Solar Power Design Documents
Solar Power Design Documents
PV SYSTEM SUMMARY:
SITE LOCATION:
CITY NOTES:
MODULE
INVERTER
ROOF
TILT
R1 & R2 - 5 PITCH
AZIMUTH
R1 - 270 & R2 - 90
INSTALLATION NOTES:
THE PV BREAKER SHALL NOT EXCEED 120% OF THE ALLOWABLE BACK FEED OF THE MAIN
SERVICE BUSS RATING.
PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESS
INVERTERS.
INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK.
RAFTER/TRUSS SIZE
ATTACHMENT TYPE
UTILITY
SITE LOCATION
TABLE OF CONTENTS
PV-1
PV-2
PV-3
PV-4
PV-5
PV-6
CLIENT:
REVISIONS:
XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx
DESCRIPTION
TITLE:
DATE:
DATE
12/22/2015
REVISION
DESIGN
BY:
XXX
JOB
NO.:
BAC-XXX
SYSTEM SUMMARY,
NIOTES, SITE
LOCATION AND
HOUSE AERIAL VIEW
SHEET:
PV-1
1
2
3'-3"
MODULES
PITCH AZIMTUH ROOF AREA ARRAY AREA
QTY
818.87 SQ FT 421.53 SQ FT
5
270
24
644.48 SQ FT 211.97 SQ FT
12
5
90
3'
ROOF LINE
24 SUNMODULE SW 265
MONO BLACK MODULES
3'
12 SUNMODULE SW 265
MONO BLACK MODULES
ATTACHMENT POINTS
@ 48" O.C. MAX (TYP)
24 SUNMODULE SW 265
MONO BLACK MODULES
ATTACHMENT POINTS
@ 48" O.C. MAX (TYP)
JUNCTION BOX
JB
JUNCTION BOX
LC INV1 INV2
JB
MSP
12 SUNMODULE SW 265
MONO BLACK MODULES
PROPOSED MODULES
EXISTING
MSP
MSP ACD FM
R-2
11'-8"
R-1
17'-10"
SMA SB 3000TL-US
INVERTER
SMA SB 5000TL-US
INVERTER
LOAD CENTER
FINANCE METER
AC DISCONNECT
EXISTING MSP
DRIVE WAY
W 4TH ST
SITE PLAN
CLIENT:
REVISIONS:
XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx
DESCRIPTION
TITLE:
DATE:
DATE
2
SHEET:
12/22/2015
REVISION
DESIGN
BY:
XXX
JOB
NO.:
BAC-XXX
PV-2
MATERIAL LIST
QUICK MOUNT
ATTACHMENTS
LABELS
ALL PLACARDS SHOULD BE WITH WHITE LETTERING IN RED BACKROUND WITH A MIN. OF 3/8"
LETTERING HEIGHT AND USING ARIAL OR SIMILAR FONT, NON-BOLD AND ALL CAPITAL LETTERS
PV MODULE
"L" BRACKET
MODULE
MOUNTING
RAIL
QTY
EQUIPMENT
36
SUNMODULE
SW 265 MONO
BLACK, SOLAR
MODULES
SMA, SB
5000TL-US-22
INVERTER WITH
INTEGRATED
DISCONNECT
600V
15A
211-264V
22A
5000W
96.5%
SMA, SB
3000TL-US-22
INVERTER WITH
INTEGRATED
DISCONNECT
600V
15A
211-264V
15A
3000W
96%
JUNCTION BOX
AC
DISCONNECT
LOAD CENTER
PV BREAKER
METER
70'
CONDUIT
66
ATTACHMENTS
QUICKMOUNTATTACHMENTS
200'
RAIL
UNIRAC
64
MID CLAMPS
16
END CLAMPS
4"
ROOF
2
SS LAG BOLT
PV-4
ATTACHMENT DETAIL
DESCRIPTION
OPEN CIRCUIT VOLTAGE (Voc) :
MAX. POWER VOLTAGE (Vmp) :
SHORT CIRCUIT CURRENT (Isc) :
MAX. POWER CURRENT (Imp) :
PTC RATING :
PV MODULE
QUICK MOUNT
ATTACHMENTS
MODULE
MOUNTING RAIL
"L" BRACKET
SS LAG BOLT
ENLARGED DETAIL
2
W 4TH ST
CLIENT:
REVISIONS:
XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx
DESCRIPTION
TITLE:
DATE:
DATE
SHEET:
12/22/2015
REVISION
DESIGN
BY:
XXX
JOB
NO.:
BAC-XXX
DETAILS, MATERIAL
LIST AND LABELS
PV-3
ELECTRICAL CALCULATIONS:
STRING 1 CIRCUIT CURRENT CALCULATION:
2 X 12 SUNMODULE 265W MODULES
CONNECTED TO 1 SMA 5000TL kW INVERTER
MAX. INVERTER OUTPUT POWER: 5000W
NOMINAL VOLATGE: 240V
RATED OUTPUT CURRENT: 22 AMPS
OVERCURRENT PROTECTION
22.0
1.25
STRING-1
12 SUNMODULE 265W
MODULES
JUNCTION
BOX
OVERCURRENT PROTECTION
12.0
1.25
15.00 AMPS
JB
TO UTILITY
POLE
BACKFEED CALCULATION
200 X 1.2 = 240 AMPS
240 - 200 = 40 MAX. BACKFEED
27.50 AMPS
SMA 5kW
INVERTER WITH
INTEGRATED
AC/DC
DISCONNECT
AC
DC
STRING-2
12 SUNMODULE 265W
MODULES
TO ARRAY
EXISTING 200A,
240VAC, MSP
LOAD
CENTER
125A,
240V
30A, 2P
240VAC
15A, 2P
240VAC
EXISTING 200A,
240VAC
DISCONNECT
FROM UTILITY
POLE
UM
60A, AC
DISCONNECT
LGATE 101
CPF METER
FM
ROOFTOP
JUNCTION BOX
TO
LOADS
FINANCE METER
MAIN SERVICE
PANEL
FM
UM
LOAD CENTER
STRING-1
12 SUNMODULE 265W
MODULES
INVERTER
JB
JUNCTION
BOX
AC DISCONNECT
AC
DC
SMA 3kW
INVERTER WITH
INTEGRATED
AC/DC
DISCONNECT
DC DISCONNECT
40A, 2POLE, PV
BREAKER
(E) GEC
3 - #8 AWG, THWN-2
1 - #8 AWG, THWN-2
FLOOR
SCALE: NTS
CLIENT:
REVISIONS:
XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx
DESCRIPTION
TITLE:
DATE:
DATE
1
SHEET:
12/22/2015
REVISION
DESIGN
BY:
XXX
JOB
NO.:
BAC-XXX
ELECTRICAL
CALCULATION, EQUIP.
ELEVATION & SINGLE
LINE DIAGRAM
PV-4
CLIENT:
REVISIONS:
XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx
DESCRIPTION
TITLE:
DATE:
DATE
SHEET:
12/22/2015
REVISION
DESIGN
BY:
XXX
JOB
NO.:
BAC-XXX
DATA SHEET:
MODULE & INVERTER
PV-5
CLIENT:
REVISIONS:
XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx
DESCRIPTION
TITLE:
DATE:
DATE
SHEET:
12/22/2015
REVISION
DESIGN
BY:
XXX
JOB
NO.:
BAC-XXX
DATA SHEET:
MOUNT & RAIL
PV-6