Cables Aetna

This document provides specifications for an interlocked armored power cable with 25,000 volt insulation. The cable has copper conductors surrounded by insulation layers, shielding tapes, and an interlocked copper armor. It is rated for wet or dry use at 90°C and comes in various conductor sizes from 1 AWG to 1000 kcmil. Electrical ratings including ampacity are provided for different conductor sizes at 40°C ambient temperature. The cable meets various industry standards for shielded power cable and has listings with Underwriters Laboratories.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
467 views

Cables Aetna

This document provides specifications for an interlocked armored power cable with 25,000 volt insulation. The cable has copper conductors surrounded by insulation layers, shielding tapes, and an interlocked copper armor. It is rated for wet or dry use at 90°C and comes in various conductor sizes from 1 AWG to 1000 kcmil. Electrical ratings including ampacity are provided for different conductor sizes at 40°C ambient temperature. The cable meets various industry standards for shielded power cable and has listings with Underwriters Laboratories.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SPEC 3-62-4

INTERLOCKED ARMORED POWER CABLE, 25000 VOLT


TR-XLP, SHIELDED
TR-XLP Insulation

Copper
Tape Shield

Binder Tape
Fillers

Copper
Conductor
Extruded
Conductor
Shield

Ver. 8.0
Revised: 07/04/13

Semi-Conducting
Insulation Shield

Copper
Ground
Wire

Interlocked Armor

PVC or CPE
Jacket

90C CONDUCTOR TEMPERATURE, WET OR DRY


Conductor
Size AWG
or KCMIL

No. of
Strands

Nominal
O.D in Inches

Insulation
in Mils

Jacket
in Mils

Size AWG
Copper
Ground
Wire

Approximate
O.D.
in Inches

Ampacity**
40C
Ambient

Approximate
Net Weight
Lbs/Kft

THREE CONDUCTOR 25000 VOLT 100% INSULATION LEVEL, SHIELDED


1

19

0.30

260

75

2.44

185

2960

1/0

19

0.34

260

75

2.50

215

3270

2/0

19

0.38

260

75

2.56

245

3640

3/0

19

0.42

260

75

2.69

285

4140

4/0

19

0.48

260

75

2.81

325

4705

250

37

0.52

260

75

2.87

360

5195

300

37

0.57

260

75

3.00

397

5865

350

37

0.62

260

75

3.12

435

6480

500

37

0.74

260

85

3.41

535

8455

750

61

0.91

260

85

1/0

3.79

670

11445

1000*

61

1.12

260

85

1/0

4.29

770

14620

THREE CONDUCTOR 25000 VOLT 133% INSULATION LEVEL, SHIELDED


1

19

0.30

320

75

2.69

185

3410

1/0

19

0.34

320

75

2.75

215

3730

2/0

19

0.38

320

75

2.87

245

4120

3/0

19

0.42

320

75

2.94

285

4625

4/0

19

0.48

320

75

3.06

325

5210

250

37

0.52

320

85

3.23

360

5855

300

37

0.57

320

85

3.29

397

6530

350

37

0.62

320

85

3.41

435

7165

500

37

0.74

320

85

3.66

535

9050

750

61

0.91

320

85

1/0

4.04

670

12095

Note:**Based one three conductor cable isolated in air per NEC. For
other installations refer to the NEC.
*Compressed conductors.
Weights based on aluminum armor assembly.

The above data is approximate and subject to normal manufacturing tolerances.

STANDARDS AND RATINGS:


1. Conforms to ICEA S-93-639/NEMA WC74 Shielded Power Cable 5-46KV.
2. Cable listed by UL as Type MV-90 or MC per Standard 1072.
3. Listed by UL as Sunlight Resistant, for Direct Burial, For CT Use and IEEE 1202.
4. Listed by UL as For CT Use & LS (Aetna 3742 LSOH jacket only)

AETNA INSULATED WIRE, LLC


1537 AIR RAIL AVENUE, VIRGINIA BEACH, VA 23455
TELEPHONE: (800) 423-6505 FAX: (757) 605-2094
WWW.AETNAWIRE.COM