Load Schedule

This document provides details of the proposed electrical system for a residential building including: - The building will have a main LV panel fed from DEWA with sub-distribution boards for various floors and areas. - Loads and cable sizes are specified for circuits feeding from the main boards down to distribution boards and meter details. - The total connected load is estimated to be 1,347 KW.

Uploaded by

Arul Sankaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
297 views32 pages

Load Schedule

This document provides details of the proposed electrical system for a residential building including: - The building will have a main LV panel fed from DEWA with sub-distribution boards for various floors and areas. - Loads and cable sizes are specified for circuits feeding from the main boards down to distribution boards and meter details. - The total connected load is estimated to be 1,347 KW.

Uploaded by

Arul Sankaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 32

PROPOSED: B+ G+12+ R RES.

BUILDING
PANEL REF:
FED FROM :

L.V PANEL-1

CIRCUIT
S/N

RATING-AMPS

FEEDER

SP /

DB. NO.

TP

INCOMER - 1

AREA: AL NAHDA SECOND


PLOT NO: 241-587
LOCATION: G.F L.V ROOM

DETAILS OF CONNECTED LOAD / MAX. DEMAND


OWNER: ESSA ABDULFATTAH KAZIM AL MULLA
CONSULTANTS: FA BAKER CONSULTANTS.

4P

ACB

MCCB

MCB

FAULT

PVC/XLPE

DUTY

SWA/PVC/SC

KA

2500A

65

XLPE/SWA/PVC

CABLE SIZE
2/4X1C

2/3/4C

mm2

mm2

ECC

LENGTH
OF CABLE
(m )

DEWA CABLE

CONNECTED LOAD-KW

KWH METER

SIZE-1C

R-PH

Y-PH

B-PH

TOTAL

1-PH

3-PH

3-PH

CT

mm2

KW

KW

KW

KW

2X 1C 150

457.36

443.91

445.81

1347.09

72

1
OUTGOING

2400/5A CT

( D.O.T @ 0.85 )

SMDB - G.LL

TP

600A

35

XLPE/SWA/PVC

2X4C 185

1X1C 185

108.58

109.23

108.08

325.90

SMDB-T1

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

25.57

23.87

25.57

75.00

SMDB-T2

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

25.57

23.87

25.57

75.00

SMDB-T3

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

25.57

23.87

25.57

75.00

SMDB-T4

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T5

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T6

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T7

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T8

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T9

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T10

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T11

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-T12

TP

160A

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

SMDB-F.P

TP

350A

35

XLPE/SWA/PVC

1X 4C 240

1X 1C 120

55.00

55.00

56.00

166.00

DB-SS

SP

40A

35

XLPE/SWA/PVC

1X3C 10

1.00

1.00

CAP BANK

TP

1000A

35

XLPE/SWA/PVC

3X 4C 240

443.91

445.81

1,347.09

3X 1C 120

TOTAL CONNECTED LOAD PER PHASE

DEMAND FACTOR 0.85

REMARKS

MAX. DEMAND

CONTRACTOR : POWER FACTOR L.L.C.

1,145.03 KW

TOTAL CONNECTED LOAD ( 3 PH )

457.36

2 of 178

72

1,347.09 KW

PROVIDE CT METER WHEN MAX. DEMAND > 100 KW


(1) UP TO 60 A
(2) UP TO 100 A
(3) 125 - 160 A
( 1 PHASE )
( 3 PHASE )

TEL:.04-3232476
FAX: 04-3232473

400 KVAR

(4) LV / CT . / . A

PROPOSED: B+ G+12+ R RES. BUILDING


PANEL REF:
FED FROM :

SMDB-G.LL

CIRCUIT
S/N

RATING-AMPS

FEEDER

SP /

DB. NO.

TP

INCOMER - 1

AREA: AL NAHDA SECOND


PLOT NO: 241-587
LOCATION: G.F L.V ROOM

DETAILS OF CONNECTED LOAD / MAX. DEMAND


OWNER: ESSA ABDULFATTAH KAZIM AL MULLA
CONSULTANTS: FA BAKER CONSULTANTS.

ACB

MCCB

TP

MCB

FAULT

PVC/XLPE

DUTY

SWA/PVC/SC

KA

600A (N/A)

CABLE SIZE
2/4X1C

2/3/4C

mm2

mm2

ECC

LENGTH
OF CABLE
(m )

CONNECTED LOAD-KW

KWH METER

SIZE-1C

R-PH

Y-PH

B-PH

TOTAL

1-PH

3-PH

3-PH

CT

mm2

KW

KW

KW

KW

35

XLPE/SWA/PVC

2X4C 185

1X 1C 185

108.58

109.23

108.08

325.90

REMARKS

OUTGOING
1

DB-B.F

TP

63A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

7.00

7.85

5.95

20.80

DB-G.F

TP

63A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

8.62

8.97

8.27

25.85

DB-G.TEL

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.20

2.40

3.75

8.35

DB-T1LL

TP

40A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

6.10

6.10

6.10

18.30

DB-T2LL

TP

40A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

6.10

6.10

6.10

18.30

DB-T3LL

TP

40A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

6.10

6.10

6.10

18.30

DB-T4LL

TP

40A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

6.10

6.10

6.10

18.30

SMDB-R

TP

300A

25

XLPE/SWA/PVC

1X 4C 185

1X 1C 95

52.17

51.42

51.52

155.10

GARBAGE ISO.

TP

32A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.00

2.00

2.00

6.00

30mA ELCB

10 WATER PUMP

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

3.00

3.00

3.00

9.00

30mA ELCB

11 SUMP PUMP-1

TP

25A

25

XLPE/SWA/PVC

1X 4C 6

1X 1C 6

1.00

1.00

1.00

3.00

30mA ELS+ALARM

12 SUMP PUMP-2

TP

25A

25

XLPE/SWA/PVC

1X 4C 6

1X 1C 6

1.00

1.00

1.00

3.00

30mA ELS+ALARM

13 B.EXHAUST FAN

TP

63A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

7.20

7.20

7.20

21.60

100mA ELS+ALARM

108.58

109.23

108.08

325.90

TOTAL CONNECTED LOAD PER PHASE

DEMAND FACTOR 0.85

MAX. DEMAND

CONTRACTOR : POWER FACTOR L.L.C.

277.02 KW
TEL:.04-3232476

TOTAL CONNECTED LOAD ( 3 PH )


325.90 KW
PROVIDE CT METER WHEN MAX. DEMAND > 100 KW
(1) UP TO 60 A
(2) UP TO 100 A
(3) 125 - 160 A

FAX: 04-3232473

( 1 PHASE )

2 of 178

( 3 PHASE )

(4) LV / CT . / . A

PROPOSED: B+ G+12+ R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

DETAILS OF CONNECTED LOAD / MAX. DEMAND

LOCATION: R.F ELE.CABINET ROOM

OWNER: ESSA ABDULFATTAH KAZIM AL MULLA

PANEL REF:

CONSULTANTS: FA BAKER CONSULTANTS.


