

75

135

135

135

75

75

75

135

135

135

135

75

100

100

100

300
300

1450
300
300

1450
75

75

160

160

160

1250
300

75

300

135

1000

135

1250

135

75

50

75

135

115

135

115

135

1000

75

115

115

75

1000

300

C (4)

1000

C (4)

C (4)

135

1250

C (4)

100

115

B4
300

B4

C (3)

C (3)

D (3)

C (3)

1250

75

50

75

1450

N12-200 U BARS
1750 LONG
N12-300 (1,4)
DISTRIBUTION

1450

1450

1250

135

1250

C (4)

1000

300
C (4)

C (4)

135

1000

1000

1250

1450

1450

75

1250

1450

75

B5
C (4)

300

135

1000

300

C (3)

C (3)

C (3)

C (3)

B5

1100

1150
600 1150
1400
1250
1000

135

1250

135

1000

135

1250

C (4)

1250

1000 (TYP)

100

1000

B6
C (4)

30
30

300

300

C (3)

C (3)

C (3)

C (3)

140

30

B6
C (4)

100

D (2)
D (3)

C (4)

120

160

1450

N12-200 U BARS
1750 LONG

N12-200 U BARS
1200 LONG

160

160

50

300

D (1)
D (4)

N16-200 U BARS
1750 LONG

135

B7

1450

1500

D (2)

D (2)
D (3)

D (3)

J (4)
N16-200 U
BARS 1750 LONG

100

30

30

1250

J (1)

C (4)

30

115

C (3)

300

1200

30

145

D (3)

B7

75

1000
1250

D (2)

D (4)

D (2)
J (3)

BG

1350
1350

1750

D (4)

100

1000

D (1)

D (3)

500

BF

1000

900

BE

115

115

1000

D (1)

N12-200 U BARS
1750 LONG

G (1)
D (4)

D (2)

REFER RAMP
REINFORCEMENT PLAN

BD

B8

600

B8

BC

50

N12-200 U BARS

BA

120

N12-200 U BARS

BG

100

BF

75

BE

100

BD

50

BC

100

BB

100

BA

100

160

1450
1450

160

160

750
145
115

30

30

1300

115
30

1300

D (1)

450 1300

J (1)
D (2)

D (4)

B1
115

J (3)
J (2)
600 1288

BUILDING 4 - LEVEL 3 REINFORCEMENT PLAN


SCALE: 1 : 100

115

B1
1500

300

1300

75

50
115

115

140

115

115
115

145

140

50

1300

115

1300

145
50

145

1000

160

D (4)
D (4)

300

1200

160

1400

300

1400

350

300

400

100

1100

400

100

1400

1300

J (3)

D (4)
1500

30

30

1400

145
900

30

1000 1000

1200
1100

30
350

1000 1000

300

1750

C (4)

250

B2

D (1)

1500

100

50

D (1)

2100

100

145

D (1)
D (3)
D (2)

2100

900

TENSION
LAP

30

750 750

N12-200 U BAR
1500 LONG (1,4)

J (3)
J (2)
TENSION
LAP

J (3)

D (2)

D (4)

D (3)
J (1)

J (3)

D (4)
D (1)

N16-200 U BARS
1750 LONG

J (4)

D (3)

N12-200 U BAR
1500 LONG (2,3)

D (3)

2500

N12-150 U BAR
2500 LONG (1,4)

B2

N12-200 U BARS
1750 LONG,
N12-300 (1,4)
DISTRIBUTION

D (2)

D (2)
D (3)

C (3)

N16-200 U
BARS 1750 LONG

D (2)

1500

1000 1000

75

140

50

110

1100

110

140

160

75

160
75

140

50

75

160

140

1000

1250

75

120

1450

75

1000

300

C (4)

160

1000 1000

C (4)

75

1100

C (4)

300

B3
2400
U.N.O.

B3
C (4)

75

1250

2400
U.N.O.

C (3)

2400
U.N.O.

C (3)

D (3)

C (3)

2400
U.N.O.

120

1450

115

1288

1000 350750 1150

1200

1200

1200

1200

1050

BUILDING 4 - LEVEL 3 POST TENSIONING LAYOUT PLAN

SCALE: 1 : 100
N12-200 U BARS

500
400

500

1050

1250

1250

1250

1250

1200

1100

400

400

1200

1100 500

400
2
1
REV

23-10-14
13-08-14
DATE

ISSUED FOR CONSTRUCTION


BUILDING 4 - ISSUED FOR CONSTRUCTION
DESCIPTION

1200

BVL
BVL
RVD

REVISIONS
CLIENT

(4)
(3)

BC

(2)

LAYER

BE

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

B8

TYPICAL EDGE REINFORCEMENT DETAILS U.N.O.

D (4)
2100

LEVEL 3

2100

TENSION
LAP

G (3)

J (3)

REINFORCEMENT LAYERING LEGEND

DISTRIBUTION BAR N12-200


TOP AND BOTTOM

BD

D (3)

(1)

J (3)

TENSION
LAP

LEVEL 2
PROJECT

J (1)
D (2)

A
B
C
D
E
F
G
H
J
K
M
N
P
R
S
T
V
W
X
Y

REINFORCEMENT TABLE
N12-350
N12-300
N12-250
N12-200
N12-150
N16-350
N16-300
N16-250
N16-200
N16-150
N16-100
N20-350
N20-250
N20-200
N20-175
N20-150
N20-100
N24-250
N24-200
N24-150

REINFORCEMENT & SPACING

STATUS

ISSUED FOR CONSTRUCTION


DRAWN

NOTES:

RAMP REINFORCEMENT PLAN L2 - L3

SCALE: 1 : 100

RE-ENTRANT BARS NOT SHOWN ON PLAN FOR CLARITY.


REFER TYP. DETAILS.
REBATES IN EDGEBEAMS FOR PRE-CAST PANEL
CONNECTIONS NOT SHOWN ON PLAN, REFER TO PRE-CAST
PANEL ELEVATIONS AND ARCH. CONCRETE OUTLINE PLAN
FOR DETAILS AND LOCATIONS.
REFER TO S-2145 FOR TYPICAL EDGE BEAM ELEVATIONS.

DESIGNED

JP
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 4 - LEVEL 3 REINFORCEMENT


AND PT LAYOUT PLANS
PROJECT No.

P13378

DRAWING No.

S-2232

REV.

2
BG&E Pty Limited

BA

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL
225

B4 L02 LOWER

REFER TO DRG S-2265


FOR FACADE STEELWORK
DETAILS

BD
650

0
100

B4 L01 UPPER

REFER TO SLAB
REINFORCEMENT
PLANS

0
65

500 TYP

BC

BE

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS
N12-200
0
65

B4 L01 UPPER
225
900 LAP
TYP.

225

225

250

B4 L01 LOWER

250

UB06

B4 L01 LOWER

REFER TO SLAB
REINFORCEMENT
PLANS

900 LAP
TYP

REFER TO SLAB
REINFORCEMENT
PLANS

SECTION

SECTION

SCALE: 1 : 20

S-2211

SCALE: 1 : 20

S-2211

5N12

B4 L01 LOWER

REFER TO SLAB
REINFORCEMENT
PLANS

5N12

180

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS

650

SECTION

SECTION

SCALE: 1 : 20

S-2211

SCALE: 1 : 20

S-2211

BD

PC
05

PC
05

BD

Z1
50
19

30 (TYP)

PC04

PC04

PC
05

UB06

UB09

340x180x32 END PLATE 4M16


HIT-V 8.8 HILTI HIT RE-500
CHEMICAL ANCHORS WITH
DYNAMIC WASHERS 125
EMBEDMENT
UB
09

225

340x180x32 END PLATE 4M16 HIT-V


HILTI RE-500 CHEMICAL ANCHORS
WITH DYNAMIC WASHERS. 125
EMBEDMENT MIN
PC
04

UB06

B4 L03 UPPER

B4 L03 UPPER

S-2241

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL

225

UB06

PC
05

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL

PC
05

7a

FULLY WELDED FRAME


8CFW ALL ROUND (TYP)

PC
05

PC
05

10 PURLIN CLEAT 2M12 8.8/S


PURLIN BOLTS (PURLIN NOT
SHOWN FOR CLARITY)

B4 L01 UPPER
225

B4 L01 UPPER
225

UB06

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL

PC
05

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL

B4 L01 LOWER

SECTION
SCALE: 1 : 10

7a
S-2241

7
S-2211

10 PLATE TEE, 4 M12 HILTI HITV 8.8 ROS WITH HIT-RE500


ADHESIVE (110 EMBEDMENT).
TYPICAL
B4 L01 LOWER

SECTION
SCALE: 1 : 20

10 CAP PLATE, 2M12 HILTI


HIT-V 8.8 RODS WITH HITRE500 ADHESIVE (110
EMBEDMENT) TYPICAL

5
S-2211

B4-CC1

225
UB06

225

UB06

PC
05

SCALE: 1 : 10
2M16 8.8/S BOLTS. TYPICAL

10 BASE PLATE, 2M12 HILTI


HIT-V 8.8 RODS WITH HITRE500 ADHESIVE (110
EMBEDMENT) TYPICAL

TYPICAL AWNING END PLATE


AND PURLIN CONNECTION
SECTION

10 PLATE,
2M16 8.8/S BOLTS.
TYPICAL
REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL

TYPICAL AWNING END PLATE CONNECTION

REFER TO POST
TENSION LAYOUT PLAN
FOR TENDON DETAILS.
TYPICAL

SECTION

SCALE: 1 : 20

S-2211

2
1
REV

17-11-14
13-08-14
DATE

ISSUED FOR CONSTRUCTION


BUILDING 4 - ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

JP
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 4 - SUSPENDED SLAB


DETAILS SHEET 1
PROJECT No.

P13378

DRAWING No.

S-2241

REV.

2
BG&E Pty Limited

BUILDING 5
1
5

S-2325

BUILDING 4

S-2325

REFER TO DRG. S-2331


FOR SUSNCREEN FRAME
ELEVATION. TYPICAL

S-2325

30

680 x 250

150

D11

180 PRE-CAST

SUNSCREEN FRAME

180 PRE-CAST

2
S-2325

200

150

BONDEK

BUILDING 2

S-2325

S-2325

100
100
150 PRE-CAST

D10
B5-ST1

200

SUNSCREEN FRAME

150 PRE-CAST

D9
100

680 x 250

7
S-2325

200

100

BONDEK
30
150 PRE-CAST

180 PRE-CAST

SUNSCREEN FRAME

680 x 250

S-2325

D8
30

150

150

180 PRE-CAST

150

KEYPLAN

200

150

BONDEK

100
100
150 PRE-CAST

D7
B5-ST1

200
150 PRE-CAST

D6
150

680 x 250

150

200

100

BONDEK

180 PRE-CAST

SUNSCREEN FRAME

100

30

30

150

D5

180 PRE-CAST

SUNSCREEN FRAME

150 PRE-CAST

680 x 250

200

150

BONDEK

S-2325

100

100
150 PRE-CAST

D4
B5-ST3

200

200
180 PRE-CAST

180 PRE-CAST

D3
100

100
30

30

150

150 PRE-CAST

200
BONDEK

200

180 PRE-CAST

180 PRE-CAST

150

BONDEK

680 x 250

D2

100

100

680 x 250

150

150

SUNSCREEN FRAME

SUNSCREEN FRAME
FULLY WELDED
S304 LOUVRE
SUPPORT FRAME

DA

DB

DC

D1
DD

DE

100

150

C3

180 PRE-CAST
150 PRE-CAST

180 PRE-CAST

180 PRE-CAST

150

150

150 PRE-CAST

BONDEK

BONDEK

200

150

150

100

680 x 250
100

680 x 250

NOTES:

300

200

150 PRE-CAST

BONDEK

200

150

SUNSCREEN FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

C1

CB

CC

CD

CE

CF

CG

CH

CJ

CK

150

SUNSCREEN FRAME

150

CA

SUNSCREEN FRAME

CL

CM

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

SCALE: 1 : 100
30

200
150 PRE-CAST

200

BUILDING 5 - LEVEL 1 - GENERAL ARRANGEMENT PLAN

100

150

BONDEK

100

680 x 250
100

680 x 250

200

30

100

200

150 PRE-CAST

BONDEK

150 PRE-CAST

200

150 PRE-CAST

BONDEK

100

680 x 250

200

30

30

100

200

150 PRE-CAST

BONDEK

150 PRE-CAST

BONDEK

150

B5-ST2

150 PRE-CAST

200

200

30

C2

300
TYP.

B5-ST1

180 PRE-CAST

150 PRE-CAST

180 PRE-CAST

B5-ST1

30

30

150 PRE-CAST

100

BVL
BVL
BVL
RVD

150

150 PRE-CAST
30

SUNSCREEN FRAME

180 PRE-CAST

B5-ST1

30
FULLY WELDED
S304 LOUVRE
SUPPORT FRAME

180 PRE-CAST

150

100

180 PRE-CAST

150

100

180 PRE-CAST

150

100

100

BONDEK

150

100

150

150

100

200

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

CLIENT

100

680 x 250

150

17-11-14
08-08-14
22-07-14
DATE

REVISIONS
+5.0mm PRESET

150 PRE-CAST

SUNSCREEN FRAME

100

3
2
1
REV

REFER TO DRG. S-2331


FOR SUSNCREEN FRAME
ELEVATION. TYPICAL

CN

FOR GENERAL NOTES REFER TO DRAWINGS S-2002 & S-2003

180

DENOTES SLAB THICKNESS

CONCRETE STRENGTH TO BE f'c = 40 MPa


BONDEK BMT TO BE 0.75mm U.N.O.
ALL BONDEK SLABS TO BE PROPPED CONTINUOUSLY AT ALL EDGES AND
AT THIRD POINTS OF SPAN.
REFER TO ARCHITECT'S DRAWINGS FOR EXTENTS OF HOBS, SETDOWNS,
FALLS AND GRADES ETC
WHERE ARCHITECT'S DRAWINGS INDICATES FALLS IN SLABS STRUCTURAL
SIZES SHOWN ARE THE MINIMUM ALLOWABLE THICKNESS
ALL EXTERNAL SLABS TO BE MEMBRANED / WATERPROOFED REFER TO
ARCHITECT'S DETAILS UNO
500x400
DENOTES BEAM IN SLAB (DEPTH x WIDTH)

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

DENOTES SPAN DIRECTION OF BONDEK

DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 5 - LEVEL 1 GENERAL


ARRANGEMENT PLAN
PROJECT No.

P13378

DRAWING No.

REV.

