Transformer Testing - Type Test and Routine Test of Transformer - Electrical
Transformer Testing - Type Test and Routine Test of Transformer - Electrical
electrical4u.com
Online Electrical Engineering
SHOW MENU
Distribution Transformer
Air Core Transformer
High Voltage Transformer
Installation of Power Transformer
Commissioning of Power Transformer
This page is all about:
Type of Transformer Testing
Type Test
Routine Tests
Special Tests
Pre Commissioning Test
Winding Resistance Measurement
Ratio Test
Magnetic Balance Test
Procedure of Magnetic Balance Test
Magnetizing Current Test
Vector Group Test
Insulation Resistance Test or Megger Tes
Procedure of Insulation Resistance Test
Dielectric Tests of Transformer
Induced Voltage Test of Transformer
Temperature Rise Test of Transformer
2. Routine tests
3. Special tests
3. Emergency tests
That means Routine tests of transformer include all the type tests
except temperature rise and vacuum tests. The oil pressure test on
transformer to check against leakages past joints and gaskets is
included.
Design a Transformer
Free samples 24 hours Easy forms on-line TRY IT!
3. Short-circuit test.
4. Measurement of acoustic noise level.
5. Measurement of the harmonics of the no-load current.
6. Measurement of the power taken by the fans and oil pumps.
7. Tests on bought out components / accessories such as buchhloz relay,
temperature indicators, pressure relief devices, oil preservation
system etc.
Left side
phase
Central
phase
Right side
phase
AN
BN
CN
230 V
180 V
50 V
115 V
230 V
115 V
50 V
180 V
230 V
1. First of all keep the tap changer in the lowest position and open all
IV & LV terminals.
2. Then apply three phase 415 V supply on the line terminals for three
phase transformers and single phase 230 V supply on single phase
transformers.
3. Measure the supply voltage and current in each phase.
4. Now repeat the magnetizing current test of transformertest with
keeping tap changer in normal position.
5. And repeat the test with keeping the tap at highest position.
Generally there are two similar higher readings on two outer limb
phases on transformer core and one lower reading on the centre limb
phase, in case of three phase transformers. An agreement to within
30% of the measured exciting current with the previous test is
usually considered satisfactory. If the measured exciting current
value is 50 times higher than the value measured during factory test,
there is likelihood of a fault in the winding which needs further
analysis.
Caution: This magnetizing current test of transformer is to be
carried out before DC resistance measurement.
4. The test shall start with a voltage lower than 1/3 the full test voltage,
and it shall be quickly increased up to
desired value.
The test is successful if no break down occurs at full test voltage
during test.
Email : -
Location : -
Suggestion / Comment : -
Regenerate Code
Submit
Reset