Reinf S1

This document provides calculations to determine if a pipe branch meets reinforcement requirements according to ASME B31.1. It analyzes dimensions, material properties, and areas for both the pipe run and branch. The summary is: 1) Dimensions, material properties, and minimum thickness requirements were analyzed for both the pipe run and branch. 2) Areas were calculated including the required reinforcement area, areas provided by excess pipe thickness, and weld areas. 3) The total contributing reinforcement area was found to be 112% of the required area, indicating the branch has sufficient reinforcement.

Uploaded by

tasingenieria
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
377 views

Reinf S1

This document provides calculations to determine if a pipe branch meets reinforcement requirements according to ASME B31.1. It analyzes dimensions, material properties, and areas for both the pipe run and branch. The summary is: 1) Dimensions, material properties, and minimum thickness requirements were analyzed for both the pipe run and branch. 2) Areas were calculated including the required reinforcement area, areas provided by excess pipe thickness, and weld areas. 3) The total contributing reinforcement area was found to be 112% of the required area, indicating the branch has sufficient reinforcement.

Uploaded by

tasingenieria
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Pipe Branch Reinforcement

per ASME B31.1 -2010 Power Piping Code


Branch (1) Calculations

3/11/2012, ReinfS1.xls

Client:

Description:

Prepared By

Page 1 of 2

Approval

Date

Ben A. Nottingham

Rev.
0

Customer No.:

Item No.:

1
2

Owner No.:

Dwg. No.:

3
4

The user is responsible to verify method and results.


Refer to para. 104.3.1 and Fig. 104.3.1(D) of the Code
-20 to

Design Temperature

400

deg. F (to 204 deg. C)

Dimensional Units

Inch

Rating is based on design

Design Pressure

Design pressure: 350 psig = 24.6 kg/cm^2 = 24.1 bar-G = 2413 kPa
Material Data per ASME B31.1 -2010, Tables A-1 thru A-9

Materials:
Run Pipe:

Appendix H, Example 4, Run & Branch: Carbon Steel, API 5L-A Seamless Pipe

UNS no.: ----

Line Pipe

Branch:

Allowable stress, SEh = 16 ksi = 110 MPa

Coefficient Y = 0.4

Notes: para. H304 in ASME B31.3

Weld: S-1

Weld joint factor, E h = 1.00


Weld strength red. factor, W h = 1.00

Appendix H, Example 4, Run & Branch: Carbon Steel, API 5L-A Seamless Pipe

UNS no.: ----

Line Pipe

Reinf:

Allowable stress, SEb = 16 ksi = 110 MPa

Coefficient Y = 0.4

Notes: para. H304 in ASME B31.3

Weld: S-1

Weld joint efficiency factor, E b = 1.00


Weld strength reduction factor, W b = 1.00

Appendix H, Example 4, Run & Branch: Carbon Steel, API 5L-A Seamless Pipe

UNS no.: ----

Line Pipe
Allowable stress, SEr = 16 ksi = 110 MPa

Weld: S-1

Notes: para. H304 in ASME B31.3

Does Branch-1 intersect a longitudinal weld on the run?

Longitudinal Weld Intersection?

Yes

Allowable stress of run for reinforcement design, SE hr = SE h when branch intersects a weld on the run,
or SE hr = SE h / E h when the branch does not intersect a weld on the run.

16.0

ksi

Dob =

4.5

in.

tnb =

0.237

in.

or h2 =

0.000

in.

Check if diameter and thickness ratios are reasonable using criteria from ASME B31.3, para. 304.3.1(b)(1) & (2).
D ob / D oh =
(D ob / D oh ) must not exceed 1.0
OK Branch OD is not greater than Run OD.

0.52

D oh / T h =

30.6

D oh / 2 =

4.3

in.

in.

Thickness allowance (corrosion, etc.)

Allowances
Run Dimensions

in.

Sch 40 per ASME B36.10M

Wall thk:
Doh =

Pipe nominal thickness

tnh =

0.322

in.

or h1 =

0.000

in.

Millh = 12.5%

(D oh /T h ) must not exceed 100, unless D ob <(D oh / 2)


Is branch size less than 1/2 of run size?

NPS 4 (DN 100)

Pipe size:

Pipe outside diameter


Thk. tolerance:

0.1882

Branch Dimensions

NPS 8 (DN 200)

Pipe size:
Wall thk:

SE hr =
A=

8.625

in.

Sch 40 per ASME B36.10M

Pipe outside diameter


Pipe nominal thickness:
Thk. tolerance:

Millb =

OK Run OD/ Run Thk. < 100. See below.

OK Branch OD may be any size not exceeding Run OD.

0.0%

Required minimum wall thicknesses. Refer to para. 104.1.2 Eq. (3) and Table 104.1.2(A) of B31.1 Code,
t m = [ P D o / (2 (SE + PY )) ] + A
t mh =

0.2817

t mhr =

0.2817

in.

Run actual measured or minimum thickness, T h = t nh (1 - Mill h ) - h 1

Th =

0.282

in.

Run actual corroded thickness (measured or minimum thickness, less corrosion allowance), t ha = T h - A

t ha =

0.094

in.

t mb =

0.2370

in.

Branch actual measured or minimum thickness, T b = t nb (1 - Mill b ) - h 2

Tb =

0.237

in.

Branch actual corroded thickness (measured or minimum thickness, less corrosion allowance), t ba = T b - A

t ba =

0.049

in.

Minimum required run thickness, t mh = [ P D oh / (2 (SE h + PY )) ] + A


Minimum required run thickness for reinforcement design, t mhr = [ P D oh / (2 (SE hr + P Y ) ] + A

OK Run thickness IS sufficient at design pressure.