S-2311

3
BG&E Pty Limited

BUILDING 5
BUILDING 4

REFER TO DRG. S-2331


FOR SUSNCREEN FRAME
ELEVATION. TYPICAL

30

150
680 x 250

D11

180 PRE-CAST

SUNSCREEN FRAME

180 PRE-CAST

150

200

BUILDING 2

100

BONDEK

100
150 PRE-CAST

D10
B5-ST1

200

SUNSCREEN FRAME

150 PRE-CAST

D9

680 x 250

200

180 PRE-CAST 180 PRE-CAST

BONDEK
30

30

SUNSCREEN FRAME

150

100

100

150

KEYPLAN

D8

680 x 250

150
150
200

100

100

BONDEK
150 PRE-CAST

D7

200

B5-ST1
150 PRE-CAST

D6

SUNSCREEN FRAME

100

150
680 x 250

200
100

BONDEK

180 PRE-CAST 180 PRE-CAST

150

30

SUNSCREEN FRAME

150 PRE-CAST

30

680 x 250

150

D5

150
200
BONDEK

100

100

150 PRE-CAST

D4
B5-ST3

200

200

180 PRE-CAST

180 PRE-CAST

150

D3
150

30

30

100

100

200

200
BONDEK
180 PRE-CAST

180 PRE-CAST

150 PRE-CAST

BONDEK

680 x 250

D2

100

100

680 x 250

150

150

150

SUNSCREEN FRAME

SUNSCREEN FRAME
FULLY WELDED
S304 LOUVRE
SUPPORT FRAME

DA

DB

DC

D1
DD

DE

100

150

180 PRE-CAST

C3

BUILDING 5 - LEVEL 2 GENERAL ARRANGEMENT PLAN

680 x 250

200

100

150

150

150

150

150

150

150

B5-ST1

180 PRE-CAST

180 PRE-CAST

100

180 PRE-CAST 180 PRE-CAST

100

B5-ST1

100

180 PRE-CAST

100

180 PRE-CAST

100

B5-ST2

100

BONDEK
B5-ST1

180 PRE-CAST

C2

30
150 PRE-CAST

150

150

150 PRE-CAST

200

BONDEK

680 x 250

150

150 PRE-CAST

BONDEK

150 PRE-CAST

200

680 x 250

C1

150

180

DENOTES SLAB THICKNESS

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

DENOTES SPAN DIRECTION OF BONDEK

150

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

SUNSCREEN FRAME

SUNSCREEN FRAME

150

SUNSCREEN FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

REFER TO DRG. S-2331


FOR SUSNCREEN FRAME
ELEVATION. TYPICAL

BVL
BVL
BVL
RVD

FOR GENERAL NOTES REFER TO DRAWINGS S-2002 & S-2003

100

680 x 250

200

30

100

680 x 250

150 PRE-CAST

150 PRE-CAST

150 PRE-CAST

200

30

100

150

200
BONDEK

BONDEK

100

680 x 250

200

30

100

200
680 x 250

150

150 PRE-CAST

200

30

100

680 x 250

30

BONDEK

BONDEK

100

BONDEK

200

100

200

150 PRE-CAST

150 PRE-CAST

BONDEK

150 PRE-CAST

100

150 PRE-CAST

200
200

680 x 250

30

150 PRE-CAST

30

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

CLIENT

CONCRETE STRENGTH TO BE f'c = 40 MPa


BONDEK BMT TO BE 0.75mm U.N.O.
ALL BONDEK SLABS TO BE PROPPED CONTINUOUSLY AT ALL EDGES AND
AT THIRD POINTS OF SPAN.
REFER TO ARCHITECT'S DRAWINGS FOR EXTENTS OF HOBS, SETDOWNS,
FALLS AND GRADES ETC
WHERE ARCHITECT'S DRAWINGS INDICATES FALLS IN SLABS STRUCTURAL
SIZES SHOWN ARE THE MINIMUM ALLOWABLE THICKNESS
ALL EXTERNAL SLABS TO BE MEMBRANED / WATERPROOFED REFER TO
ARCHITECT'S DETAILS UNO
500x400
DENOTES BEAM IN SLAB (DEPTH x WIDTH)

30

150

17-11-14
08-08-14
22-07-14
DATE

REVISIONS

NOTES:

100

150

FULLY WELDED
S304 LOUVRE
SUPPORT FRAME

SUNSCREEN FRAME

SUNSCREEN FRAME

SCALE: 1 : 100

3
2
1
REV

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

CA

CB

CC

CD

CE

CF

CG

CH

CJ

CK

CL

CM

CN

BUILDING 5 - LEVEL 2 GENERAL


ARRANGEMENT PLAN
PROJECT No.

P13378

DRAWING No.

S-2321

REV.

3
BG&E Pty Limited

BUILDING 5
BUILDING 4
1
SUNSCREEN FRAME

S-2332

D11

UA07

PC09
PC03

P1 AT 600 CRS.

BUILDING 2

PC03

3
S-2332

PC09

P3 AT 600 CRS.
PC09

UA07

PC09

UA07
PC09

P2 AT 600 CRS.

SUNSCREEN FRAME

D9

PC09

UA07

KEYPLAN

S-2332

UA07
PC09

D10

PC03
P1 AT 600 CRS.

PC09

PC03

P3 AT 600 CRS.
UA08

D8

UA07

UA08

SUNSCREEN FRAME

S-2332

UA07

PC03
P1 AT 600 CRS.
PC03

P3 AT 600 CRS.
UA07

PC09

PC09

D7
PC09

UA07

P2 AT 600 CRS.
UA07
SUNSCREEN FRAME

PC09

D6

PC09

UA07

PC03
P1 AT 600 CRS.

S304

PC03
P3 AT 600 CRS.

SUNSCREEN FRAME

PC09

S304

UA08

UA07

UA08

UA07

S304

S304

S304

S304

D5

D2
REFER TO DRG. S-2332
FOR CONNECTION TO ROOF
STEELWORK

PC03
P1 AT 600 CRS.

S304

S304

S304

S304

S304

S304

S304

S304

S304

PC03
P3 AT 600 CRS.
S304

S-2332

D4

S304

D3

S304

S304

S304

S304

S304

S304

S304

REFER TO DRG. S-2325 FOR


CONNECTION TO SUSPENDED
SLAB DETAIL

S304

S304

UA07

S304

PC09

S304

S304

P2 AT 600 CRS.

S304

UA07

S304

UA07

PC09

S304

S304

UA07

UA07

UA07

UA07

S304

P1 AT 600 CRS.

P1 AT 600 CRS.

TYPICAL LOUVRE SUPPORT FRAME ELEVATION

D2

PC09

SUNSCREEN FRAME

P3 AT 600 CRS.
PC09

PC03

PC03

UA08

UA08

PC03

PC03

PC09

P3 AT 600 CRS.

SUNSCREEN FRAME

FULLY WELDED
S304 LOUVRE
SUPPORT FRAME
BELOW

DA

DB

SCALE: 1 : 50

TYPICAL SUNSCREEN

D1

DC

DD DE
2

P1 AT 600 CRS.

PC09

C3

UA07

2
1
REV

BUILDING 5 - ROOF STEELWORK PLAN


PC03

UA07

UA08

UA07

P1 AT 600 CRS.

PC09

P1 AT 600 CRS.

PC09

PC09

PC09

P1 AT 600 CRS.

P1 AT 600 CRS.

BUILDING 5 - PURLIN SCHEDULE

C2

UA07

UA07
UA07

UA07

UA07

UA07

UA07

UA07
UA07

UA07

UA07

UA07

UA07

UA07

PC03

UA07

UA07

UA07

UA07

UA07

UA07

UA07

SUNSCREEN FRAME

PC09
P3 AT 600 CRS.

SUNSCREEN FRAME
P3 AT 600 CRS.

SUNSCREEN FRAME
P3 AT 600 CRS.

PC09

SUNSCREEN FRAME
P3 AT 600 CRS.

SUNSCREEN FRAME
P3 AT 600 CRS.

PC09

SUNSCREEN FRAME
P3 AT 600 CRS.

PC09
SUNSCREEN FRAME

PC09

PC03

PC03

PC09

PC09

PC03

PC03

UA08

UA08

PC03

PC03

PC09

PC09

PC03

PC03

UA08

UA08

PC03

PC03

PC09

PC09

PC03

PC03

UA08

UA08

P1 AT 600 CRS.

PC03

PC09

PC03

UA07

P3 AT 600 CRS.

REFER TO DRG S-2311 FOR


SUNSCREEN ELEVATION

CA

CB

CC

CD

CE

CF

CG

CH

CJ

CK

CL

MARK

SIZE

P1

Z30024

P2

Z15012

P3

Z15012

DESCRIPTION
REFER PLAN FOR SPACING, PROVIDE 2 ROWS
BRIDGING AT 3RD POINTS. TYPICAL CONNECTION
TO BE 12 PLATE, 2M12 PURLIN BOLTS
REFER PLAN FOR SPACING, PROVIDE 2 ROWS
BRIDGING AT 3RD POINTS. TYPICAL CONNECTION
TO BE 8 PLATE, 2M12 PURLIN BOLTS
REFER PLAN FOR SPACING. TYPICAL CONNECTION
TO BE 8 PLATE, 2M12 PURLIN BOLTS

NOTE: IF PURLIN CLEAT HEIGHT EXCEEDS 300mm


CONNECTION TO BE 75x75x8.0 EA, 2M12 PURLIN BOLTS

C1
PC09

SUNSCREEN FRAME

UA07

PC09

UA08

PC03

P3 AT 600 CRS.

P1 AT 600 CRS.

STEEL FRAMING SCHEDULE


MARK

SIZE

C309
PC01
PC02
PC03
PC04
PC05
PC09
PC10
R327
S304
S320
S328
S330
S333
UA07
UA08
UB04
UB06
UB07
UB08
UB09
UB10
UB14
UC05
UC07
UC08

139.7 x 3.5 CHS(C350)


75 PFC
100 PFC
125 PFC
150 PFC
180 PFC
300 PFC
380 PFC
200 x 100 x 6.0 RHS
50 x 4.0 SHS
100 x 5.0 SHS
150 x 6.0 SHS
200 x 5.0 SHS
250 x 6.0 SHS
100 x 75 x 6 UA
100 x 75 x 8 UA
180 UB 18
200 UB 18
200 UB 22
200 UB 25
200 UB 30
250 UB 26
310 UB 40
200 UC 46
200 UC 60
250 UC 73

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

REVISIONS
CLIENT

COMMENT

PC09

PC09
PC09

P1 AT 600 CRS.

SCALE: 1 : 100

P2 AT 600 CRS.

UA07

2
FULLY WELDED
S304 LOUVRE
SUPPORT FRAME
BELOW

PC09

PC09

P1 AT 600 CRS.

PC03

P2 AT 600 CRS.

P2 AT 600 CRS.

PC09

PC09

UA07

SUNSCREEN FRAME

P3 AT 600 CRS.

17-11-14
08-08-14
DATE

CM

CN

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 5 - ROOF STEELWORK PLAN


PROJECT No.

P13378

DRAWING No.

S-2331

REV.

2
BG&E Pty Limited

DD

DE

DB
250 PRE-CAST

1A

P1 AT 600 CRS.

DB
2M16 HILTI HIT RE-500
CHEMICAL ANCHORS
125mm MIN EMBEDMENT

P3 AT 600 CRS.

S-2332

P1 AT 600 CRS.

PC
09

P2 AT 600 CRS.

100

150
2M16 8.8/S BOLTS.
TYPICAL

UA07

850
FIX PFC TO PANEL WITH 4M16
HILTI HIT-RE500 CHEMICAL
ANCHORS SPACED AS SHOWN
(125mm MIN. EMBEDMENT) TYPICAL

100x75x10 UA BRACKET
6mm CFW ON 3 SIDES TO
PFC. TYPICAL

S304

UA07

FIX RAKING ANGLE TO PANEL


WITH M12 HILTI HIT-RE500
CHEMICAL ANCHOR AT EACH
PURLIN LOCATION (110mm MIN.
EMBEDMENT) TYPICAL

PC03
50

850

PC
09

PC
09

PC09

150

PC09

FIX PFC TO PANEL WITH 4M16


HILTI HIT-RE500 CHEMICAL
ANCHORS SPACED AS SHOWN
(125mm MIN. EMBEDMENT) TYPICAL

SECTION

CONNECTION TYPE 2 REFER TO DRAWINGS


S-2504 & S-2505 FOR
DETAILS. TYPICAL

1
S-2331

SCALE: 1 : 10

REFER TO SECTION 1
ON THIS DRAWING
FOR CONNECTION
DETAIL

SECTION
SCALE: 1 : 10

10 PLATE
2M12 BOLTS.
TYPICAL

SECTION

2
S-2331

250 PRE-CAST

10 TEE CLEAT
2M12 BOLTS.
TYPICAL

S304

80

LOCATE SUNSCREEN OUTRIGGER


ON SPIGOT PLATES AND SITE
WELDED ALL ROUND TO BACK
OF PFC. TYPICAL

REFER TO SECTION 1
ON THIS DRAWING FOR
CONNECTION DETAIL

140

2 OFF 10 SPIGOT PLATES


WELDED TO BACK OF PFC

80

P3 AT 600 CRS.

SCALE: 1 : 10

3
S-2331

PC09

S304

PC09

MITRE CUT PFC BEAMS


(10mm NOM. GAP).
TYPICAL

SECTION

S-2332

S3
04

SCALE: 1 : 10

1A

4B
S-2332

DB

D8

250 PRE-CAST
150 PRE-CAST

3
CONNECTION TYPE 1 REFER TO DRAWINGS
S-2504 & S-2505 FOR
DETAILS. TYPICAL

P1 AT 600 CRS.

P3 AT 600 CRS.

4A
S-2332

S304

PC
09

100

100

60

UA08

600 MIN.
UA07

100
10 PLATE,
2M12 8.8/S BOLTS.
TYPICAL

FIX RAKING ANGLE TO PANEL


WITH M16 8.8/S BOLTS FIXED
THRU PANEL LOCATED AS
SHOWN. TYPICAL

FIX RAKING ANGLE TO PANEL


WITH M16 8.8/S BOLTS FIXED
THRU PRE-CAST WALL AT EVERY
SECOND PURLIN LOCATION
(PROVIDE 2 OFF BOLTS EACH END
OF ANGLE AT 60 CENTRES AS
SHOWN) TYPICAL

60

S304

PRECAST BEYOND

CONNECTION TYPE 2 REFER TO DRAWINGS


S-2504 & S-2505 FOR
DETAILS. TYPICAL

250 PRECAST
CONNECTION TYPE 2 REFER TO DRAWINGS
S-2504 & S-2505 FOR
DETAILS. TYPICAL
250 PRECAST

SECTION
SCALE: 1 : 10

SECTION

4
S-2331

SCALE: 1 : 10

4B
S-2332

3
2
1
REV

17-11-14
22-10-14
08-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS

CLIENT

COVER
MIN.

D2

D2

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PC09

FULLY WELDED
CONNECTION

FULLY WELDED
CONNECTION

S304
UA08

50

250

200

DB

S304

150

D8
S304
UA08

UA07

250

PURLIN CLEATS (PURLINS


NOT SHOWN FOR CLARITY)

PURLINS AND PURLIN


CLEATS NOT SHOWN
FOR CLARITY

S304

S304

UA07

10 PLATE, 4M16 HILTI HIT-V


8.8/S ANCHORS WITH HILTI
RE-500 CHEMICAL ANCHORS
(110 EMBEDMENT MIN, 80 EDGE
DISTANCE)

125x125x12 CAST-IN
PLATE WITH 2N12
LUGS AT 150 CENTRES

PROJECT

N12 x 600 LONG


LACER BAR TO
EACH LUG COG

LOUVRE SUPPORT FRAME


POST-FIX OPTION

LOUVRE SUPPORT FRAME


CAST-IN OPTION

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

SECTION 4A

DETAIL

S-2332

SCALE: 1 : 10

S-2331

SCALE: 1 : 10

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1 : 10

AT

A0 SIZE

TITLE

BUILDING 5 - ROOF STEELWORK


DETAILS SHEET 1
PROJECT No.

P13378

DRAWING No.

S-2332

REV.

3
BG&E Pty Limited

DB DC

DD 11 DE

18

S-2362

S-2364

150 PRE-CAST

250 PRE-CAST

S-2361

180 PRE-CAST

REFER TO DRAWING S-2504 FOR ADDITIONAL TRIMMING


REINFORCEMENT AT OPENINGS.
DENOTES PRE-CAST PANEL THICKNESS

PJ

DENOTES PRE-CAST PANEL JOINT LOCATION

150 PRE-CAST

3
250 PRE-CAST

S-2361

SIM

2N20 EXTRA

DB

DD

2N20 EXTRA

DC

2N20 EXTRA

PC09 (FF)

UA07
UA07 (FF)

DD

2N20 EXTRA

2
250 PRE-CAST

180

150

180
150

BUILDING 5 - A_L02

DENOTES LOCATION AND TYPE OF PANEL TO PANEL


CONNECTION BRACKET. REFER TO DRAWING S-2504
FOR DETAILS

PC09

7N20-150

180

UA07

7N20-150 7N20-150

7N20-150

DENOTES BLOCK OUT IN PANEL (PANEL


REINFORCEMENT CONTINUOUS THROUGH BLOCKOUT)
REFER DRAWING S-2325 FOR DETAILS

UA08

UA07

DENOTES DANLEY REBOX TYPE C (RBXCN12200C130W)


CAST INTO PRE-CAST PANEL FAR FACE

3
180 PRE-CAST

SIM

2N20 EXTRA

PC09
250 PRE-CAST

D6

150 PRE-CAST

250 PRE-CAST

S-2361

2N20 EXTRA

DENOTES DANLEY REBOX TYPE C (RBXCN12200C130W)


CAST INTO PRE-CAST PANEL NEAR FACE

A
(FF)

D7

SIM

DC

2N20 EXTRA

150

S-2361

DB

D8

150 PRE-CAST

REFER TO DRAWING S-2504 FOR TYPICAL PRE-CAST PANEL DETAILS.

