Vol3 24 PDF
Vol3 24 PDF
OVERLOAD PROTECTION OF
THREE-PHASE MOTORS
Overload
Protection of
Three-Phase
Motors
By HARRY A. WRIGHT, P.E., Consulting Engineer
Elm Grove, Wis.
THE 1971 EDITION of the National Electrical Code requires
that an overload protective device be installed in each phase of
a 3-phase motor feeder. In the superseded 1968 edition,
protection was mandatory in only two legs of a 3-phase motor
feeder---provided that the motor was not installed in an isolated,
inaccessible, or unattended location.
The new Code does away with the exception which permitted
protection in only two phases for accessible motors, and 3-phase
overload protection is now required in all cases for 3-phase
motors, an overwhelming majority of industrial electrical
motors are in- stalled in areas where the old "minimum of two
overload elements" provision applied, and most 3-phase motors
in service today have protection in only two legs. However an
understanding of why the Code change was necessary bears out
the wisdom of providing protection in each phase, and the
advisability of retrofitting older motor branch circuits to
incorporate 3-phase overload protection.
Requirement of protection in each phase of a 3-phase
motor is, essentially, a means of minimizing motor burnouts
that are caused by unbalanced line voltages or single-phasing.
Here's what NEMA Standard MG 1-1433 has to say about the
effect of voltage unbalance on polyphase motors:
"The effect of unbalanced voltages on polyphase induction
motors is equivalent to the introduction of 'negative
sequence voltage' having a rotation opposite to that
occurring with balanced voltages. This negative sequence
voltage produces in the air gap a flux rotating against the
rotation of the rotor, tending to produce high current. A
small negative sequence voltage may produce in the
windings currents considerably in excess of those present
under balanced voltage conditions.
"The voltage unbalance (or negative sequence voltage)
in percent may be defined as follows: Per cent voltage
unbalance =
Max. voltage deviation from Avg. voltage x 100
Average voltage
Example: With voltages of 220, 215, and 210,
the average is 215, the maximum deviation from the average is
5, and the percent unbalance is
5
215