FED FROM :

SMDB-R

CIRCUIT
S/N

FEEDER

RATING-AMPS
SP /

MCB
ACB

DB. NO.

INCOMER - 1

FAULT
DUTY

PVC/XLPE
SWA/PVC/SC

CABLE SIZE

ECC

2/4X1C

2/3/4C

KA

mm2

TP

300A (N/A)

CONNECTED LOAD-KW

KWH METER

SIZE-1C

R-PH

Y-PH

B-PH

TOTAL

1-PH

3-PH

3-PH

CT

mm2

mm2

KW

KW

KW

KW

MCCB

TP

LENGTH
OF CABLE
(m )

35

XLPE/SWA/PVC

1X 4C 185

1X 1C 95

52.17

51.42

51.52

155.10

REMARKS

OUTGOING
1

DB-G.GYM

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.97

2.57

2.27

7.80

DB-L.GYM

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.87

2.67

2.27

7.80

DB-R

TP

40A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

7.13

6.78

5.63

19.55

DB-R.TEL

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.20

2.40

4.35

8.95

LIFT - 1

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.00

4.00

4.00

12.00

300mA ELCB

LIFT - 2

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.00

4.00

4.00

12.00

300mA ELCB

FAHU-

TP

125A

25

XLPE/SWA/PVC

1X 4C 50

1X 1C 25

17.00

17.00

17.00

51.00

100mA ELCB

SOLAR HETER-1

TP

63A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

5.00

5.00

5.00

15.00

30mA ELCB

SOLAR HETER-2

TP

63A

25

XLPE/SWA/PVC

1X 4C 16

1X 1C 16

5.00

5.00

5.00

15.00

30mA ELCB

10 BOOSTER PUMP

TP

32A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.00

2.00

2.00

6.00

30mA ELCB

52.17

51.42

51.52

155.10

TOTAL CONNECTED LOAD PER PHASE

DEMAND FACTOR 0.85

MAX. DEMAND

CONTRACTOR : POWER FACTOR L.L.C.

131.84 KW
TEL:.04-3232476
FAX: 04-3232473

TOTAL CONNECTED LOAD ( 3 PH )


155.10 KW
PROVIDE CT METER WHEN MAX. DEMAND > 100 KW
(1) UP TO 60 A
(2) UP TO 100 A
(3) 125 - 160 A
( 1 PHASE )
( 3 PHASE )

3 of 178

(4) LV / CT . / . A

PROPOSED: B+ G+12+ R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

DETAILS OF CONNECTED LOAD / MAX. DEMAND

LOCATION: T.F ELE. CABINET ROOM

OWNER: ESSA ABDULFATTAH KAZIM AL MULLA

PANEL REF:

CONSULTANTS: FA BAKER CONSULTANTS.


FED FROM :

SMDB-T1 TO SMDB-T3 TYP

CIRCUIT
S/N

FEEDER

RATING-AMPS
SP /
ACB

DB. NO.

INCOMER - 1

MCCB

FAULT

PVC/XLPE

DUTY

SWA/PVC/SC

ECC
2/3/4C

KA

mm2

160A (N/A)

LENGTH
OF CABLE
(m )

CONNECTED LOAD-KW

KWH METER

SIZE-1C

R-PH

Y-PH

B-PH

TOTAL

1-PH

3-PH

3-PH

CT

mm2

mm2

KW

KW

KW

KW

MCB

TP

TP

CABLE SIZE
2/4X1C

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

25.57

23.87

25.57

75.00

OUTGOING
1

FDB-101

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

5.00

5.50

4.80

15.30

FDB-102

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.70

2.60

4.80

12.10

FDB-103

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

3.03

6.03

3.33

12.40

FDB-104

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

6.23

3.23

3.33

12.80

FDB-105

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.60

2.20

5.20

12.00

FDB-106

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.00

4.30

4.10

10.40

25.57

23.87

25.57

75.00

TOTAL CONNECTED LOAD PER PHASE

DEMAND FACTOR 0.85

MAX. DEMAND

CONTRACTOR : POWER FACTOR L.L.C.

63.75 KW
TEL:.04-3232476
FAX: 04-3232473

TOTAL CONNECTED LOAD ( 3 PH )


75.00 KW
PROVIDE CT METER WHEN MAX. DEMAND > 100 KW
(1) UP TO 60 A
(2) UP TO 100 A
(3) 125 - 160 A
( 1 PHASE )
( 3 PHASE )

4 of 178

(4) LV / CT . / . A

REMARKS

PROPOSED: B+ G+12+ R RES. BUILDING


PANEL REF:
FED FROM :

SMDB-T4 TO SMDB-T12 TYP

CIRCUIT
S/N

RATING-AMPS

FEEDER

SP /

DB. NO.

TP

ACB

INCOMER - 1

AREA: AL NAHDA SECOND


PLOT NO: 241-587
LOCATION: T.F ELE. CABINET ROOM

DETAILS OF CONNECTED LOAD / MAX. DEMAND


OWNER: ESSA ABDULFATTAH KAZIM AL MULLA
CONSULTANTS: FA BAKER CONSULTANTS.

MCCB

FAULT

PVC/XLPE

DUTY

SWA/PVC/SC

ECC
2/3/4C

mm2

160A (N/A)

LENGTH
OF CABLE
(m )

CONNECTED LOAD-KW

KWH METER

SIZE-1C

R-PH

Y-PH

B-PH

TOTAL

1-PH

3-PH

3-PH

CT

mm2

mm2

KW

KW

KW

KW

MCB
KA

TP

CABLE SIZE
2/4X1C

35

XLPE/SWA/PVC

1X 4C 70

1X 1C 35

24.12

23.12

22.67

69.91

OUTGOING
1

FDB-401

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.40

5.49

4.76

14.65

FDB-402

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.50

2.55

4.40

11.45

FDB-403

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.46

4.80

2.09

11.35

FDB-404

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.60

2.28

4.90

11.78

FDB-405

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

4.20

4.30

2.62

11.12

FDB-406

TP

40 A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

1.96

3.70

3.90

9.56

24.12

23.12

22.67

69.91

TOTAL CONNECTED LOAD PER PHASE

DEMAND FACTOR 0.85

MAX. DEMAND

CONTRACTOR : POWER FACTOR L.L.C.

59.42 KW
TEL:.04-3232476
FAX: 04-3232473

TOTAL CONNECTED LOAD ( 3 PH )


69.91 KW
PROVIDE CT METER WHEN MAX. DEMAND > 100 KW
(1) UP TO 60 A
(2) UP TO 100 A
(3) 125 - 160 A
( 1 PHASE )
( 3 PHASE )

5 of 178

(4) LV / CT . / . A

REMARKS

PROPOSED: B+ G+12+ R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

DETAILS OF CONNECTED LOAD / MAX. DEMAND

LOCATION: B.F PUMP ROOM

OWNER: ESSA ABDULFATTAH KAZIM AL MULLA

PANEL REF:

CONSULTANTS: FA BAKER CONSULTANTS.