DD

PJ

150 PRE-CAST

250 PRE-CAST

SIM

D9

DC

PJ

DB

PJ

D10

S-2361

S-2361

ALL PRE-CAST PANEL REINFORCEMENT TO BE


N16-200 VERTICAL (CENTRAL),
N16-200 HORIZONTAL.
1N16 PERIMETER BAR EACH EDGE U.N.O.
REINFORCEMENT SHOWN ON PANEL ELEVATIONS IS IN ADDITION TO
THE REINFORCEMENT LISTED ABOVE

PJ

150 PRE-CAST

PJ

180 PRE-CAST

180 PRE-CAST

250 PRE-CAST

S-2361

PRE-CAST PANEL NOTES

D11

PJ

PJ

DA

150

150

N20-500

N20-500

N20-500

N20-500

A
A

N20-500

D5

A
(FF)

A
(FF)

A
(FF)

D4

150 PRE-CAST

BUILDING 5 - A_L01

N20-500

N20-500

N20-500

N20-500

PJ

N20-500

N20-500

S-2361

180 PRE-CAST

SIM

180 PRE-CAST

D3

S-2361

A
A

180 PRE-CAST

150 PRE-CAST

180 PRE-CAST

250 PRE-CAST

17

N20-500

D2

250 PRE-CAST

D1

S-2361

S-2361

180

C3
180 PRE-CAST

250 PRE-CAST

S-2362

250 PRE-CAST

250 PRE-CAST

250 PRE-CAST

180 PRE-CAST

250 PRE-CAST

14
S-2363

N20-500

N20-500

N20-500
B5-RW1

B5-SF1
B5-RW1

C2
SECTION

SCALE: 1 : 50

S-2361

B5-SF1

B5-SF2

B5-SF2

SECTION

SCALE: 1 : 50

S-2361

SECTION

SCALE: 1 : 50

S-2361

15

180 PRE-CAST

180 PRE-CAST

B5-SF1

C1

250 PRE-CAST

250 PRE-CAST

N20-500

N20-500
N20-500

180 PRE-CAST

150 PRE-CAST

150 PRE-CAST

180 PRE-CAST
150 PRE-CAST

150 PRE-CAST

180 PRE-CAST

150 PRE-CAST

180 PRE-CAST

150 PRE-CAST

180 PRE-CAST
150 PRE-CAST

150 PRE-CAST

150 PRE-CAST

S-2362

180 PRE-CAST
150 PRE-CAST

150 PRE-CAST

180 PRE-CAST

150 PRE-CAST

180

B5-RW1
150 PRE-CAST

250 PRE-CAST

S-2363

180

150

N20-500

180 PRE-CAST

12

150

RW1

150

150

BUILDING 5 - A_L00(Ground)

S-2364

A
(FF)

A
(FF)

A
(FF)

S-2364

16

13

S-2364

S-2363

CA

S-2361

S-2361

S-2361

S-2361

S-2361

S-2361

S-2361

SIM

SIM

SIM

SIM

SIM

SIM

SIM

CB CC

CD

S-2361

S-2361

SIM

SIM

CE CF

CG

CH CJ

CK

10

S-2362

S-2362

CL CM

CN

BUILDING 5 - PRE-CAST PANEL LAYOUT PLAN


SCALE: 1 : 200

D2

DA

DB

DC

DD

D2

D3

D3

DE

2N20 EXTRA

2N20 EXTRA

PJ

PJ

2N20 EXTRA
3

180

250 PRE-CAST

3
UA07 (FF)

UA07

PC09

2N20 EXTRA

PJ

2N20 EXTRA

PJ

2N20 EXTRA

2N20 EXTRA

PJ

2N20 EXTRA

3
UA08

UA07

2
2

7N20-150
180

180

7N20-150 6N20-150

180

9N20-100

5N20-150

180

180

150

250 PRECAST

150

BUILDING 5 - A_L02
N20-500

N20-500

N20-500

N20-500

N20-500

N20-500

A
2

3
2
1
REV

17-11-14
22-10-14
08-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS
180

CLIENT

N20-500

N20-500

N20-500

N20-500

PJ

150

150
Podium Level Central Park 152 - 158 St. Georges Terrace
Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

BUILDING 5 - A_L01
N20-500

N20-500

N20-500

N20-500

N20-500
A

N20-500

A
2

180
RW1

180

PROJECT

150

BUILDING 5 - A_L00(Ground)
180

180

150

180

N20-500

N20-500
180
N20-500
B5-SF1

N20-500

N20-500
B5-SF1

B5-SF1

B5-RW1

N20-500

N20-500

STATUS

B5-SF1

N20-500

ISSUED FOR CONSTRUCTION

B5-RW1

B5-SF1

B5-SF1

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

SECTION

SECTION

SECTION

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

BUILDING 5 - PRE-CAST PANEL


ELEVATIONS SHEET 1
PROJECT No.

P13378

DRAWING No.

S-2361

REV.

3
BG&E Pty Limited

(FF
)

UA08

UA07 (FF)

250 PRE-CAST

UA07

PC09

7N20-150

7N20-150 6N20-150

9N20-100

2
150

5N20-150

PC09 (FF)

150
6N20-150

6N20-150

7N20-150

150

N20-500

6N20-150
180

N20-500

PJ
3

2
UA07 (FF)

PJ

BUILDING 5 - A_L02

PJ

250 PRE-CAST
150

2N20 EXTRA

PJ

2N20 EXTRA

2N20 EXTRA

2
180

PC09 (FF)

2N20 EXTRA

C2

UA07

2N20 EXTRA

PJ

2N20 EXTRA

C1

C2

PJ

2N20 EXTRA

PJ

2N20 EXTRA

PJ

2N20 EXTRA

PJ

CB

C1

CB

PJ

CA

CA

180

N20-500

N20-500

6N20-150

150

N20-500

150

150

PJ
3

A
(FF)

A
(FF)

A
(FF)

A
(FF)

A
(FF)

150

N20-500

150

N20-500

N20-500

N20-500

N20-500

PJ
150

BUILDING 5 - A_L01

A
(FF)

N20-500

N20-500

PJ

PJ

A
(FF)

150

N20-500

N20-500

N20-500

N20-500

PJ
A
(FF)

A
(FF)

A
(FF)
180

A
(FF)

180

A
(FF)

150

150
PJ

180

A
(FF)

5N20
150

B5-SF1

B5-RW1

N20-500

B5-SF2

B5-SF2

B5-SF1

685

B5-SF1

395

B5-SF2

B5-SF1

758

SECTION

10

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

D4

D5

D6

D7

D8

180

180

180

5N20-150

2N20 EXTRA

3
5N20-150

11N20-100

11N20-100

B
(FF)

B
(FF)

B
(FF)

5N20-150

11N20-100

5N20-150

180

180

B
(FF)

B
(FF)

B
(FF)

B
(FF)

B
(FF)

B
(FF)

180
180

N20-500
PJ

N20-500

PJ

180

PJ

N20-500
PJ

BUILDING 5 - A_L01

B
(FF)

A
(FF)

BVL
BVL
BVL
RVD

N20-500

N20-500

B
(FF)

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

CLIENT

180

PJ

N20-500

PJ

PJ

B
(FF)

B
(FF)

N20-500

PJ

17-11-14
22-10-14
08-08-14
DATE

REVISIONS
180

PJ

3
2
1
REV

180

N20-500

N20-500

A
(FF)

180
PJ

B
(FF)

180

180

BUILDING 5 - A_L02

3
2

5N20-150

PJ

A
(FF)

180

11N20-100

2N20 EXTRA

180

180

180

N20-500

2N20 EXTRA

2N20 EXTRA

11N20-100

5N20-150

A
(FF)

2N20 EXTRA

PJ

2N20 EXTRA

2
3

9N20-100

180

6N20-150

7N20-150

2N20 EXTRA

180

3
2

D11

PJ

D10

PJ

2N20 EXTRA

PJ

2N20 EXTRA

PJ

2N20 EXTRA

PJ

2N20 EXTRA

PJ
(FF
)

D9

2N20 EXTRA
2N20 EXTRA

PJ

PJ

2N20 EXTRA
PJ

2N20 EXTRA
2N20 EXTRA

PJ

PJ

2N20 EXTRA

PJ

2N20 EXTRA

A
(FF)

B5-SF1

SECTION

A
(FF)

N20-500

UA07 (FF)

N20-500

SECTION

2N20 EXTRA

7N20-150

N20-500

D3

N20-500

SECTION

D2

PC09 (FF)

150

N20-500

N20-500

PJ

B5-SF2

N20-500

PJ

B5-SF1

150

N20-500

8N20-200

150

N20-500

B5-RW1

5N20

PJ

BUILDING 5 - A_L00(Ground)

4N20

150

PJ

B
(FF)

B
(FF)

N20-500

PJ

N20-500

N20-500
PJ

180
Podium Level Central Park 152 - 158 St. Georges Terrace
Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PJ

B
(FF)

B
(FF)

B
(FF)

180

B
(FF)

180
180

180
180

180

180

180
180

BUILDING 5 - A_L00(Ground)
180

B5-RW1

180

180

PROJECT

180

180
N20-500

180

N20-500

B5-SF1

180

N20-500

180

N20-500
B5-SF1

N20-500

N20-500

N20-500

N20-500

N20-500

180
180
N20-500
N20-500

N20-500

N20-500

N20-500

B5-SF2
B5-SF2

N20-500

STATUS

180
N20-500

N20-500

ISSUED FOR CONSTRUCTION

N20-500

N20-500

DRAWN

DESIGNED

Author
B5-SF2

DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1 : 50

AT

A0 SIZE

TITLE

SECTION

11

SCALE: 1 : 50

S-2361

BUILDING 5 - PRE-CAST PANEL


ELEVATIONS SHEET 2
PROJECT No.

P13378

DRAWING No.

S-2362

REV.

3
BG&E Pty Limited

CA

C1

CB

C2

C3

250 PRE-CAST

180

PJ

PJ

UA07

UA07

2N20 EXTRA

UA07

PC09

2N20 EXTRA

PJ

2N20 EXTRA

2N20 EXTRA

PJ

PJ

2N20 EXTRA

PJ

2N20 EXTRA
2N20 EXTRA

6N20-150
2

7N20-150

7N20-150

9N20-100

180

7N20-200

5N20-150

180

150

150

180

PJ

BUILDING 5 - A_L02

N20-500

N20-500

N20-500

N20-500

PJ

180

180

180
150
N20-500

N20-500

PJ

N20-500

N20-500

PJ

BUILDING 5 - A_L01

150
PJ

N20-500

N20-500

N20-500

N20-500

PJ

3
180

180

180

3
BUILDING 5 - A_L00(Ground)

150

N20-500

N20-500

N20-500

SECTION

12

SECTION

13

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

CD

CG

2N20 EXTRA

180

CK

2N20 EXTRA

11N20-100

11N20-100
180

180

2N20 EXTRA

5N20-150

11N20-100

5N20-150

11N20-100
180

180

CN

2N20 EXTRA

2N20 EXTRA

2N20 EXTRA

5N20-150

11N20-100

5N20-150

11N20-100

180

180

180

PJ

2N20 EXTRA

PJ

PJ
3

180

180

5N20-150

180

180
PJ

180

180

180

180

11N20-100

5N20-150

PJ

180

PJ
3

PJ

180

2N20 EXTRA

PJ

2N20 EXTRA

PJ

2N20 EXTRA
3

180

180

CM

PJ

BUILDING 5 - A_L02

CL

2N20 EXTRA

5N20-150

2N20 EXTRA

PJ

2N20 EXTRA

1
3

CJ

2N20 EXTRA

PJ

2N20 EXTRA

PJ

PJ

2N20 EXTRA

CH

2N20 EXTRA
PJ

2N20 EXTRA

180

CF

2N20 EXTRA

PJ

PJ
3

CE

2N20 EXTRA

N20-500

B5-SF2

B5-SF2

CC

2N20 EXTRA

N20-500

PJ

B5-SF1

PJ

B5-RW1

N20-500

180

PJ

N20-500

180

PJ

180

180

PJ

180

150

180

180

180

180

3
2
1
REV

180

17-11-14
22-10-14
08-08-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
RVD

REVISIONS
CLIENT

N20-500
N20-500

PJ

N20-500

PJ

N20-500
PJ

PJ

N20-500
N20-500

PJ

N20-500

PJ

N20-500
PJ

PJ

N20-500
N20-500

PJ

N20-500

PJ

N20-500
PJ

PJ

N20-500
N20-500

PJ

PJ
Podium Level Central Park 152 - 158 St. Georges Terrace
Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

BUILDING 5 - A_L01

180

180

180

180

180

180

180

180

180

180

180

180

180

180
PROJECT

BUILDING 5 - A_L00(Ground)

180
N20-500

N20-500

180
N20-500

N20-500

B5-SF2

N20-500

180

180
N20-500

N20-500

N20-500

N20-500

N20-500

180

N20-500

N20-500

N20-500

N20-500

N20-500

N20-500

N20-500

N20-500

N20-500

STATUS

ISSUED FOR CONSTRUCTION

N20-500

N20-500

DRAWN

B5-SF2

B5-SF2

B5-SF2

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1 : 50

AT

A0 SIZE

TITLE

SECTION

14

SCALE: 1 : 50

S-2361

BUILDING 5 - PRE-CAST PANEL


ELEVATIONS SHEET 3
PROJECT No.

P13378

DRAWING No.

S-2363

REV.

3
BG&E Pty Limited

CC

CD

CE

CF

CG

CH

CJ

CK

CL

CM

CN

1
S-2364

5N16 (FF)

N12-200 (FF)

5N16 (FF)

5N16 (FF)

N12-200 (FF)

N12-200 (FF)

2
N12-200 (NF)

N12-200 (FF)
250

250

250

5N16 (FF)

N12-200 (FF)

5N16 (FF)

5N16 (FF)

N12-200 (FF)
2

N12-200 (FF)
250

250

250

BUILDING 5 - A_L02

D4

D5

D6

SECTION

15

SCALE: 1 : 50

S-2361

D7

D8

D9

D10

D11

650 MIN

5N16 (FF)

2
5N16 (NF)

N12-200 (NF)

N12-200 (NF)

5N16 (NF)

250

250

N12-200 (NF)

N12-200

5N16 (NF)

5N16 (NF)
2

N12-200 (NF)

N12-200 (NF)
2

5N16 (NF)

2
250

5N16

50 COVER

N12-200 (NF)
2

250

250

250

TYPICAL PRE-CAST BEAM SECTION


BUILDING 5 - A_L02

SECTION

18

SCALE: 1 : 50

S-2351

C1

C2

SECTION

SCALE: 1 : 20

S-2364

C3
DA

DB

DC

DD

DE

2
1
REV

17-11-14
22-10-14
DATE

ISSUED FOR CONSTRUCTION


ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

REVISIONS
CLIENT

5N16 (NF)
5N16 (NF)

N12-200 (NF)
2

N12-200 (NF)
2

250

5N16 (NF)

5N16 (NF)
2

N12-200 (NF)

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

250

N12-200 (NF)
2

250

250

PROJECT

STATUS

PRELIMINARY

NOT TO BE USED FOR CONSTRUCTION


DRAWN

DESIGNED

Author
DATUM

Designer
GRID

CHECKED

APPROVED

Checker

Approver

SCALE

As indicated

AT

A0 SIZE

TITLE

SECTION

16

SECTION

17

SCALE: 1 : 50

S-2361

SCALE: 1 : 50

S-2361

BUILDING 5 - PRE-CAST PANEL


ELEVATIONS SHEET 4
PROJECT No.