Minimum required branch thickness, t mb = [P D ob / (2 (SE b + PY b1 )) ] + A

OK Branch thickness IS sufficient at design pressure

3/11/2012, ReinfS1.xls

Pipe Branch Reinforcement


per ASME B31.1 -2010 Power Piping Code
Branch (1) Calculations

Nom. thk. of pad:

t nr = 0.322

in. = 8.18 mm

Width of pad from edge of branch:

w r = 0.875

in. = 22.23 mm

Height of saddle above run:

h s = n/a

--

Weld at pad or ring to branch periphery:

W 1s = n/a

--

Weld at ring, pad, or saddle outer edge:

W 2s = n/a

--

Weld at saddle-to-branch periphery:

W 3s = n/a

--

Page 2 of 2

wwr r

wwr r
wr

tn

tri

thnr
tn
rs

trrnr

Optional Special Weld Dimensions:

Angle between run and branch:

= 90

Ring Reinforced (re-pad), 90-degree


Branch
Comments:
-- -- -- -- --- -- -- -- --- --

degrees

Integrally Reinforced B31.1 Branch:


t r i = n/a

--

w r i = n/a

--

Leg of 60 deg. triangle = n/a


Width integral reinf. area = (tr i) tan 30
Other Dimensions

Inside centerline longitudinal dimension of finished branch opening = [ D ob - 2 (T b - A ) ] / sin

d1 =

4.402

in.

Half width of reinf. zone = d 1 or (T b - A )+(T h -A ) + d 1 / 2, whichever is greater, but not more than D oh

d2 =

4.402

in.

Reinf. zone height outside of run pipe, for ring or saddle = 2.5 (T h - A ) or 2.5 (T b - A ) + t nr , whichever is less

Lr =

0.234

in.

Reinf. zone height outside of run pipe, for integrally reinforced fitting = 2.5 (T h - A )

Li =

0.000

in.

Reinf. zone height outside of run pipe = L r + L i

L4 =

0.234

in.

Outside dimension of reinforcing ring or saddle (along run) = 2 w r + [ (D ob ) ( 2 - sin ) ]

Dr =

6.250

in.

t min =

0.000

in.

Minimum throat of fillet weld at saddle-to-branch = (smaller of t nb or t nr ) ---[weld reference para. 127.4.8(B)]
Min. throat of weld at branch periphery (except saddle or integrally reinf.) = smaller of 6.0 mm (1/4") or 0.7 t nb
Minimum leg of weld at branch periphery (except saddle or integrally reinf.) = t c / 0.707
Leg height of weld at branch periphery (except saddle or integrally reinf.) = greater of W 1(min) or W 1s
Minimum leg of weld at outer edge of ring, pad, or saddle = 0.5 t nr / 0.707
Leg height of weld at outer edge of ring, pad, or saddle = greater of W 2(min) , or W 2s , but

tc =

0.166

in.

W 1(min) =

0.235

in.

W1 =

0.235

in.

W 2(min) =

0.228

in.

W2 =

0.228

in.

in.

not more than smaller of t nr or L 4 (must fit within the reinf. zone)
W 3(min) =

0.000

Leg height of fillet weld at saddle-to-branch periphery = greater of W 3(min) or W 3s

W3 =

0.000

in.

Maximum width of ring, pad, or saddle which would apply = d 2 - (D ob / 2 ) / sin

WR max =

2.152

in.

Minimum leg height of fillet weld at saddle-to-branch periphery = 0.7t min /0.707

Rh =

0.234

in.

Rw =

0.875

in.

Factor for complete fillet welds, other than on ring, pad, or saddle edge, which will fit within the reinf. zone height

N wh =

Factor for complete fillet welds on ring, pad, or saddle edge which will fit within reinforcement zone width

N ww =

Reinforcement height (except weld) = lesser of ( t nr or L 4 ) , or lesser of ( t r i or L 4 ), as applicable


Reinforcement width (except weld) = (lesser of w r or WR max ), or (lesser of w r i or t ri ) tan 30, as applicable
Count of Welds Within Reinforcement Zone

Strength Correction Factors


Factor for strength correction of branch area = 1 if SE b > SE h , or = (SE b / SE h ) if SE b <= SE h
Strength correction factor for reinforcing material = 1 if SE r > SE h , or = (SE r / SE h ) if SE r <= SE h
Strength correction factor for welds, F w = lesser of F b or F r
Areas
Pressure design area expected at end of service life = (t mhr - A ) d 1
Required reinforcement area = A 6 (2 - sin )
Area of excess thickness in run pipe wall = (2 d 2 - d 1 ) (T h - t mhr )
Area of excess thickness in branch pipe wall = 2 L 4 (T b - t mb ) / sin

Fb =

1.000

Fr =

1.000

Fw =

1.000

A6 =

0.412

in.^2

A7 =

0.412

in.^2

A1 =

0.000

in.^2

A2 =

0.000

in.^2

Total area of welds within zone = (N wh / 2)(W 1 )+(N wh / 2)(W 3 )+(N ww / 2)(W 2 )

A3 =

0.052

in.^2

Area of added reinforcement metal, except welds, within the reinforcement zone = 2 x R h x R w

A4 =

0.409

in.^2

Area provided in B31.1 integrally reinforced fitting [See Fig. 104.3.1(D), Example B], = R h x R w

A 4i =

0.000

in.^2

Total contributing area (with strength correction for added metal within the reinf. zone)
A c = A 1 + (A 2 )(F b ) + (A 3 )(F w ) + (A 4 + A 4i )(F r )

Ac =

0.461

in.^2

Percent of area replaced = A c / A 7 %

This branch has sufficient reinforcement.

% Area

112%