FED FROM :

SMDB-FIRE PUMP

CIRCUIT
S/N

RATING-AMPS

FEEDER

SP /

MCB
ACB

DB. NO.

PVC/XLPE

DUTY

SWA/PVC/SC

CABLE SIZE

ECC

2/4X1C

2/3/4C

KA

mm2

TP

350A (N/A)

LENGTH
OF CABLE
(m )

CONNECTED LOAD-KW

KWH METER

SIZE-1C

R-PH

Y-PH

B-PH

TOTAL

1-PH

3-PH

3-PH

CT

mm2

mm2

KW

KW

KW

KW

MCCB

TP

INCOMER - 1

FAULT

35

XLPE/SWA/PVC

1X 4C 240

1X 1C 120

55.0

55.0

56.0

166.0

REMARKS

OUTGOING
1

FIRE PUMP

TP

350A

25

XLPE/SWA/PVC

1X 4C 240

1X 1C 120

52.00

52.00

53.00

157.00

JOCKY PUMP

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

1.00

1.00

1.00

3.00

100mA ELS+ALARM

DIESEL PUMP

TP

40A

25

XLPE/SWA/PVC

1X 4C 10

1X 1C 10

2.00

2.00

2.00

6.00

100mA ELS+ALARM

55.00

55.00

56.00

166.00

TOTAL CONNECTED LOAD PER PHASE

DEMAND FACTOR 1.0

MAX. DEMAND

CONTRACTOR : POWER FACTOR L.L.C.

166.00 KW
TEL:.04-3232476
FAX: 04-3232473

TOTAL CONNECTED LOAD ( 3 PH )


166.00 KW
PROVIDE CT METER WHEN MAX. DEMAND > 100 KW
(1) UP TO 60 A
(2) UP TO 100 A
(3) 125 - 160 A
( 1 PHASE )
( 3 PHASE )

6 of 178

STARTER

100mA ELS+ALARM

(4) LV / CT . / . A

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-401

FED FROM :

SMDB - T4

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40A 4P
100mA

40 A TP ISOLATOR

40A 4P
100mA

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW

LPG COOK CCU

FCU

S A/C

0.40

R1

10

2.5

2.5

BED ROOM-1 / BATH

0.1

Y1

10

2.5

2.5

LIVING RM / DINING

0.1

B1

10

2.5

2.5

KITCHEN

0.1

R2

10

2.5

2.5

L.P.G

Y2

10

2.5

2.5

BED ROOM-2 / BATH

0.1

SPACE
SPACE

Y3

20

2.5

F.C.U-1

0.29

B3

20

2.5

F.CU-2

0.26

10

R4

20

2.5

BED ROOM-1

0.2

11

Y4

20

2.5

LIVING RM / DINING

0.2

4P

12

B4

20

2.5

KITCHEN

0.2

30 mA

13

R5

20

2.5

BED ROOM-2

0.2

14

Y5

20

2.5

KITCHEN

15

B5

20

2.5

LIVING RM / DINING

40 A

16

R6

30

FAC-1L

4P

17

Y6

30

KITCHEN

100 mA

18

B6

30

FAC-1B

0.10

0.26
0.60
0.80
0.80
0.60

0.5

0.50

0.2
1
1

2.7

0.40
2.70

3.0
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.20

0.29

B2
R3

U.V TIMER + CONT.


3.00

3.1

4.4

Page 150 of 178

REMARKS
B

0.40

0.50

0.1

KW

UNIT

40A

Cable Size:

FLAT ENTRANCE

FDB-501 , 601 , 701 , 801 , 901 , 1001 , 1101,1201 TYP

5.5

W/O 13A SSO


3.10

U.V TIMER + CONT.

4.8

14.7

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-402

FED FROM :

SMDB - T4

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
ISO

CCU

FCU

S A/C

0.40

R1

10

2.5

2.5

LIVING RM / DINING

0.1

40A

Y1

10

2.5

2.5

BED RM-1 / BATH

0.1

4P

B1

10

2.5

2.5

KITCHEN

0.1

100 mA

R2

Y2

10

2.5

2.5

BED RM-2 / BATH

0.1

10

2.5

2.5

L.P.G

B2

R3

4P

Y3

100mA

B3

REMARKS
B

0.40
0.20

SPACE

0.30

0.1

0.10

SPACE
20

2.5

F.C.U-1

0.26

0.26

SPACE

10

R4

20

2.5

BED RM-2

40A

11

Y4

20

2.5

KITCHEN

4P

12

B4

20

2.5

KITCHEN

0.2

30 mA

13

R5

20

LIVING RM / DINING

0.2

14

Y5

20

2.5

LIVING RM / DINING

0.2

15

B5

20

2.5

BED RM-1

0.2

40 A

16

R6

30

FAC-2L

4P

17

Y6

20

2.5

F.CU-2

100 mA

18

B6

30

FAC-2B

Cable Size:

KW

UNIT

40A

FLAT ENTRANCE

FDB-502 , 602 , 702 , 802 , 902 , 1002, 1102,1202 TYP

0.2
1

1
1

3.1

0.50
0.80
0.40
0.80
0.60
3.10

0.29
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.60

0.5

2.7

4.5

Page 151 of 178

U.V TIMER + CONT.


0.29

2.6

2.70

U.V TIMER + CONT.

4.4

11.5

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-403

FED FROM :

SMDB - T4

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
ISO

CCU

FCU

S A/C

0.2

R1

10

2.5

2.5

KITCHEN

0.1

40A

Y1

10

2.5

2.5

BED RM-1 / BATH

0.1

4P

B1

10

2.5

2.5

LIVING RM / DINING

0.1

100 mA

R2

20

2.5

F.C.U-1

Y2

10

2.5

2.5

L.P.G

B2

10

2.5

2.5

BED RM-2 / BATH

R3

20

2.5

KITCHEN

0.2

40A

Y3

20

2.5

BED RM-1

0.2

4P

B3

20

2.5

LIVING RM / DINING

0.2

30 mA

10

R4

20

2.5

KITCHEN

11

Y4

20

2.5

BED RM-2

LIVING RM / DINING

12

B4

20

2.5

40 A

13

R5

30

FAC-2A

4P

14

Y5

30

FAC-2B

100 mA

15

B5

20

2.5

F.CU-2

0.26

KW

UNIT

Cable Size:

FLAT ENTRANCE

FDB-503, 603 , 7073, 803 , 903, 1003, 1103,1203 TYP

0.3
0.26
0.1

0.1

0.5

0.6
0.8
0.5
0.6

0.2

1
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.3
0.8

0.2

2.7

0.4
2.70

3.1

U.V TIMER + CONT.


3.10

0.29

U.V TIMER + CONT.