P13378

DRAWING No.

S-2364

REV.

2
BG&E Pty Limited

AA

AB

AC

AD

AE

AF

AG

AH

AJ

AK

AA

AB

AC

AD

AE

AF

AG

AH

AJ

AK

AA

A10

A10

A10

A9

A9

A9

A8

A8

A8

A7

A7

A7

A6

A6

A6

A5

A5

A5

A4

A4

A4

A3

A3

A3

A2

A2

A2

A1

A1

A1

AB

AC

AD

AE

BUILDING 2 - GROUND FLOOR LOADING PLAN

BUILDING 2 - LEVEL 1 LOADING DIAGRAM

BUILDING 2 - LEVEL 2 LOADING DIAGRAM

SCALE: 1 : 200

SCALE: 1 : 200

SCALE: 1 : 200

AA

AB

AC

AD

AE

AF

AG

AH

AJ

AK

AA

A10

A10

A9

A9

A8

A8

A7

A7

AB

AC

AD

AE

AF

AG

AH

AJ

A5

A4

A4

A3

A3

A2

A2

A1

AH

AJ

AK

LOADING DIAGRAM LEGEND

A6

A5

AG

AK

PATTERN

A6

AF

A1

USAGE

LIVE LOADS
(KPa)

SUPERIMPOSED DEAD
LOADS (KPa)

APARTMENT

1.5

0.25

STAIRS/CORRIDOR

4.0

0.25

TOILETS
(RESIDENTIAL)

1.5

1.0

TOILET
(OFFICE)

3.0

2.25

BALCONIES
(TYPE 1)

2.0

1.5

BALCONIES
(TYPE 2)

4.25

1.5

STORES

5.8

0.25

ROOFS
(NON-ACCESSIBLE)

0.25

0.5

ROOFS
(NON-ACCESSIBLE)

0.25

2.5

ROOFS
(ACCESSIBLE)

2.5

2.5

RETAIL/OFFICE

3.0

1.0

PLANT

5.0

3.0

CAFE

4.0

1.0

FOYER

4.0

1.25

1
REV

17-11-14
DATE

ISSUED FOR CONSTRUCTION


DESCIPTION

BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

BUILDING 2 - LEVEL 3 LOADING DIAGRAM

BUILDING 2 - LEVEL 4 LOADING DIAGRAM

SCALE: 1 : 200

SCALE: 1 : 200

ISSUED FOR CONSTRUCTION

DRAWN

DATUM

KITCHEN

5.0

DESIGNED

CC

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

1.0

AT

A0 SIZE

TITLE

CARPARK

2.5

0.15

FUTURE
CAFE/TOILET

4.0

2.25

BUILDING 2 - GROUND, LEVELS 1, 2, 3,


& 4 LOADING DIAGRAMS
PROJECT No.

P13378

DRAWING No.

S-2401

REV.

1
BG&E Pty Limited

LOADING DIAGRAM LEGEND


PATTERN

BA

BB

BC

BD

BE

BF

B8

B7

B6

B5

B4

B3

USAGE

LIVE LOADS
(KPa)

SUPERIMPOSED DEAD
LOADS (KPa)

APARTMENT

1.5

0.25

STAIRS/CORRIDOR

4.0

0.25

TOILETS
(RESIDENTIAL)

1.5

1.0

TOILET
(OFFICE)

3.0

2.25

BALCONIES
(TYPE 1)

2.0

1.5

BALCONIES
(TYPE 2)

4.25

1.5

STORES

5.8

0.25

ROOFS
(NON-ACCESSIBLE)

0.25

0.5

ROOFS
(NON-ACCESSIBLE)

0.25

2.5

ROOFS
(ACCESSIBLE)

2.5

2.5

RETAIL/OFFICE

3.0

1.0

PLANT

5.0

3.0

CAFE

4.0

1.0

FOYER

4.0

1.25

KITCHEN

5.0

1.0

CARPARK

2.5

0.15

FUTURE
CAFE/TOILET

4.0

2.25

BG

B2

B1
BUILDING 4 - GROUND FLOOR LOADING DIAGRAM
SCALE: 1 : 200

LEVELS 1, 2, & 3 SIMILAR

1
REV

17-11-14
DATE

ISSUED FOR CONSTRUCTION


DESCIPTION

BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 4 - LOADING DIAGRAMS


PROJECT No.

P13378

DRAWING No.

S-2411

REV.

1
BG&E Pty Limited

2400 TYP
550 TYP
REFER TO PANEL ELEVATIONS
FOR REINFORCEMENT DETAILS

PANEL

CAULKING ONTO BACKING ROD


TO ARCHITECTURAL SPECIFIFATION

SL92 MESH
(CENTRAL)
LAP

REFER TO FACADE ENGINEERS


DRAWINGS FOR BAFFLE DETAILS

550

MESH
550

PANEL

PLAN VIEW

SL92 MESH
(CENTRAL)

TYPICAL VERTICAL FULL JOINT DETAIL

45

SCALE 1:10
REFER TO PANEL
ELEVATIONS FOR
ADDITIONAL REINFORCEMENT

N16 1500 LG
(CENTRAL)
3-N16-150 EXTRA AT
BRACKET LOCATIONS

REFER TO FACADE ENGINEERS


DRAWINGS FOR BAFFLE AND
REBATE DETAILS

SL92 MESH
(CENTRAL)

150 MIN
REBATE OR DUMMY JOINT TO
ARCHITECT'S DETAILS

PANEL

1-N16 PERIMETER BAR


(CENTRAL)
REFER TO PANEL
ELEVATIONS FOR
CONNECTIONS

REFER TO PANEL ELEVATIONS FOR


REINFORCEMENT DETAILS

CAULKING ONTO BACKING ROD


TO ARCHITECTURAL SPECIFIFATION

1-N16 PERIMETER BAR


(CENTRAL)

550 TYP

PLAN VIEW

TYPICAL 150mm TO 180mm THICK FACADE


PANEL ELEVATION

TYPICAL 150mm TO 180mm THICK 'L' FACADE


PANEL ELEVATION

SCALE: NTS

SCALE: NTS

LENGTH OF PANEL < 1200mm

LENGTH OF PANEL > 1200mm

TYPICAL MINIMUM STRUCTURAL


THICKNESS DETAIL

TYPICAL CORNER VERTICAL FULL JOINT DETAIL


SCALE 1:10

ADDITIONAL 1M20 x 70 RAMSET


ELEPHANT FOOT FERRULE WITH
4.6/S BOLT. 1R10 CROSS BAR
THREADED THROUGH FERRULE

SCALE 1:10

PRECAST FACADE PANEL


150

ADDITIONAL 1M20 x 70 RAMSET


ELEPHANT FOOT FERRULE WITH
4.6/S BOLT. 1R10 CROSS BAR
THREADED THROUGH FERRULE

PRECAST FACADE PANEL


150

EXTEND ANGLE AS SHOWN


WITH END PLATE THICKNESS
TO MATCH ANGLE THICKNESS
150

150

EXTEND ANGLE AS SHOWN


WITH END PLATE THICKNESS
TO MATCH ANGLE THICKNESS

300 WIDE CONCRETE


EDGE BEAM OR SLAB

300 WIDE CONCRETE


EDGE BEAM OR SLAB
50
50

150

50

250

150

150
250

PLAN VIEW

PLAN VIEW

TYPICAL MINIMUM EDGE AND BOLT


DISTANCES FOR FACADE PANELS <
1200mm

TYPICAL MINIMUM EDGE AND BOLT


DISTANCES FOR FACADE PANELS >
1200mm (UNLESS NOTED OTHERWISE)

SCALE 1:10

SCALE 1:10

PLAN VIEW

TYPICAL FACADE PANEL CORNER EDGE DETAIL #1


PLAN VIEW
NOTE:
ADOPT ONLY DETAIL ONE PANEL JOINT CONNECTION
WHERE EDGE DISTANCES DO NOT COMPLY DUE TO
PANEL LENGTH. ADOPT DETAIL 2 PANEL JOINT
CONNECTION OTHERWISE

TYPICAL FACADE PANEL CORNER EDGE DETAIL #2

1
REV

22-07-14
DATE

ISSUED FOR CONSTRUCTION


DESCIPTION

BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION


DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

TYPICAL PRECAST FACADE DETAILS


PROJECT No.

P13378

DRAWING No.

S-2507

REV.

1
BG&E Pty Limited

THE QUARTER KARRATHA


STRUCTURAL DRAWINGS

STRUCTURAL DRAWING LIST


NUMBER
TITLE
S-2001
S-2002
S-2003
S-2010
S-2101
S-2102
S-2103
S-2105
S-2111
S-2112
S-2113
S-2115
S-2116
S-2121
S-2122
S-2123
S-2131
S-2132
S-2133
S-2141
S-2142
S-2143
S-2145
S-2146
S-2151
S-2152
S-2153
S-2161
S-2162
S-2171
S-2181
S-2182
S-2183
S-2184
S-2185
S-2186
S-2187
S-2201

COVER SHEET AND DRAWING INDEX


GENERAL NOTES - SHEET 1
GENERAL NOTES - SHEET 2
TYPICAL FOOTING AND GROUND SLAB DETAILS - SHEET 1
BUILDING 2 - FOOTING AND GROUND SLAB PLAN
BUILDING 2 - COMBINED FOOTING PLANS AND DETAILS SHEET 1
BUILDING 2 - COMBINED FOOTING PLANS AND DETAILS SHEET 2
BUILDING 2 - GROUND FLOOR DETAILS
BUILDING 2 - LEVEL 1 GENERAL ARRANGEMENT PLAN
BUILDING 2 - LEVEL 1 REINFORCEMENT PLAN
BUILDING 2 - LEVEL 1 POST TENSIONING LAYOUT PLAN
BUILDING 2 - LEVEL 1 CANOPY STEELWORK PLAN
BUILDING 2 - LEVEL 1 CANOPY DETAILS
BUILDING 2 - LEVEL 2 GENERAL ARRANGEMENT PLAN
BUILDING 2 - LEVEL 2 REINFORCEMENT PLAN
BUILDING 2 - LEVEL 2 POST TENSIONING LAYOUT PLAN
BUILDING 2 - LEVEL 3 GENERAL ARRANGEMENT PLAN
BUILDING 2 - LEVEL 3 REINFORCEMENT PLAN
BUILDING 2 - LEVEL 3 POST TENSIONING PLAN
BUILDING 2 - LEVEL 4 GENERAL ARRANGEMENT PLAN
BUILDING 2 - LEVEL 4 REINFORCEMENT PLAN
BUILDING 2 - LEVEL 4 POST TENSIONING LAYOUT PLAN
BUILDING 2 - TYPICAL EDGE BEAM DETAILS
BUILDING 2 - SUSPENDED SLAB DETAILS SHEET 1
BUILDING 2 - ROOF STEELWORK PLAN
BUILDING 2 - ROOF STEELWORK SECTIONS
BUILDING 2 - ROOF STEELWORK DETAILS
BUILDING 2 - CORE WALL ELEVATIONS
BUILDING 2 - STAIR DETAILS
BUILDING 2 - FACADE ELEVATIONS AND DETAILS
BUILDING 2 - PRE-CAST PANEL ELEVATION KEY PLAN
BUILDING 2 - PANEL ELEVATIONS SHEET 1
BUILDING 2 - PANEL ELEVATIONS SHEET 2
BUILDING 2 - PANEL ELEVATIONS SHEET 3
BUILDING 2 - PANEL ELEVATIONS SHEET 4
BUILDING 2 - PANEL ELEVATIONS SHEET 5
BUILDING 2 - PANEL ELEVATIONS SHEET 6
BUILDING 4 - GROUND LEVEL - FOOTING PLAN

STRUCTURAL DRAWING LIST


NUMBER
TITLE
S-2202
S-2205
S-2211
S-2212
S-2221
S-2222
S-2231
S-2232
S-2241
S-2251
S-2255
S-2265
S-2301
S-2305
S-2311
S-2312
S-2321
S-2322
S-2325
S-2331
S-2332
S-2351
S-2361
S-2362
S-2363
S-2364
S-2401
S-2411
S-2421
S-2422
S-2501
S-2502
S-2503
S-2504
S-2505
S-2506
S-2507
S-2510

BUILDING 4 - RAFT & COMBINED FOOTING PLANS AND DETAILS


BUILDING 4 - GROUND LEVEL DETAILS SHEET 1
BUILDING 4 - LEVEL 1 GENERAL ARRANGEMENT PLAN
BUILDING 4 - LEVEL 1 REINFORCEMENT AND PT LAYOUT PLANS
BUILDING 4 - LEVEL 2 GENERAL ARRANGEMENT PLAN
BUILDING 4 - LEVEL 2 REINFORCEMENT AND PT LAYOUT PLANS
BUILDING 4 - LEVEL 3 GENERAL ARRANGEMENT PLANS
BUILDING 4 - LEVEL 3 REINFORCEMENT AND PT LAYOUT PLANS
BUILDING 4 - SUSPENDED SLAB DETAILS SHEET 1
BUILDING 4 - CORE WALL ELEVATIONS
BUILDING 4 - STAIR DETAILS
BUILDING 4 - FACADE SUPPORT STEELWORK ELEVATIONS
BUILDING 5 - FOOTING AND GROUND SLAB PLAN
BUILDING 5 - FOOTING AND GROUND SLAB DETAILS SHEET 1
BUILDING 5 - LEVEL 1 GENERAL ARRANGEMENT PLAN
BUILDING 5 - LEVEL 1 REINFORCEMENT PLAN
BUILDING 5 - LEVEL 2 GENERAL ARRANGEMENT PLAN
BUILDING 5 - LEVEL 2 REINFORCEMENT PLAN
BUILDING 5 - SUSPENDED SLAB DETAILS
BUILDING 5 - ROOF STEELWORK PLAN
BUILDING 5 - ROOF STEELWORK DETAILS SHEET 1
BUILDING 5 - STAIR DETAILS
BUILDING 5 - PRE-CAST PANEL ELEVATIONS SHEET 1
BUILDING 5 - PRE-CAST PANEL ELEVATIONS SHEET 2
BUILDING 5 - PRE-CAST PANEL ELEVATIONS SHEET 3
BUILDING 5 - PRE-CAST PANEL ELEVATIONS SHEET 4
BUILDING 2 - GROUND, LEVELS 1, 2, 3, & 4 LOADING DIAGRAMS
BUILDING 4 - LOADING DIAGRAMS
BUILDING 5 - GROUND & LEVEL 1 LOADING DIAGRAMS
BUILDING 5 - LEVEL 2 & ROOF LOADING DIAGRAMS
TYPICAL CONCRETE COLUMN DETAILS
TYPICAL CONCRETE WALL DETAILS
TYPICAL POST-TENSIONING DETAILS
TYPICAL PRECAST WALL DETAILS
PRECAST PANEL CONNECTION DETAILS
TYPICAL SUSPENDED SLAB DETAILS
TYPICAL PRECAST FACADE DETAILS
TYPICAL STAIR DETAILS

1
REV

17-11-14
DATE

ISSUED FOR CONSTRUCTION


DESCIPTION

BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION


DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1:1

AT

A0 SIZE

TITLE

COVER SHEET AND DRAWING INDEX


PROJECT No.

P13378

DRAWING No.

S-2001

REV.

1
BG&E Pty Limited

1.0 GENERAL

3.0 FOUNDATIONS

5.0 TEMPORARY WORKS

8.0 REINFORCEMENT

1.1.

3.1.

5.1

8.1.

1.2.

1.3.

1.4.

