Iec Sit Sit Sepam Curve

The document provides information about trip curves for a 3000TC relay including notes on setting methods, minimum operate thresholds, and equations for calculating operate time based on current value and curve type.

Uploaded by

yadav_sct
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views1 page

Iec Sit Sit Sepam Curve

The document provides information about trip curves for a 3000TC relay including notes on setting methods, minimum operate thresholds, and equations for calculating operate time based on current value and curve type.

Uploaded by

yadav_sct
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

3000TC0706

01/2008
LaVergne, TN, USA

Trip Curve
IEC-SIT+SIT-A-10PU(1)
Standard Inverse Time (SIT and SIT-A)
3000TC

NOTES:
1. Sepam relays have two modes of setting:
The default method shown here, uses curves that are
referenced at ten times the current setting (Is)[10 Per
Unit].
The alternate method is by TMS, which is similar to an
electromechanical time dial setting method. Curves
reflecting the TMS method are on a separate form.
2. The following minimum operate thresholds (I / Is)
apply:
SIT, VIT, LTI, EIT, UIT @ I / Is=1.2
RI, IAC-SIT, IAC-VIT, IAC-EIT @ I / Is=1.0
SIT-A, VIT-B, LTI-B, EIT-C, IEEE MI, IEEE VI, IEEE EI
@ I/ Is=1.1
3. When the monitored value is more than 20 times the
set point, the tripping time is limited to the value
corresponding to 20 times the set point.
4. if the monitored value exceeds the measurement
capacity of Sepam (40 IN for the phase current
channels, 20 INr for the residual current channels), the
tripping time is limited to the value corresponding to
the largest measurable value (40 IN or 20 INr).

100

Operating Time in Seconds

where:
td = Operate time (sec)
I = Current value
k = Coefficient values (see table)
Is = Current set point
= Coefficient values (see table)
T = time setting (sec) at I/Is = 10
= Coefficient values (see table)

1000

3000TC0706-IEC-SIT-DE50869

k
T
t d ( I ) = -------------------- --
I
---- 1
I s

12.5

10

5
2.5
1.2

0.8
0.4
0.2

0.1

0.1

0.01
1

295 Tech Park Drive, Suite 100


LaVergne, TN, USA
1-888-SquareD (1-888-778-2733)
www.us.SquareD.com

100

Current I / Is

Curve Type

Schneider Electric USA

10

Coefficient Values
k

Standard inverse / A

0.14

0.02

2.97

Very inverse / B

13.5

1.50

Long time inverse / B

120

13.33

Extremely inverse / C

80

0.808

Ultra inverse

315.2

2.5

Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
2008 Schneider Electric. All Rights Reserved.