0.29

4.5

Page 152 of 178

REMARKS
B

0.4

0.1

4.8

2.1

13.1

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-404

FED FROM :

SMDB - T4

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
SPUR
O/L

CCU

FCU

S A/C

0.10

0.10

R1

10

2.5

2.5

L.P.G

40A

Y1

10

2.5

2.5

LIVING RM / DINING

0.10

4P

B1

10

2.5

2.5

KITCHEN

0.10

100 mA

R2

10

2.5

2.5

BED ROOM-2 / BATH

Y2

20

2.5

F.C.U-1

B2

10

2.5

2.5

BED ROOM-1 / BATH

R3

20

2.5

BED ROOM-1

0.20

40A

Y3

20

2.5

LIVING RM / DINING

0.20

4P

B3

20

2.5

KITCHEN

0.20

30 mA

10

R4

20

2.5

LIVING RM / DINING

0.20

11

Y4

20

2.5

BED RM-2

0.20

12

B4

20

2.5

KITCHEN

40 A

13

R5

30

4.0

FAC-4A

4P

14

Y5

20

2.5

F.C.U-2

100 mA

15

B5

30

4.0

FAC-4A

0.10
1

KW

UNIT

Cable Size:

FLAT ENTRANCE

FDB-504 , 604 , 704 , 804 , 904 , 1004, 1104,1204 TYP

0.20
0.40
0.29

0.10

0.80
0.80
0.40
0.60

3.10

0.50
3.10

0.29
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.30
0.60

0.50
1

U.V TIMER + CONT.


0.29

3.10

4.6

Page 153 of 178

REMARKS
B

0.30

0.29

2.3

3.10

U.V TIMER + CONT.

4.9

11.8

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-405

FED FROM :

SMDB - T4

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
SPUR
O/L

CCU

FCU

S A/C

KW

UNIT

0.30

R1

10

2.5

2.5

LIVING RM / DINING

0.10

40A

Y1

10

2.5

2.5

KITCHEN

0.10

4P

B1

10

2.5

2.5

BED RM-1 / BATH

0.10

100 mA

R2

Y2

10

2.5

2.5

L.P.G

10

2.5

2.5

BED RM-2 / BATH

REMARKS
B

0.20
0.40

SPACE

B2

40A

R3

4P

Y3

100 mA

B3

20

2.5

F.CU-2

0.10

0.10

0.10

0.30

0.26

0.26

SPACE
SPACE
1

10

R4

20

2.5

LIVING RM / DINING

0.20

40A

11

Y4

20

2.5

KITCHEN

0.20

4P

12

B4

20

2.5

BED RM-1

0.20

30 mA

13

R5

20

LIVING RM / DINING

0.20

14

Y5

20

KITCHEN

15

B5

20

2.5

BED RM-2

0.80
0.80
0.40
0.50

0.20

16

R6

30

FAC-5A

2.70

4P

17

Y6

30

FAC-5A

2.70

100 mA

18

B6

20

2.5

F.C.U-1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.80

0.50

40 A

Cable Size:

FLAT ENTRANCE

FDB-505 , 605, 705 , 805 , 905 , 1005, 1105,1205 TYP

0.60
2.70

0.26

U.V TIMER + CONT.


0.26

4.2

Page 154 of 178

U.V TIMER + CONT.


2.70

4.3

2.6

11.1

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

RATING

PANEL REF:

FDB-406

SHEET : 1 / 1

FED FROM :

SMDB - T4

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

LOAD PER CIR.

CONNECTED LOAD

LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
ISO

CCU

FCU

S A/C

0.20

R1

10

2.5

2.5

KITCHEN

0.10

40A

Y1

10

2.5

2.5

BED RM-1 / BATH

0.10

4P

B1

10

2.5

2.5

LIVING RM / DINING

100 mA

R2

20

2.5

F.C.U-1

Y2

B2

10

2.5

2.5

L.P.G

R3

20

2.5

KITCHEN

0.20

Y3

20

2.5

BED RM-1

0.20

LIVING RM / DINING

0.40

0.10
1

0.26

REMARKS
B

0.50
0.26

SPACE

4P

B3

20

2.5

30 mA

10

R4

20

11

Y4

12

B4

20

2.5

LIVING RM / DINING

KITCHEN

0.10

0.10
0.80
0.60

0.20
1

0.50

0.80
0.50

SPACE

0.00
2

0.20

40 A

13

R5

20

2.5

F.CU-2

4P

14

Y5

30

FAC-6A

2.70

100 mA

15

B5

30

FAC-6B

2.10

Cable Size:

KW

UNIT

40A

FLAT ENTRANCE

FDB-506 , 606, 706 , 806 , 906 , 1006, 1106,1206 TYP

RATG.

40A TP ISOLATOR

LOCATION:

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.20

0.40
0.20
2.70

2.0

Page 155 of 178

3.7

U.V TIMER + CONT.


2.10

U.V TIMER + CONT.

3.9

9.6

05/30/2015

PROPOSED: B+ G+12 +R RES. BUILDING

PANEL REF:

DB-B.F

FED FROM :

SMDB-G.LL

AREA: AL NAHDA SECOND


PLOT NO: 241-587
SHEET : 1/2

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

63 A TP ISOLATOR

RATING

LOCATION: BASEMENT FLOOR


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

1.1

R1

16

2.5

2.5

COMPOUND WALL

11

0.1

40A

Y1

10

2.5

2.5

PUMP ROOM

0.1

4P

B1

10

2.5

2.5

LIFT LOBBY

0.05

100 mA

R2

10

2.5

2.5

PARKING

0.1

Y2

16

2.5

2.5

DRIVER WAY

11

0.1

B2

16

2.5

2.5

STAIR CASE-1

16

0.1

R3

16

2.5

2.5

PARKING

12

0.1

Y3

16

2.5

2.5

DRIVER WAY

12

0.1

B3

16

2.5

2.5

STAIRCASE-1

18

0.1

40A

10

R4

10

2.5

2.5

PARKING

0.1

4P

11

Y4

10

2.5

2.5

RAMP/GEN.RM

0.1

100 mA

12

B4

REMARKS
B

0.2
0.2
0.6
1.1
1.6
1.2
1.2
1.8
0.9
0.7

SPACE

13

R5

10

2.5

2.5

PARKING

0.1

14

Y5

16

2.5

2.5

STAIR CASE-2

15

0.1

15

B5

16

2.5

2.5

STAIRCASE-2

15

0.1

16

R6

20

2.5

PARKING

40A

17

Y6

20

2.5

PUMP ROOM

4P

18

B6

20

2.5

GATE BARRIER

30 mA

19

R7

32

2.5

PARKING

0.2

20

Y7

20

2.5

GEN.RM

0.2

SPACE

21

B7

40A

22

R8

20

2.5

4P

23

Y8

SPACE

30 mA

24

B8

SPACE

Cable Size:

KW

UNIT

0.2

1.5
0.8
0.4

0.5

0.5
1.0
0.4

0.5

0.4
0.5

7.0
Page 150 of 178

RING

0.2
1

1X 4C 16 mm2 XLPE/SWA/PVC +1C 16 mm PVC AS ECC

1.5

0.2
1

GATE BARRIER

0.9

5.5

6.0
05/30/2015

PROPOSED: B+G+12 RES.BUILDING

PANEL REF:

DB-B.F

FED FROM :

SMDB- G.LL

AREA: AL NAHDA SECOND


PLOT NO: 241-587
SHEET : 2/2

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

25

R9

4P

26

Y9

100 mA

27

B9

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

UNIT

KW
R

REMARKS
B

SPACE
30

BAC-1 PUMP

SPACE

2.35

2.4

U.V TIMER + CONT.