TECHNICAL SPECIFICATIONS OR SPECIFIC INSTRUCTIONS ON DRAWINGS TAKE


PRECEDENCE OVER THESE NOTES.
THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL
AND OTHER CONSULTANTS' DRAWINGS AND SPECIFICATIONS AND WITH ANY
OTHER WRITTEN INSTRUCTIONS AS MAY BE ISSUED DURING THE COURSE OF THE
CONTRACT. ANY DISCREPANCY SHALL BE REFERRED TO THE ENGINEER BEFORE
PROCEEDING WITH THE WORK. CONSTRUCTION FROM THESE DRAWINGS, AND THEIR
ASSOCIATED CONSULTANTS' DRAWINGS IS NOT TO COMMENCE UNTIL APPROVED
BY THE LOCAL AUTHORITIES.
ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE
RELEVANT AND CURRENTLY SPECIFIED STANDARDS AND WITH THE BY-LAWS
AND ORDINANCES OF THE RELEVANT BUILDING AUTHORITIES EXCEPT WHERE
VARIED BY THE PROJECT SPECIFICATION AND/OR DRAWINGS.
ALL DIMENSIONS AND LEVELS SHOWN ON THE DRAWINGS SHALL BE VERIFIED BY
THE CONTRACTOR ON SITE. STRUCTURAL DRAWINGS SHALL NOT BE SCALED FOR
DIMENSIONS. REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AND
SETOUT. THE DESIGN CONSULTANT SHALL BE NOTIFIED OF ANY DISCREPANCIES
PRIOR TO CONSTRUCTION.

3.2.

3.3.

FOUNDATIONS HAVE BEEN DESIGNED FOR THE FOLLOWING ALLOWABLE


PRESSURES:
ELEMENT

BEARING
PRESSURE (kPa)

PAD & STRIP FOOTINGS

300 kPa

THE FOUNDATION MATERIAL SHALL BE APPROVED BY THE GEOTECHNICAL


ENGINEER FOR THIS BEARING CAPACITY BEFORE PLACING ANY MEMBRANE,
REINFORCEMENT OR CONCRETE. WHERE NECESSARY, THE FOOTING DESIGN
MAY BE ALTERED.

5.2

REFER TO GEOTECHNICAL INVESTIGATION REPORT No. J1401001001 R REV 0


DATED 5 FEBURARY 2014 BY FALT GEOTECHNICS. THE CONTRACTOR IS DEEMED
TO HAVE VISITED THE SITE, READ, UNDERSTOOD AND MADE DUE ALLOWANCE
FOR THE SITE CONDITIONS AND THE INFORMATION IN THE REPORT.

THE BUILDER SHALL SATISFY HIMSELF THAT IN CARRYING OUT THE SUGGESTED
PROCEDURES, THE ADJOINING BUILDINGS AND AREAS BOTH INSIDE AND OUTSIDE
THE SITE BOUNDARY ARE ADEQUATELY PROTECTED AND PREVENTED FROM MOVING
BOTH VERTICALLY AND HORIZONTALLY AND THE BUILDER, IN HIS TENDER, SHALL
ALLOW FOR ANY EXTRA MATERIAL OR WORK DEEMED BY HIM TO BE NECESSARY
TO ACHIEVE THIS.
ANY CHANGE BY THE BUILDER TO THE SUGGESTED PROCEDURES SHOWN ON THESE
DRAWINGS SHALL GIVE AT LEAST EQUAL PROTECTION TO THE ADJOINING
BUILDINGS AND AREAS OUTSIDE THE SITE BOUNDARY TO THAT SHOWN IN THESE
PROCEDURES. THE BUILDER SHALL ALLOW IN HIS TENDER FOR ALL COSTS INVOLVED
IN ANY CHANGES HE MAKES. THE CHANGES PROPOSED BY THE BUILDER SHALL BE
PRESENTED IN A FORM SIMILAR IN DETAIL AND EXTENT TO THESE TENDER
DOCUMENTS AND SHALL BE SUPPORTED BY COMPUTATIONS DONE BY A CHARTERED
ENGINEER EXPERIENCED IN THIS WORK. THE BUILDER SHALL BE REQUIRED TO GAIN
THE NECESSARY APPROVALS FOR SUCH ALTERATIONS FROM THE RELEVANT
AUTHORITIES AND ADJOINING OWNERS.

3.4.

THE BUILDER SHALL BE RESPONSIBLE FOR MAINTAINING ANY EXCAVATIONS


IN A STABLE CONDITION WITHOUT ADVERSELY AFFECTING SURROUNDING
PROPERTIES INCLUDING SERVICES. THIS INCLUDES OBTAINING ALL
NECESSARY APPROVALS FOR SHORING AND ANCHORING SYSTEMS.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF


THE STRUCTURE AND ANY ASSOCIATED EXCAVATIONS UNTIL THEIR COMPLETION
AND SHALL ENSURE THAT NO PART IS OVERSTRESSED BY EXCESSIVE
CONSTRUCTION LOADING. PROVIDE TEMPORARY BRACING AND PROPPING AS
REQUIRED.

3.5.

FOOTINGS SHALL BE LOCATED CENTRALLY UNDER WALLS AND COLUMNS


UNLESS NOTED OTHERWISE.

3.6.

FOOTINGS NEAR BOUNDARIES MUST NOT BE LOCATED HIGHER OR LOWER


THAN FOOTINGS OF ADJACENT PROPERTIES UNLESS APPROVED.

6.1.

REMOVE ALL TOP SOIL INCLUDING ROOTS AND ANY OTHER ORGANIC
MATTER. STORE TOP SOIL AS REQUIRED.

1.6.

UNLESS NOTED OTHERWISE, ALL DIMENSIONS ARE IN MILLIMETRES (mm) AND ALL
LEVELS ARE IN METRES (m) TO AUSTRALIAN HEIGHT DATUM (AHD).

3.7.

6.2.

1.7.

ALL ABBREVIATIONS ARE AS FOLLOWS:

IMPORTED FILL IS TO BE CLEAN, COHESIONLESS SAND, FREE FROM SILT OR


ORGANIC MATERIAL WITH NOT MORE THAN 5% BY WEIGHT OF MATERIAL
FINER THAN 0.075mm AND PLASTICITY INDEX = 0. MATERIAL EXCAVATED
FROM THE SITE CAN BE USED AS FILL PROVIDED IT COMPLIES WITH THESE
REQUIREMENTS.

EXCAVATE TO THE REQUIRED FORMATION LEVEL AND PROOF ROLL


FORMATION WITH 6 PASSES OF 10 TONNE SMOOTH WHEELED ROLLER.
SOFT AREAS ARE TO BE REMOVED AND REPLACED WITH SUITABLE FILL
COMPACTED TO THE DENSITY NOMINATED BELOW.

6.3.

WHERE SHOWN ON THE DRAWINGS, BASE AND SAND BLINDING ARE TO


BE PLACED AND COMPACTED AS SPECIFIED.

1.5.

ALT
BTM
CRS
EF
EGL
EW
FF
FFL
LV
NF
NSOE
NSOP
PT
RC
REINF
RL
UNO
U/S
SSL
1.8.

ALTERNATING BARS
BOTTOM
CENTRES
EACH FACE
EXISTING GROUND LEVEL
EACH WAY
FAR FACE
FINISHED FLOOR LEVEL
LENGTH VARIES
NEAR FACE
NOT SHOWN ON ELEVATION
NOT SHOWN ON PLAN
POST TENSIONED
REINFORCED CONCRETE
REINFORCEMENT
REDUCED LEVEL
UNLESS NOTED OTHERWISE
UNDERSIDE
STRUCTURAL SLAB LEVEL

PLACE AND COMPACT FILL IN LAYERS TO ACHIEVE MINIMUM SPECIFIED


DENSITY BUT NOT EXCEEDING 300mm.

3.9.

COMPACT SOIL BENEATH FOOTINGS TO 70% DENSITY IN AND 60% DENSITY


INDEX BELOW SLABS ON GROUND FOR A MINIMUM OF 750mm BELOW THE
STRUCTURE.

6.4.

3.11.

GENERAL NON LOAD


BEARING FILL

3.12. OBTAIN THE APPROVAL OF THE ENGINEER FOR ALL EXCAVATIONS PRIOR TO
CONCRETING.

LOT FILL (RESIDENTIAL)

PRIOR TO CONSTRUCTION OF ALL CONCRETE FLOORS AND WALLS, THE


CONTRACTOR SHALL PREPARE, FOR REVIEW BY THE ARCHITECT AND DESIGN
CONSULTANT, FULLY CO-ORDINATED FLOOR PLANS AND WALL ELEVATIONS
SHOWING ALL PROPOSED PENETRATIONS, OPENINGS AND CAST-IN FIXINGS, WHICH
SHALL ALSO REQUIRE THE PLANNING AND CO-ORDINATION OF ALL SERVICES WHO
MAY REQUIRE SUCH PENETRATIONS, OPENINGS AND FIXINGS.

THE STRUCTURAL COMPONENTS DETAILED ON THESE DRAWINGS HAVE BEEN


DESIGNED IN ACCORDANCE WITH THE RELEVANT SPECIFIED STANDARDS AND
LOCAL AUTHORITY REQUIREMENTS FOR THE FOLLOWING LOADINGS. REFER TO
ARCHITECTURAL DRAWINGS FOR PROPOSED FLOOR USAGE.
LIVE LOADS ARE IN ACCORDANCE WITH AS 1170.1 - 2002
FOR LOADS REFER TO LOADING DRAWINGS

2.3.

WIND LOADS ARE IN ACCORDANCE WITH AS1170.2 - 2011.

3.13. WHERE FOOTINGS ARE OVER-EXCAVATED, FILL OVER-EXCAVATED AREAS


WITH BLINDING CONCRETE SAME GRADE AS FOOTING TO A MINIMUM
THICKNESS OF 50mm.

D250
D500
D500
D500
S250

S
N
L
L
N

HOT ROLLED DEFORMED BARS TO AS 4671


DEFORMED BARS TO AS 4671
DEFORMED BARS (SQUARE MESH) TO AS 4671
DEFORMED BARS (RECTANGULAR MESH) TO AS 4671
HOT ROLLED ROUND BARS TO AS 4671.
BAR DIAMETER (mm)

17N20-250
BAR GRADE

BAR SPACING (mm)

THE FIGURES FOLLOWING THE FABRIC SYMBOL SL, RL AND TM IS THE REFERENCE
NUMBER FOR FABRIC TO AS 4671.
8.2.

ALL REINFORCEMENT SHALL BE FIRMLY SUPPORTED ON MILD STEEL PLASTIC TIPPED


CHAIRS, PLASTIC CHAIRS OR CONCRETE CHAIRS AT NO GREATER THAN 1m CENTRES
IN BOTH DIRECTIONS. BARS SHALL BE TIED AT ALTERNATE INTERSECTIONS. IN
EXPOSURE CONDITIONS GREATER THAN B1 USE ONLY PLASTIC CHAIRS.

8.3.

REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT NECESSARILY IN


TRUE PROJECTION.

8.4.

SLAB REINFORCEMENT SHALL EXTEND AT LEAST 75mm ONTO SUPPORT WALLS AND
50 PERCENT OF BOTTOM REINFORCEMENT SHALL BE COGGED TO ACHIEVE
ANCHORAGE AT SIMPLY SUPPORTED ENDS.

8.5.

SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN POSITIONS SHOWN OR


OTHERWISE APPROVED IN WRITING BY THE ENGINEER. LAPS SHALL BE IN
ACCORDANCE WITH THE FOLLOWING:
SLABS/STAIRS
TENSION SPLICE LAP LENGTH (mm)
CONCRETE GRADE 32MPa
BAR
N12
N16
N20
N24
N28
N32
N36

MINIMUM RELATIVE COMPACTION (%)


NON-COHESIVE SOILS
COHESIVE SOILS
LIGHT ROLLING/No. OF
LIGHT ROLLING/No. OF
PASSES
PASSES
97% OF STANDARD OR
95% OF STANDARD
65% DENSITY INDEX

LESS THAN 300mm CONCRETE


CAST BELOW BAR
550
750
1000
1250
1500
1800
2100

MORE THAN 300mm CONCRETE


CAST BELOW BAR
700
1000
1300
1650
1950
2350
2700

THESE LAP LENGTHS ARE BASED ON THE FOLLOWING MINIMUM COVER TO


REINFORCEMENT:

BEAMS/BANDS

3.14. KEEP FOOTINGS CLEAN AND FREE OF LOOSE MATERIAL BEFORE INSPECTION,
IMMEDIATELY PRIOR TO POURING OF CONCRETE, AND DURING POURING.

7.1.

THE DESIGN CERTIFICATION, CONSTRUCTION AND PERFORMANCE OF THE FORMWORK


AND PROPPING SHALL BE THE RESPONSIBILITY OF THE BUILDER.

BAR

3.15. ZONE OF INFLUENCE BETWEEN ADJACENT FOOTINGS OF EXCAVATION IS NOT


TO EXCEED A SLOPE OF 1 VERTICAL TO 3 HORIZONTAL UNLESS APPROVED
BY THE GEOTECHNICAL ENGINEER.

7.2.

FORMWORK DESIGN, CONSTRUCTION TOLERANCES AND STRIPPING TIMES SHALL


COMPLY WITH AS 3600 CLAUSE 4.4 & AS 3610 UNLESS NOTED OTHERWISE
APPROVED BY THE ENGINEER.

3.16. DO NOT BACKFILL RETAINING WALLS (OTHER THAN CANTILEVER WALLS)


UNTIL FLOOR CONSTRUCTION AT TOP AND BOTTOM IS COMPLETED. ENSURE
FREE DRAINING BACKFILL AND DRAINAGE IS IN PLACE.

7.3.

BUILD FORMWORK TO SPECIFIED STANDARDS AND FROM ARCHITECTURAL


DRAWINGS. PROVIDE FOR BUILT-IN FIXINGS, REBATES, FLASHINGS, TIES &
MECHANICAL, ELECTRICAL AND PLUMBING SERVICES ETC.

N12
N16
N20
N24
N28
N32
N36

3.17. FOOTINGS ARE TO BE CONSTRUCTED AND BACKFILLED AS SOON AS POSSIBLE


FOLLOWING EXCAVATION TO AVOID SOFTENING OR DRYING OUT BY EXPOSURE.

7.4.

DURING CONSTRUCTION, SUPPORT PROPPING WILL BE REQUIRED WHERE LOADS


FROM STACKED MATERIALS, FORMWORK AND OTHER SUPPORTED SLABS INDUCE
LOADS IN A SLAB OR BEAM WHICH EXCEED THE DESIGN LOAD FOR STRENGTH OR
SERVICEABILITY AT THAT AGE. ONCE THE NOMINATED 28 DAY STRENGTH HAS
BEEN ATTAINED, THESE LOADS SHALL NOT EXCEED THE DESIGN SUPERIMPOSED
LOADS SETOUT IN THE DESIGN DATA NOTES.

REGIONAL WIND SPEED VR = 88 m/s


ANNUAL PROBABILITY OF EXCEEDANCE = 1/500
REGION: D

THE FORMWORK SHALL NOT BE DESIGNED TO RELY ON RESTRAINT OR SUPPORT


FROM THE PERMANENT STRUCTURE WITHOUT PRIOR APPROVAL FROM THE
ENGINEER.

7.7.

FORMWORK SHALL BE DESIGNED TO ACCOMMODATE MOVEMENTS AND LOAD REDISTRIBUTION DUE TO POST TENSIONING.

7.8.

CONCRETE FORMED SURFACES TO HAVE FINISHES IN ACCORDANCE WITH AS 3610,


AS SPECIFIED BY THE ARCHITECT. WHERE SURFACE FINISHES HAVE NOT BEEN
SPECIFIED BY THE ARCHITECT, THE FOLLOW SCHEDULE MAY BE USED.

