Specified Conditions As Per Heat Load Calculations Requirement

The document provides specifications for air conditioning units required for various villa types in the Bermuda Villas project. It lists 11 villa types with details such as the location, unit type (ducted or split), nominal tonnage, CFM, quantity and calculated total and sensible cooling capacity in tons for each air conditioning unit. The specifications are based on design conditions of an entering air temperature of 70°F DB and 60°F WB, ambient temperature of 115°F and using R-407C refrigerant. A total of 754 air conditioning units are specified.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views

Specified Conditions As Per Heat Load Calculations Requirement

The document provides specifications for air conditioning units required for various villa types in the Bermuda Villas project. It lists 11 villa types with details such as the location, unit type (ducted or split), nominal tonnage, CFM, quantity and calculated total and sensible cooling capacity in tons for each air conditioning unit. The specifications are based on design conditions of an entering air temperature of 70°F DB and 60°F WB, ambient temperature of 115°F and using R-407C refrigerant. A total of 754 air conditioning units are specified.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Project: Bermuda Villas

AS PER HEAT LOAD CALCULATIONS


REQUIREMENT

SPECIFIED CONDITIONS
SN.

Location

UNIT TYPE

TMBH
(NOM)

CFM

QTY

TMBH

SMBH

DCFM

TR

VILLA TYPE - A [ 5 VILLAS]

AC-GF-FCU-01

Ducted

18

480

17.99

15.8

685

1.499

AC-GF-FCU-02

Ducted

18

640

17.46

16.36

779

1.455

AC-GF-FCU-03

Ducted

32

640

30.9

25.29

981

2.575

AC-GF-FCU-04

Ducted

72

1920

67.36

61

2757

5.613

AC-GF-FCU-05

Ducted

60

1600

55.28

51.44

2426

4.607

AC-FF-FCU-01

Ducted

18

480

19.06

17.97

862

1.588

AC-FF-FCU-02

Ducted

24

480

25.41

24.31

1189

2.118

AC-FF-FCU-03

Ducted

12

480

13.04

11.94

551

1.087

AC-FF-FCU-04

Ducted

24

640

11.2

10.83

494

0.933

10

AC-FF-FCU-05

Ducted

36

960

29.84

28.75

1418

2.487

11

AC-FF-FCU-06

Ducted

32

800

28.9

27.25

588

2.408

55
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Design conditions selected based on 27/19 air on coil & 46 deg C ambient temp.
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C

FIT-410.01 R0 D01/06/2010

Project: Bermuda Villas

AS PER HEAT LOAD CALCULATIONS


REQUIREMENT

SPECIFIED CONDITIONS
SN.

Location

UNIT TYPE

TMBH
(NOM)

CFM

QTY

TMBH

SMBH

DCFM

TR

VILLA TYPE - B [ 20 VILLAS]

AC-GF-FCU-01

Ducted

18

480

20

14.62

13.72

896

1.22

AC-GF-FCU-02

Ducted

18

480

20

15.78

15.33

1001

1.32

AC-GF-FCU-03

Ducted

24

640

20

22.88

20.84

1361

1.91

AC-GF-FCU-04

Ducted

60

1600

20

63.15

61.8

4037

5.26

AC-GF-FCU-05

Ducted

36

960

20

38.1

36.06

2355

3.18

AC-FF-FCU-01

Ducted

30

800

20

27.97

27.52

1798

2.33

AC-FF-FCU-02

Ducted

24

640

20

20.23

19.78

1292

1.69

AC-FF-FCU-03

Ducted

30

800

20

27.27

26.82

1752

2.27

AC-FF-FCU-04

Ducted

36

1120

20

38.71

38026

2499

3.23

10

AC-FF-FCU-05

Ducted

36

1120

20

38.23

37.1

2423

3.19

200
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C

FIT-410.01 R0 D01/06/2010

Project: Bermuda Villas

AS PER HEAT LOAD CALCULATIONS


REQUIREMENT

SPECIFIED CONDITIONS
SN.

Location

UNIT TYPE

TMBH
(NOM)

CFM

QTY

TMBH

SMBH

DCFM

VILLA TYPE - C [23 VILLAS]

AC-GF-FCU-01

Ducted

18

480

23

14.62

13.72

896

1.22

AC-GF-FCU-02

Ducted

18

480

23

15.78

15.33

1001

1.32

AC-GF-FCU-03

Ducted

24

640

23

22.88

20.84

1361

1.91

AC-GF-FCU-04

Ducted

72

1600

23

63.15

61.8

4037

5.26

AC-GF-FCU-05

Ducted

36

960

23

38.1

36.06

2355

3.18

AC-FF-FCU-01

Ducted

24

800

23

14.22

13.12

612

1.19

AC-FF-FCU-02

Ducted

18

480

23

18.66

17.56

841

1.56

AC-FF-FCU-03

Ducted

42

1120

23

23.82

22.72

1107

1.99

AC-FF-FCU-04

Ducted

48

1280

23

31.47

27.62

1198

2.62

207
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C

FIT-410.01 R0 D01/06/2010

Project: Bermuda Villas

AS PER HEAT LOAD CALCULATIONS


REQUIREMENT

SPECIFIED CONDITIONS
SN.

Location

UNIT TYPE

TMBH
(NOM)

CFM

QTY

TMBH

SMBH

DCFM

TR

VILLA TYPE - C [ 61 VILLAS]

AC-GF-SP-01

Split

160

61

8.04

6.94

293

0.67

AC-GF-FCU-02

Ducted

24

640

61

29.59

27.39

1283

2.47

AC-GF-FCU-03

Ducted

72

1920

61

61.4

57

2681

5.12

AC-FF-FCU-01

Ducted

36

960

61

30.75

29.11

1404

2.56

AC-FF-FCU-02

Ducted

42

1120

61

45.34

42.05

1974

3.78

AC-FF-FCU-03

Ducted

18

480

61

16.51

15.42

730

1.38

366
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C

FIT-410.01 R0 D01/06/2010

Project: Bermuda Villas

AS PER HEAT LOAD CALCULATIONS


REQUIREMENT

SPECIFIED CONDITIONS
SN.

Location

UNIT TYPE

TMBH
(NOM)

CFM

QTY

TMBH

SMBH

DCFM

TR

VILLA TYPE - C [ 48 VILLAS]

AC-GF-FCU-01

Split

12

320

48

10.95

9.85

443

0.91

AC-GF-FCU-02

Ducted

42

1280

48

58.66

53.17

2418

4.89

AC-FF-FCU-01

Ducted

18

480

48

17.6

16.5

786

1.47

AC-FF-FCU-02

Ducted

30

800

48

22.81

17.87

630

1.90

AC-FF-FCU-03

Ducted

24

640

48

24.96

22.77

1045

2.08

240
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C

FIT-410.01 R0 D01/06/2010