63A TP ISOLATOR

40A

LOCATION: BASEMENT FLOOR

Cable Size:

1X 4C 16 mm2 XLPE/SWA/PVC +1C 16 mm PVC AS ECC

7.00

Page 151 of 178

7.85

5.95

20.80

05/30/2015

PROPOSED: B+G+12 RES.BUILDING

PANEL REF:

DB-GTEL

FED FROM :

SMDB-G.LL

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587
SHEET : 1 / 1

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

10

2.5

2.5

SPACE

20

TEL. CU-1
SPACE

40 A TP ISOLATOR

RATING

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

0.1

0.2

R1

4P

Y1

100 mA

B1

40A

R2

4P

Y2

20

2.5

TELEPHONE ROOM

0.2

30 mA

B2

20

2.5

TELEPHONE ROOM

0.2

40A

R3

20

4P

Y3

AMP

100 mA

B3

TP

6.0

4.0

KW

UNIT

40A

Cable Size:

TELEPHONE ROOM

LOCATION: TEL. ROOM

1.35

REMARKS
B

1.4

U.V TIMER + CONT.

0.4
0.4
2.0

TEL. ISOLATOR-1

6.0

2.0
2.0

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

2.2

Page 152 of 178

2.4

3.8

8.4

05/30/2015

PROPOSED: B+G+12 RES.BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

DB-T1LL , DB-T2LL , DB-T3LL AND DB-T4LL TYP

FED FROM :

SMDB-G.LL

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

RATING

SHEET : 1/2

LOCATION: FIRST FLOOR ELE.CABINET


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

0.6

R1

10

2.5

2.5

1ST F. CORRIDOR

12

0.05

40A

Y1

10

2.5

2.5

1ST F. CORRIDOR

0.1

4P

B1

10

2.5

2.5

2ND F. CORRIDOR

12

0.05

100 mA

R2

10

2.5

2.5

2ND F. CORRIDOR

0.1

Y2

10

2.5

2.5

3RD F. CORRIDOR

12

0.05

B2

10

2.5

2.5

3RD F. CORRIDOR

0.1

R3

20

2.5

1ST F. CORRIDOR

0.2

40A

Y3

20

2.5

1ST F. CORRIDOR

0.2

4P

B3

20

2.5

2ND F. CORRIDOR

0.2

30 mA

10

R4

20

2.5

2ND F. CORRIDOR

0.2

11

Y4

20

2.5

3RD F. CORRIDOR

0.2

12

B4

20

2.5

3RD F. CORRIDOR

0.2

13

R5

20

2.5

1ST F. CORRIDOR

0.5

40A

14

Y5

20

2.5

1ST F. CORRIDOR

0.5

4P

15

B5

20

2.5

2ND F. CORRIDOR

0.5

30 mA

16

R6

20

2.5

2ND F. CORRIDOR

0.5

17

Y6

20

2.5

3RD F. CORRIDOR

0.5

18

B6

20

2.5

3RD F. CORRIDOR

0.5

Cable Size:

1X 4C 16 mm2 XLPE/SWA/PVC +1C 16 mm PVC AS ECC

KW

UNIT

REMARKS
B

0.3
0.6
0.3
0.6
0.3
0.4
0.4

FOR CCTV
0.4

0.4

FOR CCTV
0.4
0.4

0.5

FOR CCTV
FIRE DAMPER

0.5

FIRE DAMPER
0.5

0.5

FIRE DAMPER
FIRE DAMPER

0.5

FIRE DAMPER
0.5

2.7

Page 153 of 178

2.7

FIRE DAMPER

2.7

05/30/2015

PROPOSED: B+ G+12 +R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

PANEL REF:

DB-T1LL , DB-T2LL , DB-T3LL AND DB-T4LL TYP

FED FROM :

SMDB-G.LL

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

SHEET : 2/2

LOCATION: FIRST FLOOR ELE.CABINET


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

KW

UNIT

3.1

19

R7

30

4.0

1ST F. CORRIDOR

3.1

4P

20

Y7

30

4.0

2ND F. CORRIDOR

3.1

100 mA

21

B7

30

4.0

3RD F. CORRIDOR

3.1

40A

22

R8

20

2.5

1ST F. CORRIDOR

0.3

4P

23

Y8

20

2.5

2ND F. CORRIDOR

0.3

100 mA

24

B8

20

2.5

3RD F. CORRIDOR

0.3

REMARKS
B

3.1

U.V TIMER + CONT.


3.1

0.3
0.3
0.3

40A TP ISOLATOR

40A

Cable Size:

1X 4C 16 mm2 XLPE/SWA/PVC +1C 16 mm PVC AS ECC

6.10

Page 154 of 178

6.10

6.10

18.3

05/30/2015

PROPOSED: B+G+12 RES.BUILDING

PANEL REF:

DB-G.F

FED FROM :

SMDB-G.LL

AREA: AL NAHDA SECOND


PLOT NO: 241-587
SHEET : 2/2

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

63A TP ISOLATOR

RATING

LOCATION: G.F L.V ROOM


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

1.1

R1

10

2.5

2.5

COMPOUND WALL

11

0.1

40A

Y1

10

2.5

2.5

PARKING

0.1

4P

B1

10

2.5

2.5

DRIVER WAY

0.1

100 mA

R2

10

2.5

2.5

GARBAGE ROOM

0.1

Y2

10

2.5

2.5

PARKING

0.1

B2

10

2.5

2.5

L.V ROOM

0.1

R3

10

2.5

2.5

LIFT LOBBY / ENT.HALL

11

0.05

40A

Y3

10

2.5

2.5

PASSAGE / ENT.LOBBY

4P

B3

20

2.5

F.C.U-1

100 mA

10

R4

10

2.5

2.5

ENTRANCE HALL

11

Y4

12

B4

10

2.5

2.5

SECURITY ROOM

0.3
0.4
0.6
0.2
0.6
0.4

0.5

12

0.1

0.1

REMARKS
B

0.8

0.05
1

0.5
1.2

SPACE

13

R5

20

2.5

GARBAGE ROOM

0.2

40A

14

Y5

20

2.5

PASSAGE / ENT.LOBBY

0.2

4P

15

B5

20

2.5

L.V ROOM

0.2

30 mA

16

R6

32

2.5

LIFT LOBBY / ENT.HALL

0.2

17

Y6

20

2.5

PASSAGE / ENT.LOBBY

0.2

18

B6

20

2.5

SECURITY ROOM

0.2

40A

19

R7

20

2.5

LIFT LOBBY / ENT.HALL

0.2

4P

20

Y7

20

2.5

GATE BARRIER

0.5

30 mA

21

B7

20

2.5

GATE BARRIER

0.5

40A

22

R8

SPACE

4P

23

Y8

20

GAC-1LV

2.35

100 mA

24

B8

20

GAC-2GEN

2.2

Cable Size:

KW

UNIT

1X 4C 16 mm2 XLPE/SWA/PVC +1C 16 mm PVC AS ECC

0.2
0.4
0.4
0.6
1.2
0.6
0.4
0.4
0.5
0.5

2.4

U.V TIMER + CONT.