WALLS
TENSION SPLICE LAP LENGTH (mm)
CONCRETE GRADE 32MPa
BAR
N12
N16
N20
N24
N28
N32
N36

THE CONCRETE ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING


EXPOSURE CLASSIFICATIONS IN ACCORDANCE WITH AS 3600.
ELEMENT

CLASSIFICATION

SURFACE OF ELEMENTS IN
CONTACT WITH GROUND

A2

SURFACE OF ELEMENTS IN
INTERIOR ENVIRONMENTS

A1

SURFACE OF ELEMENTS IN
ABOVE GROUND ENVIRONMENTS

B1

BUILDING 2
EXPOSED COLUMNS
CONCEALED COLUMNS
EXPOSED SOFFITS
CONCEALED SOFFITS
SHEAR/CORE WALLS
STAIRS
BUILDING 4
COLUMNS
SOFFITS
SHEAR WALLS/CORES
SLAB/BEAM SIDES
STAIRS
BUILDING 5
COLUMNS
EXPOSED SOFFITS
CONCEALED SOFFITS
SLAB/BEAM SIDES
STAIRS
GENERAL

7.9.

CLASS OF FINISH
CLASS
CLASS
CLASS
CLASS
CLASS
CLASS

2
3
2
3
3
2

CLASS
CLASS
CLASS
CLASS
CLASS

2
2
2
2
2

N/A
CLASS
CLASS
CLASS
CLASS

2
3
2
2

ANY OTHER
EXPOSED FACES

CLASS 2

ANY OTHER
CONCEALED FACES

CLASS 3

MORE THAN 300mm CONCRETE


CAST BELOW BAR
850
1250
1700
2100
2550
3000
3550

WALLS - 20mm

INSITU FORMWORK CLASS OF FINISH SCHEDULE


LOCATION/ITEM

LESS THAN 300mm CONCRETE CAST


BELOW BAR OR VERTICAL BAR
700
1000
1300
1650
1950
2350
2700

THESE LAP LENGTHS ARE BASED ON THE FOLLOWING MINIMUM COVER TO


REINFORCEMENT:

HAZARD FACTOR Z = 0.09


PROBABILITY FACTOR kP = 1.0

MORE THAN 300mm CONCRETE


CAST BELOW BAR
600
850
1150
1500
1850
2250
2700

BEAMS/BANDS - 37mm CLEAR COVER TO LONGITUNDAL BAR (25mm COVER +12mm LINK)

EARTHQUAKE DESIGN CATEGORY: II


SITE SUB-SOIL CLASS: Ce

LESS THAN 300mm CONCRETE


CAST BELOW BAR
450
650
900
1150
1450
1800
2100

THESE LAP LENGTHS ARE BASED ON THE FOLLOWING MINIMUM COVER TO


REINFORCEMENT:

IT IS TO BE ANTICIPATED IN MULTI-STOREY CONSTRUCTION THAT PROPPING MAY


EXTEND AT LEAST 3 LEVELS BELOW THE FLOOR BEING CAST. PROP REMOVAL IS TO
BE PROGRAMMED TO AVOID DISTRESS TO PREVIOUSLY CAST FLOORS. RE-SHORING
OR BACKPROPPING IS SUBJECT TO THE APPROVAL OF THE ENGINEER.

7.6.

TERRAIN CATEGORY: 1
SEISMIC LOADS IN ACCORDANCE WITH AS1170.4 - 2007 AS FOLLOWS:

TENSION SPLICE LAP LENGTH (mm)


CONCRETE GRADE 32MPa

7.0 FORMWORK

7.5.

2.5.

GRADE
GRADE
GRADE
GRADE
GRADE

SLABS AND STAIRS - 20mm

2.2.

2.4.

DENOTES
DENOTES
DENOTES
DENOTES
DENOTES

NUMBER OF BARS

FILL MATERIAL SHALL MEET THE REQUIREMENTS OF THE SPECIFICATION.


PLACE IN MAXIMUM 150mm THICK LAYERS IN ACCORDANCE WITH AS
1289.5.4.1 FOR COHESIVE SOILS AND IN ACCORDANCE WITH AS 1289.5.6.1
FOR GRANULAR SOILS. MAXIMUM DEPTH OF FILL IS TO BE 750mm UNLESS
NOTED OTHERWISE BY THE ENGINEER. THE FOLLOWING TABLE SHALL BE
USED FOR MINIMUM RELATIVE COMPACTION LEVELS OF FILL MATERIAL.
LOCATION

SELECT COMPACTION METHOD THAT WILL NOT DAMAGE ADJACENT BUILDINGS.

S
N
SL
RL
R

THE BUILDER IS TO PROVIDE ANY PROPPING, SHORING, ETC, NECESSARY TO


SAFELY SUPPORT THE SIDES AND FACES OF ANY EXCAVATION SO AS TO
PREVENT MOVEMENT.

6.0 SLAB ON GRADE

3.10. COMPACTION TO BE TESTED BY AN APPROVED TESTING AUTHORITY AT


THE CONTRACTORS EXPENSE. A SUITABLY CALIBRATED PERTH SAND
PENETROMETER CAN BE USED TO TEST THE COMPACTION IN ACCORDANCE
WITH AS 1289.

2.0 DESIGN DATA


2.1.

3.8.

15.3

REINFORCEMENT SYMBOLS:

MESH SHALL BE LAPPED SUCH THAT THE TWO OUTERMOST WIRES OF ONE
SHEET OVERLAP THE TWO OUTERMOST WIRES OF THE OTHER SHEET BY 25mm
MINIMUM.

COMMENTS

25 MIN.

INTERNAL FINISH OF CORES TO BE CLASS 2

A MAXIMUM OF THREE SHEETS OF MESH SHALL BE LAPPED AT ANY POINT.


N12
500
8.6.

COMPRESSION SPLICE LAP LENGTH OF COLUMN BARS U.N.O


N16
N20
N24
N28
N32
650
800
1000
1150
1300

N36
1450

COMPRESSION & TENSION LAPPED SPLICES FOR BUNDLED BARS:


3 - BAR BUNDLE, INCREASE THE ABOVE VALUES BY 20% (= *1.20)
4 - BAR BUNDLE, INCREASE THE ABOVE VALUES BY 33% (= *1.33)
INDIVIDUAL BAR SPLICES WITHIN A GROUP SHALL NOT OVERLAP.

INSITU OFF FORM

DO NOT PLACE PERMANENT LOADS, INCLUDING MASONRY WALLS AND THE LIKE,
ON THE CONCRETE STRUCTURE UNTIL AFTER FORMWORK AND PROPPING IS
REMOVED.

8.7.

WELDING OF REINFORCEMENT SHALL NOT BE PERMITTED UNLESS SHOWN ON THE


STRUCTURAL DRAWINGS OR APPROVED BY THE ENGINEER.

8.8.

JOGGLES TO BARS SHALL BE 1 BAR DIAMETER OVER A LENGTH OF 12 BAR


DIAMETERS

8.9.

WHERE TRANSVERSE TIE BARS ARE NOT SHOWN PROVIDE N12-300 SPLICED
WHERE NECESSARY AND LAP WITH MAIN 450mm U.N.O.

1
REV

17-11-14
DATE

ISSUED FOR CONSTRUCTION


DESCIPTION

BVL
RVD

REVISIONS
7.10. DESIGN INFORMATION CONCERNING THE FOUNDATION FORMWORK SHALL BE
DETERMINED FROM THE CONDITIONS EXISTING ON SITE AT THE TIME OF
CONSTRUCTION. REFER ALSO TO THE GEOTECHNICAL REPORT.
7.11.

THE CONTRACTOR SHOULD BE AWARE OF TERMITE INFESTATION AND ENSURE


THAT NO TIMBER INCLUDING LOST OR BURIED FORMWORK IS LEFT ON OR
ADJACENT TO THE SITE. EXPANSION JOINT MATERIALS SHOULD BE OF NONORGANIC ORIGIN TO AVOID TERMITE ATTACK.

CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

7.12. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS OF CHAMFERS AND


REBATES. MAINTAIN COVER TO REINFORCEMENT AT THESE DETAILS.
7.13. DIMENSIONAL TOLERANCE SCHEDULE
DIMENSION OR
LOCATION OR ELEMENT
MEASUREMENT

TOLERANCE (mm)
PROJECT

THICKNESS

SLABS

VERTICAL DIMENSION

FLOOR TO FLOOR AT
EDGE OF BUILDING

+ 10mm - 0mm
10mm

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1:1

AT

A0 SIZE

TITLE

GENERAL NOTES - SHEET 1


PROJECT No.

P13378

DRAWING No.

S-2002

REV.

1
BG&E Pty Limited

9.0 CONCRETE

10.0 POST TENSIONING

11.0 STRUCTURAL STEEL

12.0 PRECAST CONCRETE WALL PANELS

9.1.

10.1.

11.1.

12.1

ALL PRECAST CONCRETE TO COMPLY WITH AS 3600 AND AS 3850.

12.2

REFER TO SPECIFICATION FOR REQUIREMENTS FOR SHOP DRAWINGS.

UNLESS NOTED OTHERWISE, ALL STEEL SHALL BE IN ACCORDANCE WITH AS 3678


GRADE 250, OR AS 3679, OR AS 1163 GRADE C350 AS APPROPRIATE.

12.3

TWO (2) COPIES OF WORKSHOP FABRICATION DRAWINGS SHALL BE SUBMITTED TO


THE ENGINEER FOR REVIEW AT LEAST 7 DAYS PRIOR TO COMMENCEMENT OF
FABRICATION. FABRICATION IS NOT TO COMMENCE WITHOUT ENGINEER'S APPROVAL
OF WORKSHOP DRAWINGS. ALL DIMENSIONS AND SETOUTS TO BE OBTAINED FROM
ARCHITECTURAL DRAWINGS WHERE NOT INDICATED ON STRUCTURAL DRAWINGS.

PANEL SIZE TO SUIT CRANE LIFTING CAPABILITIES. PROPOSED PANEL SIZES BY


PRECAST SUBCONTRACTOR TO BE SUBMITTED TO ENGINEER FOR REVIEW AND
APPROVAL.

12.4

SUBCONTRACTOR TO MAKE ALLOWANCES FOR ADDITIONAL CONNECTIONS REQUIRED


DURING LIFTING, ERECTION, BACK PROPPING AND TRANSPORTATION OF PRECAST
WALLS.

BOLT CATEGORIES AS SHOWN ON THE DRAWINGS:

12.5

SUBCONTRACTOR TO DESIGN PANELS FOR CONSTRUCTION CONDITIONS


INCLUDING MANUFACTURING, STORAGE, TRANSPORTATION AND ERECTION.
TEMPORARY BRACING SHALL BE PROVIDED BY BUILDER TO KEEP WORKS
STABLE DURING CONSTRUCTION.

12.6

MINIMUM COVER TO PRECAST PANELS TO BE AS BELOW:

ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS


3600 CURRENT EDITION WITH AMENDMENTS, EXCEPT WHERE VARIED BY THE
CONTRACT DOCUMENTS.

9.2.

PRE-MIXED CONCRETE SUPPLY SHALLC OMPLY WITH AS 1379

9.3.

NO ADMIXTURES SHALL BE USED IN CONCRETE UNLESS APPROVED IN WRITING.

9.4.

CONCRETE MIX DESIGNS TO BE SUBMITTED FOR REVIEW PRIOR TO USE.

9.5.

ALL PRESTRESSING WORK SHALL BE IN ACCORDANCE WITH AS 3600 CURRENT EDITION


WITH AMENDMENTS AND ITS REFERENCED CODES.

10.2. POST-TENSIONED SLAB AND BAND BEAM ELEMENTS HAVE BEEN DESIGNED AND
DETAILED ON THE BASIS OF INDUSTRY WIDE PRESTRESSING SYSTEMS APPROVED BY
THE POST TENSIONING INSTITUTE OF AUSTRALIA. THIS DOES NOT EXCLUDE THE USE
OF OTHER PRESTRESSING SYSTEMS, PROVIDED FULL ALTERNATIVE DETAILS ARE
SUBMITTED FOR REVIEW.
10.3. TENDONS TO CONSIST OF 12.7mm DIA. STRESS-RELIEVED SUPER GRADE STRAND TO
AS 4672 & HAVE A MINIMUM BREAKING LOAD 184kN PER STRAND UNLESS NOTED
OTHERWISE ON THE DRAWINGS. CABLES SHALL BE LOW RELAXATION. REFER TO
STRUCTURAL PLANS FOR NUMBER OF STRANDS IN EACH DUCT.

ENSURE CLEAR COVER TO REINFORCEMENT IS AS FOLLOWS UNLESS NOTED


OTHERWISE.

11.2.

11.3.

11.4.

ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 4100


EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.

COVER (mm)

ELEMENT

INTERIOR
ENVIRONMENT

EXTERIOR
ENVIRONMENT

10.4. SUBMIT SHOP DRAWINGS FOR APPROVAL OF THE TENDON LAYOUT FOR EACH FLOOR
SHOWING TENDON PROFILES. ANCHOR DETAILS INCLUDING NON PRESTRESSED
REINFORCEMENT AND PROPOSED STRESSING SEQUENCES.

IN GROUND

10.5. SUBMIT DETAILS FOR APPROVAL OF ALL STRESSING JACKS TO BE USED. THIS
SUBMISSION SHOULD INCLUDE A CALCULATION OF ALL LOSSES OCCURRING
THROUGHOUT THE ANCHOR AND THE STRESSING JACKS.
FOOTINGS
SLAB ON GROUND

40 TOP

10.6. SUBMIT CALIBRATION DATA FOR APPROVAL FOR EACH JACK USED ON THE PROJECT.
KEEP CALIBRATION DATA CURRENT AND SUBMIT AT LEAST 2 DAYS PRIOR TO ANY
STRESSING OPERATION BEING CARRIED OUT.

20 TOP
30 BOTTOM
30 SIDES

40

WALLS

40

40

COLUMNS

40

40

COREWALLS

40

40

REMAINDER

40

40

10.7. THE SLAB DESIGN ASSUMES A 70mm WIDE x 19mm DEEP SHEATH OF ZINC COATED
STEEL HAVING A FRICTION COEFFICIENT OF 0.20 AND A PARASITIC FRICTION
COEFFICIENT (WOBBLE FACTOR) OF 0.025rad/m. SHEATHS HAVING THESE PROPERTIES
ARE TO BE USED BY THE BUILDER UNLESS NOTED OTHERWISE.

SOME ELEMENTS MAY HAVE COVER WHICH VARIES FROM THE ABOVE TO
AVOID CLASHES etc. REFER DRAWINGS.
COVER SHOWN IS THE MINIMUM COVER TO ALL GROOVES AND CHAMFERS.

LOCATION

STRENGTH (MPa)
U.N.O

TARGET SLUMP
(mm)

F'c AT
28 DAYS

F'c AT
4 DAYS

INITIAL

PRIOR TO
PLACEMENT

CEMENT
TYPE

MIN. CEMENT
kg/m2

MAXIMUM
AGGREGATE
SIZE (mm)

MAXIMUM SHRINKAGE AT
56 DAYS (mm/mmx10-6)
(AS 1012 part 12)

MAX W/C

COMMENTS

FOOTINGS

ALL

32

80

(GB)

300

20

SLABS ON GROUND

ALL

32

80

(GB)

300

20

SUSPENDED SLABS
AND BEAMS

ALL

S40

22

80

GP

330

20

700

0.55

COLUMNS

ALL

S40

80

GP

330

20

700

0.62

CORE AND STAIR


WALLS

ALL

S40

80

GP

330

20

700

0.62

PRECAST

ALL

S40

80

GP

330

20

700

0.55

NOTES:
a.
FOR THESE CONCRETE MIXES THE REQUIREMENTS SPECIFIED FOR STRENGTH AND
SHRINKAGE ARE MANDATORY, OTHER PARAMETERS FOR THESE MIXES HAVE BEEN
SUGGESTED BUT MAY BE VARIED.
b.
PROJECT CONTROL TESTING SHALL BE CARRIED OUT IN ACCORDANCE WITH AS 1379 2007- SECTION 6.
c.
MINIMUM CONCRETE STRENGTHS SHALL BE IN ACCORDANCE WITH AS 3600 SECTION
4.4 AND 4.5.
d.
THE CONTRACTOR SHALL SUBMIT CONCRETE MIX DESIGNS FOR APPROVAL.
9.6.

CONCRETE SIZES SHOWN DO NOT INCLUDE THICKNESSES OF APPLIED FINISHES.

9.7.

DEPTHS OF BEAMS ARE GIVEN FIRST AND INCLUDE SLAB THICKNESS.

9.8.

FOR CHAMFERS, DRIP GROOVES, REGLETS, ETC., REFER TO ARCHITECTURAL


DETAILS. MAINTAIN COVER TO REINFORCEMENT AT THESE DETAILS.

9.9.

NO HOLES, CHASES OR EMBEDMENT OF PIPES OTHER THAN THOSE SHOWN ON THE


STRUCTURAL DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT THE
PRIOR WRITTEN APPROVAL OF THE ENGINEER.

9.10. CONSTRUCTION JOINTS WHERE NOT SHOWN SHALL BE LOCATED TO THE


APPROVAL OF THE ENGINEER.
9.11.

8.8/S

HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252 SNUG


TIGHTENED.

8.8/TB

HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252 FULLY


TENSIONED TO AS 4100 AS BEARING TYPE JOINT.

8.8/TF

HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252 FULLY


TENSIONED TO AS 4100 AS A FRICTION TYPE JOINT WITH FACING
SURFACES LEFT UNCOATED.

11.5.

10.8. ALL TENDON PROFILE DIMENSIONS SHOWN ON DRAWINGS ARE TO UNDERSIDE OF DUCTS
FROM SLAB SOFFIT EXCEPT AT ANCHORAGES WHERE DIMENSIONS ARE TO THE CENTRE
LINE OF THE TENDON. TENDON DUCTS SHALL BE LOCATED TO WITHIN 5mm OF CORRECT
POSITION. TENDON PROFILES SHALL BE PARABOLIC BETWEEN HIGH AND LOW POINTS
UNLESS NOTED OTHERWISE, AND SHALL BE SUPPORTED AT A MAXIMUM 1000 CENTRES
ALONG ITS LENGTH.

UNLESS NOTED OTHERWISE:


(a) ALL PLATES TO BE 10mm THICK MINIMUM, WELDED ALL ROUND.
(b) ALL BOLTS SHALL BE M20 CATEGORY 8.8/S.
(c) ALL HOLDING DOWN BOLTS SHALL BE M20 CATEGORY 4.6/S.
(d) ALL BOLTS, NUTS AND WASHERS SHALL BE HOT DIPPED GALVANISED.
(e) ALL CONNECTIONS SHALL HAVE A MINIMUM OF 2 BOLTS.

11.6.

/TB AND /TF BOLTS TO BE INSTALLED IN ACCORDANCE WITH SECTION 15 OF AS


4100, USING EITHER THE PART-TURN METHOD OR THE DIRECT-TENSION INDICATOR
METHOD. FOR TYPE /TF BOLTS, ALL CONTACT SURFACES ARE TO REMAIN
UNPAINTED.

10.9. DUCTS ARE TO BE GALVANISED AND RIGID ENOUGH TO RETAIN THEIR SHAPE. ALL
DUCT JOINTS SHALL BE TAPED TO PREVENT INGRESS OF CONCRETE SLURRY.

11.7.

ALL FABRICATION SHALL COMPLY WITH AS 4100, SECTION 14.

11.8.

ALL ERECTION SHALL COMPLY WITH AS 4100, SECTION 15.

11.9.

UNLESS NOTED OTHERWISE, ALL FILLET WELDS SHALL BE 6mm CONTINUOUS


CATEGORY SP USING E41XX ELECTRODES. ALL BUTT WELDS SHALL BE COMPLETE
PENETRATION BUTT WELDS CATEGORY SP TO AS 1554.1. UNLESS NOTED OTHERWISE,
ALL PURLIN CLEAT WELDS SHALL BE 6mm CONTINUOUS CATEGORY GP USING E41XX
ELECTRODES.

10.10. RECORDS OF TENSIONING OPERATION SHALL BE COMPILED BY THE STRESSING


CONTRACTOR AND FORWARDED TO THE STRUCTURAL ENGINEER TOGETHER WITH
CALCULATED THEORETICAL STRAND EXTENSIONS FOR APPROVAL.

CONCRETE MIX PERFORMANCE CRITERIA TABLE


ELEMENT

COMMERCIAL BOLTS OF GRADE 4.6 TO AS 1111 SNUG TIGHTENED.

50

40

BAND & BEAMS

25 TOP

20 TOP
30 BOTTOM
30 SIDES

SUSPENDED SLABS

50

4.6/S

THE FINISHED CONCRETE SHALL BE A DENSE HOMOGENEOUS MASS, COMPLETELY


FILLING THE FORMWORK THOROUGHLY EMBEDDING THE REINFORCEMENT AND FREE
OF STONE POCKETS. ALL CONCRETE INCLUDING SLABS ON GROUND AND FOOTINGS
SHALL BE COMPACTED WITH MECHANICAL VIBRATORS.

9.12. CURING OF ALL CONCRETE IS TO BE ACHIEVED BY KEEPING SURFACES


CONTINUOUSLY WET FOR A PERIOD OF 3 DAYS, AND PREVENTION OF LOSS OF
MOISTURE FOR A TOTAL OF 7 DAYS FOLLOWED BY A GRADUAL DRYING OUT.
APPROVED SPRAYED ON CURING COMPOUNDS THAT COMPLY WITH AS 3799 MAY
BE USED WHERE FLOOR FINISHES WILL NOT BE AFFECTED (REFER
MANUFACTURER'S SPECIFICATION). POLYTHENE SHEETING OR WET HESSIAN MAY
BE USED TO RETAIN CONCRETE MOISTURE WHERE PROTECTED FROM WIND AND
TRAFFIC (REFER SPECIFICATION).

REFER
DRAWINGS
REFER COLUMN
SCHEDULE
REFER
DRAWINGS

10.11. ALL DUCTS ARE TO BE FULLY PRESSURE GROUTED AS SOON AS PRACTICABLE AFTER
STRESSING RECORDS HAVE BEEN APPROVED BY THE STRUCTURAL ENGINEER. GROUT
TO COMPLY WITH CLAUSE 17.1.8, AS 3600.
10.12. ALL STRESSING OPERATIONS ARE TO TAKE PLACE IN THE PRESENCE OF EXPERIENCED
PERSONNEL. CARE SHALL BE TAKEN TO ENSURE SAFETY OF ALL SITE PERSONNEL
DURING STRESSING.

INTERNAL FACE = 25mm


EXTERNAL FACE = 35mm
12.7

ALL REINFORCEMENT WITHIN COVER ZONE TO EXTERNAL FACE OF PANELS TO BE


GALVANISED.

12.8

ALL EXTERNAL PACKERS AND REINFORCEMENT CHAIRS TO BE NON-FERROUS


MATERIAL.

11.10. STEELWORK INTENDED TO BE CONCRETE ENCASED SHALL BE UNPAINTED ENCASING


CONCRETE TO BE GRADE N25 PROVIDING A COVER ADEQUATE TO SUIT FIRE RATING
OR EXPOSURE CONDITIONS. CONCRETE ENCASEMENT SHALL BE CENTRALLY
REINFORCED WITH 5mm WIRE TO AS1303 OR 6mm STRUCTURAL BARS TO AS 1302
AT 150mm PITCH.

10.13. STRANDS SHALL BE TENSIONED FROM THE END INDICATED ON THE DRAWING.
10.14. ANCHORAGES ARE REPRESENTED ON PLANS AS FOLLOWS:
DENOTES LIVE END ANCHORAGE.

11.11. PROVIDE SEAL PLATES TO THE ENDS OF ALL HOLLOW SECTIONS, WITH 'BREATHER'
HOLES IF MEMBERS ARE TO BE HOT DIP GALVANISED.
11.12. ALL STEELWORK SHALL BE SECURELY TEMPORARILY BRACED BY THE ERECTOR AS
NECESSARY TO STABILISE THE STRUCTURE DURING ERECTION.

DENOTES LIVE END PAN ANCHORAGE.


DENOTES DEAD END ANCHORAGE.
DENOTES COUPLER.
10.15. EACH 12.7mm DIA STRAND SHALL BE TENSIONED WITH TOTAL JACKING FORCE OF
156kN (85% OF ULTIMATE TENSILE STRENGTH) UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
10.16. TOLERANCE ON REQUIRED TENDON EXTENSION TO BE IN ACCORDANCE WITH CLAUSE
17.3.4.5, AS 3600.
10.17. LOCATE LIVE ENDS OUTSIDE COLUMNS.
10.18. POST TENSIONING IS REQUIRED IN TWO STAGES (APPROX. 24 HOURS (F'/cp = 7 MPa)
AND 5 DAYS (F'/cp = 22 MPa) AFTER CASTING) UNLESS NOTED OTHERWISE. CONCRETE
STRENGTH TEST USING SITE CURED CYLINDERS SHALL BE TESTED TO ENSURE MINIMUM
CONCRETE STRENGTH BEFORE FULL PRESTRESS IS APPLIED.
10.19. MINIMUM EXPECTED LOSSES FOR SHRINKAGE, CREEP, RELAXATION, FRICTION AND
DRAW-IN ARE TO BE CALCULATED BY THE STRESSING CONTRACTOR AND SUPPLIED TO
THE ENGINEER FOR CHECKING AT LEAST ONE WEEK PRIOR TO ASSEMBLING CABLES ON
SITE.
10.20. ON COMPLETION OF STRESSING APPROVAL AND GROUTING, PERMANENTLY PROTECT
ALL ANCHORAGE PARTS AND PARTS OF TENDONS ANCHORED THERETO.

11.13. STRUCTURAL STEELWORK NOT ENCASED IN CONCRETE SHALL HAVE SURFACE


TREATMENT IN ACCORDANCE WITH THE SPECIFICATION.
11.14. THE BUILDER SHALL PROVIDE ALL CLEATS AND DRILL ALL HOLES NECESSARY FOR
FIXING STEEL TO STEEL AND TIMBER TO STEEL WHETHER OR NOT DETAILED IN THE
DRAWINGS.
11.15 FREE ALL MEMBERS FROM TWISTS AND DISTORTIONS BEFORE AND AFTER WELDING.
.
11.16 ALL MEMBERS TO BE IN ONE LENGTH, UNLESS OTHERWISE APPROVED.
.
11.17. CAMBERS TO BE AS NOTED ON THE DRAWINGS. NATURAL CAMBERS TO BE
UPWARDS.
11.18. WHERE MASONRY ANCHORS ARE SHOWN, THE SIZE REFERS TO THE STUD THREAD
DIAMETER.
11.19. WHERE THE FABRICATOR PROVIDES A SPLICE FOR AN APPROVED REASON (EG.
TRANSPORTATION) THE SPLICE SHALL BE COMPLETE PENETRATION BUTT WELDED
(CATEGORY SP) AND TESTED AS SPECIFIED.
11.20. WELDING IS TO BE EXAMINED BY AN INDEPENDENT TESTING AUTHORITY. TEST
RESULTS ARE TO BE SUBMITTED FOR APPROVAL.
TYPE OF WELD
AND CATEGORY

EXAMINATION
METHOD

EXTENT
(% OF TOTAL LENGTH
OF WELD TYPE)

FILLET

VISUAL

100

VISUAL

100

ULTRASONIC OR
RADIOGRAPHIC

10

VISUAL

100

VISUAL

100

ULTRASONIC OR
RADIOGRAPHIC

10

BUTT FULL
PENETRATION
SITE FILLET
SITE BUTT FULL
PENETRATION

9.13. CONSTRUCTION SUPPORT PROPPING IS TO BE LEFT IN PLACE WHERE NEEDED TO


AVOID OVERSTRESSING THE STRUCTURE DUE TO CONSTRUCTION LOADING. NO
MASONRY OR PARTITION WALLS ARE TO BE CONSTRUCTED ON SUSPENDED
LEVELS UNTIL ALL PROPPING IS REMOVED AND THE SLAB HAS ABSORBED ITS
DEAD LOAD DEFLECTION.
9.14. THE ENGINEER SHALL BE GIVEN 24 HOURS NOTICE FOR REINFORCEMENT
INSPECTION AND CONCRETE SHALL NOT BE DELIVERED UNTIL FINAL APPROVAL
OBTAINED.
9.15. CONDUITS, PIPES, ETC. SHALL ONLY BE LOCATED IN THE MIDDLE THIRD OF THE
SLAB DEPTH. PIPES OR CONDUITS SHALL NOT BE PLACED WITHIN THE COVER TO
REINFORCEMENT.
9.16. SLABS AND BEAMS SHALL BE CONSTRUCTED TO BEAR ONLY ON THE BEAMS,
WALLS, COLUMNS, ETC. SHOWN ON THE DRAWINGS. ALL OTHER BUILDING ELEMENTS
SHALL BE KEPT 25mm MINIMUM CLEARANCE FROM SOFFITS OF STRUCTURE.
9.17. TESTING OF CONCRETE SPECIMENS SHALL BE CARRIED OUT IN ACCORDANCE WITH
AS1012, AS1379 AND THE PROJECT SPECIFICATIONS.

1
REV

17-11-14
DATE

ISSUED FOR CONSTRUCTION


DESCIPTION

BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

PROJECT

STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

1:1

AT

A0 SIZE

TITLE

GENERAL NOTES - SHEET 2


PROJECT No.

P13378

DRAWING No.

S-2003

REV.

1
BG&E Pty Limited

C6
-C
2
B

CJ

250

C6
-C
2
B

150
CJ

30

S-2162

EXTERNAL GROUND LEVEL 50mm-150mm


BELOW INTERNAL S.S.L.

26
R3

26
R3

2
CC
B2
4
CC
B2

4
CC
B2

C3
-C
2
B

C5
-C
2
B

C5
-C
2
B

T.O.F. 10.700

B2-PF4 T.O.F. 10.900

26
R3
26
R3

250 INSITU

CJ

CJ

6
CC
B2

3
CC
B2

CJ

24
S3

CJ

B2-ST2
150

6
CC
B2

250 INSITU

50

26
R3

250

MASS CONCRETE
STAIR/LANDING SL72 MESH TOP

24
S3

C7
-C
2
B

C5
-C
2
B

250 INSITU
B2-PF5

B2-PF6
T.O.F. 10.450

B2-PF7
T.O.F. 10.350

T.O.F. 10.500

B2-PF6
T.O.F. 10.850

B2-PF6 T.O.F. 10.900

CJ

100

100

150

4
CC
B2
C4
-C
2
B

4
CC
B2

C4
-C
2
B

B2-PF4 T.O.F. 10.300

C5
-C
2
B

B2-PF2 T.O.F. 9.950

B2-PF4 T.O.F. 9.700

RAMP
UP

B2-PF3 T.O.F. 10.550

B2-PF4 T.O.F. 10.550

B2-PF4 T.O.F. 10.700


1000

26
R3

26
R3

S-2105

BUILDING 2 - FOOTING AND GROUND SLAB PLAN


SCALE: 1 : 100

NOTES:

FOR GENERAL NOTES REFER TO DRAWING S-2002 & S-2003.