2.2

5.25
Page 155 of 178

RING

5.60

4.90
05/30/2015

PROPOSED: B+G+12 RES.BUILDING

PANEL REF:

DB-G.F

FED FROM :

SMDB-G.LL

AREA: AL NAHDA SECOND


PLOT NO: 241-587
SHEET : 2/2

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

25

R9

20

4P

26

Y9

AMP

100 mA

27

B9

TP

6.0

4.0

40A

28

R10

20

4P

29

Y10

AMP

100 mA

30

B10

TP

6.0

4.0

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU S A/C

UNIT

KW
R

REMARKS
B

1.4
GAC-4ENT

4.1

1.4

U.V TIMER + CONT.


1.4

2.0
EXHAUST FAN

2.0
2.0

63A TP ISOLATOR

40A

LOCATION: G.F L.V ROOM

Cable Size:

1X 4C 16 mm2 XLPE/SWA/PVC +1C 16 mm PVC AS ECC

8.62

Page 156 of 178

8.97

8.27

25.9

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

PANEL REF:

DB-G.GYM

FED FROM :

SMDB-R

SHEET : 1 / 1

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

RATING

LOCATION: GYM ROOM


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
SPUR
O/L

CCU

FCU

S A/C

0.6

40A

R1

10

2.5

2.5

GENTS GYM

0.1

4P

Y1

10

2.5

2.5

GENTS GYM TOILETS

0.1

100 mA

B1

20

2.5

F.C.U-1

R2

32

2.5

GENTS GYM

0.2

Y2

20

2.5

GENTS GYM

0.2

4P

B2

SPACE

30 mA

R3

SPACE

Y3

B3

20

2.5

0.2

10

R4

20

4P

11

Y4

AMP

100 mA

12

B4

TP

Cable Size:

REMARKS
B

0.8
0.5
1.0

RING
0.4

SPACE
GENTS GYM

0.5

40A

40A

KW

UNIT

0.0
0.4
1.4

6.0

4.0

1X 4C 10 mm2 XLPE/SWA/PVC

RAC-2GG

4.1

1.4

U.V TIMER + CONT.


1.4

+1C 10 mm PVC AS ECC

2.97

Page 150 of 178

2.57

2.27

9.60

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

PANEL REF:

DB-L.GYM

FED FROM :

SMDB-R

SHEET : 1 / 1

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

RATING

LOCATION: GYM ROOM


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
SPUR
O/L

CCU

FCU

S A/C

0.7

40A

R1

10

2.5

2.5

LADIES GYM

0.1

4P

Y1

10

2.5

2.5

LADIES GYM TOILETS

0.1

100 mA

B1

20

2.5

F.C.U-1

R2

20

2.5

LADIES GYM

0.2

Y2

20

2.5

LADIES GYM

0.2

4P

B2

SPACE

30 mA

R3

SPACE

Y3

B3

20

0.2

10

R4

20

4P

11

Y4

AMP

100 mA

12

B4

TP

Cable Size:

2.5

LADIES GYM TOILETS

REMARKS
B

0.9
0.5
0.8

RING
0.4

SPACE
4

0.5

40A

40A

KW

UNIT

0.0
0.4
1.4

6.0

4.0

1X 4C 10 mm2 XLPE/SWA/PVC

RAC-1LG

4.1

1.4

U.V TIMER + CONT.


1.4

+1C 10 mm PVC AS ECC

2.87

Page 151 of 178

2.67

2.27

9.60

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241-587

PANEL REF:

DB-R

FED FROM :

SMDB-R

SHEET : 1 / 1

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

10

2.5

2.5

40 A TP ISOLATOR

RATING

LIFT MACHINE ROOM

LOCATION: ROOF FLOOR


LOAD PER CIR.

CONNECTED LOAD
15A

13A

FAN

S/O

S/O

0.1

0.2

W/H

W/M

ISO.

CCU

FCU

S A/C

R1

40A

Y1

4P

B1

10

2.5

2.5

ROOF CORRIDOR

10

0.1

100 mA

R2

10

2.5

2.5

TERRACE

0.1

Y2

10

2.5

2.5

TERRACE / ROOF

0.1

B2

SPACE
SPACE

REMARKS
B

SPACE

40A

R3

4P

Y3

30 mA

B3

10

R4

40A

11

Y4

20

2.5

ROOF CORRIDOR

0.5

4P

12

B4

20

2.5

ROOF CORRIDOR

0.5

30 mA

13

R5

20

2.5

ROOF CORRIDOR

0.5

14

Y5

20

2.5

ROOF CORRIDOR

0.5

1.0
0.6
0.7

SPACE
20

2.5

CORRIDOR

0.2

0.6

SPACE

15

B5

20

2.5

LIFT MACHINE ROOM

40A

16

R6

30

4.0

CORRIDOR CU-

4P

17

Y6

30

4.0

LIFT CU-

100 mA

18

B6

20

2.5

CORRIDOR F.C.U-

40A

19

R7

20

4P

20

Y7

AMP

6.0

4.0

SPF-1 ISOLATOR

100 mA

21

B7

TP

40A

22

R8

20

4P

23

Y8

AMP

100 mA

24

B8

TP

40A

25

R9

20

4P

26

Y9

AMP

100 mA

27

B9

TP

40A

28

R10

20

4P

29

Y10

AMP

100 mA

30

B10

TP

Cable Size:

KW

UNIT

LTG C.FAN

EX.

KW

0.5

0.5

3.1

2.35

FIRE DAMPER
FOR CCTV

0.5

0.5
1

FIRE DAMPER
0.5

FOR CCTV
0.5

3.1

FIRE DAMPER
U.V TIMER + CONT.

2.4

0.3

U.V TIMER + CONT.