FOR TYPICAL SLAB ON GROUND DETAILS REFER TO DRAWING S-2010
100 MINIMUM SLAB ON GROUND UNO.
SLABS TO BE POURED ON AN APPROVED DAMP PROOF MEMBRANE
REINFORCE SLABS WITH SL72 MESH (25 TOP COVER INTERNAL, 40 TOP COVER
EXTERNAL) THROUGHOUT.
PROVIDE 1N12 PERIMETER BAR TO SLAB LAPPED 500 MIN. AT CORNERS AND
WHERE REQIRED.
FOR EXTRA REINFORCEMENT AROUND COLUMNS REFER TO DRG. S-2010.
FOR EXTRA REINFORCEMENT AT RE-ENTRANT CORNERS REFER TO DRG. S-2010.
PROVIDE 10 JOINTEX OR APPROVED EQUIVALENT BETWEEN COLUMNS, WALLS
AND SLABS. TYPICAL.
ALL GRADES AND FALLS TO ARCHITECTS DETAILS
REFER ARCHITECT'S DRAWINGS FOR LOCATIONS OF HOBS, SPOON DRAINS AND
KERBS.
REFER TO ARCHITECT'S AND HYDRAULIC ENGINEERS DRAWINGS FOR LOCATION
OF HYDRAULIC PITS, PERIMETER DRAINS AND SERVICES INFORMATION.
NON LOADBEARING MASONRY WALLS NOT SHOWN ON PLAN FOR CLARITY.
REFER ARCHITECT'S DRAWINGS FOR LOCATIONS. REFER DRG. S-2010 FOR
TYPICAL THICKENING REQUIRED UNDER ALL NON-LOADBEARING MASONRY
WALLS.
SLAB ON GROUND EDGE THICKENINGS NOT SHOWN ON PLAN FOR CLARITY.
REFER TO DRG. S-2010 FOR TYPICAL DETAILS.
DOOR REBATES AND DISHES NOT SHOWN ON PLAN REFER TO ARCH.
DRAWINGS FOR LOCATIONS AND SETOUTS. REFER TO DRG. S-2010 FOR
STRUCTURAL DETAILS.

BUILDING 2 - CONCRETE COLUMN SCHEDULE


SIZE

MARK

SIZE

B2-CC1
B2-CC2
B2-CC3
B2-CC4
B2-CC5
B2-CC6
B2-CC7

300
350
400
450
500
550
600

MC01
R326
S313
S320
S324
S330
S333
UB08

152.4 x 4.8 CHS(C350)


200 x 100 x 5.0 RHS
75 x 5.0 SHS
100 x 5.0 SHS
125 x 5.0 SHS
200 x 5.0 SHS
250 x 6.0 SHS
200 UB 25

BUILDING 2 - PAD FOOTING SCHEDULE


MARK

B2-PF1
B2-PF2
B2-PF3
B2-PF4
B2-PF5
B2-PF6
B2-PF7
B2-PF8
B2-PF9

1600
2100
2400
2700
3000
3300
3500
900
2300

1600
2100
2400
2700
3000
3300
3500
900
3600

400
500
600
700
800
900
1100
300
500

B1

B2

7N16
8N20
13N20
17N20
14N24
14N32
16N32
4N16
18N20

7N16
8N20
13N20
17N20
14N24
14N32
16N32
4N16
13N20

DENOTES LOADBEARING ELEMENT BELOW SLAB

DENOTES LOADBEARING ELEMENT ABOVE SLAB

MARK

COMMENTS

DENOTES LOADBEARING ELEMENTS ABOVE AND BELOW SLAB

B2-CF1
B2-CF2

REFER TO DRG. S-2102


REFER TO DRG. S-2103

450 MAX.

GIRTS BETWEEN COLUMNS FOR


EXTENTS SHOWN TO BE:

C20019 AT 1200 MAX CTS


FOR LENGTHS > 2000mm

C15019 AT 1200 MAX CTS


OTHERWISE

1 ROW BRIDGING (TYP)

4
3
2
1
REV

17-11-14
22-10-14
05-09-14
22-07-14
DATE

STEPS UPDATED TO SUIT ARCH.


ISSUED FOR CONSTRUCTION
LEVELS UPDATED
FORWARD WORKS ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
BVL
BVL
RVD

REVISIONS
CLIENT

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

REINFORCEMENT

30
S3

24
S3

BUILDING 2 - STEEL COLUMN SCHEDULE

MARK

FOOTING SIZE
W
D

26
26
R3 R3

950
650

150 MIN.

24
S3
C4
-C
2
B

C5
-C
2
B
26
R3

NOTE:
R326/S324/S330 COLUMN BASEPLATE
CONNECTION TO BE 10 THICK OFFSET
BASEPLATE FIXED TO SLAB EDGE
THICKENING WITH 4M12 HILTI HITRE500 ANCHORS (110 EMBEDMENT)
PROVIDE 80 MIN EDE DISTANCE.

S-2105

200

5
CC
B2

24
S324
S3
24
S3 4
2
S3
24
S3
24
S3

DENOTES KEYED SLAB JOINT.


REFER TO DRG. S-2010 FOR
DETAILS. TYPICAL

24
S3

TRENCH

CJ

50

B2-PF1
T.O.F. 10.200

300

24
S3

50

C6
-C
2
B

B2-PF3
T.O.F. 10.100

C4
-C
2
B

MAX.

50

B2-PF3

300

24
S3

C4
-C
2
B

100

C3
-C
2
B

3
CC
B2

CJ

50
350
C6
-C
2
B

B2-PF6 T.O.F. 9.600

A1

100

MC
01

MC
01

MC
01
S-2105

RAMP UP

4
CC
B2

950

200

50

B2-PF4 T.O.F. 10.250 B2-RW1


T.O.F. 9.600
B2-RW1
T.O.F. 9.600
C5
C
B2

01
MC

B2-CF2 T.O.F. 10.600

26
R3

300

250 INSITU

B2-RW1

A2

B2-PF8
T.O.F. 11.000

B2-PF4 T.O.F. 10.850

26
R3

4
CC
B2

9
CJ

B2-ST1

C4
-C
2
B

B2-PF1
T.O.F. 9.900

B2-PF8
T.O.F. 11.000

CJ

A3

26
R3

C5
-C
2
B

50

250

B2-PF2
T.O.F. 9.900

B2-PF8
T.O.F. 11.000

B2-PF3 T.O.F. 10.650


30
S3

26
R3

300
MASS CONCRETE
STAIR/LANDING SL72 MESH TOP

B2-PF8
T.O.F. 11.000

1850

B2-PF4 T.O.F. 10.650


26
26
R3
R3

200

RAMP UP

CJ

C5
-C
2
B

26
R3
26
R3

S-2105

250 INSITU

250 INSITU

26
R3
C4
-C
2
B

BETWEEN COLUMNS FOR EXTENTS SHOWN TO BE:


C20019 AT 1200 MAX CTS FOR LENGTHS > 2000mm
C15019 AT 1200 MAX CTS OTHERWISE
1 ROW BRIDGING (TYP)

250 INSITU
700

A4

B2-RW1

30
30

26
R3

26
R3

26
R3

CJ

B2-RW1

30
S3

CJ

200

B2-PF2 T.O.F. 10.700

250 INSITU

26
R3

GIRTS

CJ

4
GIRTS BETWEEN COLUMNS FOR 2-CC
B
EXTENTS SHOWN TO BE:

C20019 AT 1200 MAX CTS


FOR LENGTHS > 2000mm

C15019 AT 1200 MAX CTS


OTHERWISE
B2-PF3
T.O.F. 9.900

1 ROW BRIDGING (TYP)

CASE 4
EXTERNAL GROUND LEVEL 1mm-250mm
ABOVE INTERNAL S.S.L.

EDGE THICKENING TO SLAB ON


GROUND. REFER TYPICAL EDGE
CONDITIONS DETAIL. TYPICAL

B2-RW1

A5

DPM

3N12
N12-200

7
CC
B2

26
R3
B2-PF4 T.O.F. 10.550

250 INSITU

250 INSITU

B2-PF2
T.O.F. 9.900

400

B2-PF1
T.O.F. 10.600
C2
-C
2
B

250 INSITU
C4
-C
2
B

50 MIN.
150 MAX.

CASE 2

250 INSITU

A6

S-2105

B2-PF9
T.O.F. 10.550

CJ

B2-RW1

4
4
CC
B2

C7
-C
2
B

KEYPLAN

N12-200
1
2

300

4N12

50

C5
-C
2
B

CJ

30

26
R3

50

250 INSITU

B2-RW1
30
S3

250 INSITU

26
R3
26
R3

4
GIRTS BETWEEN COLUMNS FOR
CC
EXTENTS SHOWN TO BE:
B2

C20019 AT 1200 MAX CTS


FOR LENGTHS > 2000mm

C15019 AT 1200 MAX CTS


OTHERWISE
B2-PF2

1 ROW BRIDGING (TYP)


T.O.F. 9.900

B2-ST1

MASS CONCRETE
STAIR/LANDING SL72 MESH TOP

B2-PF1
T.O.F. 10.650
C2
-C
2
B

B2-RW1

INTERNAL S.S.L.

DPM

2
CC
B2

EXTERNAL G.L.

EXTERNAL G.L.
1

BUILDING 2

SCALE: 1 : 20
5500

250 INSITU

250 INSITU

700

CJ

EXTERNAL G.L.

BUILDING 2 - SLAB ON GROUND EDGE CONDITIONS

CJ

5
CC
B2

100

300

B2-PF1
T.O.F. 10.500

B2-RW1 T.O.F. 10.000

B2-RW1
T.O.F. 9.600

B2-CF1 T.O.F. 9.600

B2-PF4
T.O.F. 10.700

B2-PF6 T.O.F. 10.700


C6
-C
2
B

BUILDING 4

EXTERNAL GROUND LEVEL 150mm-450mm


BELOW INTERNAL S.S.L.

MASS CONCRETE
STAIR/LANDING SL72 MESH TOP

B2-PF6
T.O.F. 10.000

B2-PF6 T.O.F. 10.000

MASS CONCRETE
STAIR/LANDING SL72 MESH TOP

CJ

400

CASE 3

INTERNAL S.S.L.

S-2105

CJ

A7

3L8TM

EXTERNAL GROUND LEVEL 0mm-50mm


BELOW INTERNAL S.S.L.

B2-RW1

S-2105

B2-PF3
T.O.F. 9.900

1
DPM

CASE 1

7
CC
B2

C2
-C
2
B

300

DPM

B2-PF2
B2-PF1
T.O.F. 10.500
T.O.F. 10.500

C3
-C
2
B

150
MIN.

5
CC
B2

4
CC
B2

INTERNAL S.S.L.

EXTERNAL G.L.

200

250

B2-PF4 T.O.F. 9.900

A8

5
CC
B2

REFER TO DRG. S-2010 FOR


STEP IN SLAB ON GROUND
DETAIL. TYPICAL

CJ

B2-PF2
T.O.F. 9.900

26
R3

BUILDING 5

CJ

S-2105

4
CC
B2

AK
INTERNAL S.S.L.

B2-PF2
T.O.F. 10.500
26
26
R3
R3

B2-PF4 T.O.F. 10.000


B2-RW1
26
R3

5
CC
B2

B2-PF3 T.O.F. 10.000


C4
-C
2
B

AJ

150 MIN
300 MAX.

C2
-C
2
B

A9

AH

50
MIN.

B2-PF4 T.O.F. 10.000

B2-PF1
T.O.F. 10.000

B2-PF1
T.O.F. 9.900

AG

S-2105

T.O.F. 10.000

A10

AF

200

EDGE THICKENING TO SLAB ON


GROUND. REFER TYPICAL EDGE
CONDITIONS DETAIL. TYPICAL

AE

300

AD

0 MIN.
50 MAX.

AC

100

AB

1765

AA

GIRTS BETWEEN COLUMNS FOR


EXTENTS SHOWN TO BE:

C20019 AT 1200 MAX CTS FOR


LENGTHS > 2000mm

C15019 AT 1200 MAX CTS


OTHERWISE

1 ROW BRIDGING (TYP)

PROJECT

BUILDING 2 - COMBINED FOOTING SCHEDULE


STATUS

ISSUED FOR CONSTRUCTION

DRAWN

DESIGNED

CC
DATUM

MW/DB
GRID

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - FOOTING AND GROUND


SLAB PLAN
PROJECT No.

P13378

DRAWING No.

REV.

S-2101

4
BG&E Pty Limited

2
S-2102

AB

AC

AB

AC

1600

1000

C5
-C
2
B

A7

A7

N24-200 (2)

DENOTES U-BARS TO MATCH


FOOTING TOP REINFORCEMENT
SIZE AND SPACING. PROVIDE
N16-300 HORIZONTAL SIDE
REINFORCEMENT ALL VERTICAL
FACES NSOP.

N24-125 (1)

N24-125 (4)

N20-150 STARTER
BARS EACH FACE

C4
-C
2
B

A6

LAP

LAP

N24-200 (3)

A6

N24-200 (4)

N24-200 (3)

N20-200 (3)
N24-200 (4)

N24-200 (3)

IT
TP
LIF

P
DEE

S-2102

N20-200 (2)

N24-200 (4)

1300

N20-150 STARTER
BARS EACH FACE

C4
-C
2
B

A5

AB

AC

250

250

250

N24-125 (4)

LAP

250

10mm COMPRESSIBLE
FILLER. TYPICAL
REFER TO PLAN FOR
SLAB REINFORECMENT.
TYPICAL

DPM

250

REFER ARCH.

N24-100 (1)

N24-200 (3)

A4

U-BARS TO MATCH FOOTING


TOP REINFORCEMENT SIZE AND
SPACING. PROVIDE N16-300
HORIZONTAL SIDE
REINFORCEMENT ALL VERTICAL
FACES NSOP.

N16-300 SIDE
REINFORCEMENT
ALL FACES

1300

A4

TENSION LAP

250

5
CC
B2

REFER TO PLAN FOR WALL


STARTER BAR SIZE AND
SPACING. TYPICAL

SLAB PERIMETER BAR.


TYPICAL

100

N24-200 (2)

N20-150 STARTER
BARS EACH FACE

1
2

TYPICAL

LAP

A5

350

TENSION LAP
TYPICAL

10900

BUILDING 2 - COMBINED FOOTING TYPE CF1 PLAN

BUILDING 2 - COMBINED FOOTING TYPE CF1 REINFORCEMENT PLAN

SCALE: 1 : 50

SCALE: 1 : 50

A4

A5

A6

SECTION

SCALE: 1 : 20

S-2102

A7
2

2
250

250

250

250

250

250

10mm COMPRESSIBLE
FILLER. TYPICAL
REFER TO PLAN FOR WALL
STARTER BAR SIZE AND
SPACING. TYPICAL

SLAB PERIMETER BAR.


TYPICAL

300

DPM. TYPICAL

TYPICAL

TYP.

1
2

TENSION LAP

REFER ARCH.

B2-RW1

N16-300 SIDE
REINFORCEMENT
ALL FACES

BLOCKWORK WALLS REMOVED FROM DETAIL


FORWARD WORKS ISSUED FOR CONSTRUCTION
DESCIPTION

BVL
BVL
RVD

CLIENT

U-BARS TO MATCH FOOTING


TOP REINFORCEMENT SIZE AND
SPACING. PROVIDE N16-300
HORIZONTAL SIDE
REINFORCEMENT ALL VERTICAL
FACES NSOP.

TYP.

17-11-14
22-07-14
DATE

REVISIONS

MASS CONCRETE STAIRS

MASS CONCRETE STAIRS


TENSION LAP

REFER DRG. S-2105


FOR B5-RW1 DETAILS

250

900 LAP TYP.

REFER TO DRG. S-2101


FOR SLAB REINFORCEMENT.
TYPICAL

2
1
REV

Podium Level Central Park 152 - 158 St. Georges Terrace


Perth, Western Australia 6000
T 61 8 6477 6000 Fx 61 8 6477 6100
Email [email protected]

1300

PROJECT

TENSION LAP
TYPICAL

STATUS

B2-CF1

ISSUED FOR CONSTRUCTION

20100
DRAWN

DESIGNED

CC
DATUM

SECTION
SCALE: 1 : 20

MW/DB
GRID

2
S-2102

CHECKED

APPROVED

BVL

BVL

SCALE

As indicated

AT

A0 SIZE

TITLE

BUILDING 2 - COMBINED FOOTING


PLANS AND DETAILS SHEET 1
PROJECT No.

P13378

DRAWING No.

S-2102

REV.

2
BG&E Pty Limited

You might also like