0.3

0.5
1

1.5

0.5

ELS+ALARM
0.5

0.5
6.0

4.0

SPF-1 ISOLATOR

1.5

0.5

ELS+ALARM
0.5

1.0
6.0

4.0

LLPF- ISOLATOR

3.0

1.0

ELS+ALARM
1.0

0.7
6.0

4.0

1X 4C 16 mm2 XLPE/SWA/PVC

SEF- ISOLATOR

2.2

0.7

ELS+ALARM
0.7

+1C 16 mm PVC AS ECC

7.1
Page 152 of 178

6.8

5.6

19.6
05/30/2015

Cable Size:

1X 4C 16 mm2 XLPE/SWA/PVC

+1C 16 mm PVC AS ECC

7.1

Page 153 of 178

6.8

5.6

19.6

05/30/2015

PROPOSED: B+G+12 RES.BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

DB-R.TEL

FED FROM :

SMDB-R

SHEET : 1 / 1

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

10

2.5

2.5

SPACE

20

ROOF TELEPHONE ROOM CU-

40 A TP ISOLATOR

RATING

40A

R1

4P

Y1

100 mA

B1

40A

R2

4P

Y2

20

2.5

30 mA

B2

40A

R3

20

4P

Y3

AMP

6.0

4.0

100 mA

B3

TP

Cable Size:

ROOF TELEPHONE ROOM

LOCATION: GSM. ROOM


LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW
ISO.

CCU

FCU

S A/C

KW

UNIT

0.1

0.2

2.35

REMARKS
B

2.4

U.V TIMER + CONT.

SPACE
ROOF TELEPHONE ROOM

0.2

0.4

SPACE
2.0

1X 4C 10 mm2 XLPE/SWA/PVC

ISOLATOR FOR TEL.RM -1

6.0

2.0
2.0

+1C 10 mm PVC AS ECC

2.2

Page 154 of 178

2.4

4.4

9.0

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-101

FED FROM :

SMDB - T1

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40A 4P
100mA

40 A TP ISOLATOR

40A 4P
100mA

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

KW

LPG COOK CCU

FCU

S A/C

0.4

R1

10

2.5

2.5

BED ROOM-1 / BATH

0.1

Y1

10

2.5

2.5

LIVING RM / DINING

0.1

B1

10

2.5

2.5

KITCHEN

0.1

R2

10

2.5

2.5

L.P.G

Y2

10

2.5

2.5

BED ROOM-2 / BATH

0.1

SPACE
SPACE

Y3

20

2.5

F.C.U-1

0.3

B3

20

2.5

F.CU-2

0.3

10

R4

20

2.5

BED ROOM-1

0.2

11

Y4

20

2.5

LIVING RM / DINING

0.2

4P

12

B4

20

2.5

KITCHEN

0.2

30 mA

13

R5

20

2.5

BED ROOM-2

0.2

14

Y5

20

2.5

KITCHEN

15

B5

20

2.5

LIVING RM / DINING

40 A

16

R6

30

FAC-1L

4P

17

Y6

30

KITCHEN

100 mA

18

B6

30

FAC-1B

0.1

0.3
0.6
0.8
0.8
0.6

0.5

0.5

0.2
1
1

3.3

0.4
3.3

3.0
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.2

0.3

B2
R3

U.V TIMER + CONT.


3.0

3.1

5.0

Page 150 of 178

REMARKS
B

0.4

0.5

0.1

KW

UNIT

40A

Cable Size:

FLAT ENTRANCE

FDB-201 , 301 TYP

5.5

W/O 13A SSO


3.1

U.V TIMER + CONT.

4.8

15.3

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-102

FED FROM :

SMDB - T1

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
ISO

CCU

FCU

S A/C

0.4

R1

10

2.5

2.5

LIVING RM / DINING

0.1

40A

Y1

10

2.5

2.5

BED RM-1 / BATH

0.1

4P

B1

10

2.5

2.5

KITCHEN

0.1

100 mA

R2

Y2

10

2.5

2.5

BED RM-2 / BATH

0.1

10

2.5

2.5

L.P.G

B2

R3

4P

Y3

100mA

B3

REMARKS
B

0.4
0.2

SPACE

0.3

0.1

0.1

SPACE
20

2.5

F.C.U-1

0.3

0.3

SPACE

10

R4

20

2.5

BED RM-2

40A

11

Y4

20

2.5

KITCHEN

4P

12

B4

20

2.5

KITCHEN

0.2

30 mA

13

R5

20

LIVING RM / DINING

0.2

14

Y5

20

2.5

LIVING RM / DINING

0.2

15

B5

20

2.5

BED RM-1

0.2

40 A

16

R6

30

FAC-2L

4P

17

Y6

20

2.5

F.CU-2

100 mA

18

B6

30

FAC-2B

Cable Size:

KW

UNIT

40A

FLAT ENTRANCE

FDB-202, 302 TYP

0.2
1

1
1

3.3

0.5
0.8
0.4
0.8
0.6
3.3

0.3
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.6

0.5

3.1

4.7

Page 151 of 178

U.V TIMER + CONT.


0.3

2.6

3.1

U.V TIMER + CONT.

4.8

12.1

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-103

FED FROM :

SMDB - T1

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
ISO

CCU

FCU

S A/C

0.2

R1

10

2.5

2.5

KITCHEN

0.1

40A

Y1

10

2.5

2.5

BED RM-1 / BATH

0.1

4P

B1

10

2.5

2.5

LIVING RM / DINING

0.1

100 mA

R2

Y2

10

2.5

2.5

L.P.G

B2

10

2.5

2.5

BED RM-2 / BATH

R3

20

2.5

KITCHEN

0.2

40A

Y3

20

2.5

BED RM-1

0.2

4P

B3

20

2.5

LIVING RM / DINING

0.2

30 mA

10

R4

20

2.5

KITCHEN

11

Y4

20

2.5

BED RM-2

3
2

SPACE

12

B4

20

2.5

LIVING RM / DINING

40 A

13

R5

20

2.5

F.C.U-1

4P

14

Y5

30

4.0

FAC-3A

100 mA

15

B5

20

2.5

F.C.U-2

40 A

16

R6

20

4P

17

Y6

AMP

6.0

4.0

FAC-3B

100 mA

18

B6

TP

KW

UNIT

Cable Size:

FLAT ENTRANCE

FDB-203, 303 TYP

REMARKS
B

0.4
0.3
0.0

0.1

0.1

0.1

0.5

0.3
0.8
0.6
0.8
0.5

0.2

0.6

0.2
1

0.3
1

0.4
0.3

3.1

3.1

0.3

U.V TIMER + CONT.


0.3

1.2
1

3.7

1.2

U.V TIMER + CONT.


1.2

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

3.0

Page 152 of 178

6.0

3.3

13.1

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-104

FED FROM :

SMDB - T1

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
SPUR
O/L

CCU

FCU

S A/C

KW

UNIT

0.1

0.1

R1

10

2.5

2.5

L.P.G

40A

Y1

10

2.5

2.5

LIVING RM / DINING

0.1

4P

B1

10

2.5

2.5

KITCHEN

0.1

100 mA

R2

10

2.5

2.5

BED ROOM-2 / BATH

0.1

Y2

10

B2

10

2.5

2.5

BED ROOM-1 / BATH

R3

20

2.5

BED ROOM-1

0.2

40A

Y3

20

2.5

LIVING RM / DINING

0.2

4P

B3

20

2.5

KITCHEN

0.2

30 mA

10

R4

20

2.5

BED ROOM-2

0.2

11

Y4

20

2.5

LIVING RM / DINING

0.2

12

B4

20

2.5

KITCHEN

13

R5

30

4.0

FAC-4A

REMARKS
B

0.3
0.2
0.4

SPARE

40 A

0.2
3

0.1

3.3

4P

14

Y5

20

2.5

F.C.U-1

0.3

15

B5

20

2.5

F.C.U-2

0.3

40 A

16

R6

20

4P

17

Y6

AMP

6.0

4.0

FAC-4B

100 mA

18

B6

TP

FUTURE LOAD
0.3

0.6
0.8
0.8
0.6
0.4

0.5
1

100 mA

Cable Size:

FLAT ENTRANCE

FDB-204, 304 TYP

0.5
3.3

U.V TIMER + CONT.


0.3
0.3

1.2
1

3.7

1.2

U.V TIMER + CONT.


1.2

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

6.2

Page 153 of 178

3.2

3.3

12.8

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

PANEL REF:

FDB-105

FED FROM :

SMDB - T1

SHEET : 1 / 1

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40 A TP ISOLATOR

LOCATION:

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
SPUR
O/L

CCU

FCU

S A/C

0.3

R1

10

2.5

2.5

LIVING RM / DINING

0.1

40A

Y1

10

2.5

2.5

KITCHEN

0.1

4P

B1

10

2.5

2.5

BED RM-1 / BATH

0.1

100 mA

R2

Y2

10

2.5

2.5

L.P.G

10

2.5

2.5

BED RM-2 / BATH

B2

R3

4P

Y3

100 mA

B3

REMARKS
B

0.2
0.4

SPACE
1

0.1

0.1

0.1

0.3

SPACE
20

2.5

F.CU-2

0.3

0.3

SPACE

10

R4

20

2.5

LIVING RM / DINING

0.2

40A

11

Y4

20

2.5

KITCHEN

0.2

4P

12

B4

20

2.5

BED RM-1

0.2

30 mA

13

R5

20

LIVING RM / DINING

0.2

14

Y5

20

KITCHEN

15

B5

20

2.5

BED RM-2

40 A

16

R6

30

FAC-5A

4P

17

Y6

20

2.5

F.C.U-1

100 mA

18

B6

30

FAC-5B

Cable Size:

KW

UNIT

40A

FLAT ENTRANCE

FDB-205, 305 TYP

0.8
0.8
0.4

0.5

0.5

0.2
1
1

3.1

0.6
3.1

0.3
1

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.8

3.1

4.6

Page 154 of 178

U.V TIMER + CONT.


0.3

2.2

3.1

U.V TIMER + CONT.

5.2

12.0

05/30/2015

PROPOSED: B+ G+12+R RES. BUILDING

AREA: AL NAHDA SECOND


PLOT NO: 241 - 587

RATING

PANEL REF:

FDB-106

SHEET : 1 / 1

FED FROM :

SMDB - T1

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

LOAD PER CIR.

CONNECTED LOAD

LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

W/M

LPG

KW
ISO

CCU

FCU

S A/C

0.2

R1

10

2.5

2.5

KITCHEN

0.1

40A

Y1

10

2.5

2.5

BED RM-1 / BATH

0.1

4P

B1

10

2.5

2.5

LIVING RM / DINING

100 mA

R2

20

2.5

F.C.U-1

Y2

B2

10

2.5

2.5

L.P.G

R3

20

2.5

KITCHEN

0.2

Y3

20

2.5

BED RM-1

0.2

LIVING RM / DINING

0.4

0.1
1

0.3

REMARKS
B

0.5
0.3

SPACE

4P

B3

20

2.5

30 mA

10

R4

20

11

Y4

12

B4

20

2.5

LIVING RM / DINING

KITCHEN

0.1

0.1
0.8
0.6

0.2
1

0.5

0.8
0.5

SPACE

0.0
2

0.2

40 A

13

R5

20

2.5

F.CU-2

4P

14

Y5

30

FAC-6A

3.3

100 mA

15

B5

30

FAC-6B

2.3

Cable Size:

KW

UNIT

40A

FLAT ENTRANCE

FDB-206, 306 TYP

RATG.

40A TP ISOLATOR

LOCATION:

1X 4C 10 mm2 XLPE/SWA/PVC +1C 10 mm PVC AS ECC

0.2

0.4
0.2
3.3

2.0

Page 155 of 178

4.3

U.V TIMER + CONT.


2.3

U.V TIMER + CONT.

4.1

10.4

05/30/2015

PROJECT : B+G+6 FLOORS DIP HEADQUARTERS

AREA: DUBAI INVESTMENT PARK

PLANNED COMPLETION DATE : DECEMBER - 2009

PLOT: 598 - 1205

PANEL REF:

DB - SS

FED FROM :

LV MDB - 3

LOCATION: TRANSFORMER ROOM

SHEET : 1 / 1

GROUND FLOOR

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

C1

10

2.5

2.5

C2

16

C3

20

2.5

2.5

C4

20

TRANSFORMER ROOM

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

H/D

KW
SPUR
O/L

CCU

FCU S A/C

KW

UNIT

0.1

0.8

SPARE

REMARKS

F1

0.6

TRANSFORMER ROOM

0.2

SPARE

1.2
0.6

5
6
7
8
40 A TP ISOLATOR

9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Cable Size:

2X1C 6mm2 XLPE/SWA/PVC

SINGLE PHASE

+1C 6 mm PVC AS ECC

Page 178 of 178

05/30/2015

PROJECT : B+G+12+R RES. BUILDING

AREA: AL NAHDA SECOND

PLANNED COMPLETION DATE :

PLOT: 241-587

PANEL REF:

DB - SS

FED FROM :

LV MDB - 1

LOCATION: TRANSFORMER ROOM

SHEET : 1 / 1

GROUND FLOOR

RATING

RATG.

SL.

CIR

MCB

CCT

ECC

OF

OF

No.

No.

RTG.

WIRE

WIRE

ROOM /

INCOMER

ELCB

IN

SIZE

SIZE

AREA

mm

mm

40A 2P

B1

10

2.5

2.5

100mA

B2

TRANSFORMER ROOM
SPACE

40A 2P

B3

20

TRANSFORMER ROOM

30mA

B4

SPACE

LOAD PER CIR.

CONNECTED LOAD
LTG C.FAN

EX.

15A

13A

FAN

S/O

S/O

W/H

H/D

KW
SPUR
O/L

CCU

FCU S A/C

4
3

KW

UNIT

0.1

0.4

0.2

0.6

REMARKS

5
6
7
8
40A SP ISOLATOR

9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Cable Size:

SINGLE PHASE

1X3C 10mm2 XLPE/SWA/PVC

Page 178 of 178

1.0